CAN Protocol EN
CAN Protocol EN
Protocol
Used values:
Data-transfer-rate max: 1 M bits/s up to 40m Distance
" Demag-Standard: 615 Kbits/s up to 70m Distance
There is always one TXobject and one RXobject, with each 3 Descriptorbytes
and 8 Byte Data.
Circuit 1 = Can-Stationnumber 13
Circuit 2 = Can-Stationnumber 14
Circuit 3 = " 15
Circuit 4 = " 16
2. CAN-PROTOCOL
2.1. TXOBJECT
Transmit-Object:
11 Bit-Identifier,
Baseaddres: 700H +SID(0-30)
Datalength: 8 Byte
Bit: 7 6 5 4 3 2 1 0
Descriptor Byte1 1 1 1 1 0 0 0 s
Descriptor Byte2 s s s s 0 x 0 0
Descriptor Byte3 0 0 0 0 a 0 0 0
2.2. RXOBJECT
Receive-Object:
11 Bit-Identifier,
Baseaddres: 700H +SID(0-30)
Datalength: 8 Byte
Bit: 7 6 5 4 3 2 1 0
Descriptor Byte1 1 1 1 1 0 0 0 s
Descriptor Byte2 s s s s 0 x 0 0
Descriptor Byte3 0 0 0 0 a 0 0 0
s = Stationnumber, for conditioning unit see „1. Condition Units aT CAN-
Bus“
x = 1/ TXobject
= 0 / RXobject
a = 8 Byte Data
The condition unit has to answer to each message within 4 msec, otherwise the machine will set the
Offline-message.
1 Source Identifier
CAN_Protocol_EN.docx Seite 3 ©Stange/Zochowski
Temperiergerät-Protokoll 1.62 14.06.2022
6 Databyte 2
7 Databyte 3
Response on „Set Data“ (sends the conditioning unit as answer on „Set Data“):
Offset (Byte) Meaning
0 F1H=Acknowledge, F2H=No Acknowledge
1 SID of answering device
2 State CPU (01H=RUN)
3 06H for Set Data
4 not used
5 not used
6 not used
7 not used
Response on “Get Data” (sends the conditioning unit as answer on „Get Data“)
Offset Meaning
0 41H = Answer Get Data
1 Blocknumber
2 Databyte 0
3 Databyte 1
4 Databyte 2
5 Databyte 3
6 Databyte 4
7 Databyte 5
The Command: 06h Set Data is equal to SYS # 160 (Sigmatek- Control)
The Command: 40h Get Data is equal to SYS # 161 (Sigmatek- Control)
The extension of the protocol with the optional parameters ia available on request.
3.1. CONTROLCOMMANDS
ASCII-Code Meaning
A Control with internal Sensor
Attention: send at first the Command ‚K‘
B Control with external Sensor
Attention: send at first the Command ‚K‘
C Standby (Control, Heating and Cooling off, Pump on)
D Stop (all off)
E Cool down to lowering temperature and hold this temperature
F Cool down to lowering temperature and Stop
G Cool down to safety temperature and stop
H Suck with lowering temperature and Stop
I Suck to safety temperature and Stop
J Suck mode (Leak-stop-mode)
K Pump mode (normal mode)
Q Undefinined setting (stay with old setting, no modification)
4. SCREEN-MASK
The Command can be selected under „Mode CU Set“. The response of the condition unit will be shown
under “Mode CU act”.
5. LEGEND
1.62, UEX, 11.May 2012: translated to english
1.62, UEX, 20.October 2008: Enlarged Protocol for actual values
1.61, EZO,15 May 2008: Slight grammatical corrections.
1.6, EZO,19.11.2007: Length bits of the telegram Set DataSet Datamean exactly the length [not
(0..3) -> (1..4)]