Product Data Sheet Rosemount 848t High Density Temperature Measurement Family en 73330

Download as pdf or txt
Download as pdf or txt
You are on page 1of 56

Product Data Sheet

00813-0100-4697, Rev SB
December 2021

Rosemount™ 848T High Density Temperature


Measurement Family

■ Innovative temperature measurement for high density applications that provide installation and
operational savings.
■ Independently configurable inputs that support RTD, thermocouple, ohm, mV, 0–10 volt, and 4–20 mA
signals.
■ Enclosure options and intrinsically safe design allows for installation close to any process, including
hazardous areas.
■ WirelessHART® capabilities extends the full benefits of Plantweb™ to previously inaccessible locations.
■ Industry first measurement validation diagnostic can identify a variety of process concerns including
sensor degradation, sensor wiring connectivity, high vibration (affecting the measurement), and
abnormal process variations.
Rosemount 848T December 2021

High density temperature measurement


Wireless delivers innovative wireless solutions for temperature
■ Self-organizing network delivers information rich data with
greater than 99 percent data reliability and establishes a
highly stable network.
■ IEC-approved WirelessHART protocol.
■ Emerson SmartPower™ Solutions provide an intrinsically safe
power module, allowing field replacements without
removing the transmitter from the process, keeping
personnel safe and reducing maintenance costs.
■ Emerson’s layered approach to wireless network security
ensures data transmissions are secure.

Contents
High density temperature measurement...........................................................................................................................................2

Rosemount 848T FOUNDATION Fieldbus Temperature Transmitter.................................................................................................... 6

Specifications for Rosemount 848T FOUNDATION Fieldbus............................................................................................................... 11
Product certifications...................................................................................................................................................................... 17
Dimensional drawings for Rosemount 848T FOUNDATION Fieldbus....................................................................................................29
Rosemount 848T Wireless Temperature Transmitter...................................................................................................................... 37
Specifications for Rosemount 848T Wireless................................................................................................................................... 42
Product certifications...................................................................................................................................................................... 49
Dimensional drawings for Rosemount 848T Wireless...................................................................................................................... 53

2 Emerson.com/Rosemount
December 2021 Rosemount 848T


FOUNDATION Fieldbus provides effective measurements with reduced wiring
costs
■ Internationally recognized digital network (IEC 61158)
supports the connection of up to 16 devices on a single
twisted wire pair.
■ Allows advanced computations through use of function
blocks.
■ Provides continuous measurement status for each
measurement point.
■ Lower costs by reducing wiring, terminations, and required
number of I.S. Barriers.


Explore the benefits of Complete Point Solution from Rosemount
Temperature Measurement
■ Emerson offers a selection of RTDs and thermocouples that
bring superior durability and Rosemount reliability to
temperature sensing.
■ A broad thermowell offering meets the demanding
requirements of a variety of process applications.

Experience global consistency and local support from worldwide Rosemount


Temperature manufacturing site
■ World-class manufacturing provides globally consistent
product from every factory and the capacity to fulfill the
needs of any project.
■ Experienced instrumentation consultants help select the
right products for each temperature application.
■ An extensive global network of Emerson service and support
personnel can be onsite when and where they are needed.

Emerson.com/Rosemount 3
Rosemount 848T December 2021

Increase performance with High Density transmitters


■ Transmit multiple measurements with one set of
electronics.
■ Mount close to process to reduce sensor wire length and
increase measurement reliability.
■ Enhance accuracy with EMI correction, cold junction
compensation, and device diagnostics.
■ Reduce installation costs by as much as 70 percent.

Avoid unnecessary process shutdowns, on-scale failure related issues, and


unsafe process conditions with measurement validation diagnostic
■ Detect measurement abnormalities and take preventive
action before shutdown is necessary.
■ Determine validity of data points that are outside of alarm
limits.
■ Identify on-scale failures and take action before process
efficiency and safety is compromised.
■ Detect abnormally fast process rates of change before alarm
state is reached.

High density temperature measurement


Ideal solution for taking multiple measurements in close
proximity to each other such as:
■ Bearing temperature on pumps and motors
■ Distillation columns
■ Furnaces and boilers
■ Reactors, storage tanks, and many more

Simplify installation and reduce wiring costs


■ Eliminate marshalling
■ Less wire routing and fewer terminations
■ Faster startups with fewer devices

4 Emerson.com/Rosemount
December 2021 Rosemount 848T

Access powerful information with new device dashboards


■ Leverage Human Centered Design practices to create an
intuitive user interface
■ Instantly see status and output of each sensor
■ Direct links to graphical diagnostics and troubleshooting
help
■ Drastically lower configuration time

Access information when you need it with asset tags


Newly shipped devices include a unique QR code asset tag that enables you to access serialized information directly from the
device. With this capability, you can:
■ Access device drawings, diagrams, technical documentation, and troubleshooting information in your MyEmerson account
■ Improve mean time to repair and maintain efficiency
■ Ensure confidence that you have located the correct device
■ Eliminate the time-consuming process of locating and transcribing nameplates to view asset information

Emerson.com/Rosemount 5
Rosemount 848T December 2021

Rosemount 848T FOUNDATION™ Fieldbus Temperature


Transmitter
The Rosemount 848T offers a low cost solution for high density
measurements. The transmitter accepts eight independently
configurable sensor inputs, and can be mounted close to the
process to improve data quality. FOUNDATION Fieldbus
architecture allows up to 128 temperature measurements to be
transmitted on a single H1 Fieldbus line. Additionally, the
transmitter is bus-powered, further reducing the amount of
required wiring to install the device. The robust design has
proven itself in thousands of successful installations.
Capabilities include:
■ Eight independently configurable inputs, including 2- and 3-
wire RTDs, thermocouples, mV, 2- and 3-wire ohms, and 4–
20 mA signals
■ Industry first measurement validation diagnostic
■ Fieldbus functionality with eight AI blocks, two MAI blocks,
four ISEL Blocks, and backup LAS capabilities
■ 600 Vdc isolation and integral transient protection

CONFIGURE > VIEW PRODUCT >

Online product configurator


Many products are configurable online using our Product Configurator. Select the Configure button or visit our website to start.
With this tool's built-in logic and continuous validation, you can configure your products more quickly and accurately.

Model codes
Model codes contain the details related to each product. Exact model codes will vary; an example of a typical model code is shown
in the following figure.
Figure 1: Model Code Example

1. Required model components (choices available on most)


2. Additional options (variety of features and functions that may be added to products)

Specifications and options


See the Specifications and options section for more details on each configuration. Specification and selection of product materials,
options, or components must be made by the purchaser of the equipment. See the Material selection section for more information.

6 Emerson.com/Rosemount
December 2021 Rosemount 848T

Optimizing lead time


The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings
are subject to additional delivery lead time.

Required model components

Model

Code Description
848T High Density Temperature Measurement Family ★

Transmitter output

Code Description
F FOUNDATION™ Fieldbus digital signal (includes AI, MAI, and ISEL function blocks, and Backup Link Active Scheduler) ★

Product certification
Consult factory for availability.

Code Description Rosemount junction box required?


I1 ATEX Intrinsic Safety No ★
I2 INMETRO Intrinsic Safety No ★
I3 NEPSI Intrinsic Safety No ★
I4 TIIS Intrinsically Safety (FISCO) Type 'ia’ No
H4 TIIS Intrinsic Safety (FISCO) Type 'ib’ No
I5(1) FM Intrinsically Safe No ★
I6(1) CSA Intrinsically Safe No ★
I7 IECEx Intrinsic Safety No ★
IA ATEX FISCO Intrinsic Safety No ★
IB INMETRO FISCO Intrinsic Safety No ★
IE FM FISCO Intrinsically Safe No ★
IF(1) CSA FISCO Intrinsically Safe, Division 2 No ★
IG IECEx FISCO (Intrinsic Safety) No ★
IM Technical Regulations Customs Union (EAC) Intrinsic Safety No ★
KG FM, CSA, ATEX, and IECEx Intrinsic Safety No ★
N1 ATEX Type n (enclosure required) Yes ★
N3 China Type n (enclosure required) Yes ★
N5 FM Class I, Division 2, and Dust Ignition proof (enclosure Yes ★
required)

Emerson.com/Rosemount 7
Rosemount 848T December 2021

Code Description Rosemount junction box required?


N6 CSA Class I, Division 2 No ★
N7 IECEx Type n (enclosure required) Yes ★
NC ATEX Type n Component (Ex nA nL) No(2) (3) ★
ND ATEX Dust (enclosure required) Yes ★
NJ IECEx Type n Component (Ex nA nL) No(2) ★
NK FM Class I, Division 2 Yes ★
IM Technical Regulations Customs Union (EAC) Intrinsic Safety No ★
IP Korea Intrinsic Safety No ★
NA No approval No ★
(1) Available only with S001 option.
(2) The Rosemount 848T ordered with component approval is not approved as a stand-alone unit. Additional system certification is required.

Input types

Code Description
S001 RTD, thermocouple, mV, Ohm inputs ★
S002(1) RTDs, thermocouple, mV, Ohm and 4–20 mA inputs ★
(1) S002 is only available with Product Certification N5, N6, N1, NC, NK, and NA.

Additional options

Plantweb™ advanced diagnostics


Code Description
D04 Measurement validation diagnostic ★

Transient protection

Code Description
T1 Integral transient protector ★

Mounting bracket
Code Description
B6 Mounting bracket for 2 in (51 mm) pipe mounting – SST bracket and bolts ★

Enclosure options
Code Description
JA1 Aluminum junction box; no entries ★

8 Emerson.com/Rosemount
December 2021 Rosemount 848T

Code Description
JA2 Aluminum cable glands (9 × M20 nickel-plated brass glands for 7.5–11.9 mm unarmored cable) ★
JA3 Aluminum conduit entries (five plugged holes, suitable for installing ½-in. NPT fittings) ★
JA4 Aluminum with cable glands (9 x ½-in. NPT for 7.5 to 11.9 mm) ★
JA5 Aluminum with conduit entries (nine plugged holes, suitable for installing ½-in. NPT fittings ★
JS1 Stainless steel junction box; no entries ★
JS2 Stainless steel box, cable glands (9 × M20 nickel-plated brass glands for 7.5–11.9 mm unarmored cable) ★
JS3 Stainless steel box, conduit entries (five plugged holes, suitable for installing ½-in. NPT fittings) ★

Software configuration

Code Description
C1 Custom configuration of date, descriptor, message, and wireless parameters (requires CDS with order) ★

Line filter
Code Description
F5 50 Hz line voltage filter ★
F6 60 Hz line voltage filter ★

Calibration certificate
Code Description
Q4 Calibration certificate (3-point calibration) ★

Special temperature test


Code Description
LT Test to -60 °F (-51 °C) ★

Conduit electrical connector

Code Description
GE M12, 4-pin, male connector (eurofast®) ★
GM A size mini, 4-pin, male connector (minifast®) ★

Extended product warranty


Code Description
WR3 3-year limited warranty ★
WR5 5-year limited warranty ★

Emerson.com/Rosemount 9
Rosemount 848T December 2021

Wiring
Figure 2: Rosemount 848T Sensor Wiring Diagram

1 2 3 1 2 3 1 2 3 1 2 3
2-wire RTD and ohms 3-wire RTD and ohms(1) Thermocouples/ohms and 2-wire RTD with compensation
millivolts loop(2)
(1) Emerson provides 4-wire sensors for all single-element RTDs. Use these RTDs in 3-wire configurations by clipping the fourth lead or leaving it
disconnected and insulated with electrical tape.
(2) The transmitter must be configured for a 3-wire RTD in order to recognize an RTD with a compensation loop.

Standard configuration
Unless otherwise specified, the transmitter will be shipped as follows for all eight sensors:

Standard configuration settings


Sensor type(1) Thermocouple Type J
Damping(1) Five seconds
Measurement units(1) °C
Output(1) Linear with temperature
Line voltage filter(1) 60 Hz
Temperature specific blocks Sensor transducer block (1)
FOUNDATION™ Fieldbus function blocks Analog input (8)
Multiple analog input (2)
Input selector (4)
Input transient filter Enabled
(1) For all eight sensors.

10 Emerson.com/Rosemount
December 2021 Rosemount 848T

Specifications for Rosemount 848T FOUNDATION™ Fieldbus


Functional specifications

Inputs
Inputs include:
■ Eight independently configurable channels including combinations of 2- and 3-wire RTDs, thermocouples, mV, 2- and 3-wire
and ohm inputs
■ 4–20 mA inputs using optional connector(s)

Outputs
Outputs consist of Manchester-encoded digital signal that conforms to IEC 61158 and ISA 50.02.

Status
■ 600 Vdc channel to channel isolation(1)
■ 10 Vdc channel to channel isolation for all operating conditions with maximum 500 ft (152 m) of sensor lead length 18 AWG
(0.823 mm²).

Ambient temperature limits


-40 °F (-40 °C) to 185 °F (85 °C)

Accuracy
(Pt 100 at reference condition: 20 °C) ±0.30 °C (±0.54 °F)

Related information
Accuracy — input options

Isolation
■ 600 Vdc channel to channel isolation(2).
■ 10 Vdc channel to channel isolation for all operating conditions with maximum 500 ft (152 m) of sensor lead length 18 AWG
(0.823 mm²).

Power supply
Powered over FOUNDATION Fieldbus with standard fieldbus power supplies. The transmitter operates between 9.0 and 32.0 Vdc, 22
mA maximum. (transmitter power terminals are rated to 42.4 Vdc.)

Transient protection
The transient protector (option code T1) helps to prevent damage to the transmitter from transients induced on the loop wiring by
lightning, welding, heavy electrical equipment, or switch gears. This option is installed at the factory for the Rosemount 848T and is
not intended for field installation.

(1) Reference conditions are -40 °F (-40 °C) to 140 °F (60 °C) with 100 ft (30 m) of sensor lead length 18 AWG (0.823 mm²) wire.
(2) Reference conditions are -40 °F (-40.0 °C)- to 140 °F (60 °C) with 100 ft (30 m) of sensor lead length 18 AWG (0.823 mm²) wire.

Emerson.com/Rosemount 11
Rosemount 848T December 2021

Update time
Approximately 1.5 seconds to read all eight inputs

Humidity limits
0–99 percent non-condensing relative humidity

Turn-on time
Performance within specifications is achieved in less than 30 seconds after power is applied to the transmitter.

Alarms
The AI and ISEL function blocks allow the user to configure the alarms to HI-HI, HI, LO, or LO-LO with a variety of priority levels and
hysteresis settings.

Electromagnetic compatibility (EMC)


Meets all industrial environment requirements of EN61326 and NAMUR NE-21. Maximum deviation < 1 percent span during EMC
disturbance.

Stability
■ ±0.1 percent of reading or 0.18 °F (0.1 °C), whichever is greater, for two years for RTDs.
■ ±0.1 percent of reading or 0.18 °F (0.1 °C), whichever is greater, for one year for thermocouples.

Self calibration
The transmitter’s analog-to-digital circuitry automatically self-calibrates for each temperature update by comparing the dynamic
measurement to extremely stable and accurate internal reference elements.

Vibration effect
Tested to the following with no effect on performance per IEC 60770-1, 1999.

Frequency acceleration
10-60 Hz 0.21 mm peak displacement
60-2000 Hz 3g

Backup Link Active Scheduler (LAS)


The transmitter is classified as a device link master, which means it can function as a LAS if the current link master device fails or is
removed from the segment.
The host or other configuration tool is used to download the schedule for the application to the link master device. In the absence
of a primary link master, the transmitter will claim the LAS and provide permanent control for the H1 segment.

Software upgrade in the field


Software for the Rosemount 848T with FOUNDATION Fieldbus is easy to upgrade in the field using the FOUNDATION Fieldbus Common
Device Software Download procedure.

12 Emerson.com/Rosemount
December 2021 Rosemount 848T

FOUNDATION Fieldbus parameters


Schedule Entries 20
Links 30
Virtual Communications Relationships (VCR) 20

Physical specifications

Conformance to specifications (±3σ [Sigma])


Technology leadership, advanced manufacturing techniques, and statistical process control ensure specification conformance to at
least ±3σ.

Mounting
The transmitter can be mounted directly onto a DIN rail or it can be ordered with an optional junction box. When using the optional
junction box, the transmitter can be mounted onto a panel or a 2 in (51 mm) pipe stand (with option code B6).

Entries for optional junction box


No entry Used for custom fittings.
Cable gland for aluminum junction box (JA4) 9 x ½-in. NPT nickel-plated brass glands for 7.5–11.9 mm unarmored cable
Cable gland for stainless steel junction box (JS2) 9 x M20 nickel-plated brass glands for 7.5–11.9 mm unarmored cable
Conduit Five plugged 0.86-in. diameter holes suitable for installing ½-in. NPT fittings.

Materials of construction for optional junction box


Junction box type Paint
Aluminum Epoxy resin
Stainless steel N/A

Weight
Weight
Assembly
oz lb kg
Rosemount 848T only 7.5 .47 .208
Rosemount 848T aluminum(1) 76 4.75 2.2
Stainless steel(1) 77.0 4.81 2.18
(1) Add 35.2 oz (2.2 lb, 0.998 kg) for nickel-plated brass glands.

Environmental ratings
Type 4X and IP66 with optional junction box.

Emerson.com/Rosemount 13
Rosemount 848T December 2021

Function blocks
Analog Input (AI)
■ Processes the measurement and makes it available on the fieldbus segment.
■ Allows filtering, alarming, and engineering unit changes.

Input Selector (ISEL)


■ Used to select between inputs and generate an output using specific selection strategies such as minimum, maximum,
midpoint, or average temperature.
■ Since the temperature value always contains the measurement status, this block allows the selection to be restricted to the first
“good” measurement.

Multiple Analog Input Block (MAI)


■ The MAI block allows the eight AI blocks to be multiplexed together so they serve as one function block on the H1 segment,
resulting in greater network efficiency.

Accuracy — input options


Table 1: 2- and 3-wire RTDs

Input ranges Accuracy over range(s)


Sensor option Sensor reference
°C °F °C °F
Pt 50 (α = 0.00391) GOST 6651-94 –200 to 550 –328 to 1022 ± 0.57 ± 1.03
Pt 100 (α = 0.00391) GOST 6651-94 –200 to 550 –328 to 1022 ± 0.28 ± 0.50
Pt 100 (α = 0.00385) IEC 751; α = 0.00385, –200 to 850 –328 to 1562 ± 0.30 ± 0.54
1995
Pt 100 (α = 0.003916) JIS 1604, 1981 –200 to 645 –328 to 1193 ± 0.30 ± 0.54
Pt 200 (α = 0.00385) IEC 751; α = 0.00385, –200 to 850 –328 to 1562 ± 0.54 ± 0.98
1995
Pt 200 (α = 0.003916) JIS 1604; α = 0.003916, –200 to 645 –328 to 1193 ± 0.54 ± 0.98
1981
Pt 500 IEC 751; α = 0.00385, –200 to 850 –328 to 1562 ± 0.38 ± 0.68
1995
Pt 1000 IEC 751; = 0.00385, –200 to 300 –328 to 572 ± 0.40 ± 0.72
1995
Ni 120 Edison curve no. 7 –70 to 300 –94 to 572 ± 0.30 ± 0.54
Cu 10 Edison curve no. 7 –50 to 250 –58 to 482 ± 3.20 ± 5.76
Cu 100 (a=428) GOST 6651-94 –185 to 200 –301 to 392 ± 0.48 ±0.86
Cu 50 (a=428) GOST 6651-94 –185 to 200 –301 to 392 ± 0.96 ±1.73
Cu 100 (a=426) GOST 6651-94 –50 to 200 –58 to 392 ± 0.48 ±0.86
Cu 50 (a=426) GOST 6651-94 –50 to 200 –58 to 392 ± 0.96 ±1.73

14 Emerson.com/Rosemount
December 2021 Rosemount 848T

Table 2: Thermocouples—cold junction adds + 0.5 °C to listed accuracy

Input ranges Accuracy over range(s)


Sensor option Sensor reference
°C °F °C °F
NIST Type B (Accuracy NIST Monograph 175 100 to 300 212 to 572 ± 6.00 ± 10.80
varies according to 301 to 1820 573 to 3308 ± 1.54 ± 2.78
input range)
NIST Type E NIST Monograph 175 –200 to 1000 –328 to 1832 ± 0.40 ± 0.72
NIST Type J NIST Monograph 175 –180 to 760 –292 to 1400 ± 0.70 ± 1.26
NIST Type K NIST Monograph 175 –180 to 1372 –292 to 2501 ± 1.00 ± 1.80
NIST Type N NIST Monograph 175 –200 to 1300 –328 to 2372 ± 1.00 ± 1.80
NIST Type R NIST Monograph 175 0 to 1768 32 to 3214 ± 1.50 ± 2.70
NIST Type S NIST Monograph 175 0 to 1768 32 to 3214 ± 1.40 ± 2.52
NIST Type T NIST Monograph 175 –200 to 400 –328 to 752 ± 0.70 ± 1.26
DIN L DIN 43710 –200 to 900 –328 to 1652 ± 0.70 ± 1.26
DIN U DIN 43710 –200 to 600 –328 to 1112 ± 0.70 ± 1.26
w5Re26/W26Re ASTME 988-96 0 to 2000 32 to 3632 ± 1.60 ± 2.88
Type L GOST R 8.585-2001 –200 to 800 –328 to 1472 ± 0.71 ±1.28
Terminal temperature –50 to 85 –58 to 185 ±0.50 ±0.90
Millivolt input—Not approved for use with CSA –10 to 100 mV ± 0.05 mV
Option Code I6
2- and 3-wire Ohm input 0 to 2000 ohms ± 0.90 ohm
4–20 mA (Rosemount)(1) 4–20 mA ± 0.01 mA
4–20 mA (NAMUR)(1) 4–20 mA ± 0.01 mA
(1) Requires the S002 option code.

Related information
Accuracy

Differential configuration notes


Differential capability exists between any two sensor types.
For all differential configurations, the input range is X to Y where
X = Sensor A minimum - Sensor B max.
Y = Sensor A maximum - Sensor B min.

Accuracy for differential configurations


If sensor types are similar (for example, both RTDs or both thermocouples), the accuracy = 1.5 times worst case accuracy of either
sensor type. If sensor types are dissimilar (for example, one RTD and one thermocouple), the accuracy = Sensor 1 Accuracy + Sensor
2 Accuracy.

Emerson.com/Rosemount 15
Rosemount 848T December 2021

Analog sensors 4-20 mA


Two types of alarm levels are available with 4–20 mA sensors on the Rosemount 848T. These types must be ordered with the S002
option code complete with an analog connector kit. The alarm levels, accuracy for each type are listed in the following table.
Table 3: Analog sensors

Sensor option Alarm levels Accuracy


4–20 mA (Rosemount standard) 3.9 to 20.8 mA ± 0.01 mA
4–20 mA (NAMUR) 3.8 to 20.5 mA ± 0.01 mA

Ambient temperature effect


Transmitters may be installed in locations where the ambient temperature is between -40 °F (-40 °C) and 185 °F (85 °C).
Table 4: RTD

NIST type Accuracy per 1.0 °C (1.8 °F) change in Temperature range (°C)
ambient temperature(1)(2)
Pt 50 (α = 0.00391) 0.004 °C (0.0072 °F) N/A
Pt 100 (α = 0.00391) 0.002 °C (0.0036 °F) N/A
Pt 100 (α = 0.00385) 0.003 °C (0.0054 °F) N/A
Pt 100 (α = 0.003916) 0.003 °C (0.0054 °F) N/A
Pt 200 (α = 0.003916) 0.004 °C (0.0072 °F) N/A
Pt 200 (α = 0.00385) 0.004 °C (0.0072 °F) N/A
Pt 500 0.003 °C (0.0054 °F) N/A
Pt 1000 0.003 °C (0.0054 °F) N/A
Cu 10 0.03 °C (0.054 °F) N/A
Cu 100 (a = 428) 0.002 °C (0.0036 °F) N/A
Cu 50 (a = 428) 0.004 °C (.0072 °F) N/A
Cu 100 (a = 426) 0.002 °C (0.0036 °F) N/A
Cu 50 (a = 426) 0.004 °C (.0072 °F) N/A
Ni 120 0.003 °C (0.0054 °F) N/A
(1) Change in ambient is in reference to the calibration temperature of the transmitter 6868 °F (20 °C) typical from the factory).
(2) Ambient temperature effect specification valid over minimum temperature span of 28 °C (50 °F).

Table 5: Thermocouple (R = the value of the reading)

NIST type Accuracy per 1.0 °C (1.8 °F) change in Temperature range (°C)
ambient temperature(1)(2)
Type B 0.014 °C R ≥ 1000
0.032 °C - (0.0025% of [R - 300]) 300 ≤ R < 1000
0.054 °C - (0.011% of [R - 100]) 100 ≤ R < 300
Type E 0.005 °C + (0.00043% of R) All
Type J, DIN Type L 0.0054 °C + (0.00029% of R) R≥0
0.0054 °C + (0.0025% of |R|) R<0

16 Emerson.com/Rosemount
December 2021 Rosemount 848T

Table 5: Thermocouple (R = the value of the reading) (continued)

NIST type Accuracy per 1.0 °C (1.8 °F) change in Temperature range (°C)
ambient temperature(1)(2)
Type K 0.0061 °C + (0.00054% of R) R≥0
0.0061 °C + (0.0025% of |R|) R<0
Type N 0.0068 °C + (0.00036% of R) All
Type R, Type S 0.016 °C R ≥ 200
0.023 °C - (0.0036% of R) R < 200
Type T, DIN Type U 0.0064 °C R≥0
0.0064 °C - (0.0043% of |R|) R<0
GOST Type L 0.007 °C R≥0
0.007 °C + (0.003% of IRI) R<0
Type w5Re26 0.016 °C R > (less than or equal to) 200
0.023 °C - (0.0036% of R) R < 200
Millivolt 0.0005 mV N/A
2- and 3-wire Ohm 0.0084 ohms N/A
4–20 mA (Rosemount) 0.0001 mA N/A
4-20 mA (NAMUR) 0.0001 mA N/A
(1) Change in ambient is in reference to the calibration temperature of the transmitter 6868 °F (20 °C) typical from the factory).
(2) Ambient temperature effect specification valid over minimum temperature span of 28 °C (50 °F).

Ambient temperature notes


Examples
When using a Pt 100 (α = 0.00385) sensor input at 30 °C ambient temperature:
■ Ambient temperature effects: 0.003 °C x (30 – 20) = 0.03 °C
■ Worst case error: Sensor accuracy + Ambient temperature effects = 0.30 °C + 0.03 °C = 0.33 °C
■ Total probable error:
0.302 + 0.032 − 0.30 °C

Product certifications
Rev 3.13

European Directive Information


A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC
Declaration of Conformity can be found at Emerson.com/Rosemount.

Emerson.com/Rosemount 17
Rosemount 848T December 2021

Ordinary Location Certification


As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical,
and fire protection requirements by FM Approvals, a nationally recognized test laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).

North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in
Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature
class. This information is clearly defined in the respective codes.

USA

I5 USA Intrinsically Safe and Nonincendive


Certificate 3011568
Standards FM Class 3600:1998, FM Class 3610:2010, FM Class 3611:2004, FM Class 3810:2005, ANSI/ISA 60079-0:2009,
ANSI/ISA 60079-11:2009, NEMA 250:1991, IEC 60529:2011
Markings IS CL I, DIV 1, GP A, B, C, D; T4(–50 °C ≤ Ta ≤ +60 °C); NI CL I, DIV 2, GP A, B, C, D; T4A(–50 °C ≤ Ta ≤ +85 °C); T5(–50 °C
≤ Ta ≤ +70 °C) when installed per Rosemount drawing 00848-4404.

Note
Transmitters marked with Nonincendive CL I, DV 2 can be installed in Division 2 locations using general Division 2 wiring methods
or Nonincendive Field Wiring (NIFW). See Drawing 00848-4404.

IE USA FISCO
Certificate 3011568
Standards FM Class 3600:1998, FM Class 3610:2010, FM Class 3611:2004, FM Class 3810:2005, ANSI/ISA 60079-0:2009,
ANSI/ISA 60079-11:2009, NEMA 250:1991, IEC 60529:2011
Markings IS CL I, DIV 1, GP A, B, C, D; T4(–50 °C ≤ Ta ≤ +60 °C); NI CL I, DIV 2, GP A, B, C, D; T4A(–50 °C ≤ Ta ≤ +85 °C); T5(–50 °C
≤ Ta ≤ +70 °C) when installed per Rosemount drawing 00848-4404.

N5 USA Nonincendive and Dust-Ignitionproof


Certificate 3011568
Standards FM Class 3600:1998, FM Class 3611:2004, FM Class 3810:2005, ANSI/ISA 60079-0:2009, NEMA 250:1991, IEC
60529:2011
Markings NI CL I, DIV 2, GP A, B, C, D; DIP CL II/III, DIV 1, GP E, F, G; T4A(–50 °C ≤ Ta ≤ +85 °C); T5(–50 °C ≤ Ta ≤ +70 °C) when
installed per Rosemount drawing 00848-4404; Type 4X

NK USA Nonincendive
Certificate 3011568
Standards FM Class 3600:1998, FM Class 3611:2004, FM Class 3810:2005, ANSI/ISA 60079-0:2009, NEMA 250:1991, IEC
60529:2001

18 Emerson.com/Rosemount
December 2021 Rosemount 848T

Markings NI CL I, DIV 2, GP A, B, C, D; T4A(–50 °C ≤ Ta ≤ +85 °C); T5(–50 °C ≤ Ta ≤ +70 °C) when installed per Rosemount
drawing 00848-4404

Note
Only the N5 and NK are valid with the S002 option.

Table 6: MAI Block Parameters

Fieldbus (input) FISCO (input) Nonincendive (input) Sensor field terminal


(output)
VMAX = 30 V VMAX = 17.5 VMAX = 42.4 VOC = 12.5 V
IMAX = 300 mA IMAX = 380 mA Ci = 2.1 nF ISC = 4.8 mA
Pi = 1.3 W Pi = 5.32 W Li = 0 PO = 15 mW
Ci = 2.1 nF Ci = 2.1 nF N/A CA = 1.2 μF
Li = 0 Li = 0 N/A LA = 1 H

Canada

E6 Canada Explosionproof, Dust-Ignitionproof, Division 2 (JX3 Enclosure Required)


Certificate 1261865
Standards CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std. C22.2 No. 25.1966, CSA Std. C22.2 No. 30-M1986, CAN/CSA C22.2 No.
94-M91, CSA Std. C22.2 No. 142-M1987, CSA Std. C22.2 No. 213-M1987, CSA Std. C22.2 No. 60529:05
Markings Explosionproof for Class I, Division 1, Groups B, C, and D; T4(–40 °C ≤ Ta ≤ +40 °C) when installed per Rosemount
drawing 00848-1041; Dust-Ignitionproof for Class II, Division 1, Groups E, F, and G; Class III; Class I, Division 2, Groups
A, B, C, and D; T3C(–50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount drawing 00848-4405; Conduit Seal Required

I6 Canada Intrinsically Safe and Division 2


Certificate 1261865
Standards CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA C22.2 No. 94-M91, CSA Std. C22.2 No. 142-M1987, CSA Std. C22.2
No. 157-92, CSA Std. C22.2 No. 213-M1987, CSA Std. C22.2 No. 60529:05
Markings Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D; T3C(–50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount
drawing 00848-4405; Class I, Division 2, Groups A, B, C, D; T3C(–50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount
drawing 00848-4405

IF Canada FISCO
Certificate 1261865
Standards CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA C22.2 No. 94-M91, CSA Std. C22.2 No. 142-M1987, CSA Std. C22.2
No. 157-92, CSA Std. C22.2 No. 213-M1987, CSA Std. C22.2 No. 60529:05
Markings Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D; T3C(–50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount
drawing 00848-4405; Class I, Division 2, Groups A, B, C, D; T3C(–50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount
drawing 00848-4405

N6 Canada Division 2 and Dust-Ignitionproof (enclosure required)


Certificate 1261865

Emerson.com/Rosemount 19
Rosemount 848T December 2021

Standards CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std. C22.2 No. 30-M1986, CAN/CSA C22.2 No. 94-M91, CSA Std. C22.2 No.
142-M1987, CSA Std. C22.2 No. 213-M1987, CSA Std. C22.2 No. 60529:05
Markings Class I, Division 2, Groups A, B, C, and D; T3C(–50 °C ≤ Ta ≤ +60 °C) when installed per Rosemount drawing
00848-4405; Dust-Ignitionproof for Class II, Division 1, Groups E, F, and G; Class III; Conduit Seal Required

Europe

I1 ATEX Intrinsic Safety


Certificate Baseefa09ATEX0093X
Standards EN IEC 60079-0:2018, EN 60079-11:2012
Markings
II 1 G Ex ia IIC T4 Ga (–50 °C ≤ Ta ≤ +60 °C) when installed per drawing 00848-4406

Special Conditions for Safe Use (X):


1. The equipment must be installed in an enclosure that provides a degree of protection of at least IP20. Non-metallic
enclosures must be suitable to prevent electrostatic hazards and light alloy or zirconium enclosures must be protected from
impact and friction when installed.
2. The equipment is not capable of withstanding the 500 V insulation test required by EN 60079-11:2011, clause 6.3.13. This
must be taken into account when installing the equipment.

Fieldbus (input) Sensor field terminal (output)


Ui = 30 V UO = 12.5 V
Ii = 300 mA IO = 4.8 mA
Pi = 1.3 W PO = 15 mW
Ci = 2.1 nF CO = 1.2 μF
Li = 0 LO = 1 H

IA ATEX FISCO Intrinsic Safety


Certificate Baseefa09ATEX0093X
Standards EN IEC 60079-0:2018, EN 60079-11:2012
Markings
II 1 G Ex ia IIC T4 Ga (–50 °C ≤ Ta ≤ +60 °C) when installed per drawing 00848-4406

Special Conditions for Safe Use (X):


1. The equipment must be installed in an enclosure that provides a degree of protection of at least IP20. Non-metallic
enclosures must be suitable to prevent electrostatic hazards and light alloy or zirconium enclosures must be protected from
impact and friction when installed.
2. The equipment is not capable of withstanding the 500 V insulation test required by EN 60079-11:2011, clause 6.3.13. This
must be taken into account when installing the equipment.

FISCO (input) Sensor field terminal (output)


Ui = 17.5 V UO = 12.5 V
Ii = 380 mA IO = 4.8 mA

20 Emerson.com/Rosemount
December 2021 Rosemount 848T

FISCO (input) Sensor field terminal (output)


Pi = 5.32 W PO = 15 mW
Ci = 2.1 nF CO = 1.2 μF
Li = 0 LO = 1 H

N1 ATEX Zone 2 (with enclosure)


Certificate Baseefa09ATEX0095X
Standards EN IEC 60079-0:2018, EN 60079-7:2015 + A1:2018, EN 60079-15:2010
Markings
II 3G Ex nA IIC T5 Gc (-40 °C ≤ Ta ≤ +65 °C), Ex ec IIC T5 Gc (-40 °C ≤ Ta ≤ +65 °C)

Special Conditions for Safe Use (X):


1. The equipment must only be installed in an area of pollution degree 2 or better, as defined in IEC 60664-1.
2. Provision must be made, external to the equipment, to ensure the rated voltage of the equipment supply is not exceeded by
transient disturbances of more than 40 percent.
3. The electrical circuit is connected directly to earth; this must be taken into account when installing the apparatus.

NC ATEX Zone 2 Component (without enclosure)


Certificate Baseefa09ATEX0094U
Standards EN IEC 60079-0:2018, EN 60079-7:2015 + A1:2018, EN 60079-15:2010
Markings
II 3G Ex nA IIC T4 Gc (-50 °C ≤ Ta ≤ +85 °C) or Ex nA IIC T5 Gc (-50 °C ≤ Ta ≤ +70 °C), Ex ec IIC T4 Gc (-50 °C ≤ Ta ≤
+85 °C) or Ex ec IIC T5 Gc (-50 °C ≤ Ta ≤ +70 °C)

Schedule of Limitations (U):


1. The equipment must only be installed in an area of pollution degree 2 or better, as defined in IEC 60664-1, and in an
enclosure that provides a degree of protection of at least IP54 in accordance with EN 60079-0.
2. Provision must be made, external to the component, to ensure the rated voltage of the component supply is not exceeded
by transient disturbances of more than 40 percent.
3. The electrical circuit is connected directly to earth; this must be taken into account when installing the apparatus.

International

I7 IECEx Intrinsic Safety


Certificate IECEx BAS 09.0030X
Standards IEC 60079-0:2017, IEC 60079-11:2011
Markings Ex ia IIC T4 Ga (–50 °C ≤ Ta ≤ +60 °C)

Emerson.com/Rosemount 21
Rosemount 848T December 2021

Special Conditions for Safe Use (X):


1. The apparatus must be installed in an enclosure that provides a degree of protection of at least IP20. Non-metallic
enclosures must be suitable to prevent electrostatic hazards and light alloy or zirconium enclosures must be protected from
impact and friction when installed.
2. The apparatus is not capable of withstanding the 500 V insulation test required by IEC 60079-11:2011, clause 6.3.13. This
must be taken into account when installing the appartus.

IG IECEx FISCO Intrinsic Safety


Certificate IECEx BAS 09.0030X
Standards IEC 60079-0:2017, IEC 60079-11:2011
Markings Ex ia IIC T4 Ga (-50 °C ≤ Ta ≤ +60 °C)

Special Conditions for Safe Use (X):


1. The equipment must be installed in an enclosure that provides a degree of protection of at least IP20. Non-metallic
enclosures must be suitable to prevent electrostatic hazards and light alloy or zirconium enclosures must be protected from
impact and friction when installed.
2. The equipment is not capable of withstanding the 500 V insulation test required by EN 60079-11:2012, clause 6.3.13. This
must be taken into account when installing the equipment.

FISCO (input) Sensor field terminal (output)


Ui = 17.5 V UO = 12.5 V
Ii = 380 mA IO = 4.8 mA
Pi = 5.32 W PO = 15 mW
Ci = 2.1 nF CO = 1.2 μF
Li = 0 LO = 1 H

N7 IECEx Type n (with enclosure)


Certificate: IECEx BAS 09.0032X
Standards: IEC 60079-0:2017, IEC 60079-7:2017, IEC 60079-15:2010
Markings: Ex nA IIC T5 Gc (-40 °C ≤ Ta ≤ +65 °C), Ex ec IIC T5 Gc (-40 °C ≤ Ta ≤ +65 °C)

Special Conditions for Safe Use (X):


1. The equipment must only be installed and used in an area of pollution degree 2 or better, as defined in IEC 60664-1.
2. Provision must be made, external to the apparatus, to ensure the rated voltage of the apparatus supply is not exceeded by
transient disturbances of more than 40 percent.
3. The electrical circuit is connected directly to earth. This must be taken into account when installing the apparatus.

NJ IECEx Type n (without enclosure)


Certificate: IECEx BAS 09.0031U
Standards: IEC 60079-0:2017, IEC 60079-7:2017, IEC 60079-15:2010
Markings: Ex nA IIC T4 Gc(-50 °C ≤ Ta ≤ +85 °C), Ex nA IIC T5 Gc (-50 °C ≤ Ta ≤ +70 °C), Ex ec IIC T4 Gc(-50 °C ≤ Ta ≤ +85 °C), Ex ec
IIC T5 Gc (-50 °C ≤ Ta ≤ +70 °C)

22 Emerson.com/Rosemount
December 2021 Rosemount 848T

Schedule of Limitations (U):


1. The component must be only installed and used in an area of pollution degree 2 or better, as defined in IEC 60664-1, and in
an enclosure that provides a degree of protection of at least IP54 in accordance with IEC 60079-0
2. Provision must be made, external to the component, to ensure the rated voltage of the component supply is not exceeded
by transient disturbances of more than 40 percent.
3. The electrical circuit is connected directly to earth; this must be taken into account when installing the apparatus.

Brazil

I2 Brazil Intrinsic Safety


Certificate UL-BR 16.0086X
Standards ABNT NBR IEC 60079-0:2008 + Errata 1:2011 ABNT NBR IEC 60079-11:2009
Markings Ex ia IIC T4(–50 °C ≤ Ta ≤ +60 °C)

Special Conditions for Safe Use (X):


1. The apparatus must be installed in an enclosure that provides a degree of protection of at least IP20. Non-metallic
enclosures must be suitable to prevent electrostatic hazards (see manufacturer's instructions manual) and light alloy or
zirconium enclosures must be protected from impact and friction when installed.
2. The apparatus is not capable of withstanding the 500 V isolation test required by ABNT NBR IEC 60079-11. This must be
taken into account when installing the apparatus --- see manufacturer's instructions manual.

Fieldbus (input) Sensor field terminal (output)


Ui = 30 V UO = 12.5 V
Ii = 300 mA IO = 4.8 mA
Pi = 1.3 W PO = 15 mW
Ci = 2.1 nF CO = 1.2 μF
Li = 0 LO = 1 H

IB Brazil Intrinsic Safety


Certificate UL-BR 16.0086X
Standards ABNT NBR IEC 60079-0:2008 + Errata 1:2011, ABNT NBR IEC 60079-11:2009
Markings Ex ia IIC T4(–50 °C ≤ Ta ≤ +60 °C)

Special Conditions for Safe Use (X):


1. The apparatus must be installed in an enclosure that provides a degree of protection of at least IP20. Non-metallic
enclosures must be suitable to prevent electrostatic hazards (see manufacturer's instructions manual) and light alloy or
zirconium enclosures must be protected from impact and friction when installed.
2. The apparatus is not capable of withstanding the 500 V isolation test required by ABNT NBR IEC 60079-11. This must be
taken into account when installing the apparatus --- see manufacturer's instruction manual.

FISCO (input) Sensor field terminal (output)


Ui = 17.5 V UO = 12.5 V

Emerson.com/Rosemount 23
Rosemount 848T December 2021

FISCO (input) Sensor field terminal (output)


Ii = 380 mA IO = 4.8 mA
Pi = 5.32 W PO = 15 mW
Ci = 2.1 nF CO = 1.2 μF
Li = 0 LO = 1 H

China

I3 China Intrinsic Safety


Certificate GYJ21.1125X
Standards GB3836.1-2010, GB3836.4-2010, GB3836.20-2010
Markings Ex ia IIC T4/T5 Ga

产品安全使用特殊条件:
产品防爆合格证后缀“X”代表产品安全使用有特殊条件:
输出为 FOUNDATION Fieldbus 时:
1. 温度变送器须安装于外壳防护等级不低于国家标准 GB4208-2008 规定的 IP20 的壳体中,方可用于爆炸性危险场所,金
属壳体须符合国家标准 GB3836.1-2010 第 8 条的规定,非金属壳体须符合 GB3836.1-2010 第 7.4 条的规定。
2. 此设备不能承受 GB3836.4-2010 标准中第 6.3.12 条规定的 500V 交流有效值试验电压的介电强度试验。
输出为 Wireless 时:
1. 天线的表面电阻大于 1 GΩ,不允许用溶剂清洗或用干布擦拭,以避免电荷积聚。
2. 电源模块表面电阻大于 1 GΩ,必须置于无线设备外壳内使用,现场安装及运输过程中避免电荷积聚。
3. 产品需使用厂家提供的由 2 块 Tadiran TL-5920 Lithium Thionyl-Chloride 原电池组成的电池组。
产品使用注意事项:
1. 产品环境温度为:

输出代码 温度组别 环境温度


F T4 –50 ℃ ≤ Ta ≤+ 60 ℃
W T4 –60 ℃ ≤ Ta ≤+ 70 ℃
T5 –60 ℃ ≤ Ta ≤ + 40 ℃

2. 参数:
供电端(1-2)

输出代码 最高输 入电压 最大输 入电流 最大输 入功率 最大内部等效参数


Ui (V) Ii (mA) Pi (mW) Ci (μF) Li (H)
F 30 300 1.3 2.1 0
F (FISCO) 17.5 380 5.32 2.1 0

24 Emerson.com/Rosemount
December 2021 Rosemount 848T

注 1:上表中非 FISCO 参数必须来自于使用电阻限流的线性输出。


注 2:本安电气参数符合 GB3836.19-2010 对 FISCO 现场仪表的参数要求。当其连接符合 FISCO 模型的电路板时,其本安
参数及内部最大等效参数见上表。
传感器端:

输出代码 端子 最高输 出电压 最大输 出电流 最大输 出功率 最大外部等效参数


Uo (V) Io (mA) Po (mW) Co (μH) Lo (H)
F 1-8 12.5 4.8 15 1.2 1
F (FISCO) 1-20 6.6 3.2 5.3 22 1

3. 输出代码为 F 时,该产品必须与已通过防爆认证的关联设备配套共同组成本安防爆系统方可使用于爆炸性气体环境。其
系统接线必须同时遵守本产品和所配关联设备的使用说明书要求,接线端子不得接错。
4. 该产品于关联设备的连接电缆应为带绝缘护套的屏蔽电缆,其屏蔽层应为安全接地。
5. 用户不得自行更换该产品的零部件,应会同产品制造商共同解决运行中出现的故障,以杜绝损坏现象的发生。 产品的安
装、使用和维护应同时遵守产品使用说明书、GB3836.13-2013“爆炸性环境 第 13 部分:设备的修理、检修、修复和改
造”、GB3836.15-2000“爆炸性气体环境用电气设备 第 15 部分:危险场所电气安装(煤矿除外)”、GB3836.16-2006“爆
炸性气体环境用电气设备 第 16 部分:电气装置的检查和维护(煤矿除外)”、GB3836.18-2010“爆炸性环境 第 18 部
分:本质安全系统”和 GB50257-2014“电气装置安装工程爆炸和火灾危险环境电力装置施工及验收规范”的有关规定。

N3 China Type n
Certificate GYJ21.3428U
Standards GB3836.1-2010, GB3836.8-2014
Markings Ex nA IIC T4/T5 Gc

产品安全使用特殊条件:
1. 设备不能承受 GB3836.8-2014 标准中第 6.5.1 条规定的 500V 耐压试验,安装时必须考虑在内。
2. 此设备必须安装于具有不低于 IP54 外壳防护等级的 Ex 元件外壳,外壳应符合 GB3836.1-2010 和 GB3836.8-2014 标准中
对外壳材料和环境的相关要求。
3. 在此设备外部应采取措施以防额定电压因瞬态干扰而超过 40%。

产品使用注意事项:
1. 产品使用环境温度范围:

温度组别 环境温度
T4 –50 °C ≤ Ta ≤ +85 °C
T5 –50 °C ≤ Ta ≤ +70 °C

2. 最高工作电压:42.4V。
3. 用户不得自行更换该产品的零部件,应会同产品制造商共同解决运行中出现的故障,以杜绝损坏现象的发生。
4. 产品的安装、使用和维护应同时遵守产品使用说明书、GB3836.13-2013“爆炸性环境 第 13 部分:设备的修理、检修、修
复和改造”、GB3836.15-2000“爆炸性气体环境用电气设备 第 15 部分:危险场所电气安装(煤矿除外)”、
GB3836.16-2006“爆炸性气体环境用电气设备 第 16 部分:电气装置的检查和维护(煤矿除外)” 、B50257-2014“电气装
置安装工程爆炸和火灾危险环境电力装置施工及验收规范”的有关规定。

Emerson.com/Rosemount 25
Rosemount 848T December 2021

Japan

I4 Japan FISCO Intrinsic Safety (ia)


Certificate TC19713
Markings ia IIC T4

Japan Wi-HART Intrinsic Safety (ia)


Certificate TC19154
Markings ia IIC T4

H4 Japan FISCO Intrinsic Safety (ib)


Certificate TC20737
Markings ia IIC T4

Korea

IP Korea Intrinsic Safety


Certificate 20-KA4BO-0921X
Markings Ex ia IIC T4 (–50 °C ≤ Ta ≤ +60 °C)

EAC - Belarus, Kazakhstan, Russia

IM Technical Regulation Customs Union (EAC) Intrinsic Safety


Markings [FOUNDATION Fieldbus]: 0Ex ia IIC T4 Ga X, T4(–50 °C ≤ Ta ≤ +60 °C)
See certificate for entity parameters.

Special Condition for Safe Use (X):


See certificate for special conditions.

IN Technical Regulation Customs Union (EAC) FISCO


Markings: [FISCO]: 0Ex ia IIC T4 Ga X, T4(-50 °≤ Ta ≤ +60 °C)
See certificate for entity parameters.

Special Condition for Safe Use (X):


See certificate for special conditions.

26 Emerson.com/Rosemount
December 2021 Rosemount 848T

Combinations
KG Combination of I1/IA, I5/IE, I6/IF, and I7/IG

Conduit Plugs and Adapters


ATEX Flameproof and Increased Safety

Certificate FM13ATEX0076X
Standards EN 60079-0:2012, EN 60079-1:2007, IEC 60079-7:2007
Markings: 2 G Ex de IIC Gb

Special Conditions for Safe Use (X):


1. When the thread adapter or blanking plug is used with an enclosure in type of protection increased safety “e” the entry
thread shall be suitably sealed in order to maintain the ingress protection rating (IP) of the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G½ and PG 13.5 thread forms are only
acceptable for existing (legacy) equipment installations.

IECEx Flameproof and Increased Safety

Certificate IECEx FMG 13.0032X


Standards IEC 60079-0:2011, IEC 60079-1:2007, IEC 60079-7:2006-2007
Markings Ex de IIC Gb

Special Conditions for Safe Use (X):


1. When the thread adapter or blanking plug is used with an enclosure in type of protection increased safety “e” the entry
thread shall be suitably sealed in order to maintain the ingress protection rating (IP) of the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G½ and PG 13.5 thread forms are only
acceptable for existing (legacy) equipment installations.
Table 7: Conduit Plug Thread Sizes

Thread Identification mark


M20 x 1.5 M20
½–14 NPT ½ NPT
G½ G½

Table 8: Thread Adapter Thread Sizes

Male thread Identification mark


M20 x 1.5–6H M20
½–14 NPT ½–14 NPT
¾–14 NPT ¾–14 NPT
Female thread Identification mark
M20 x 1.5–6H M20

Emerson.com/Rosemount 27
Rosemount 848T December 2021

Table 8: Thread Adapter Thread Sizes (continued)

Male thread Identification mark


½–14 NPT ½–14 NPT
PG 13.5 PG 13.5

28 Emerson.com/Rosemount
December 2021 Rosemount 848T

Dimensional drawings for Rosemount 848T FOUNDATION


Fieldbus
Junction boxes
External dimensions for junction boxes with no entries are the same as those outlined for the other junction box materials in this
section.
Figure 3: Rosemount 848T
A B C

1.7
D E
(43)
6.7 (170)

3.7 (93)

Dimensions are in inches (millimeters).


A. Top view
B. 3-D view
C. Side view
D. Security switch
E. Simulation switch
F. Removable wiring connection

Emerson.com/Rosemount 29
Rosemount 848T December 2021

Aluminum junction box


Figure 4: Aluminum junction box with cable glands (option code JA4)
10.21
[259]

1.70 6.70
[43] [170]
D
C

3.67
[93]

B
A

2.27 1.88
[58] [48]
1.33
[34]
8.42
[214] 6.00
[152]

3.98
[101]
2.30
[58]
.80
[20]

E
A. Nameplate
B. Removable wiring connector
C. Security switch
D. Simulation switch
E. External ground screw (optional)
Dimensions are in inches (millimeters).

30 Emerson.com/Rosemount
December 2021 Rosemount 848T

Figure 5: Aluminum junction box with plugged holes (option code JA5)
10.21 1.70 6.70
[259] [43] [170] D
C

1.88
A 7.14
3.21
[48] [181]
1.33 [81] 6.00
[34] [152]

3.97
[101]
2.30
[58]

.80
[20]
E

A. Nameplate
B. Removable wiring connection
C. Security switch
D. Simulation switch
E. External ground screw (optional)
Dimensions are in inches (millimeters).

Emerson.com/Rosemount 31
Rosemount 848T December 2021

Stainless steel junction box


Figure 6: Stainless steel junction box with cable glands (option code JS2)

A B

9.91 (231)
7.7 (196)

D E

1.8 (46) 9.14 (232.2)


1.1 (28) 7.72 (196)
1.73 (44) 6.61 (168)

4.0 (102)
2.4 (62)
1.2 (30) 1.8 (47)

A. Top view
B. 3-D view
C. Ground screw
D. Front view
E. Side view
Dimensions are in inches (millimeters).

32 Emerson.com/Rosemount
December 2021 Rosemount 848T

Figure 7: Stainless steel junction box with a conduit entry (option code JS3)

A B
9.1 (231)
7.7 (196)

4.0 (102)

D E
1.2 (30)
1.4 (35)
1.1 (27) 2.8 (70)

4.0 (102)
2.4 (62)
1.8 (4.7)
1.6 (42)
F

A. Top view
B. 3-D view
C. Ground screw
D. Front view
E. Side view
F. Five plugged 0.86 in (21.8 mm) diameter holes suitable for installing ½-in. NPT fittings
Dimensions are in inches (millimeters).

Emerson.com/Rosemount 33
Rosemount 848T December 2021

Mounting options
Figure 8: Mount an aluminum junction box
․ ‥
A B

7.55
[193]

5.08
[129]
A. Front view
B. Side view
Dimensions are in inches (millimeters)

34 Emerson.com/Rosemount
December 2021 Rosemount 848T

Figure 9: Mount a stainless steel junction box


A B

4.7 (119)

7.5 (190)

A. Front view
B. Side view
C. Fully assembled
Dimensions are in inches (millimeters)

Figure 10: Mount aluminum on a vertical pipe

Emerson.com/Rosemount 35
Rosemount 848T December 2021

Figure 11: Mount stainless steel on vertical pipe

36 Emerson.com/Rosemount
December 2021 Rosemount 848T

Rosemount 848T Wireless Temperature Transmitter


The Rosemount 848T is the premier choice for Wireless High
Density measurements. Four independently configurable inputs
are transmitted through WirelessHART®. Costs per point are
dramatically reduced through the use of smart wireless
networks, with the same reliability and security of wired
solutions. Additionally, the field hardened enclosure is suitable
for installation in IS areas. Capabilities include:
Four independently configurable inputs, including 2-, 3- and 4-
wire RTDs, thermocouples, 0-1000 mV and 0-10V, 2-, 3- and 4-
wire ohms, and 4-20 mA signals.
CONFIGURE > VIEW PRODUCT >

Online product configurator


Many products are configurable online using our Product Configurator. Select the Configure button or visit our website to start.
With this tool's built-in logic and continuous validation, you can configure your products more quickly and accurately.

Model codes
Model codes contain the details related to each product. Exact model codes will vary; an example of a typical model code is shown
in the following figure.
Figure 12: Model Code Example

1. Required model components (choices available on most)


2. Additional options (variety of features and functions that may be added to products)

Specifications and options


See the Specifications and options section for more details on each configuration. Specification and selection of product materials,
options, or components must be made by the purchaser of the equipment. See the Material selection section for more information.

Optimizing lead time


The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings
are subject to additional delivery lead time.

Emerson.com/Rosemount 37
Rosemount 848T December 2021

Required model components

Model

Code Description
848T High Density Temperature Measurement Family ★

Product certification

Code Description
I1 ATEX Intrinsic Safety ★
I2 INMETRO Intrinsic Safety ★
I3 NEPSI Intrinsic Safety ★
I4 TIIS Intrinsic Safety ★
I5 FM Intrinsically Safe ★
I6 CSA Intrinsically Safe ★
I7 IECEx Intrinsic Safety ★
N5 FM Class I, Division 2, and Dust Ignition-proof (enclosure required) ★
N6 CSA Class I, Division 2 ★
IM Technical Regulations Customs Union (EAC) Intrinsic Safety ★
NA No Approval ★

Transmitter output

Code Description
X Wireless ★

Input type

Code Description
S001 RTD, thermocouple, mV, ohm inputs ★
S002(1) RTD, thermocouple, mV, ohm and 4–20 mA inputs ★
(1) Only available with product certifications NA and N5. Stable resistors included.

38 Emerson.com/Rosemount
December 2021 Rosemount 848T

Additional options

Wireless update rate, operating frequency, and protocol


Code Description
WA3 User configurable update rate, 2.4 GHz, WirelessHART ★

Omnidirectional wireless antenna and SmartPower™


Black power module must be shipped separately, order Model 701PBKKF.

Code Description
WK1 Long Range, Integral Antenna, Power Module Adapter, Intrinsically Safe (Power Module separate) ★
WM1 Extended Range, External Antenna, Adapter for Black Power Module (I.S. Power Module Sold Separately) ★

Mounting bracket
Code Description
B6 Mounting bracket for 2 in (51 mm) pipe mounting – SST bracket and bolts ★

Enclosure options
Option HA1 or HA2 required for wireless.

Code Description
HA1 Aluminum with cable glands (5 × ½-in. NPT for 7.5-11.9 mm) ★
HA2 Aluminum with conduit entries (5 plugged holes, suitable for installing ½-in. NPT fittings) ★

Software configuration

Code Description
C1 Custom configuration of date, descriptor, message, and wireless parameters (requires CDS with order) ★

Line filter
Code Description
F5 50 Hz line voltage filter ★
F6 60 Hz line voltage filter ★

5-point calibration
Code Description
C4 5-point calibration (requires Q4 option code to generate a calibration certificate) ★

Emerson.com/Rosemount 39
Rosemount 848T December 2021

Calibration certificate
Code Description
Q4 Calibration certificate (3-point calibration) ★

Shipboard certification

Code Description
SBS American Bureau of Shipping (ABS) Type Approval ★
SBV Bureau Veritas (BV) Type Approval ★
SDN Det Norske Veritas (DNV) Type Approval ★
SLL Lloyd's Register (LR) Type Approval ★

Special temperature test


Code Description
LT Test to -60 °F (-51 °C) ★

Conduit electrical connector

Code Description
GE M12, 4-pin, male connector (eurofast®) ★
GM A size mini, 4-pin, male connector (minifast®) ★

Extended product warranty


Code Description
WR3 3-year limited warranty ★
WR5 5-year limited warranty ★

40 Emerson.com/Rosemount
December 2021 Rosemount 848T

WirelessHART...industry standard

Self-organizing adaptive mesh routing


■ No wireless expertise required—devices automatically find the best
communication paths
■ Network continuously monitors paths for degradation and repairs itself
■ Adaptive behavior provides reliable, hands-off operation and simplifies network
deployments, expansion, and reconfiguration
■ Supports both star and mesh topologies

Industry standard radio with channel hopping


■ Standard IEEE 802.15.4 radios
■ 2.4 GHz ISM band sliced into 16 radio-channels
■ Continually “hop” across channels to avoid interference and increase reliability
■ Frequency hopping spread spectrum (FHSS) technology delivers high reliability in challenging radio environment

Self-healing network
■ If an obstruction is introduced into the mesh network, devices will automatically find the best alternate communication path.
■ This allows the network to instantly change to the new path without any loss in data.

Seamless integration to existing hosts


■ Transparent and seamless integration
■ Same control system applications
■ Gateways connect using industry protocols

Emerson.com/Rosemount 41
Rosemount 848T December 2021

Specifications for Rosemount 848T Wireless


Functional specifications
Input
Four independently configurable input channels that supports Thermocouple, RTD, mV, 0–10 V, ohm, and 4–20 mA, input types.
See Accuracy for sensor options.

Output
IEC 62591 (WirelessHART), 2.4 GHz DSSS

Ambient temperature limits


-40 °F (-40 °C) to 185 °F (85 °C)

Humidity limits
0–99 percent non-condensing relative humidity

Update rate
User selectable, 4 seconds to 60 minutes

Accuracy
(Pt 100 at reference condition: 20 °C)
±0.54 °F (±0.30 °C)
For the complete list see Accuracy.

Isolation
Isolation between all sensor channels is rated to 10 Vdc over all operating conditions. No damage will occur to the device with up to
250 Vdc between any sensor channels.

Alerts
Message sent when open or short sensor is detected

Electromagnetic Compatibility (EMC)


Meets all industrial environment requirements of EN61326 and NAMUR NE-21. Maximum deviation < 1 percent span during EMC
disturbance.

Transmitter stability
■ ±0.15 percent of reading or 0.27 °F (0.15 °C), whichever is greater, for two years for RTDs
■ ±0.15 percent of reading or 0.27 °F (0.15 °C), whichever is greater, for one year for thermocouples

Self calibration
The analog-to-digital measurement circuitry automatically self-calibrates for each temperature update by comparing the dynamic
measurement to extremely stable and accurate internal reference elements.

42 Emerson.com/Rosemount
December 2021 Rosemount 848T

Vibration effect
Tested to the following with no effect on performance per IEC 60770-1, 1999.

Frequency acceleration
10-60 Hz 0.21 mm peak displacement
60-2000 Hz 3g

Physical specifications

Material selection
Emerson provides a variety of Rosemount product with various product options and configurations including materials of
construction that can be expected to perform well in a wide range of applications. The Rosemount product information presented
is intended as a guide for the purchaser to make an appropriate selection for the application. It is the purchaser’s sole responsibility
to make a careful analysis of all process parameters (such as all chemical components, temperature, pressure, flow rate, abrasives,
contaminants, etc.), when specifying product, materials, options and components for the particular application. Emerson is not in a
position to evaluate or guarantee the compatibility of the process fluid or other process parameters with the product, options,
configuration or materials of construction selected.

Conformance to specifications (±3σ [Sigma])


Technology leadership, advanced manufacturing techniques, and statistical process control ensure specification conformance to at
least ±3σ.

Electrical connections
Power module
The Emerson SmartPower™ power module is field replaceable, featuring keyed connections that eliminate the risk of incorrect
installation. The power module is an Intrinsically Safe solution, containing the Lithium-thionyl chloride with a polybutadine
terephthalate (PBT) enclosure. The 848T Wireless has a power module life time rating of six years with a one-minute update rate, at
reference conditions.(3)

Sensor terminals
Sensor terminals permanently fixed to terminal block.

Field Communicator connections


Communication terminals
Clips permanently fixed to terminal block.

(3) Reference conditions are 68 °F (20 °C), and routing data for three additional network devices. Note: Continuous exposure to ambient temperature limits -40 °F
(-40 °C) or 185 °F (85 °C) may reduce specified life to less than 20 percent.

Emerson.com/Rosemount 43
Rosemount 848T December 2021

Materials of construction
Enclosure

Component Material
Housing Low-copper aluminum
Paint Polyurethane
Cover O-ring Silicone

Terminal block and power module


PBT

Antenna
PBT/Polycarbonate (PC) integrated omni-directional antenna

Mounting
Transmitter can be panel mounted, or be mounted onto a 2-in. pipe stand (with option code B6). Sensors must be remotely
mounted, as transmitter conduit entries are not designed for direct sensor mounting.

Weight
Rosemount 848T Wireless - 4.75 lb (2.2 kg)

Enclosure ratings (Rosemount 848T Wireless)


Housing option codes HA1 or HA2 are Type 4x and IP66.

Sensor connections
Figure 13: Rosemount 848T Wireless Sensor Connections Diagram

1 1
2 2
A 3 3 C
4 4
5 5

1
+

1
2 2
3 D
-

B 3
4 4
5 5

A. 2-wire RTD and Ω


B. 4-wire RTD and Ω
C. 3-wire RTD and Ω
D. Thermocouple and mV

44 Emerson.com/Rosemount
December 2021 Rosemount 848T

Accuracy
Table 9: 2-, 3-, and 4-wire RTDs

Input ranges Accuracy over range(s)


Sensor option Sensor reference
°C °F °C °F
Pt 50 (α = 0.00391) GOST 6651-94 –200 to 550 –328 to 1022 ± 0.57 ± 1.03
Pt 100 (α = GOST 6651-94 –200 to 550 –328 to 1022 ± 0.28 ± 0.50
0.00391)
Pt 100 (α = IEC 751; α = –200 to 850 –328 to 1562 ± 0.30 ± 0.54
0.00385) 0.00385, 1995
Pt 100 (α = JIS 1604, 1981 –200 to 645 –328 to 1193 ± 0.30 ± 0.54
0.003916)
Pt 200 (α = IEC 751; = 0.00385, –200 to 850 –328 to 1562 ± 0.54 ± 0.98
0.00385) 1995
PT 200 (α = JIS 1604, 1981 ( = –200 to 645 –328 to 1193 ± 0.54 ± 0.98
0.003916) 0.003916)
Pt 500 (α = IEC 751; = 0.00385, –200 to 850 –328 to 1562 ± 0.38 ± 0.68
0.00385) 1995
Pt 1000 (α = IEC 751; = 0.00385, –200 to 300 –328 to 572 ± 0.40 ± 0.72
0.00385) 1995
Ni 120 Edison Curve No. 7 –70 to 300 –94 to 572 ± 0.30 ± 0.54
Cu 10 Edison Copper –50 to 250 –58 to 482 ± 3.20 ± 5.76
Winding No. 15
Cu 100 (a=428) GOST 6651-94 –185 to 200 –301 to 392 ± 0.48 ±0.86
Cu 50 (a=428) GOST 6651-94 –185 to 200 –301 to 392 ± 0.96 ±1.73
Cu 100 (a=426) GOST 6651-94 –50 to 200 –58 to 392 ± 0.48 ±0.86
Cu 50 (a=426) GOST 6651-94 –50 to 200 –58 to 392 ± 0.96 ±1.73

Table 10: Thermocouples — cold junction adds + 0.5 °C to listed accuracy

Input ranges Accuracy over range(s)


Sensor option Sensor reference
°C °F °C °F
NIST Type B NIST Monograph 100 to 300 212 to 572 ± 6.00 10.80
(Accuracy varies 175 301 to 1820 573 to 3308 ± 1.54 ± 2.78
according to input
range)
NIST Type E NIST Monograph –200 to 1000 –328 to 1832 ± 0.40 ± 0.72
175
NIST Type J NIST Monograph –180 to 760 –292 to 1400 ± 0.70 ± 1.26
175
NIST Type K NIST Monograph –180 to 1372 –292 to 2502 ± 1.00 ± 1.80
175
NIST Type N NIST Monograph –200 to 1300 –328 to 2372 ± 1.00 ± 1.80
175
NIST Type R NIST Monograph 0 to 1768 32 to 3214 ± 1.50 ± 2.70
175

Emerson.com/Rosemount 45
Rosemount 848T December 2021

Table 10: Thermocouples — cold junction adds + 0.5 °C to listed accuracy (continued)

Input ranges Accuracy over range(s)


Sensor option Sensor reference
°C °F °C °F
NIST Type S NIST Monograph 0 to 1768 32 to 3214 ± 1.40 ± 2.52
175
NIST Type T NIST Monograph –200 to 400 –328 to 752 ± 0.70 ± 1.26
175
DIN L DIN 43710 –200 to 900 –328 to 1652 ± 0.70 ± 1.26
DIN U DIN 43710 –200 to 600 –328 to 1112 ± 0.70 ± 1.26
w5Re/W26Re ASTME 988-96 0 to 2000 32 to 3632 ± 1.60 ± 2.88
Type L GOST R.8.585-2001 –200 to 800 –328 to 1472 ±0.71 ±1.28
Terminal –50 to 85 –58 to 185 ±3.50 ±6.30
Temperature
Input units
Ohm input 0 to 2000 ohms ±0.90 ohms
Millivolt input –10 to 100 mV ±0.05 mV
1000 mV input –10 to 1000 mV ±1.0 mV
4–20 mA (Rosemount)(1) 4–20 mA ±0.01 ±0.01 mA
4–20 mA (NAMUR)(1) 4–20 mA ±0.01 ±0.01 mA
(1) Requires the S002 option code.

Analog sensors 4–20 mA


Two types of alarm levels are available with 4–20 mA sensors on the Rosemount 848T. These types must be ordered with the S002
option code complete with an analog connector kit. The alarm levels, accuracy for each type are listed in the table below.
Table 11: Analog sensors

Sensor option Alarm levels Accuracy


4–20 mA (Rosemount Standard) 3.9 to 20.8 mA ± 0.01 mA
4–20 mA (NAMUR) 3.8 to 20.5 mA ± 0.01 mA

Ambient temperature effect


Transmitters may be installed in locations where the ambient temperature is between -40 °F (-40 °C) and 185 °F (85 °C).
Table 12: RTD

NIST type Accuracy per 1.8 °F (1.0 °C) change in Temperature range (°C)
ambient temperature (1)(2)
Pt 50 (α = 0.003910) 0.004 °C (0.0072 °F) N/A
Pt 100 (α = 0.00391) 0.002 °C (0.0036 °F) N/A
Pt 100 (α = 0.00385) 0.003 °C (0.0054 °F) N/A
Pt 100 (α = 0.003916) 0.003 °C (0.0054 °F) N/A
Pt 200 (α = 0.00385) 0.004 °C (0.0072 °F) N/A
PT 200 (α = 0.003916) 0.004 °C (0.0072 °F) N/A

46 Emerson.com/Rosemount
December 2021 Rosemount 848T

Table 12: RTD (continued)

NIST type Accuracy per 1.8 °F (1.0 °C) change in Temperature range (°C)
ambient temperature (1)(2)
Cu 10 0.03 °C (0.054 °F) N/A
Pt 500 0.003 °C (0.0054 °F) N/A
Pt 1000 0.003 °C (0.0054 °F) N/A
Cu 100 (a=428) 0.002 °C (0.0036 °F) N/A
Cu 50 (a=428) 0.004 °C (.0072 °F) N/A
Cu 100 (a=426) 0.002 °C (0.0036 °F) N/A
Cu 50 (a=426) 0.004 °C (.0072 °F) N/A
Ni 120 0.003 °C (0.0054 °F) N/A
(1) Change in ambient is in reference to the calibration temperature of the transmitter 68 °F (20 °C) typical from the factory).
(2) Ambient temperature affects valid specifications over a minimum temperature span of 50 °F (28 °C).

Table 13: Thermocouple (R = the value of the reading)

NIST type Accuracy per 1.8 °F (1.0 °C) change in Temperature range (°C)
ambient temperature (1)(2)
Type B 0.014 °C R ≥ 1000
0.032 °C - (0.0025% of [R - 300]) 300 ≤ R < 1000
0.054 °C - (0.011% of [R - 100]) 100 ≤ R < 300
Type E 0.005 °C + (0.00043% of R) All
Type J, Din Type L 0.0054 °C + (0.00029% of R) R≥0
0.0054 °C + (0.0025% of |R|) R<0
Type K 0.0061 °C + (0.00054% of R) R≥0
0.0061 °C + (0.0025% of |R|) R<0
Type N 0.0068 °C + (0.00036% of R) All
Type R, Type S 0.016 °C R ≥ 200
0.023 °C - (0.0036% of R) R < 200
Type T, DIN Type U 0.0064 °C R≥0
0.0064 °C - (0.0043% of |R|) R<0
GOST Type L 0.007 °C R≥0
0.007 °C + (0.003% of IRI) R<0
Input units
Ohm input 0.0084 ohms N/A
100 mV input 0.0005 mV N/A
1000 mV input 0.005 mV N/A
4–20 mA (Rosemount) 0.0001 mA N/A
4–20 mA (NAMUR) 0.0001 mA N/A
(1) Change in ambient is in reference to the calibration temperature of the transmitter 68 °F (20 °C) typical from the factory).
(2) Ambient temperature affects valid specifications over a minimum temperature span of 50 °F (28 °C).

Emerson.com/Rosemount 47
Rosemount 848T December 2021

Ambient temperature notes


Examples
When using a Pt 100 (α = 0.00385) sensor input at 30 °C ambient temperature:
■ Ambient temperature effects: 0.003 °C x (30 – 20) = 0.03 °C
■ Worst case error: Sensor accuracy + Ambient temperature effects = 0.30 °C + 0.03 °C = 0.33 °C
■ Total probable error:
0.302 + 0.032 − 0.30 °C

48 Emerson.com/Rosemount
December 2021 Rosemount 848T

Product certifications
Rev 1.11

Telecommunication compliance
All wireless devices require certification to ensure that they adhere to regulations regarding the use of the RF spectrum. Nearly
every country requires this type of product certification. Emerson is working with governmental agencies around the world to
supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage.

FCC and IC
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause
harmful interference. This device must accept any interference received, including interference that may cause undesired
operation. This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons.

European Directive Information


A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC
Declaration of Conformity can be found at Emerson.com/Rosemount.

Ordinary Location Certification


As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical,
and fire protection requirements by FM Approvals, a nationally recognized test laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).

North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in
Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature
class. This information is clearly defined in the respective codes.

USA

I5 USA Intrinsically Safe


Certificate 3034378
Standards FM Class 3600:1998, FM Class 3610:2010, FM Class 3810:2005, NEMA®-250:1997, ANSI/ISA-60079-0:2009, ANSI/
ISA-60079-11:2009, IEC 60529:2004
Markings IS CL I, DIV 1, GP A, B, C, D; NI CL I, DIV 2, GP A, B, C, D; IS CL I, Zone 0, AEx ia IIC T4(–50 °C ≤ Ta ≤ +70 °C) , when
installed per Rosemount drawing 00849-1000; Type 4X; IP66

See Table at the end of the Product Certifications section for entity parameters.

Emerson.com/Rosemount 49
Rosemount 848T December 2021

N5 USA Class 1, Division 2, and Dust Ignition-proof


Certificate 3034378
Standards FM Class 3600:1998, FM Class 3610:2010, FM Class 3810:2005, NEMA-250:1997, IEC 60529:2004
Markings NI CL I, DIV 2, GP A, B, C, D; T4(–50 °C ≤ Ta ≤ +70 °C); DIP CL II/III DIV 1, GP E, F, G; T5 (–50 °C ≤ Ta ≤ +85 °C); when
installed per Rosemount drawing 00849-1000; Type 4X; IP66

Canada

I6 Canada Intinsic Safety


Certificate 1261865
Standards CSA Std. C22.2 No. 25-1966, CSA Std. C22.2 No. 30-M1986, CAN/CSA C22.2 No. 94-M91, CSA C22.2 No. 142-
M1987, CAN/CSA C22.2 No. 157-92, CSA Std. C22.2 No. 213-M1987, CSA Std. C22.2 No 60529:05
Markings Intrinsically Safe for CL I, DIV 1 GP A, B, C, D; Suitable for CL I DIV 2 GP A, B, C, D; when installed per Rosemount
drawing 00849-1016; T3C; Type 4X, IP66

See Table at the end of the Product Certifications section for entity parameters.

N6 Canada Class I, Division 2


Certificate 1261865
Standards CSA Std. C22.2 No. 25-1966, CSA Std. C22.2 No. 30-M1986, CAN/CSA C22.2 No. 94-M91, CSA C22.2 No. 142-
M1987, CSA Std. C22.2 No. 213-M1987, CSA Std. C22.2 No 60529:05
Markings Suitable for CL I DIV 2 GP A, B, C, D; T3C; when installed per Rosemount drawing 00849-1016; Type 4X, IP66

Europe

I1 ATEX Intrinsic Safety


Certificate Baseefa09ATEX0022X
Standards EN 60079-0:2012, EN 60079-11:2012
Markings
II 1 G Ex ia IIC T4/T5 Ga T4(–60 °C ≤ Ta ≤ +70 °C), T5(–60 °C ≤ Ta ≤ +40 °C)

See Table at the end of the Product Certifications section for entity parameters.

Special Conditions for Safe Use (X):


1. The surface resistivity of the antenna is greater than 1 GΩ. To avoid electrostatic charge build-up, it must not be rubbed or
cleaned with solvents or a dry cloth.
2. The Model 701PBKKF Power Module or Intelligent Power Module 71008 may be replaced in a hazardous area. The Power
Modules have surface resistivity greater than 1 GΩ and must be properly installed in the wireless device enclosure. Care
must be taken during transportation to and from the point of installation to prevent electrostatic charge build-up.
3. The enclosure may be made from aluminum alloy and given a protective polyurethane paint finish; however, care should be
taken to protect it from impact or abrasion when located in a zone 0 area.

50 Emerson.com/Rosemount
December 2021 Rosemount 848T

International

I7 IECEx Intrinsic Safety


Certificate IECEx BAS 09.0004X
Standards IEC 60079-0:2011, IEC 60079-11:2011
Markings Ex ia IIC T5/T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C), T5(–60 °C ≤ Ta ≤ +40 °C)

See Table at the end of the Product Certifications section for entity parameters.

Special Conditions for Safe Use (X):


1. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic charge build-up, it must not be rubbed or
cleaned with solvents or a dry cloth.
2. The Model 701PBKKF Power Module or Intelligent Power Module 71008 may be replaced in a hazardous area. The Power
Modules have surface resistivity greater than 1 GΩ and must be properly installed in the wireless device enclosure. Care
must be taken during transportation to and from the point of installation to prevent electrostatic charge build-up.
3. The enclosure may be made from aluminum alloy with a protective polyurethane paint finish; however, care should be
taken to protect it from impact or abrasion when located in Zone 0.

Brazil

I2 Brazil Intrinsic Safety


Certificate UL-BR 15.0034X
Standards ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-11:2013
Markings Ex ia IIC T4/T5, T4(–60 °C ≤ Ta ≤ +70 °C), T5(–60 °C ≤ Ta ≤ +40 °C)

See Table at the end of the Product Certifications section for entity parameters.

Special Condition for Safe Use (X):


1. The surface resistance of the antenna is greater than 1 GΩ. To avoid electrostatic charge build-up, it must not be rubbed or
cleaned with solvents or a dry cloth.
2. The Model 701PBKKF Power Module, MHM-89004 Blue Power Module or Intelligent Power Module 71008 may be replaced
in a hazardous area. The power module has surface resistance greater than 1 GΩ and must be properly installed in the
wireless device enclosure. Care must be taken during transportation to and from the point of installation to prevent
electrostatic charge build-up.
3. The 848T enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should
be taken to protect it from impact or abrasion if located in areas that requires EPL Ga (Zone 0).

China

I3 China Intrinsic Safety


Certificate GYJ21.1125X
Markings Ex ia IIC T4/T5 Ga, T4(–60 °C ≤ Ta ≤ +70 °C), T5(–60 °C ≤ Ta ≤ +40 °C)

See Table at the end of the Product Certifications section for entity parameters.

Emerson.com/Rosemount 51
Rosemount 848T December 2021

Special Condition for Safe Use (X):


1. The surface resistance of the antenna is greater than 1 GΩ. To avoid electrostatic charge build-up, it must not be rubbed or
cleaned with solvents or a dry cloth.
2. The power module may be replaced in a hazardous area. The power module has surface resistance greater than 1 GΩ and
must be properly installed in the wireless device enclosure. Care must be taken during transportation to and from the point
of installation to prevent electrostatic charge build-up.
3. Manufacture-provided battery pack made up of two Tadiran TL-5920 Lithium Thionyl-Chloride primary cells should be used.
4. The product should be used with Ex-certified associated apparatus to establish explosion protection system that can be
used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of the product and
associated apparatus.
5. The cables between this product and associated apparatus should be shielded cables (the cables must have insulated
shield). The shield has to be grounded reliably in non-hazardous area.
6. End user is not permitted to change any components inside, but to settle the problem in conjunction with manufacturer to
avoid damage to the product.
7. When installation, use and maintenance of this product, observe following standards: GB3836.13-2013 “Electrical
apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres”
GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area
(other than mines)” GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and
maintenance of electrical installation (other than mines)” GB3836.18-2010 “Explosive Atmospheres Part 18: Intrinsically
Safe System GB50257-2014 “Code for construction and acceptance of electric device for explosion atmospheres and fire
hazard electrical equipment installation engineering”

EAC - Belarus, Kazakhstan, Russia

IM Technical Regulations Customs Union (EAC) Intrinsic Safety


Markings 0Ex ia IIC T4, T5 Ga X, T4(–60 °C ≤ Ta ≤ +70 °C), T5(–60 °C ≤ Ta ≤ +40 °C); IP66/IP67

See Table at the end of the Product Certifications section for entity parameters.

Japan

I4 Japan Intrinsic Safety


Certificate CML 19JPN2037X
Markings Ex ia IIC T4/T5 Ga (–60/40°C ≤ Ta≤ +40/70°C)

See Table at the end of the Product Certifications section for entity parameters.

Korea

IP Korea Intrinsic Safety


Certificate 10-KB4BO-0087X
Markings Ex ia IIC T5/T4, –60 °C ≤ Ta ≤ +40 °C(T5)/+70 °C(T4)

52 Emerson.com/Rosemount
December 2021 Rosemount 848T

Dimensional drawings for Rosemount 848T Wireless

5.55
(141,1)
6.81
(173)
2.20
(55,8) 3.46
(87,8)

7.0
(177,8)

3.00
(76,3)
6.38
(162)
10.22 3.978
(259,7) (101)

Dimensions are in inches (millimeters).

Emerson.com/Rosemount 53
Rosemount 848T December 2021

54 Emerson.com/Rosemount
December 2021 Rosemount 848T

Emerson.com/Rosemount 55
00813-0100-4697
Rev. SB
December 2021

For more information: www.emerson.com