Lecture 9 (33-38)
Lecture 9 (33-38)
33
Design Step 3: Assume that the desired closed loop poles for observer pole locations as
follows: 𝑠1,2 = −4.5
Then, the observer gain matrix is given as (using Ackermann’s Formula):
−1
𝑘𝑒 = [ ]
6.25
Design Step 3: We shall determine the transfer function of the observer controller from the
following equation:
𝑈(𝑠) 𝑛𝑢𝑚
𝐺𝑐 (𝑠) = = = − [𝑪 ̃ )−𝟏 𝑩
̃ (𝒔𝑰 − 𝑨 ̃+𝐷
̃]
−𝑌(𝑠) 𝑑𝑒𝑛
Therefore;
1.2109𝑠 2 + 11.2125𝑠 + 25.3125 1.2109(𝑠 + 5.3582)(𝑠 + 3.0012)
𝐺𝑐 (𝑠) = =
𝑠 2 + 6𝑠 + 2.1406 (𝑠 + 5.619)(𝑠 + 0.381)
As seen, the poles of the controller are located at lift hand side of s-plane; it means the
transfer function of the designed controller is stable.
35
Figure 14 Unit step input of the controlled system
The Simulink tools of MATLAB program has been used to plot figure 14 and 15 as shown in
Figure 16 below:
Figure 16
36
Configuration 2: A different configuration of the control system is shown in Figure 17. The
observer controller is placed in the feedback path. The input r is introduced into the closed-
loop system through the box with gain N. From this block diagram, the closed-loop transfer
function is obtained as
Figure 19
38