Valves & Equipments TDS Approved

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

1.

All FG 200 to be replaced by FG 220


2. Gland packing should be done by PTFE
3. Valves from 50mm NB & above will be double eccentric type.
4. For painting two coat of red oxide primer & two coat of synthetic enamel with each
quote of 50micron is required.
5. A Double layer of anti-corrosive tape shall be provided.
6. For painting two coat of red oxide primer & two coat of synthetic enamel with each
quote of 50micron is required.
7. Hand wheel to be provided for 65mm NB & above.
8.GA Drawing of Hydrant System to be provided.
9. Internal Hose length will be 15m X 2 instead of 15m only.
10. Hose box will be made by heavy duty Aluminum checkered plate.
11.Hose box Coupling will be SS. internal hose pipe will be 15m X 2. ISI marked.
12. Monitor will be 2580 LPM instead of 1750LPM