This document provides information on the SmartOne Addressable Signal Module, which connects to the signaling line circuit of compatible fire alarm control panels. It can be programmed in the field to support either 24VDC notification appliances or 25Vrms speakers with Class A or B wiring. The module supervises its own components and circuits and can be configured and addressed using a handheld programmer or control panel interface. It is compatible with several Kidde fire alarm control units with the appropriate firmware.

Uploaded by

Liana Than
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
455 views1 page

Kidde SmartOne Addressable Signal Module ASM K-76-234

This document provides information on the SmartOne Addressable Signal Module, which connects to the signaling line circuit of compatible fire alarm control panels. It can be programmed in the field to support either 24VDC notification appliances or 25Vrms speakers with Class A or B wiring. The module supervises its own components and circuits and can be configured and addressed using a handheld programmer or control panel interface. It is compatible with several Kidde fire alarm control units with the appropriate firmware.

Uploaded by

Liana Than
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SmartOne®

Addressable Signal Module

K-76-234 Effective: August 2022

FEATURES MAXIMUM LINE RESISTANCE (#12 AWG WIRE)


• Full digital communications Load (amps) Resistance (ohms) Length (ft.)
• Addressable notification appliance circuit (NAC) 0.2 20.0 12.0K
• Class A or Class B wiring on NAC 0.5 8.0 5.0K
• Field-programmable for 24VDC notification
1.0 4.0 2.5K
appliances or 25 Vrms speakers
1.5 2.7 1.6K
• Supervises power for notification appliances
2.0 2.0 1.2K
• For use with Kidde® intelligent control units
operating SmartOne® communications protocol * SPECIFICATIONS
• UL Listed Mounting:
• FM Approved • A 4-inch, 2-1/8-inch deep (for #18 AWG) or 4-11/16-inch, 2-1/8-inch
• CSFM Approved deep (for #12 AWG) standard, square electrical box can be used.
Wiring specifications are recommended as minimums for ease of
* PEGAsys™, PEGAsys LV, FENWALNET™ 2000 and FENWALNET 2000 LT
wiring. See National Electrical Code (370).
control units may require a firmware upgrade before ASMs can be installed.
Shipping Weight: 10.5oz (298g)
Current Draw: 500 μA in standby or alarm
DESCRIPTION
Operating Voltage Range: 18.5 to 27.5 VDC
The SmartOne Addressable Output Circuit Rating:
Signal Module (ASM), P/N • 2 A max. @ 24 VDC regulated
70-200200-003, is a notifica-
• 20 W max. @ 25.0 Vrms
tion appliance circuit that con-
nects to the Signaling Line Output Circuit limited to 1.6A at operating
Circuit of a compatible control temperature ≥ 113 ºF (45ºC)
unit. The ASM is an intelligent WARNING
field device that contains its Failure to adhere to this specification may result in limited output
own microprocessor, memory circuit performance: Notification Appliance(s) may not sound
and the necessary electronics continuously.
to provide either 24 VDC for conventional notification-appliances or
Notification Appliance Circuit End Of Line Resistor:
25 Vrms for speakers. Operation can be changed on-site using on- • 4.7K ohms, 0.5 W
board switches and jumpers. Notification Appliance Circuit Output
PROGRAMMING • 24 VDC, 2 A (max.), power limited, reverse polarity supervised
Each ASM can be configured to support speakers or audible-visual Audio Circuit Output
• 25 Vrms, 20 W (max), non-power limited, reverse polarity supervised
notification appliances, and Class B or Class A operation. The mod-
ule can also be programmed to support water flow, walk test, and Power Supply Trouble Circuit End Of Line Resistor: 4.7K, 0.5 W
drill modes. As with other SmartOne devices, addressing can be Operating Temperature Range: -13° F to 151° F, (-25° C to 66°C)
Operating Humidity Range: 0 to 95%, non-condensing
imple-mented from the SmartOne Hand-Held Programmer or from
the con-trol unit keypad/menu. The ASM can also be alarm COMPATIBLE CONTROL UNITS
tested upon command from the control unit. Module faults are
individually reported to compatible control units by module Fire Alarm Control Current Legacy
address, fault type, and fault-location message. A status LED is Unit (FACU) Type Product Product
mounted on the unit.
Single Loop ARIES®-SLX ARIES
SUPERVISION
FenwalNET™ 6000
The module provides continuous internal supervision of:
PEGAsys™ **
• Alarm contact position FenwalNET 2000 **
• Communications with the control unit
• Internal power supply Multiple Loop ARIES®-MLX ARIES NETLink
• Connections to external power supply for notification appliances FenwalNET 8000-ML
• Memory status module supervision prevents switching audible PEGAsys **
or audio power into a shorted circuit. FenwalNET 2000 **

Kidde, SmartOne and ARIES are registered trademarks of Kidde-Fenwal, Inc., or its ** FACUs running sotware revision 82.4 are compatibility-tested but not agency
parents, subsidiaries or affiliates. listed with the device(s) in this data sheet.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. believes this data to be accurate, but it is published and presented without any
guarantee or warranty whatsoever. KIDDE-FENWAL, INC. assumes no responsibility for the product's suitability for a particular application. The fire suppression system
design, installation, maintenance, service and troubleshooting must be performed by trained, authorized Kidde Fire Systems distributors for the product to work correctly.
If you need more information on this product, or if you have a particular problem or question, contact:
KIDDE-FENWAL, INC., Ashland, MA 01721 USA, Telephone: (508) 881-2000.
Kidde Fire Systems
EXPORT INFORMATION (USA)
400 Main Street