Symmetra™ PX 160: Installation

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Symmetra™ PX 160

Maintenance Bypass Enclosure


Installation
SYWMBP96K160H2
12/2023

www.schneider-electric.com
Legal Information
The information provided in this document contains general descriptions, technical
characteristics and/or recommendations related to products/solutions.
This document is not intended as a substitute for a detailed study or operational and
site-specific development or schematic plan. It is not to be used for determining
suitability or reliability of the products/solutions for specific user applications. It is the
duty of any such user to perform or have any professional expert of its choice
(integrator, specifier or the like) perform the appropriate and comprehensive risk
analysis, evaluation and testing of the products/solutions with respect to the relevant
specific application or use thereof.
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this document are the property of Schneider Electric SE or
its subsidiaries. All other brands may be trademarks of their respective owner.
This document and its content are protected under applicable copyright laws and
provided for informative use only. No part of this document may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the
document or its content, except for a non-exclusive and personal license to consult it
on an "as is" basis.
Schneider Electric reserves the right to make changes or updates with respect to or in
the content of this document or the format thereof, at any time without notice.
To the extent permitted by applicable law, no responsibility or liability is
assumed by Schneider Electric and its subsidiaries for any errors or omissions
in the informational content of this document, as well as any non-intended use
or misuse of the content thereof.
Maintenance Bypass Enclosure

Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS .........................................................................................5
Safety Precautions .....................................................................................6
Electrical Safety....................................................................................8
Specifications ............................................................................................10
Compliance.............................................................................................. 11
Product Overview......................................................................................12
Installation ..................................................................................................14
Prepare for Cables ...................................................................................14
Mount the Maintenance Bypass Enclosure to the Wall .................................15
Connect the Power Cables ........................................................................15
Connect the Communication Cables ..........................................................17
Diagram...................................................................................................17

990-4907B-001 3
Important Safety Instructions — SAVE THESE
INSTRUCTIONS Maintenance Bypass Enclosure

Important Safety Instructions — SAVE THESE


INSTRUCTIONS
Read these instructions carefully and look at the equipment to become familiar
with it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.

The addition of this symbol to a “Danger” or “Warning” safety


message indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential


personal injury hazards. Obey all safety messages with this symbol
to avoid possible injury or death.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.

NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.

Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.

990-4907B-001 5
Important Safety Instructions — SAVE THESE
Maintenance Bypass Enclosure INSTRUCTIONS

Per IEC 62040-1: "Uninterruptible power systems (UPS) -- Part 1: Safety


Requirements," this equipment, including battery access, must be inspected,
installed and maintained by a skilled person.
The skilled person is a person with relevant education and experience to enable
him or her to perceive risks and to avoid hazards which the equipment can create
(reference IEC 62040-1, section 3.102).

Safety Precautions

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All safety instructions in this document must be read, understood and followed.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read all instructions in the Installation Manual before installing or working on
this UPS system.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the UPS system until all construction work has been completed
and the installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream breakers, battery breakers,
cabling, etc.) and environmental requirements. No responsibility is assumed
by Schneider Electric if these requirements are not respected.
• After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by Schneider Electric.
Failure to follow these instructions will result in death or serious injury.

6 990-4907B-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS Maintenance Bypass Enclosure

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection
against overcurrent), or
• NEC NFPA 70, or
• Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Install the UPS system in a temperature controlled indoor environment free
of conductive contaminants and humidity.
• Install the UPS system on a non-flammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or
radiant heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or cut holes for cables or conduits with the gland plates installed and
do not drill or cut holes in close proximity to the UPS.
Failure to follow these instructions will result in death or serious injury.

WARNING
HAZARD OF ARC FLASH
Do not make mechanical changes to the product (including removal of cabinet
parts or drilling/cutting of holes) that are not described in the Installation Manual.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

990-4907B-001 7
Important Safety Instructions — SAVE THESE
Maintenance Bypass Enclosure INSTRUCTIONS

NOTICE
RISK OF OVERHEATING
Respect the space requirements around the UPS system and do not cover the
product’s ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in equipment damage.

NOTICE
RISK OF EQUIPMENT DAMAGE
Do not connect the UPS output to regenerative load systems including
photovoltaic systems and speed drives.
Failure to follow these instructions can result in equipment damage.

Electrical Safety

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Electrical equipment must be installed, operated, serviced, and maintained
only by qualified personnel.
• The UPS system must be installed in a room with restricted access (qualified
personnel only).
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices.
• Turn off all power supplying the UPS system before working on or inside the
equipment.
• Before working on the UPS system, check for hazardous voltage between all
terminals including the protective earth.
• The UPS contains an internal energy source. Hazardous voltage can be
present even when disconnected from the utility/mains supply. Before
installing or servicing the UPS system, ensure that the units are OFF and
that utility/mains and batteries are disconnected. Wait five minutes before
opening the UPS to allow the capacitors to discharge.
• A disconnection device (e.g. disconnection circuit breaker or switch) must be
installed to enable isolation of the system from upstream power sources in
accordance with local regulations. This disconnection device must be easily
accessible and visible.
• The UPS must be properly earthed/grounded and due to a high leakage
current, the earthing/grounding conductor must be connected first.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
In systems where backfeed protection is not part of the standard design, an
automatic isolation device (backfeed protection option or other device meeting
the requirements of IEC/EN 62040–1 or UL1778 5th Edition – depending on
which of the two standards apply to your local area) must be installed to prevent
hazardous voltage or energy at the input terminals of the isolation device. The
device must open within 15 seconds after the upstream power supply fails and
must be rated according to the specifications.
Failure to follow these instructions will result in death or serious injury.

8 990-4907B-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS Maintenance Bypass Enclosure

When the UPS input is connected through external isolators that, when opened,
isolate the neutral or when the automatic backfeed isolation is provided external to
the equipment or is connected to an IT power distribution system, a label must be
fitted at the UPS input terminals, and on all primary power isolators installed
remote from the UPS area and on external access points between such isolators
and the UPS, by the user, displaying the following text (or equivalent in a language
which is acceptable in the country in which the UPS system is installed):

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and
check for hazardous voltage between all terminals including the protective
earth.
Failure to follow these instructions will result in death or serious injury.

990-4907B-001 9
Maintenance Bypass Enclosure Specifications

Specifications
Electrical
UPS rating 96 kVA 160 kVA

Input voltage (V) 380 400 415 380 400 415

Nominal input 154 146 141 256 243 234


current (A)

Maximum rated 169 160 155 281 267 258


input current
(340 V input )(A)

Input frequency 50/60


(Hz)

Maximum short- Rated conditional short-circuit current Icc: 30 kA symmetrical rms


circuit current Rated peak short-circuit current Ipk: 63 kA
(kA) Icc Device: NSX400F Mic2.3 3P 320 A setting (manufacturer: Schneider Electric) for 160 kVA, or
NSX250F TMD200 3P (manufacturer: Schneider Electric) for 96 kVA

Maximum short- Rated short-time withstand current Icw: 10 kA symmetrical rms


circuit withstand Rated peak withstand current Ipk: 26 kA
(kA) Icw Short-circuit withstand time: 3 cycles

Switch Sizes
Mains input switch Q1 (A) 400

UPS output switch Q2 (A) 250

Maintenance bypass switch Q3 (A) 250

Upstream Protection

NOTICE
For a maximum short-circuit withstand higher than 10 kA, it is mandatory to
install a circuit breaker (NSX250F TMD200 3P or NSX400F Mic2.3 3P 320 A
setting) upstream of the maintenance bypass enclosure.
Failure to follow these instructions can result in equipment damage.

UPS rating Required protection Max input current

96 kVA NSX250F TMD200 3P 169 A


160 kVA NSX400F Mic2.3 3P 320 A setting 281 A

Recommended Cable Sizes


NOTE: Use only copper conductors with a minimum rating for 90 °C.
NOTE: 30 ℃ ambient temperature, IEC standard 60364-5-52, Table A.52-4
(52-C3), "C" method of installation. If the ambient room temperature is higher
than 30 ℃, larger conductors are to be selected in accordance with the
correction factors of the IEC.

UPS rating 96 kVA UPS 160 kVA UPS

Input cable (L1, L2, L3, N, PE) (mm2) 70 120

Output cable (L1, L2, L3, N, PE) (mm2) 50 95

10 990-4907B-001
Specifications Maintenance Bypass Enclosure

UPS rating 96 kVA UPS 160 kVA UPS

Maintenance bypass to UPS input cable 70 120


(mm2)

UPS output to maintenance bypass cable 50 95


(mm2)

Weights and Dimensions


Weight (kg) Height (mm) Width (mm) Depth (mm)

Without packaging 90 1200 800 300

With packaging 105 1230 830 350

Environmental
Storage Operation

Temperature -25 °C to 55 °C 0 °C to 40 °C

Relative humidity 0 to 95% non-condensing

Elevation 0 to 15000 m 0 to 3000 m


Protection class IP20
Color Black

Torque
Torque (Nm) Screws

Mains input terminal block 23 M8 X 25 MSC HXG STL

Mains input to UPS terminal block 23 M8 X 25 MSC HXG STL

UPS output terminal block 23 M8 X 25 MSC HXG STL

System output terminal block 23 M8 X 25 MSC HXG STL

Compliance
Safety IEC 61439-1: 2020, Edition 3.0, Low-voltage switchgear and control gear assemblies - Part 1: General rules

IEC 61439-2: 2020, Edition 3.0, Low-voltage switchgear and control gear assemblies - Part 2: Power switchgear
and controlgear assemblies

Earthing system TN, TT, TNC, IT, TN-S, TNC-S

Protective class 1
Pollution degree 2

990-4907B-001 11
Maintenance Bypass Enclosure Product Overview

Product Overview
Front view (interior)

A. Cable entry
B. PE busbar
C. Q2 – UPS output switch
D. Q3 – Maintenance bypass switch
E. Q1 – Mains input switch
F. Q10 – LED protection breaker
G. LED H3 – OK to operate Q3 when light is ON
H. LED H2 – OK to operate Q2 when light is ON
I. Terminal block – signal connection to UPS

Site Planning
NOTE: Select a location for the maintenance bypass enclosure which
provides easy access to all breakers and internal components.
NOTE: Select a wall that is structurally sound and able to support the size and
weight of the maintenance bypass enclosure.

12 990-4907B-001
Product Overview Maintenance Bypass Enclosure

Clearance
Follow the listed clearance requirements and consult local codes for any
additional requirements.
The best location for the maintenance bypass enclosure is close to the UPS.

Front view

A. Minimum front clearance: 650 mm


B. Minimum enclosure–to–floor clearance: 600 mm
C. Minimum side clearance: 100 mm

990-4907B-001 13
Maintenance Bypass Enclosure Installation

Installation
Prepare for Cables
NOTE: All power cables must be connected on site. External power cables are
not supplied with the maintenance bypass enclosure.
NOTE: Schneider Electric recommends to create the necessary holes for
cable access before mounting the maintenance bypass enclosure to the wall.
NOTE: The size of the holes and glands must be adapted to fit the size of the
cables.
1. Open the front door of the enclosure.
2. Remove the front panel.
3. Remove the bottom plate.
4. Drill holes for cables in the bottom plate. Make sure that the hole locations
correspond to the connector locations in the enclosure.
5. Reinstall the bottom plate.

Front view

14 990-4907B-001
Installation Maintenance Bypass Enclosure

Mount the Maintenance Bypass Enclosure to the Wall


1. Measure and mark the four mounting hole locations on the wall.

2. Drill holes in each of the four marked locations and mount the anchor bolts.
3. Lift the maintenance bypass enclosure, position it against the backing and
line it up with the four holes/anchor bolts. Secure the enclosure with the four
bolts and flat washers.

Connect the Power Cables

NOTICE
For a maximum short-circuit withstand higher than 10 kA, it is mandatory to
install a circuit breaker (NSX250F TMD200 3P or NSX400F Mic2.3 3P 320 A
setting) upstream of the maintenance bypass enclosure.
Failure to follow these instructions can result in equipment damage.

990-4907B-001 15
Maintenance Bypass Enclosure Installation

1. Route the cables through the holes in the bottom plate of the maintenance
bypass enclosure.
2. Connect the UPS input cables (L1, L2, L3, N) to the UPS input terminals and
the PE cable to the PE bar.
3. Connect the AC input cables (L1, L2, L3, N) to the AC input terminal block
and the PE cable to the PE bar.
4. Connect the system output cables from the UPS (L1, L2, L3, N) to the system
output terminals and the PE cable to the PE bar.
5. Connect the UPS output cables (L1, L2, L3, N) to the UPS output terminals
and the PE cable to the PE bar.

16 990-4907B-001
Installation Maintenance Bypass Enclosure

Connect the Communication Cables


Located in Located in
maintenance UPS J2
bypass

Q1 1 1
2 2
Q2 3 3
4 4
Q3
5 5
6 6
From Q10 H2
L1 7 7 MBB
N 8 8 Dry
H3
contact
9 9
10 10
11
12
13
14

Diagram

NOTICE
For a maximum short-circuit withstand higher than 10 kA, it is mandatory to
install a circuit breaker (NSX250F TMD200 3P or NSX400F Mic2.3 3P 320 A
setting) upstream of the maintenance bypass enclosure.
Failure to follow these instructions can result in equipment damage.

990-4907B-001 17
Maintenance Bypass Enclosure Installation

18 990-4907B-001
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmason
France
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com

As standards, specifications, and design change from time to time,


please ask for confirmation of the information given in this publication.

© 2013 – 2023 Schneider Electric. All rights reserved.


990-4907B-001