Manufacturing Data Sheet: High Voltage XLPE Cable

Design Code : MVIS16AXSFYL003C400SA001S


Date : Rev No. :

S.No Particulars 3 X 400 MM²

1 Name of Manufacturer Polycab Wires Pvt. Ltd


2 Type of Cable A2XFY
3 Voltage Grade kV 33/33
4 No of cores X size in sqmm 3 X 400
Maximum conductor temperature under
5 a) 90°C
normal operating conditions
Maximum conductor temperature at the
b) 250°C
termination of short circuit
6 a) Permissible Voltage Variation ± 10%
b) Permissible Frequency Variation ± 5%

c) Combined Voltage & Frequency variation ± 10%

7 Conductor
H4 Grade Aluminium as per Class 2 of IS:
a) Material
8130/84,latest
Maximum d.c. resistance of conductor at 20°
b) 0.0778
C (ohm/km)
c) Shape Stranded Compact Circular
8 Conductor Screening
a) Material Extruded Semi-conducting Compound
b) Nominal thickness (mm) 0.3
9 Insulation
a) Material XLPE as per IS 7098(Pt-2)
b) Nominal thickness (mm) 9.5
c) Core Identification By coloured strips (Red, Yellow & Blue)
10 Insulation Screening
(i) Non - Metallic
a) Material Extruded Semi-conducting Compound
b) Nominal thickness (mm) 0.3
(ii) Metallic
a) Material Single layer of copper tape
11 Inner Sheath
S.No Particulars 3 X 400 MM²

a) Material Extruded PVC Type ST2 to IS:5831/84


b) Minimum thickness (mm) 0.7
12 Armouring
a) Material Gal.Steel
b) Type of armouring Flat Strip
c) Nominal size of armour (mm) ± 10% 4.0 x 0.8
13 Outer Sheath
a) Material Extruded FR-LSH PVC Type ST2 to IS:5831/84
b) Thickness (mm) 3.00 (Min.)
c) Outer Sheath Colour Black
FR-LSH PROPERTIES
a) Oxygen Index Min. 29% as per ASTM D- 2863
b) Temperature Index Min. 250 Deg.C as per ASTM D- 2863
c) Smoke Density Rating Max. 60% as per ASTM D- 2843
d) Acid Gas Generation Max. 20% as per IEC- 754- 1
14 Electrical Parameters
Max. a.c. resistance of conductor at 90° C
a) 0.102
(ohm/km)
b) Approx. Cable Capacitance (mfd/km) 0.22
c) Approx. Cable reactance (ohm/km) 0.103
d) Impedance of cable (ohm/km) 0.145
e) Test voltage for 5 minutes (kV) 82.5 kV(rms) for 5 Minute
15 Continuous Current carrying capacities :-
(a) In Ground at 30°C (A) 400
(b) In Air at 40°C (A) 519
Short Circuit rating of conductor for the
16 37.79
duration of 1 sec (kA)
IS 8130/84,Generally as per IS 7098 Part 2, IS
17 Standard to which the cables confirm 5831/84, IS 3975/88 etc. with latest up to date
amendments
18 Nominal Overall diameter (mm) 105 ± 3 mm
Standard Drum Length with ± 5% tolerance
19 500 ± 5%
(m)
20 Non-Standard Drum Length mtrs Max. 5% Order Quantity
YEAR POLYCAB ELECTRIC 33/33 KV (UE) GRADE
XLPE FR-LSH, CABLE SIZE, CABLE TYPE WITH
22 Printing
SEQUENTIAL MARKING at every one meter
interval.
Note:-The values given above are subject to tolerances as per the relevant standards.