Wh07-Cctv-Ups-Xx0001 - 001001 Rev-00

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

GENERAL NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE


SPECIFIED.
2. POWER SUPPLY SECURITY SYSTEM TO BE TAKEN FROM
NEAREST POWER SOURCES (UPS) (UN-INTERRUPTED
POWER SUPPLY).
3. MINIMUM SIZE OF PVC / EMT / RGS FLEXIBLE CONDUIT
SHALL BE 3/4 INCH.
4. ALL CABLES AND DEVICES SHALL BE LABELED IN
ACCORDANCE WITH THE RELEVANT EIA/TIA
SPECIFICATIONS.
WAREHOUSE # 7 POWER SOURCE FEEDER BREAKER 5. MAXIMUM 3 DATA CABLE TO BE PULL FROM 3/4" CONDUIT.
6. NETWORK SWITCH SHALL BE PLACED IN IT & FILED
EQUIPMENT CABINET.
7. ALL OUTDOOR UNDER GROUND CABLES SHOULD BE
INSTALLED IN PVC SLEEVES.
CCTV SYSTEM:
30AT/50AF
1. ALL CAMERAS AND ACCESS CONTROL PANEL SHALL BE
3P, MCCB CONNECTED TO POE NETWORK SWITCH.
2. ALL DATA CABLING WILL BE DONE WITH CAT-6 CABLE FOR
POWER LOAD CALCULATION: CCTV AND SEPARATE CABLES TO BE CONSIDER FOR
EQUIPMENT CONNECTION.
3. MAXIMUM DISTANCE OF CAMERA FROM NETWORK SWITCH
SWITCH 1 = 715W SHALL BE MAXIMUM 90 METERS.
4. CCTV IP CAMERA WILL BE POWERED THROUGH IP BASED
SWITCH 2 = 715W POE SWITCH.
3CX 4 Sq.mm+1CX 2 Sq.mm 5. OUTDOOR FIXED CAMERA SHALL BE INSTALLED WITHIN 5
METER FROM THE FLOOR LEVEL.
SWITCH 3 = 715W 6. OUTDOOR RATED CABLE TO BE USED IN OUTDOOR AREA.
7. FIBER OPTIC CABLING TO BE DONE FOR NETWORK
SWITCH 4 = 715W COMMUNICATION.
SECURITY EQUIPMENT ROOM:
1. 2ALL SECURITY EQUIPMENT SHALL BE PLACED IN
EQUIPMENT ROOM.
2. 3 DISPLAY OF VIDEOS AND ALARMS EVENTS SHALL BE
PROVIDED IN GUARD ROOM.
TOTAL LOAD CALCULATION: 4450VA.
SECURITY SYSTEM LEGENDS
PROPOSED UPS 5 KVA IT CABINET
BULLET CAMERA
DOME CAMERA

DOME CAMERA
LOCATION : IT ROOM CAT-6

POWER CABLE

FOC SENSING CABLE

SWITCH (PoE Switch)


UPS-10KVA
NETWORK SWITCH 48P (INDOOR)

CORE SWITCH

FILED CABINET (PoE Switch)

REFERENCE DRAWING:
SL
NO DRAWING NUMBER DESCRIPTION
CAT-6 CABLE CONDUIT EXTERNAL NETWORK
3CX 4 Sq.mm+1CX 2 Sq.mm 1 EX00-CCTV-CN-XX0001 -001005
GENERAL LAYOUT
CAT-6 CABLE CONDUIT EXTERNAL NETWORK
2 EX00-CCTV-CN-XX0002 -001005
GENERAL LAYOUT

3 EX00-CCTV-GN-XX0001 -001005 EXTERNAL NETWORK GENERAL LAYOUT

UPS-DB-01 4 EX00-CCTV-FV-XX0001 -001005 EXTERNAL NETWORK FIELD VIEW LAYOUT

LOCATION : WAREHOUSE # 07 IT ROOM 5 EX00-CCTV-RD-XX0001 -001001 EXTERNAL NETWORK RISER DIAGRAM LAYOUT

ESSENTIAL LOAD 6 EX00-CCTV-TN-XX0001 -001001 EXTERNAL NETWORK TOPOLOGY LAYOUT

7 EX00-CCTV-ED-XX0001 -001001 EXTERNAL ELECTRICAL SINGLE LINE DIAGRAM

Rated Voltage 250V 8 WH07-CCTV-CN-XX0001-001003


WAREHOUSE 07 CCTV - CONDUIT LAYOUT
LOWER LEVEL 0.00 FFL
WAREHOUSE 07 CCTV - CONDUIT LAYOUT
9 WH07-CCTV-CN-XX0002-001003
HIGH LEVEL 2.30 FFL

PDU PDU 10 WH08-CCTV-CN-XX0001-001003 WAREHOUSE 08 CCTV - CONDUIT LAYOUT

11 WH10-CCTV-CN-XX0001-001003 WAREHOUSE 10 CCTV - CONDUIT LAYOUT


8 OUTLET / 15 AMP 8 OUTLET / 15 AMP
U.T.M.

WAREHOUSES GRID
NORTH

LOCATION

15°
PROJECT
NORTH

42 41 40 39 38 37 36 35 34

MA
KK
AH
L
K
J
I
3CX 2.5 Sq.mm 3CX 2.5 Sq.mm 3CX 2.5 Sq.mm 3CX 2.5 Sq.mm H
G
..\..\..\Downloads\DACO-Master-Logo-With-Strapline-RGB.jpg

.\PLC LOGO - FINAL.gif

F
E
D
C
B
ACCESS SWITCH # 4

CORE SWITCH # 1
ACCESS SWITCH # 2

ACCESS SWITCH # 3
KEY PLAN

REVISION:

00 05/05/2022 ISSUED FOR APPROVAL. -

REV. DATE DESCRIPTION OF REVISION APP.

DRAWN BY: DESIGNED BY: REVIEW BY: APPROVED BY: DATE:

AQM AQM SAM/MM AMH 05/05/2022

PROJECT

WALL MOUNT CABINET 42U CABINET CCTV CAMERA FOR


DACO WAREHOUSES
CLIENT:

WAREHOUSE # 7 SECURITY SYSTEM ELECTRICAL INTER CONNECTION DIAGRAM


NTS
CONTRACTOR:

DRAWING TITLE:

WAREHOUSE CCTV ELECTRICAL INTER


CONNECTIVITY DIAGRAM LAYOUT FOR
UPS
PROJECT NUMBER DRAWING NUMBER SHEET REV.
DACP-SS01
001
SCALE (A1) WH07-CCTV-UPS-XX0001 00
N.T.S 001