Files
Files
OsiSense XCC
PROFIBUS-DP Multi-Turn Absolute
Encoder
User’s Manual
Version
04/2011
1690024 02A55 02
www.schneider-electric.com
© 2011 Schneider Electric. All rights reserved.
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
General Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Chapter 2 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Connection Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Wiring the Bus and the Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Wiring the Encoder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Installation Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Chapter 3 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Encoder Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Chapter 4 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Encoder Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Software Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
SyCon Configuration Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Chapter 5 Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Description of the Encoder Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Description of Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Data Exchange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Commissioning Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Chapter 6 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Diagnostic Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Status Indication Provided by the LEDs in the Base . . . . . . . . . . . . . . . . . 57
FAQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with
the device before trying to install, operate, or maintain it. The following special
messages may appear throughout this documentation or on the equipment to warn
of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
At a Glance
Document Scope
This manual explains how to install and configure the absolute rotary encoder with
PROFIBUS-DP interface connected on a bus.
Related Documents
You can download these technical publications and other technical information from
our website at www.schneider-electric.com.
User Comments
We welcome your comments about this document. You can reach us by e-mail at
[email protected].
Introduction
1
Overview
The purpose of this section is to provide general information about the encoder
described in this documentation.
References of the PROFIBUS-DP encoders:
Description Reference
PROFIBUS-DP encoder with a solid shaft XCC 3510PV84FBN
PROFIBUS-DP encoder with a hollow shaft XCC 3515CV84FBN
Introduction
Principle
This manual explains how to install and configure the absolute rotary encoder with
PROFIBUS-DP interface.
The encoder casing provides access to two rotary switches for configuring the
address. It also incorporates two LEDs that assist diagnostics. The encoder acts as
a T with two PG9s for the Bus In and Bus Out signals.
The encoders comply with international standards IEC61158 and IEC61784 for
PROFIBUS-DP communication and the PROFIBUS-DP standard EN50170 CLASS
2 according to encoder profile 3.062 version 1.1 for the encoder application. They
are certified by the PNO organization and satisfy Schneider-Electric’s interopera-
bility standards.
The encoder configuration GSD file can be downloaded from "www.schneider-
electric.com".
General Presentation
Description
The absolute rotary encoder with PROFIBUS-DP interface looks like this:
Encoder elements:
No. Description
1 Encoder body
2 Connection base
The encoder body connects to the base via a 15-pin SUB-D connector.
Networking
The absolute rotary encoder interface is based on the PROFIBUS-DP standard
(standard EN 50170). In order to be able to use the encoder as a slave with the
PROFIBUS-DP interface, an interface card is required in the control system which
acts as a PROFIBUS master.
The power to the encoders is supplied directly via the central PG9 of each encoder.
Bus Architecture
The maximum number of stations on PROFIBUS is 126. The encoder can be
addressed from 0 to 99.
The maximum number of nodes per segment (including repeaters) is 32 (a bus is
divided into segments via repeaters).
Between 2 nodes, there are 4 repeaters maximum.
The available transmission speeds are: 9.6, 19.2, 45.45, 93.75, 187.5, 500, 1500,
3000, 6000, 12000 kBaud
CAUTION
UNINTENDED EQUIPMENT OPERATION
Warranty invalidated if dismantled.
Handle with care.
In environments subject to interference, it is advisable to connect the encoder
to ground, using one of the fixing screws.
Failure to follow these instructions can result in injury or equipment damage.
Installation
2
Overview
The absolute encoder is connected to a connection base by means of a 15-pin SUB-
D connector. The base can be removed from the encoder (encoder without supply)
by undoing two screws located on the side of the base. The bus and the electrical
supply are routed into the base with PG9 cable glands and are connected to the
terminal blocks.
Connection Base
Description
Unscrew the encoder base to access the encoder settings:
DANGER
RISK OF ELECTROCUTION
Switch off the power supply before working on this device.
Check that the rotating machine is immobilized before working on this device.
Close the cover correctly after configuration or wiring the microswitch.
Failure to follow these instructions will result in death or serious injury.
Encoder Address
The rotary switches located in the base are used to set the encoder network address
(node):
The switch marked (x1) is used to set the units and the switch marked (x10) is used
to set the tens. The possible addresses are between 0 and 99, and any one address
can only be used once in the network. The change of address is taken into account
after a restart.
Line Terminator
If the encoder is connected at one end of the bus line, the line terminator must be
enabled (set the switch to the "ON" position).
NOTE: If the terminator is set to "ON", the "Bus Out" terminals shall be disconnected
(see Wiring the Bus and the Power Supply, page 18).
The base must be connected to the encoder for the bus to be wired correctly. If it is
necessary to change the encoder during operation, a separate line terminator must
be used.
Description
With the power off, remove the base to access the encoder wiring:
The electrical supply must be connected to the "Bus In" terminal block.
NOTE: If the terminator is set to "ON", the "Bus Out" terminals are disconnected.
DANGER
RISK OF ELECTROCUTION
Switch off the power supply before working on this device.
Check that the rotating machine is immobilized before working on this device.
Close the cover correctly after configuration or wiring the microswitch.
Failure to follow these instructions will result in death or serious injury.
Step Action
1 Remove the screw, the seal gasket and the cable gland collar.
2 Prepare the cable as shown in the diagram below.
3 Place the screw and the seal gasket on the cable.
4 Fit the collar under the shielding.
5 Insert the cable assembly in the cable gland and tighten the screw.
Wiring diagram:
NOTE: Shielded cables should be used for data transmission to avoid problems with
electromagnetic interference. The shielding should be connected to ground at both
ends of the cable.
NOTE: If the cable linking two encoders transmits data as well as the power supply,
use a cable consisting of two twisted pairs that are shielded separately.
Accessories
List of accessories
The list of available accessories is as follows:
Description Type
Reducing ring * 0.59 in to 0.55 in XCC R358RDL14
Reducing ring * 0.59 in to 0.47 in XCC R358RDL12
Reducing ring * 0.59 in to 0.39 in XCC R358RDL10
Reducing ring * 0.59 in to 0.31 in XCC R358RDL08
Reducing ring * 0.59 in to 0.24 in XCC R358RDL06
Assembly instructions
Encoder with output shaft:
Connect the encoder shaft to the revolving shaft using an XCC RA coupling.
Encoder with hollow shaft:
Position the encoder, fix it on the revolving shaft using the loop clamp, with or
without the reducing ring. Then attach the flexible kit to a fixed support.
Do not tighten the fixing ring if the driving shaft and the bushing are missing from the
encoder.
Installation Precautions
Precautions
Follow the instructions below:
Do not knock over the encoder and do not expose it to excessive vibration. The
encoder is a precision device.
Do not open the encoder casing (this does not mean that the connection base
cannot be removed).
The encoder shaft must be connected to the shaft to be measured by means of
an appropriate coupling. This coupling is used to dampen vibrations and
compensate for any imbalance at the encoder shaft, and also to prevent any
significant unauthorized force. Schneider-Electric offers appropriate couplings.
Schneider-Electric absolute encoders are robust, but when used in difficult
environmental conditions they must still be protected appropriately. The encoder
must not be used as a handle or a step.
Only qualified personnel can commission and operate these encoders. Such
personnel are authorized to commission, connect to ground and identify the
devices, systems and circuits in compliance with current safety standards.
No electrical modifications should be made to the encoder.
Route the connection cable from the bus to the encoder, ensuring it is a sufficient
distance or completely separate from the power supply cables and associated
electromagnetic interference. Use fully shielded cables to obtain reliable data
transfer and ensure correct grounding.
In environments subject to interference, it is advisable to ground the encoder.
DANGER
RISK OF ELECTROCUTION
Switch off the power supply before working on this device.
Check that the rotating machine is immobilized before working on this device.
Close the cover correctly after configuration or wiring the microswitch.
Failure to follow these instructions will result in death or serious injury.
WARNING
UNINTENDED EQUIPMENT OPERATION
Check the electrical connections to avoid short-circuits and voltage peaks.
Check the connections before use and when carrying out maintenance
operations.
Comply with the recommendations for use
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
LOSS OF PROTECTION LEVEL IP
Close the cover correctly after configuration or wiring the microswitch.
Failure to follow these instructions can result in equipment damage.
Characteristics
3
Encoder Characteristics
Mechanical Characteristics
The mechanical characteristics are as follows:
Electrical Characteristics
The electrical characteristics are as follows:
Environmental Characteristics
The environmental characteristics are as follows:
Conformity CE
Ambient air Operation -40...+85C (-40...+185F)
temperature
Storage -40...+85C (-40...+185F)
Degree of protection IP 64
Vibration resistance 10 g (f = 10...2000 Hz), acc. to IEC 60068-2-6
Shock resistance 100 g (6 ms, 1/2 sine wave) acc. to IEC 60068-
2-27
Configuration
4
Overview
The purpose of this chapter is to describe the configuration parameters for the
absolute encoder with PROFIBUS-DP interface.
Encoder Configuration
General
The absolute encoder with PROFIBUS-DP interface can be programmed to suit the
user’s requirements. The GSD file corresponding to the encoder must be installed
in the software workshop of the configuration master of the PROFIBUS network
used.
The file contains various configurations.
NOTE: THE 2.2 MULTI-TURN VERSION IS THE ONLY ONE AVAILABLE.
The encoder supports specific functions and the encoder configuration that are
stored in the PROFIBUS master. When the PROFIBUS network starts up
("DDLM_Set_Prm"), they are sent to the slave (encoder). The parameters and the
configuration cannot be modified when the encoder is operating in normal mode
(exception: "Commissioning mode", see Commissioning Mode, page 48).
After receiving the parameter-setting and configuration data, the absolute encoder
switches to normal operating mode (cyclic data transmission –
"DDLM_Data_Exchange"). In this mode, the process values (example: position
value) are transmitted. The data length and format are determined by the user when
selecting an encoder configuration.
Configuration
Download the GSD file and its 3 associated images from
"www.telemecanique.com":
TELE4711.gsd
TELE4711_R.bmp
TELE4711_S.bmp
TELE4711_D.bmp
Functions
The table below contains the encoder functions:
Data Format
Data exchanged between the master and the encoder:
Software Configuration
Principle
The encoders described in this section are configured using the following software:
Please refer to the software documentation for the minimum PC configuration used.
Presentation
Using this software tool, it is possible to configure the PROFIBUS network and
generate an ASCII file for the Premium PLC.
Step Action
1 To configure the slave, obtain the TELE4711.GSD file and place it in the
appropriate directory:
Example: "C:\Program Files\Schneider
Electric\SyCon\Fieldbus\PROFIBUS\GSD".
Also obtain the 3 associated images and place them in the appropriate directory:
Example: "C:\Program Files\Schneider
Electric\SyCon\Fieldbus\PROFIBUS\BMP".
In this example, a Schneider Premium controller acts as PROFIBUS MASTER
with the TSX PBY 100 PROFIBUS interface.
2 Start SyCon.
3 Select the PROFIBUS fieldbus system.
Step Action
4 Insert the Master:
In the menu, select "Insert/Master" (you should specify where the master should
be inserted).
Select "TSX PBY 100" from the available masters.
Click "Add".
Enter the network address and the designation of the master:
5 Using the rotary switches, adjust the encoder in order to configure the address
(see Encoder Address, page 17).
Step Action
6 Insert the slave (encoder):
In the menu, select "Insert/Slave" (you should specify where the slave should be
inserted).
Select the encoder and click "Add".
Enter the network address (in accordance with the position of the rotary switches)
and also the designation of the encoder.
If the network includes several masters, select the required master for the
encoder. In this example, it is the TSX PBY 100 interface:
Step Action
7 By clicking twice on NODE2, you can configure the encoder.
Slave configuration window:
Click "OK" to confirm the value, then click "OK" again to close the window.
For further information on the encoder parameters, see Functions, page 37.
Step Action
9 In the menu, select "File/Save As…" :
Result
The fieldbus master file is now ready.
The "CNF" file created with the SyCon software should be integrated by the PLC
software in order to be available.
Functions
5
Overview
The purpose of this section is to describe the various parameters that can be
configured in order to customize use of the encoders.
List of Functions
CAUTION
UNINTENDED EQUIPMENT OPERATION
For double-word writing, write words WORD 0 and WORD 1 in the correct order
according to the PLC used.
Failure to follow these instructions can result in injury or equipment damage.
Description of Functions
Note
Check the difference in the function numbers given by the PROFIBUS-DP standard
and the SyCon software. The configurable function numbers in SyCon run from 1 to
31 whereas they run from 9 to 39 in the PROFIBUS-DP standard (function number
1 in SyCon = function number 9 for PROFIBUS-DP).
Code Sequence
The "Code sequence" parameter defines the counting direction for the position
value. The code is incremented when the shaft turns in a clockwise (CW) or counter-
clockwise (CCW) direction (as seen from the shaft). The code sequence is defined
in bit 0 of byte 9:
Classe 2 functionnality
Allows Class 2 encoders to be used as Class 1 encoders. The scaling parameters
are deactivated. To use Class 2 functionality, bit 1 of byte 9 must be activated.
Commissioning diagnostics
This function is not implemented.
The user only needs to monitor this point if the parameters are entered "manually"
(using hexadecimal code directly).
Byte 10 11 12 13
Bit 31-24 23-16 15-8 7-0
Data 2 31
... 2 24
2 23
... 2 16
2 15
... 2 8
27 ... 20
Function Desired measuring units
The basis for the desired measuring units is specified with the "Basis for desired
measuring units" parameter (see Basis for desired measuring units, page 42). If "Per
revolution" is selected, the measuring range can be adapted with the "Total
measuring range" parameter. Follow the rules specified for the Total measuring
range, page 41.
Note: Many software tools require the value to be divided into least significant and
most significant words.
Byte 14 15 16 17
Bit 31-24 23-16 15-8 7-0
Data 2 31
... 2 24
2 23
... 2 16
2 15
... 2 8
27 ... 20
Function Total measuring range
The "Total measuring range" parameter is used to adapt the encoder measuring
range to the actual measuring range of the application. The encoder counts until the
position value has reached the programmed total resolution and starts again from 0
(loopback).
Many software tools require the value to be divided into least significant and most
significant words. In total resolution, the following rule must be adhered to:
Desired measuring units per revolution: The position value is incremented by the
number of programmed steps (desired measuring units) during a revolution. The
"Total resolution" parameter is used to adapt the measuring range (see Total
measuring range, page 41).
Desired measuring units per maximum total measuring range: The "Desired
measuring units" parameter refers to the complete measuring range of the encoder:
the encoder indicates the programmed number of measuring units for the whole
measuring range (4096 revolutions with the multi-turn encoder).
Desired measuring units per physical impulse: The measuring units refer to the
physical impulses specified in bytes 35-39 (see Physical impulses, page 45). The
physical impulses correspond to the actual value read internally from the encoder
disk (for example: 8192 points per revolution).
With this option, it is possible to set the reduction factors without restriction:
Shorter diagnostics
Some PROFIBUS masters encounter problems with the length of the full diagnostic
data (57 bytes). The Telemecanique encoder offers an option which allows the
length of this data to be reduced to 16 bytes. In Class 1, the standard diagnostic data
length is 16 bytes.
Byte 27 28 29 30
Bit 31-24 23-16 15-8 7-0
Data 2 31
... 2 24
2 23
... 2 16
2 15
... 2 8
27 ... 20
Function Lower limit switch
(in measuring steps, compared to the scaling value)
Byte 31 32 33 34
Bit 31-24 23-16 15-8 7-0
Data 231 ... 224 223 ... 216 215 ... 28 27 ... 20
Function Upper limit switch
(in measuring steps, compared to the scaling value)
Activation of Bytes 27 to 39
Bit 7 of byte 26 is used to activate other parameter bytes (27-39)
Physical impulses
Byte 35 36 37 38
Bit 31-24 23-16 15-8 7-0
Data 231 ... 224 223 ... 216 215 ... 28 27 ... 20
Function Physical impulses
This parameter is assessed if the basis for the "Desired measuring units" is
expressed in "Physical impulses" (see Basis for desired measuring units, page 42).
Encoder type
The encoder type (Single-turn or Multi-turn) is specified in bit 1 of byte 39:
Data Exchange
ID F1 Hex D0 Hex
Encoder Status Position value Speed
-> Master 31 25
2 -2 224 223 - 216 215 - 28 27 - 20 215 - 28 27 - 20
Master -> Status Preset value
Encoder 31 25
2 -2 224 223 - 216 215 - 28 27 - 20
Commissioning Mode
Commissioning
If commissioning mode is activated in the encoder parameters, the scale factor can
be determined directly in the machine with a "Teach-In" procedure. Commissioning
mode is indicated by the green LED flashing and bit 26 in the input word (bit 26 set
to 0).
If the encoder starts in commissioning mode, the parameters specified in the system
configuration (code sequence, scaling) are ignored. The parameters used are
stored in an internal EEPROM memory. If the code sequence or the scale factor are
modified in commissioning mode, the new values are stored in a non-volatile
memory and the encoder uses these new parameters.
To switch to commissioning mode, proceed as follows:
Step Action
1 Install the encoder in the machine/system.
2 Activate commissioning mode (parameter settings, seeCommissioning, page 48
3 Change the counting direction (if necessary).
4 Place the machine/system in the startup position.
5 Send the encoder the "Teach-In-Start" command.
6 Place the machine/system in the stop position.
7 Indicate the desired number of steps to the encoder with the "Teach-In-Stop"
command.
8 Define the preset value.
9 Assign the values determined with the "Teach-In" procedure to the system
configuration parameters.
10 Deactivate commissioning mode (parameter setting).
Note: The scale factor is set to 1; the zero point offset is set to zero.
To replace the encoder at a later date without using a new "Teach-In" procedure, the
total measuring range determined with the "Teach-In" procedure must be
transferred to the system configuration. For this, "Total resolution" must be specified
in the "Desired measuring units" parameter field (see Desired measuring units,
page 41) and the basis (see Basis for desired measuring units, page 42) must be
set to "Maximum total measuring range". When setting the parameters, check the
Code sequence (the counting direction set in commissioning mode must be
transferred to the system configuration). Commissioning mode can then be
deactivated and the encoder can be used in normal mode.
"Preset" Values
Using the preset function, it is possible to adapt the encoder zero point according to
the application zero point. With this function, the current encoder position value is
set to the desired preset value. The integrated microcontroller calculates the internal
zero point offset. This value is stored in a non-volatile EEPROM memory (this
operation takes less than 40 ms).
The preset value is activated if bit 31 of the double output (peripheral) word is set to
1 (rising edge). As the preset function is used after receipt of the scaling parameters,
the preset value corresponds to the scaling position value.
When bit 31 of the input double word is set to 1, an acknowledgement is sent.
Diagnostics
6
Overview
This chapter describes the various diagnostic messages that can be generated by
the encoder.
Diagnostic Messages
Principle
At the master’s request, the encoder sends diagnostic data ("DDLM_Slave_Diag").
The length of this data is 57 bytes (Exception: diagnostics, Shorter diagnostics,
page 44). The format of the diagnostic data depends on the PROFIBUS standard
(bytes 1-6) and the Encoder profiles (beginning with byte 7).
Diagnostic Function
The table below gives the list of encoder diagnostic functions:
Memory Error
Bit 4 of diagnostic byte 8 indicates a memory error.
We talk about a memory error when the encoder internal EEPROM memory no
longer works correctly and it is not possible to guarantee that the values (the offset
values for example) have been stored in non-volatile memory.
Bit Definition 0 1
4 Memory error (EEPROM default) No Yes
Operating Status
Diagnostic byte 9 contains the parameters set in the system configuration.
Bit Definition 0 1
0 Direction of rotation CW CCW
1 Class 2 functionality Inactive Active
2 Diagnostic routine Inactive Active
3 Scaling function Inactive Active
Encoder Type
Diagnostic byte 10 specifies the encoder version (Single-turn or Multi-turn).
Byte 10 Definition
0 Single-turn encoder
1 Multi-turn encoder
Single-turn Resolution
Diagnostic bytes 11-14 specify the actual resolution (physical) per encoder
revolution.
Number of Revolutions
Diagnostic bytes 15 and 16 specify the actual number (physical) of revolutions
completed by the encoder. The multi-turn version goes from 1 to 4096 revolutions
maximum.
Profile Version
Diagnostic bytes 24 and 25 indicate the encoder profile version.
Byte 24 25
Bit 15-8 7-0
Data 2 7
-2 0
27-20
Revision no. Index
Software Version
Diagnostic bytes 26 and 27 indicate the encoder software version.
Byte 26 27
Bit 15-8 7-0
Data 27-20 27-20
Revision no. Index
Operating Time
The encoder operating time is indicated in diagnostic bytes 28 to 31. If the encoder
is supplied with power, the operating time is saved to the EEPROM memory every
six minutes in steps of 0.1 hour.
Zero Offset
The zero offset is indicated in diagnostic bytes 32 to 35.
Programmed Resolution
The programmed resolution per revolution is indicated in diagnostic bytes 40 to 43.
The value is only valid if the scale factor is based on the "Step per revolution"
parameter (see Basis for desired measuring units, page 42).
Serial Number
Diagnostic bytes 48-57 are reserved for the serial number.
Note: With the current version, the serial number is not saved in the encoder, so the
bytes contain the default hexadecimal value 2A.
Principle
Two LEDs are located on the base. They indicate the status of the encoder in the
PROFIBUS network.
The red LED indicates errors. The green LED indicates the encoder status.
These two LEDs can be either off, on or flashing. Seven of the nine possible
combinations indicate a special condition.
In the event of problems on system startup, the LED status can provide invaluable
information on the cause of the error.
Description
LED on the base:
No. Description
1 RED LED
2 GREEN LED
FAQ
Glossary
Address
Number, assigned to each node, irrespective of whether it is a master or slave. The
address (non-volatile) is configured in the base with rotary switches.
ARE
Abbreviation: absolute rotary encoder
Baud rate
Data transmission speed specified in the form of a number of bits transferred per
second (baud rate = data rate).
Bus node
Device that can send and/or receive or amplify data by means of the bus.
Byte
8-bit unit of data = 1 byte
Configuration
When the master configures the slave, the properties of the latter are specified (for
example: number of input and output bytes).
DDLM
Direct Data Link Mapper: interface between the PROFIBUS-DP functions and the
encoder software.
DDLM_Data_Exchange
Bus operating status, for standard data transfers.
DDLM_Set_Prm
Bus operating status, the configuration and parameters are transmitted.
DDLM_Slave_Diag
Operating status, the diagnostic data are requested from the slave (for example:
encoder).
Diagnostics
Identification, location, classification, display, additional evaluation of errors and
messages.
DP
Distributed Peripherals
FAQ
Frequently Asked Questions
Freeze
Command from the master sent to the slave that can be used to freeze the state of
the inputs. The input data is only updated after receipt of the UNFREEZE command.
GSD file
Standardized file containing the description of the parameters and the
communication methods of the associated device.
Master
"Active" device within the network, that can send data without having received a
request. Monitors data exchanges.
PNO
PROFIBUS Nutzerorganisation
PROFIBUS
Process fieldbus, European standard for fieldbuses defined in the PROFIBUS
standard (EN 50170). Specifies the mechanical, electrical and functional character-
istics of a fieldbus system.
Slave
Bus node that sends data at the request of the master. Absolute rotary encoders are
always slaves.
SyCon
Software tool with a uniform interface under Windows. Description files (GSD, EDS,
etc.) are used as basic information by the software.
Word
Expression used for a unit of data consisting of two bytes.
Index
B
AC
Symbols Description of the Encoder Profile, 38
Desired measuring units, 41
"Preset" Values, 50
Diagnostic Function, 54
Diagnostic Messages, 54
A
Accessoires, 21 E
Activate commissioning mode, 43
Electrical Characteristics, 25
Activation of Bytes 27 to 39, 45
Encoder Address, 17
Activation of Manufacturer-Specific Parame-
Encoder type, 46
ters, 40
Encoder Type, 55
Assembly instructions, 21
Environmental Characteristics, 25
Extended Diagnostic Header, 54
B
Basis for desired measuring units, 42 F
FAQ, 59
C
Class 2 functionality, 40 L
Code Sequence , 40
Line Terminator, 17
Commissioning, 48
List of accessories, 21
Commissioning diagnostics, 40
Commissioning Mode, 48
Connecting the Connection Base, 20 M
Connection Base, 16
Mechanical Characteristics, 25
Memory Error, 55
D
Data Exchange, 47 N
Description, 16
Number of Revolutions, 55
Description of Functions, 40
O
Operating Status, 55
Operating Time, 56
Operating Time Alarm, 55
P
Physical impulses, 45
Profile Version, 56
Programmed Resolution, 56
S
Scaling function control, 40
Serial Number, 56
Setting the Counting Direction, 49
Shorter diagnostics, 44
Single-turn Resolution, 55
Software Limit Switch, 44
Software Version, 56
Starting the "Teach-In" Procedure, 49
Status Indication Provided by the LEDs in
the Base, 57
Stopping the "Teach-In" Procedure, 50
T
Total measuring range, 41
Total Programmed Resolution, 56
V
Velocity output unit, 46
W
Wiring the Bus and the Power Supply, 18
Wiring the Encoder, 20
Z
Zero Offset, 56