P635IC
P935IC
35kV Deadbreak Insulating Cap
Product Data Sheet
The Richards 35kV Deadbreak Insulating
Cap provides a means to insulate 600 or
900A 35kV Deadbreak interfaces (IEEE
386, Interface 13). The Deadbreak Cap is
often utilized to insulate unused positions
on Deadbreak Junctions or to insulate an
R-Stack, Connecting Plug or Apparatus
Bushing interface.
The Deadbreak Insulating Cap is molded
with an integral threaded stud and
supplied with a factory installed 48" #12
AWG tinned copper ground wire.
Basic Dimensions
Features
6.96in
<<100% EPDM Composition (176.66mm)
<<Injection Molded & Peroxide-Cured 2.34in
(59.36mm)
<<Made in the USA
<<Fully-Shielded/Deadfront
<<Submersible
3.23in 4.39in
(82.04mm) (111.39mm)
Richards Manufacturing, Inc. | 517 Lyons Avenue, Irvington, NJ 07111 | 973.371.1771 | www.richards-mfg.com 0618
P635IC
P935IC
35kV Deadbreak Insulating Cap
Detail View
Installation
Stainless
35kV Deadbreak Insulating Cap installation is covered by: Steel Bail
RP-II-IC
Stack Height
Related Products 2.34in
(59.44mm)
P635HIP-STUD P935HIP-STUD
35kV Aluminum Threaded 35kV Copper Threaded
Stud Stud
P635HIP P935HIP
35kV Aluminum Insulating 35kV Copper Insulating
Plug Plug 5/8-11 UNC-2A
P635CPR P935CPR Threaded Stud
35kV 600A Deadbreak 35kV 900A Deadbreak
Connecting Plug Connecting Plug
P635AB P935AB
35kV 600A Deadbreak 35kV 900A Deadbreak
Apparatus Bushings Apparatus Bushings
Accepts
IEEE 386
Interface 13
(35kV Class
Interface) 48" #12 AWG
Ground Wire
Production Testing
Product Ratings
IEEE requires a Partial Discharge test and choice between AC
withstand and Impulse.
Richards runs 3/3 tests on all Medium Voltage products governed Voltage Ratings
by IEEE 386. Maximum Voltage Rating – (phase to ground) 21.1kV
Corona Voltage Level – (partial discharge extinction voltage) 26kV
100% Routine Electrical Test:
AC Withstand – (1 minute) 50kV
<<Partial Discharge
Impulse-Withstand Voltage – (BIL) 162kV BIL
<<AC Withstand
<<Impulse Withstand Continuous Current Ratings
Aluminum 600A
Copper 900A
Short-Time Current Ratings
Aluminum 40kA, 10c. and 10kA, 3s.
Copper 40kA, 10c. and 10kA, 3s.
The 35kV Deadbreak Insulating Cap is qualified to the following industry standards:
<<IEEE Std 386: For Separable Insulated Connector Systems
<<ANSI C119.4: For Electric Connectors
<<IEEE Std 592: For Exposed Semiconducting Shields
Exceeds IEEE 386 requirement
Richards Manufacturing, Inc. | 517 Lyons Avenue, Irvington, NJ 07111 | 973.371.1771 | www.richards-mfg.com 0618