ABB Short Form Motor Protection and Control
ABB Short Form Motor Protection and Control
The currents given below concern standard three-phase four-pole cage motors (1500 r.p.m. at 50 Hz 1800 r.p.m. at 60 Hz).
These values are given for guidance and may vary according to the motor manufacturer and depending on the number of poles.
IEC Motor nominal current: standardized values in blue colour UL / CSA Motor nominal current: standardized values
(according to IEC 60947-4-1 Annex G) (according to IEC 60947-4-1 Annex G and UL 508)
Motor Motor
power 220 V 230 V 240 V 380 V 400 V 415 V 440 V 500 V 660 V 690 V power 208 V 220-240 V 380-415 V 440-480 V 550-600 V
kW A A A A A A A A A A hp A A A A A
0.06 0.37 0.35 0.34 0.21 0.2 0.19 0.18 0.16 0.13 0.12 1/2 2.4 2.2 1.3 1.1 0.9
0.09 0.54 0.52 0.50 0.32 0.3 0.29 0.26 0.24 0.18 0.17 3/4 3.5 3.2 1.8 1.6 1.3
0.12 0.73 0.7 0.67 0.46 0.44 0.42 0.39 0.32 0.24 0.23 1 4.6 4.2 2.3 2.1 1.7
0.18 1 1 1 0.63 0.6 0.58 0.53 0.48 0.37 0.35 1-1/2 6.6 6 3.3 3 2.4
0.25 1.6 1.5 1.4 0.9 0.85 0.82 0.74 0.68 0.51 0.49 2 7.5 6.8 4.3 3.4 2.7
0.37 2.0 1.9 1.8 1.2 1.1 1.1 1 0.88 0.67 0.64 3 10.6 9.6 6.1 4.8 3.9
0.55 2.7 2.6 2.5 1.6 1.5 1.4 1.3 1.2 0.91 0.87 5 16.7 15.2 9.7 7.6 6.1
0.75 3.5 3.3 3.2 2.0 1.9 1.8 1.7 1.5 1.15 1.1 7-1/2 24.2 22 14 11 9
1.1 4.9 4.7 4.5 2.8 2.7 2.6 2.4 2.2 1.7 1.6 10 30.8 28 18 14 11
1.5 6.6 6.3 6 3.8 3.6 3.5 3.2 2.9 2.2 2.1 15 46.2 42 27 21 17
2.2 8.9 8.5 8.1 5.2 4.9 4.7 4.3 3.9 2.9 2.8 20 59.4 54 34 27 22
3 11.8 11.3 10.8 6.8 6.5 6.3 5.7 5.2 4 3.8 25 74.8 68 44 34 27
4 15.7 15 14.4 8.9 8.5 8.2 7.4 6.8 5.1 4.9 30 88 80 51 40 32
5.5 20.9 20 19.2 12.1 11.5 11.1 10.1 9.2 7 6.7 40 114 104 66 52 41
7.5 28.2 27 25.9 16.3 15.5 14.9 13.6 12.4 9.3 8.9 50 143 130 83 65 52
11 39.7 38 36.4 23.2 22 21.2 19.3 17.6 13.4 12.8 60 169 154 103 77 62
15 53.3 51 48.9 30.5 29 28 25.4 23 17.8 17 75 211 192 128 96 77
18.5 63.8 61 58.5 36.8 35 33.7 30.7 28 22 21 100 273 248 165 124 99
22 75.3 72 69 43.2 41 39.5 35.9 33 25.1 24 125 343 312 208 156 125
30 100 96 92 57.9 55 53 48.2 44 33.5 32 150 396 360 240 180 144
37 120 115 110 69 66 64 58 53 40.8 39 200 528 480 320 240 192
45 146 140 134 84 80 77 70 64 49.1 47 250 – 604 403 302 242
55 177 169 162 102 97 93 85 78 59.6 57 300 – 722 482 361 289
75 240 230 220 139 132 127 116 106 81 77 350 – 828 560 414 336
90 291 278 266 168 160 154 140 128 97 93 400 – 954 636 477 382
110 355 340 326 205 195 188 171 156 118 113 450 – 1030 – 515 412
132 418 400 383 242 230 222 202 184 140 134 500 – 1180 786 590 472
160 509 487 467 295 280 270 245 224 169 162
200 637 609 584 368 350 337 307 280 212 203
250 782 748 717 453 430 414 377 344 261 250
315 983 940 901 568 540 520 473 432 327 313
355 1109 1061 1017 642 610 588 535 488 370 354
400 1255 1200 1150 726 690 665 605 552 418 400
500 1545 1478 1416 895 850 819 745 680 515 493
560 1727 1652 1583 1000 950 916 832 760 576 551
630 1928 1844 1767 1116 1060 1022 929 848 643 615
710 2164 2070 1984 1253 1190 1147 1043 952 721 690
800 2446 2340 2243 1417 1346 1297 1179 1076 815 780
900 2760 2640 2530 1598 1518 1463 1330 1214 920 880
1000 3042 2910 2789 1761 1673 1613 1466 1339 1014 970
1SBC101589S0201
Motor protection and control
Manual motor starters, contactors and overload relays
1
Overview
2
Manual motor starters
3
B mini contactors
4
AS contactors with screw terminals
5
DRAS enclosed starter
6
AF and EK contactors with screw terminals
7
Overload relays
8
R contactors
9
General technical data
10
Index
11
Marketing material
For direct product details information, use product type or order code, ex:
Summary_1
www.abb.com/productdetails/AF09-30-10-13 or www.abb.com/productdetails/1SBL137001R1310
1/2 | ABB
1
HVAC, General Machinery, Rail, Critical Power, Wind, Solar, Marine and Water & Wastewater
1/4 | ABB
AF technology
Benefits
Reliable in all networks Four coils for the entire voltage range
The electronic system within the AF contactor rectifies the The AF contactor features both AC and DC support. With the
AC or DC control circuit voltage to a DC control voltage that complete AF contactor range, functionality is improved. Still,
is applied on the coil. The contactor is safely operated in an the total number of product variants compared to a conventi-
always optimized condition making it virtually noise free. onal range is reduced by 90 %. Only four coils are required to
cover 24 V AC, 20 V DC - 500 V AC/DC.
ABB | 1/5
Contactors and motor protection
Advanced but simple
Coil terminal access in the front More functionality without adding width
The AF contactor has its coil terminals accessible from the The AF116 ... AF2650 can take up to 2 side mounted auxiliary
front. The cables or bars do not have to be disconnected in contact blocks without adding to its width and are delivered
order to perform voltage measurement or servicing work. with 1 N.O. + 1 N.C. as standard.
1/6 | ABB
Contactors and motor protection
Mechanical features
Top-mounted Bottom-mounted
Easy-to-use accessories
Contactors up to 96 A offer free choice of coil terminal access
and can take side and front mounted auxiliary contact blocks.
All the accessories: Coil connection terminals, mechanical and
electrical interlocks and electronic timers are easily connected Additional LDC4 Front-mounted
through the snap-to-connect function. coil terminal block
ABB | 1/7
3-pole contactors Mini contactors Contactors for motor control and
IEC (1) AC-3 Rated operational power θ ≤ 60 °C (2), 400 V kW 4 5.5 4 5.5 7.5 4 5.5 7.5 11 15 18.5
UL/CSA 3-phase motor rating 480 V hp 3 5 5 7.5 10 5 7.5 10 15 20 25
AC Control supply Type B6 B7 AS09 AS12 AS16 AF09 AF12 AF16 AF26 AF30 AF38
DC Control supply Type BC6 BC7 ASL09 ASL12 ASL16 AF09 AF12 AF16 AF26 AF30 AF38
IEC AC-3 Rated operational current θ ≤ 60 °C (2), 400 V A 8.5 11.5 9 12 15.5 9 12 18 26 32 38
AC-1 Rated operational current θ ≤ 40 °C, 690 V A 20 (400 V) 20 (400 V) 22 24 24 25 28 30 45 50 50
UL/CSA General use rating 600 V A 12 (300 V) 16 20 20 20 25 28 30 45 50 50
NEMA NEMA Size — — 00 00 0 00 0 — 1 — —
(1) 1000 V IEC ratings available for AF80, AF96 and AF146 … AF2650 contactors.
(2) θ ≤ 55 °C for mini contactors and AF400 ... AF2650 contactors.
Main accessories
Auxiliary contact blocks Front mounting CAF6 CA3-10 (1 x N.O.) CA4-10 (1 x N.O.)
CA3-01 (1 x N.C.) CA4-01 (1 x N.C.)
Side mounting CA6 CAL4-11 (1 x N.O. + 1 x N.C.)
Timers Electronic TEF3-ON TEF4-ON
TEF3-OFF TEF4-OFF
Interlocking units (3) Mechanical VM3 VM4
(3) See available reversing contactors VB6, VB7 and VAS09 ... VAS16.
Overload relays
Thermal relays Class 10 T16 (0.10…16 A) T16 (0.10…16 A) TF42 (0.10…38 A)
(Class 10A for TF140, TA200DU)
Electronic relays Class 10E, 20E, 30E E16DU (0.10…18.9 A) EF19 (0.10…18.9 A) EF19 (0.10…18.9 A)
EF45 (9…45 A)
1/8 | ABB
power switching
18.5 22 30 37 45 55 75 75 90 110 132 160 200 200 250 315 400 — 475 560 — —
30 40 50 60 60 75 100 100 125 150 200 250 300 350 400 500 600 — 800 900 — —
AF40 AF52 AF65 AF80 AF96 AF116 AF140 AF146 AF190 AF205 AF265 AF305 AF370 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050 AF2650
AF40 AF52 AF65 AF80 AF96 AF116 AF140 AF146 AF190 AF205 AF265 AF305 AF370 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050 AF2650
AF40 AF52 AF65 AF80 AF96 AF116 AF140 AF146 AF190 AF205 AF265 AF305 AF370 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050 AF2650
40 53 65 80 96 116 140 146 190 205 265 305 370 400 460 580 750 — 860 1060 — —
70 100 105 125 130 160 200 225 275 350 400 500 600 600 700 800 1050 1260 1350 1650 2050 2650
60 80 90 105 115 160 200 200 250 300 350 400 520 550 650 750 900 1210 1350 1650 2100 2700
2 — — 3 — — 4 — — — 5 — — — 6 — 7 — — 8 — —
MS495 (45…100 A)
Ics up to 50 kA
1SBC101753S0201 - Rev. C
MO496 (32…100 A)
Ics up to 100 kA
MO450 (40…50 A) MO495
Ics up to 50 kA (63…100 A)
Ics up to 50 kA
ABB | 1/9
4-pole contactors Mini contactors
1
IEC AC-1 Rated operational current θ ≤ 40 °C, 690 V A 16 20
UL/CSA General use rating 600 V A 12 (300 V) 16
2 2 3 1 4 0
1/10 | ABB
Contactors
1
25 30 45 55 70 100 125 160 200 275 350 400 500 525 800 1000
25 30 45 55 60 80 105 160 175 230 250 300 350 420 540 —
AF09 AF16 AF26 AF38 AF40 AF52 AF80 AF116 AF140 AF190 AF205 AF265 AF305 AF370 — —
AF09 AF16 AF26 AF38 AF40 AF52 AF80 AF116 AF140 AF190 AF205 AF265 AF305 AF370 EK550 EK1000
AF09 AF16 AF26 AF38 AF40 AF52 AF80 AF116 AF140 AF190 AF205 AF265 AF305 AF370 EK550 EK1000
Contactor relays
3 3
A600, Q300 A600, Q600
2 2 3 1 4 0 2 2 3 1 4 0
Capacitor switching
1SBC101638S0201 - Rev. D
12.5 to 80 kvar
UA16..RA to UA110..RA types
UA16 to UA110 types
ABB | 1/11
2
Summary_2
2/0 | ABB
Manual motor starters
Overview 2/4
I CS up to 100 kA
MS132 manual motor starters 2/7
For direct product details information, use product type or order code, ex:
Summary_2
www.abb.com/productdetails/AF09-30-10-13 or www.abb.com/productdetails/1SBL137001R1310
ABB | 2/1
Manual motor starters
Benefits
2/2 | ABB
Manual motor starters
Features
1
1
2
2-1
3
4 2
5 4
6 3
2CDC131072C0201
ABB | 2/3
Manual motor starters
2/4 | ABB
MO132 MO450 MO495 MO496 MO325 MS132-T
2
- - - - Yes
Yes Yes Yes Yes -
- - - - Yes
ON/OFF/TRIP ON/OFF/TRIP ON/OFF/TRIP ON/OFF ON/OFF/TRIP
- - - - Yes
Yes Yes Yes - Yes
Yes Yes Yes Yes Yes
45 mm 55 mm 70 mm 54 mm 45 mm
0.16 ... 32 A 40 ... 50 A 63 ... 100 A 32 ... 100 A 0.4 ... 25 A 0.16 ... 32 A
- - - - 0.1 ... 25 A
-25 ... +60 °C -20 ... +60 °C -20 ... +60 °C -25 ... +50 °C -25 ... +60 °C * )
Standard range High performance range Modular DIN rail design Transformer protection
MO132, MO450, MO495 MO132, MO496 MO325 MS132-T
ABB | 2/5
MS116 manual motor starters
0.10 to 32 A – with thermal and electromagnetic protection
Description
Manual motor starters (MMS) are protection devices for the main circuit. They combine motor control and
protection in a single device. MMS are used mainly to switch motors manually ON/OFF and protect them
and the installation fuse-less against short-circuit, overload and phase failures. Fuse-less protection with
a manual motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by
2 switching off the motor within milliseconds.
2CDC241010F0011
MS116 is a compact and economic range for motor protection up to 15 kW (400 V) / 32 A in width of 45 mm.
Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and
a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and
single-phase applications. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, three-
phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes
MS116-16
are available as accessory.
Ordering details
Rated Setting Short-circuit Rated instan- Type Order code Weight
operational range breaking taneous short- (1 pcs)
power capacity ICS at circuit current
400 V 400 V AC setting li
AC-3
2CDC241001F0011
kW A kA A kg
0.03 0.10 ... 0.16 50 2.00 1) MS116-0.16 1SAM250000R1001 0.225
0.06 0.16 ... 0.25 50 3.10 1) MS116-0.25 1SAM250000R1002 0.225
0.09 0.25 ... 0.40 50 5.00 1) MS116-0.4 1SAM250000R1003 0.225
MS116-25 0.12 0.40 ... 0.63 50 7.90 1) MS116-0.63 1SAM250000R1004 0.225
0.25 0.63 ... 1.00 50 12.5 1) MS116-1.0 1SAM250000R1005 0.225
0.55 1.00 ... 1.60 50 20.0 1) MS116-1.6 1SAM250000R1006 0.265
0.75 1.60 ... 2.50 50 31.3 1) MS116-2.5 1SAM250000R1007 0.265
1.5 2.50 ... 4.00 50 50.0 MS116-4.0 1SAM250000R1008 0.265
2.2 4.00 ... 6.30 50 78.8 MS116-6.3 1SAM250000R1009 0.265
4.0 6.30 ... 10.0 50 150 MS116-10 1SAM250000R1010 0.265
5.5 8.00 ... 12.0 25 180 MS116-12 1SAM250000R1012 0.265
2CDC241013F0011
1.7 0.07"
1.38"
2.95"
1.77"
3.54"
3.85"
1.77"
2.95"
35 1.38"
2.3"
2.3"
45
35
75
90
27.5 1.1"
57.8
97.8
45
75
27.5 1.1"
57.8
2CDC131062C0201_1s10
2CDC242002F0010
2CDC242001F0011
14 0.55" 14 0.55"
45 1.77" 14 0.55" 14 0.55"
45 1.77"
MS116 ≤ 16 A & MS116-HKF1-11 ≤ 16 A MS116 ≥ 20 A & MS116-HKF1-11 ≥ 20 A
2/6 | ABB
MS132 manual motor starters
0.10 to 32 A – with thermal and electromagnetic protection
Description
Manual motor starters (MMS) are protection devices for the main circuit. They combine motor control and
protection in a single device. MMS are used mainly to switch motors manually ON/OFF and protect them and
the installation fuse-less against short-circuit, overload and phase failures. Fuse-less protection with a manual
motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by switching off
the motor within milliseconds. 2
MS132 is a compact and powerful range for motor protection up 15 kW (400 V) / 32 A in width of 45 mm. This
1SBC101232F0010
type has also a clear and reliable indication of fault in a separate window in the event of short-circuit tripping.
Further features are the build-in disconnect function, temperature compensation, trip-free mechanism
and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three-
and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary
MS132-10 contacts, signaling contacts, undervoltage releases, shunt trips, three-phase bus bars, power in-feed
blocks.
Ordering details
Rated Setting Short-circuit Rated instan- Type Order code Weight
operational range breaking taneous short- (1 pcs)
power capacity ICS at circuit current
400 V 400 V AC setting li
AC-3
2CDC241001F0011
kW A kA A kg
0.03 0.10 … 0.16 100 2.00 1) MS132-0.16 1SAM350000R1001 0.215
0.06 0.16 … 0.25 100 3.10 1) MS132-0.25 1SAM350000R1002 0.215
0.09 0.25 … 0.40 100 5.00 1) MS132-0.4 1SAM350000R1003 0.215
0.12 0.40 … 0.63 100 7.90 1) MS132-0.63 1SAM350000R1004 0.215
MS132-32
0.25 0.63 … 1.00 100 12.5 1) MS132-1.0 1SAM350000R1005 0.215
0.55 1.00 … 1.60 100 20.0 1) MS132-1.6 1SAM350000R1006 0.265
0.75 1.60 … 2.50 100 31.3 1) MS132-2.5 1SAM350000R1007 0.265
1.5 2.50 … 4.00 100 50.0 MS132-4.0 1SAM350000R1008 0.265
2.2 4.00 … 6.30 100 78.8 MS132-6.3 1SAM350000R1009 0.265
4.0 6.30 … 10.0 100 150 MS132-10 1SAM350000R1010 0.265
5.5 8.00 … 12.0 100 180 MS132-12 1SAM350000R1012 0.310
2CDC241014F0011
97.8 3.85"
75 2.95"
45 1.77"
35 1.38"
35 1.38"
45" 1.77"
3.54"
2.95"
2CDC131062C0201_2s10
75
90
2CDC242015F0009
2CDC242016F0009
45 1.77" 45 1.77"
MS132 ≤ 10 A MS132 ≥ 12 A
ABB | 2/7
MO132 manual motor starters magnetic only
0.16 to 32 A – with electromagnetic protection
Description
Manual motor starters magnetic only are electromechanical protection devices for the main circuit. They are
used mainly to switch motors manually ON/OFF and protect them fuse-less against short-circuit.
Fuse-less protection with a manual motor starter saves costs, space and ensures a quick reaction under
short-circuit condition, by switching off the motor within milliseconds. Fuse-less starter combinations are setup
2 together with contactors and overload relays.
2CDC241009F0011
Ordering details
Rated Rated Short-circuit Rated instan- Type Order code Weight
operational operational breaking taneous short- (1 pcs)
MO132-6.3 power current capacity ICS at circuit current
400 V 400 V AC setting li
AC-31)
kW A kA A kg
0.03 0.16 100 2.00 2) MO132-0.16 1SAM360000R1001 0.215
0.06 0.25 100 3.10 2) MO132-0.25 1SAM360000R1002 0.215
0.09 0.40 100 5.00 2) MO132-0.4 1SAM360000R1003 0.215
0.12 0.63 100 7.90 2) MO132-0.63 1SAM360000R1004 0.215
2CDC241008F0011
72.2 2.84"
81.25 3.2"
1.5 0.06" 5.5 0.22" 43.3 0.22"
72.4 2.85"
97.8 3.85"
75 2.95"
45 1.77"
35 1.38"
35 1.38"
45" 1.77"
3.54"
2.95"
75
90
2CDC131062C0201_3s10
2CDC242005F0011
2CDC242006F0011
45 1.77" 45 1.77"
MO132 ≤ 10 A MO132 ≥ 12 A
2/8 | ABB
MS132-T circuit breakers for transformer protection
0.10 to 25 A – with thermal and electromagnetic protection
Description
Circuit breakers for transformer protection are electro mechanical protection devices specially designed to
protect control transformers on the primary side. They allow fuse-less protection against overload and short-
circuit, saving space and cost and ensuring a quick reaction under short-circuit condition by switching off
the transformer within milliseconds. The short-circuit current setting is fixed to 20 times the operating current
to handle the high inrush current generated by transformers. The device allows manual connection and 2
2CDC241001F0014
Ordering details
Setting range Short-circuit Rated instantane- Type Order code Weight
breaking ous short-circuit (1 pce)
2CDC241002F0014
97.8 3.85"
75 2.95"
45 1.77"
35 1.38"
35 1.38"
45" 1.77"
3.54"
2.95"
75
90
2CDC131062C0201_4s10
2CDC242015F0009
2CDC242016F0009
45 1.77" 45 1.77"
MS132T ≤ 10 A MS132T ≥ 12 A
ABB | 2/9
MS116, MS132, MO132, MS132-T
Main accessories
HK1
2 SK1
HK1
MS116
MO132
HK1
AA1
HKF1
2CDC246001F0013
UA1
Manual motor starter with accessories (MS132) and circuit breaker for transformer protection (MS132-T)
HK1
SK1
HK1
HK1
SK1
MS132
MS132-T HK1
CK1
CK1
AA1
HKF1
1SBC500311F0000
2CDC131050C0201_1s9
UA1
2/10 | ABB
MS116, MS132, MO132, MS132-T
Main accessories
1SBC101208F0014
Description
MMS and MS132-T can be equipped with auxiliary contacts for lateral/front mounting, signaling contact
for lateral mounting, undervoltage release and shunt trips. Two different signaling contacts are available.
The accessories can be fitted wiring free and without tools. A variety of combinations is possible as
HKF1-11 required for the application. The auxiliary contacts change position with the main contacts. The signaling
contact SK signals tripping regardless if it was caused by short-circuit or overload. The signaling contact 2
CK signals tripping in case it was caused by short-circuit. Undervoltage release are used for remote
tripping of the manual motor starter especially for emergency stop circuits. Shunt trips release the MMS
used for remote tripping.
Ordering details
Suitable for Auxiliary Auxiliary Description Type Order code Pkg Weight
contacts contacts qty (1 pce)
1SBC101209F0014
N.O. N.C.
pce kg
Auxiliary contacts – mountable on the front
HK1-11
MS116, MS132, 1 1 HKF1-11 1SAM201901R1001 10 0.015
MO132, 2 0 HKF1-20 1SAM201901R1002 10 0.015
MS132-T
Auxiliary contacts – mountable on the right
MS116, MS132, 1 1 max. 2 pieces HK1-11 1SAM201902R1001 2 0.035
MO132, 2 0 max. 2 pieces HK1-20 1SAM201902R1002 2 0.035
MS132-T
0 2 max. 2 pieces HK1-02 1SAM201902R1003 2 0.035
2 0 with lead contacts HK1-20L 1SAM201902R1004 2 0.035
1SBC101210F0014
CK1-11
3.54"
42.1 1.66"
90
2CDC131050C0201_2s9
2CDC242001F0012
HK1
ABB | 2/11
MS116, MS132, MO132, MS132-T
Main accessories
Ordering details
Suitable for Rated control supply voltage Type Order code Pkg Weight
qty (1 pce)
50 Hz 60 Hz
V AC V AC pce kg
2
Shunt trips – mountable on the left
MS116, MS132, 20 ... 24 20 ... 24 AA1-24 1SAM201910R1001 1 0.100
1SBC101211F0014
37 1.46"
90
45
2CDC131050C0201_3s9
2CDC242002F0012
70 2.76"
AA1, UA1
2/12 | ABB
MS116, MS132, MO132
Main accessories
PS1-..-65 PS1-..-100
2
S1-M1-25
BS1-3
PS1-..-65
2CDC242020F0013
2CDC242021F0013
SA1
2CDC131050C0201_6s9
ABB | 2/13
MS116, MS132, MO132, MS132-T
Main accessories
Description
Three-phase busbars ensure a quick and safe connection and are therefore a cost effective solution.
2CDC241017F0010
A variety of different three-phase busbars up to 100 A are in the assortment. Between 2 and 5 manual
motor starters with none, one or two lateral auxiliary contacts can be connected. Different three-phase
feeder terminals are available according to the application.
2 Phase connecting links and phase power infeed blocks are also available for single-phase applications.
PS1-2-0-65 Ordering details
Suitable for Rated Number of Number of Type Order code Pkg Weight
2CDC241014F0010
Suitable for Rated Rated cross Mounting Type Order code Pkg Weight
SA2 operational section form qty (1 pce)
current
A mm² pce kg
Three-phase feeder terminals
MS116, 65 25 Flat S1-M1-25 1SAM201907R1101 10 0.038
MS132, 65 25 High S1-M2-25 1SAM201907R1102 10 0.051
MO132
65 25 UL type E S1-M3-25 1SAM201907R1103 10 0.042
SK0108B91
and IEC
100 35 UL type E S1-M3-35 1SAM201913R1103 10 0.060
SA1 and IEC
2CDC241004F0014
S1-PB1-25
2/14 | ABB
MS116, MS132, MO132
Main accessories
Description
IB132 are IP65 enclosures for single MMS installation. Additional mounting of auxiliary and signaling
contacts, shunt trips and undervoltage release is possible. The handle is lockable in OFF position. For
detailed specification see installation instruction.
DMS132 are IP65 door mounting kits for MMS installation in any enclosure. Additional mounting of
2
2CDC241004F0010
auxiliary, signaling, shunt trips and undervoltage release is possible. The handle is lockable in OFF
position. For detailed specification see installation instruction.
Ordering details
IB132-Y Suitable for Description Color Type Order code Pkg Weight
qty (1 pce)
pce kg
IP65 enclosures (UL: Type 12)
MS116, MS132, Padlockable max. Yellow/red IB132-Y 1SAM201911R1011 1 0.370
MO132 3 padlocks with Grey/black IB132-G 1SAM201911R1010 1 0.370
bail diameter 4 ...
2CDC241003F0010
6.5 mm
DMS132-Y
2CDC241001F0010
DMS132-G
I ON
183 7.2"
174 6.85"
194 7.64"
0
OFF
2CDC242011F0011
IB132
I ON
121 4.76"
0
OFF
2CDC131050C0201_9s9
2CDC242012F0011
116.15 4.57"
DMS132
ABB | 2/15
MS450, MS495, MS497 manual motor starters
22 to 100 A – with thermal and electromagnetic protection
Description
Manual motor starters (MMS) are protection devices for the main circuit. They combine motor control and
protection in a single device. MMS are used mainly to switch motors manually ON/OFF and protect them
and the installation fuse-less against short-circuit, overload and phase failures. Fuse-less protection with
a manual motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by
2 switching off the motor within milliseconds.
Further features are the build-in disconnect function, temperature compensation, trip-free mechanism
2CDC241004F0009
and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three-
and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary
contacts, signalling contacts, undervoltage releases, shunt trips, three-phase busbars, power in-feed
blocks are available as accessory.
MS450-40
Ordering details
Rated Setting Short-circuit Rated instan- Type Order code Weight
operational range breaking taneous short- (1 pcs)
power capacity ICS at circuit current
400 V 400 V AC setting li
AC-3
kW A kA A kg
MS450 manual motor starters
18.5 28.0 … 40.0 25 520.00 MS450-40 1SAM450000R1005 1.047
1SBC101184F0014
MS497-100
45 1.77"
85 3.35"
130 5.12"
140 5.51"
155 6.10"
45 1.77"
165 6.50"
116 4.57"
150 5.91"
2CDC131042C0201_1s4
2CDC242013F0011
2CDC242014F0011
30 1.18" 8 0.32"
5 0.20" 109 4.29" 30 1.18" 7 0.28"
55 2.17" 127 5.0" 5 0.20" 132 5.20"
132 5.2" 70 2.56" 153 6.02"
144 5.67" 169 6.65"
2/16 | ABB
MO450, MO495, MO496 manual motor starters magnetic only
32 to 100 A – with electromagnetic protection
Description
The manual motor starter magnetic only is used to manually switch on and off motors and to protect them
reliably and without the need for a fuse from short-circuits.
Further features are the build-in disconnect function, trip-free mechanism and a rotary handle with a clear
switch position indication. The manual motor starter magnetic only is suitable for three- and single-phase
applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signalling 2
contacts, undervoltage releases, shunt trips, three-phase busbars, power in-feed blocks are available as
accessory.
Ordering details
ST02501
1)
For overload protection of motors, an appropriate thermal or electronic overload relay must be used
MO496-100
45 1.77"
85 3.35"
130 5.12"
140 5.51"
155 6.10"
45 1.77"
165 6.50"
116 4.57"
150 5.91"
2CDC242015F0011
2CDC242016F0011
2CDC131038C0201_1s4
30 1.18" 8 0.32"
5 0.20" 109 4.29" 30 1.18" 7 0.28"
55 2.17" 127 5.0" 5 0.20" 132 5.20"
132 5.2" 70 2.56" 153 6.02"
144 5.67" 169 6.65"
ABB | 2/17
MS45x, MS49x, MO45x, MO49x manual motor starters
Main accessories
2CDC242025F0011
MO49x
MO49x
2CDC242025F0011
2CDC131051C0201_1s6
2/18 | ABB
MS45x, MS49x, MO45x, MO49x manual motor starters
Main accessories
2CDC241026F0011
Description
Manual motor starters can be equipped with auxiliary contacts for lateral/front mounting, signalling contact
for lateral mounting, undervoltage release and shunt trips. The accessories can be fitted wiring free and
HK4-11
without tools. A variety of combinations is possible as required for the application. The auxiliary contacts
change position with the main contacts. Undervoltage release are used for remote tripping of the manual
motor starter especially for emergency stop circuits. Shunt trips release the MMS used for remote tripping. 2
Ordering details
Suitable Auxiliary Auxiliary Description Type Order code Pkg Weight
for con- con- qty (1 pcs)
tacts tacts
N.O. N.C.
kg
2CDC241022F0011
Suitable Rated control supply Frequency Type Order code Pkg Weight
for voltage qty (1 pcs)
V Hz kg
Shunt trip units – mountable on the right
MS45x, 20 ... 24 50/60 AA4-24 1SAM401907R1001 1 0.135
MS49x, 90 ... 110
2CDC241023F0011
UA4-110
2CDC131051C0201_2s6
ABB | 2/19
MS45x, MS49x, MO45x, MO49x manual motor starters
Main accessories
Description
2CDC241003F0012
Three-phase busbars ensure a quick and safe connection and are therefor a cost effective solution.
A variety of different three-phase busbars up to 108 A are in the assortment. Between 2 and 4 manual
motor starter with none or two lateral auxiliary contacts can be connected.
2 Ordering details
PS4-2-0 Suitable for Rated opera- Number of Number of Type Order code Pkg Weight
tional current MMS lateral aux. qty (1 pcs)
2CDC241004F0012
A kg
Three-phase busbars
MS450, 108 A 2 0 PS4-2-0 1SAM401911R1001 5 0.134
MO450 108 A 3 0 PS4-3-0 1SAM401911R1002 5 0.206
PS4-3-0 108 A 4 0 PS4-4-0 1SAM401911R1003 5 0.280
108 A 2 1 PS4-2-2 1SAM401911R1004 5 0.148
108 A 3 1 PS4-3-2 1SAM401911R1005 5 0.250
2CDC241005F0012
PS4-4-0 Suitable for Rated opera- Rated cross Mounting Type Order code Pkg Weight
tional current section form qty (1 pcs)
A mm² kg
Three-phase feeder terminals
2CDC241023F0013
SA2
Suitable for Description Type Order code Pkg Weight
qty (1 pcs)
kg
MS450, MO450 Protection cover for busbar BS4-3 1SAM401911R1008 10 0.001
Disconnector module TB450 1SAM401910R1001 1 0.315
Terminal shroud KA450 1SAM401908R1001 1 0.154
MS495, MS497, Terminal shroud KA495 1SAM501901R1001 10 0.018
MO495, MO496 Terminal shroud KA495C 1) 1SAM501902R1001 10 0.038
Terminal insulation barrier for DX495 1SAM401912R1001 1 0.154
UL508E
MS450, MS495, MS497, Padlock + two keys SA2 GJF1101903R0002 10 0.020
MO450, MO495, MO496
1)
Is plugged onto the housing after removing the box terminals, if using cable lugs.
2CDC131051C0201_5s6
2/20 | ABB
MS325 manual motor starters
0.10 to 25 A – with thermal and electromagnetic protection
Description
Manual motor starters (MMS) are protection devices for the main circuit. They combine motor control and
protection in a single device. MMS are used mainly to switch motors manually ON/OFF and protect them and
the installation fuse-less against short-circuit, overload and phase failures. Fuse-less protection with a manual
motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by switching off
the motor within milliseconds.
2
2CDC241500F0009
MS325 is a compact and powerful range for motor protection up to 12.5 kW (400 V) / 25 A in width of
54 mm with modular DIN rail design. Further features are the build-in disconnect function, temperature
compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The
manual motor starters are suitable for three- and single-phase applications. Auxiliary contacts, signalling
MS325-16 contacts, undervoltage releases, shunt trips, three-phase busbars, power in-feed blocks are available as
accessories.
Ordering details
Rated Setting Short-circuit Rated instan- Type Order code Weight
operational range breaking taneous short- (1 pce)
power capacity ICS at circuit current
400 V 400 V AC setting li
AC-3
kW A kA A kg
0.03 0.10 … 0.16 100 1.56 MS325-0.16 1SAM150000R1001 0.280
0.06 0.16 … 0.25 100 2.44 MS325-0.25 1SAM150000R1002 0.280
0.09 0.25 … 0.40 100 3.9 MS325-0.4 1SAM150000R1003 0.280
0.12 0.40 … 0.63 100 6.14 MS325-0.63 1SAM150000R1004 0.280
0.25 0.63 … 1.00 100 11.5 MS325-1 1SAM150000R1005 0.310
0.55 1.00 … 1.60 100 18.4 MS325-1.6 1SAM150000R1006 0.340
0.75 1.60 … 2.50 100 28.75 MS325-2.5 1SAM150000R1007 0.340
1.5 2.50 … 4.00 100 50 MS325-4 1SAM150000R1008 0.340
2.2 4.00 … 6.30 100 78.75 MS325-6.3 1SAM150000R1009 0.340
4.0 6.30 … 9.00 100 135 MS325-9 1SAM150000R1010 0.340
5.5 9.00 … 12.5 75 180 MS325-12.5 1SAM150000R1011 0.340
7.5 12.5 … 16.0 60 240 MS325-16 1SAM150000R1012 0.340
9.0 16.0 … 20.0 55 300 MS325-20 1SAM150000R1013 0.340
12.5 20.0 … 25.0 50 375 MS325-25 1SAM150000R1014 0.340
0.03 0.10 … 0.16 100 1.56 MS325-0.16-HKF11 1SAM150005R0001 0.300
0.06 0.16 … 0.25 100 2.44 MS325-0.25-HKF11 1SAM150005R0002 0.300
0.09 0.25 … 0.40 100 3.9 MS325-0.4-HKF11 1SAM150005R0003 0.300
0.12 0.40 … 0.63 100 6.14 MS325-0.63-HKF11 1SAM150005R0004 0.300
0.25 0.63 … 1.00 100 11.5 MS325-1-HKF11 1SAM150005R0005 0.330
0.55 1.00 … 1.60 100 18.4 MS325-1.6-HKF11 1SAM150005R0006 0.360
0.75 1.60 … 2.50 100 28.75 MS325-2.5-HKF11 1SAM150005R0007 0.360
1.5 2.50 … 4.00 100 50 MS325-4-HKF11 1SAM150005R0008 0.360
2.2 4.00 … 6.30 100 78.75 MS325-6.3-HKF11 1SAM150005R0009 0.360
4.0 6.30 … 10.0 100 135 MS325-9-HKF11 1SAM150005R0010 0.360
5.5 8.00 … 12.0 75 180 MS325-12.5-HKF11 1SAM150005R0011 0.360
7.5 10.0 … 16.0 60 240 MS325-16-HKF11 1SAM150005R0012 0.360
9.0 16.0 … 20.0 55 300 MS325-20-HKF11 1SAM150005R0013 0.360
12.5 20.0 … 25.0 50 375 MS325-25-HKF11 1SAM150005R0014 0.360
43 1.69"
1.77"
35 1.38"
45 1.77"
35 1.38"
45
44.5 1.75"
44.5 1.75"
HKF
2CDC131064C0201_1s5
2CDC242010F0011
-11
2CDC242017F0011
10.5 .41"
44 1.73"
54 2.13"
62 2.44" 5.5 .22" 44 1.73" 16 .63"
62 2.44"
70 2.76" 69.5 2.74"
ABB | 2/21
MO325 manual motor starters magnetic only
0.4 to 25 A – with electromagnetic protection
Description
The MO325 manual motor starters magnetic only are 54 mm width devices with modular DIN rail design. These
devices are used to manually switch on and off motors and to protect them reliably and without the need for a
fuse from short-circuits.
2 Further features are the build-in disconnect function, trip-free mechanism and a rotary handle with a clear
switch position indication. The manual motor starter magnetic only is suitable for three- and single-phase
applications. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips, three-phase busbars,
2CDC241003F0009
Ordering details
Rated Rated Short-circuit Rated instan- Type Order code Weight
MO325-16 operational operational breaking taneous short- (1 pce)
power current capacity ICS at circuit current
400 V 400 V AC setting li
AC-31)
kW A kA A kg
0.09 0.40 100 3.9 MO325-0.4 1SAM160000R1003 0.280
0.12 0.63 100 6.14 MO325-0.63 1SAM160000R1004 0.280
0.25 1.0 100 11.5 MO325-1 1SAM160000R1005 0.310
0.55 1.6 100 18.4 MO325-1.6 1SAM160000R1006 0.340
0.75 2.5 100 28.75 MO325-2.5 1SAM160000R1007 0.340
1.5 4.0 100 50 MO325-4 1SAM160000R1008 0.340
2.2 6.3 100 78.75 MO325-6.3 1SAM160000R1009 0.340
4.0 9.0 100 135 MO325-9 1SAM160000R1010 0.340
5.5 12.5 75 180 MO325-12.5 1SAM160000R1011 0.340
7.5 16 60 240 MO325-16 1SAM160000R1012 0.340
9.0 20 55 300 MO325-20 1SAM160000R1013 0.340
12.5 25 50 375 MO325-25 1SAM160000R1014 0.340
1)
For overload protection of motors, an appropriate thermal or electronic overload relay must be used
45
44.5 1.75"
2CDC242010F0011
2CDC131064C0201_2s5
44 1.73"
62 2.44"
70 2.76"
MO325
2/22 | ABB
MS325, MO325 manual motor starters
Main accessories
Description
Three-phase busbars ensure a quick and safe connection and are therefore a cost effective solution.
A variety of different three-phase busbars up to 63 A are in the assortment. Between 2 and 5 manual
motor starters with none, one or two lateral auxiliary contacts can be connected. Different three-phase
2CDC241014F0010
Suitable for Rated Rated cross Mounting Type Order code Pkg Weight
SA3 operational section form qty (1 pce)
current
A mm² kg
Three-phase feeder terminals
MS325, 63 25 Flat S3-M1 1SAM101938R0001 10 0.041
MO325 63 25 High S3-M2 1SAM101938R0002 10 0.053
63 35 UL type E S3-M3 1SAM101938R0004 10 0.050
and IEC
ABB | 2/23
MS325, MO325 manual motor starters
Main accessories
Description
MS325 and MO325 manual motor starters can be equipped with auxiliary contacts for lateral/front
mounting, signalling contact for lateral mounting, undervoltage release and shunt trips. A variety of
combinations is possible as required for the application. The auxiliary contacts change position with
the main contacts. The signalling contact signals tripping regardless if it was caused by short-circuit or
2 overload. Undervoltage release are used for remote tripping of the manual motor starter especially for
emergency stop circuits. Shunt trips release the MMS used for remote tripping.
Ordering details
Suitable Auxiliary Auxiliary Description Type Order code Pkg Weight
for contacts contacts qty (1 pce)
N.O. N.C.
kg
Auxiliary contacts – mountable on the front
MS325, 1 1 HKF-11 1SAM101928R0001 10 0.015
MO325 2 0 HKF-20 1SAM101928R0002 10 0.020
Auxiliary contacts – mountable on the left
MS325, 1 1 Max. 2 pieces HK-11 1SAM101901R0001 2 0.030
MO325 2 0 Max. 2 pieces HK-20 1SAM101901R0002 2 0.030
0 2 Max. 2 pieces HK-02 1SAM101901R0003 2 0.030
Signalling contacts – mountable on the left
MS325, 1 1 For tripped alarm, SK-11 1SAM101904R0003 10 0.030
MO325 max. 1 piece
Signalling contacts – mountable on the right
MS325, 1 1 For short-circuit alarm CK-11 1SAM101943R0001 10 0.035
MO325
Suitable Rated control supply Frequency Type Order code Pkg Weight
for voltage qty (1 pce)
V Hz kg
Shunt trips – mountable as slide in
MS325, 24 ... 60 50/60 AA-24 1SAM101909R0001 10 0.025
MO325 110 ... 240 50/60 AA-230 1SAM101909R0002 10 0.025
220 ... 415 50/60 AA-400 1SAM101909R0003 10 0.025
Undervoltage releases – mountable as slide in
MS325, 24 50 UAF-24 1SAM101903R0024 10 0.02
MO325 48 50 UAF-48 1SAM101903R0048 10 0.02
60 50 UAF-60 1SAM101903R0060 10 0.02
110 50 UAF-110 1SAM101903R0110 10 0.02
230 50 UAF-230 1SAM101903R0230 10 0.02
400 50 UAF-400 1SAM101903R0400 10 0.02
415 50 UAF-415 1SAM101903R0415 10 0.02
500 50 UAF-500 1SAM101903R0500 10 0.02
2CDC131052C0201_2s4
2/24 | ABB
MS325, MO325 manual motor starters
Main accessories
Description
IB325 are IP65 enclosures for single MMS installation. Additional mounting of auxiliary and signalling con
tacts, shunt trips and undervoltage release is possible. The handle is lockable in OFF position. For detailed
specification see installation instruction.
DMS325 are IP65 door mounting kits for MMS installation in any enclosure. Additional mounting of aux 2
2CDC241004F0010
iliary, signalling, shunt trips and undervoltage release is possible. The handle is lockable in OFF position.
For detailed specification see installation instruction.
Ordering details
IB325-Y Suitable Description Color Type Order code Pkg Weight
for qty (1 pce)
kg
IP65 enclosures
MS325, Padlockable max. 3 padlocks Yellow/red IB325-G 1SAM101940R1000 1 0.370
MO325 with bail diameter 4 ... 6.5 mm Grey/black IB325-Y 1SAM101940R1001 1 0.370
2CDC241003F0010
DMS325-Y
2CDC241001F0010
DMS325-G
I ON
I ON
183 7.2"
174 6.85"
194 7.64"
121 4.76"
0
2CDC131052C0201_4s4
OFF 0
OFF
2CDC242011F0011
2CDC242012F0011
116.15 4.57"
IB325 DMS325
ABB | 2/25
MS116, MS132, MO132, MS4xx, MO4xx, MS325, MO325
General accessories
Description
With this solution of door coupling rotary mechanism it is possible to operate a manual motor starter in the
back of a switch cabinet from outside. The door coupling mechanism prevents opening of the door of a
switch cabinet with the manual motor starter in ON position.
The complete mechanism includes handle, shaft, driver, shaft alignment ring and shaft supporter.
2CDC241003F0011
2 All accessories fit for 6 mm shafts with a maximum length of 180 mm. The degree of protection for
handles MSHD is IP64.
Ordering details
Suit- Description Shaft Color Type Order code Pkg Weight
MSHD-LB
able length qty (1 pcs)
for
mm kg
Shafts
MS116, For MSHD handles. Shaft 85 OXS6X85 1SCA101647R1001 1 0.020
MS132, diameter 6 mm. Shaft extension 105 OXS6X105 1SCA108043R1001 1 0.020
MO132, for door coupling driver.
2CDC241002S0011
MS4xx,
MO4xx,
MS325,
MO325
MSH-AR
Shaft alignment ring
MS116, The MSH-AR supports the MSH-AR 1SAM201920R1000 1 0.010
MS132, long shafts for alignment to the
MO132, handle inlet. It makes closing
MS4xx, panel doors more easy. Use for
MO4xx, OXS6X > 105 mm.
MS325,
MO325
2CDC241017V0013
Shaft supporter
MS116, With the MSAH it is possible MSAH1 1SAM201909R1021 1 0.035
MS132, to support the shaft in the
MO132 extension of handle (MSHD). It
is mandatory for the usage of
MSAH1 shafts >130 mm.
1)
Indication I-O and ON-OFF (recommended for MS116, MS4xx, MO4xx)
2)
Indication I-O and ON-OFF + Trip indication
3)
Coded - Positioning of ON indication dependent from mounting orientation of the MMS
4)
Uncoded - Positioning of ON indication independent from mounting orientation of the MMS
2CDC131053C0201
2/26 | ABB
MS116, MS132, MO132, MS4xx, MO4xx, MS325, MO325
General accessories
MSMN
MSMNO
MSAH1
OXS6X
MSH-AR
2CDC242022F0013
MSHD
2CDC131053C0201
ABB | 2/27
3
Summary_3
3/0 | ABB
B mini contactors
K mini contactor relays
Overview 3/2
4-pole contactors
B6, B7 AC operated 3/10
BC6, B7D DC operated 3/11
Contactor relays
K6 AC operated 3/13
KC6 DC operated 3/14
Accessories 3/17
For direct product details information, use product type or order code, ex:
Summary_3
www.abb.com/productdetails/AF09-30-10-13 or www.abb.com/productdetails/1SBL137001R1310
ABB | 3/1
Mini contactors
Screw terminals
AC Control supply
3-pole contactors Coil consumption 3.5 W Type B6 B7 - -
DC Control supply
3-pole contactors Coil consumption 3.5 W Type BC6 BC7 - -
3
B7D1)
3-pole interface contactors Coil consumption 1.4 ... 2.4 W Type BC6 BC7 - -
Main accessories
Auxiliary contact blocks Front mounting CAF6
Side mounting CA6
Connection sets For reversing contactors BSM6-30
Surge suppressors Varistor (AC/DC) RV-BC6
Overload relays
Thermal overload relays Class 10 T16
Thermal and phase failure protection, with single setup possible
Electronic overload relays Class 10E, 20E, 30E E16DU
With single setup possible
Contactor relays
Screw terminals
AC Control supply
4-pole contactor relays Coil consumption 3.5 W Type K6
DC Control supply
4-pole contactor relays Coil consumption 3.5 W Type KC6
4-pole interface contactor relays Coil consumption 1.4 ... 2.4 W Type KC6
Wide range types Extended coil voltage and Type TKC6
temperature
IEC Rated operational current AC-15 220-230-240 V A 4
380-400 V A 3
Rated operational current DC-13 24 V A 2.5
Main accessories
Auxiliary contact blocks Front mounting CAF6
Side mounting CA6-11K
3/2 | ABB
Soldering pins Flat pins
- -
CA6-11K-P CA6-11K-F
- -
- -
- -
- -
K6...P K6...F
KC6...P KC6...F
KC6...P KC6...F
4 4
3 3
2CDC102050C0201
2.5 2.5
- -
CA6-11K-P CA6-11K-F
ABB | 3/3
B6, B7 3-pole mini contactors – with screw terminals
4 to 5.5 kW
AC operated
Description
B6, B7 3-pole mini contactors are compact control products mainly used for switching resistive or motor
loads up to 690 V AC.
2CDC211001F0010
Ordering details
2CDC211014F0011
IEC UL/CSA Rated control circuit Auxiliary Type Order code Pkg Weight
Rated operational 3-phase General voltage contacts qty (1 pce)
power current motor use UC fitted
θ ≤ 40 °C rating rating
400 V 480 V 50 Hz 60 Hz
B7-30-10 AC-3 AC-1
kW A hp V AC V AC kg
B6 mini contactors
4 20 3 300 V / 24 24 1 0 B6-30-10-01 GJL1211001R0101 10 0.175
12 A 0 1 B6-30-01-01 GJL1211001R0011 10 0.175
42 42 1 0 B6-30-10-02 GJL1211001R0102 10 0.175
0 1 B6-30-01-02 GJL1211001R0012 10 0.175
48 48 1 0 B6-30-10-03 GJL1211001R0103 10 0.175
0 1 B6-30-01-03 GJL1211001R0013 10 0.175
110 … 127 110 … 127 1 0 B6-30-10-84 GJL1211001R8104 10 0.175
0 1 B6-30-01-84 GJL1211001R8014 10 0.175
220 … 240 220 … 240 1 0 B6-30-10-80 GJL1211001R8100 10 0.175
0 1 B6-30-01-80 GJL1211001R8010 10 0.175
380 … 415 380 … 415 1 0 B6-30-10-85 GJL1211001R8105 10 0.175
0 1 B6-30-01-85 GJL1211001R8015 10 0.175
B7 mini contactors
5.5 20 5 600 V / 24 24 1 0 B7-30-10-01 GJL1311001R0101 10 0.175
16 A 0 1 B7-30-01-01 GJL1311001R0011 10 0.175
42 42 1 0 B7-30-10-02 GJL1311001R0102 10 0.175
0 1 B7-30-01-02 GJL1311001R0012 10 0.175
48 48 1 0 B7-30-10-03 GJL1311001R0103 10 0.175
0 1 B7-30-01-03 GJL1311001R0013 10 0.175
110 … 127 110 … 127 1 0 B7-30-10-84 GJL1311001R8104 10 0.175
0 1 B7-30-01-84 GJL1311001R8014 10 0.175
220 … 240 220 … 240 1 0 B7-30-10-80 GJL1311001R8100 10 0.175
0 1 B7-30-01-80 GJL1311001R8010 10 0.175
380 … 415 380 … 415 1 0 B7-30-10-85 GJL1311001R8105 10 0.175
0 1 B7-30-01-85 GJL1311001R8015 10 0.175
1.78"
1.66"
57.5
45.2
42.2
2CDC212001F0011
2CDC102008C0201
4.5 0.18"
B6, B7
3/4 | ABB
BC6, BC7, B7D 3-pole mini contactors – with screw terminals
4 to 5.5 kW
DC operated
Description
BC6, BC7, B7D 3-pole mini contactors are compact control products mainly used for switching resistive or
motor loads up to 690 V AC.
2CDC211040F0011
1.78"
1.66"
57.5
45.2
42.2
2CDC212001F0011
2CDC102015C0201
4.5 0.18"
ABB | 3/5
VB6, VB7 3-pole mini reversing contactors – with screw terminals
4 to 5.5 kW
AC operated
Description
2CDC211006F0011
VB6, VB7 3-pole compact design reversing contactors are space optimized control products mainly used
for switching resistive or motor loads up to 690 V AC.
These reversing contactors are designed with:
– – built-in mechanical interlock. The coils must be mutually interlocked electrically and coils must be de-
energised for 50 ms at least to prevent phase to phase short circuit on the arc.
– – control circuit: AC operated
VB7-30-10 – – low coil consumption (3.5 VA at pull-in and at holding)
3 – – hum-free coil
–– add-on auxiliary contact blocks for front mounting
–– designed for rail or wall mounting
Ordering details
IEC UL/CSA Rated control circuit Auxiliary Type Order code Pkg Weight
Rated operational 3-phase General voltage contacts qty (1 pce)
power current motor use UC fitted
θ ≤ 40 °C rating rating
400 V 480 V 50 Hz 60 Hz
AC-3 AC-1
kW A hp V AC V AC kg
VB6 mini reversing contactors
4 20 3 300 V / 24 24 1 0 VB6-30-10-01 GJL1211901R0101 5 0.355
12 A 0 1 VB6-30-01-01 GJL1211901R0011 5 0.355
42 42 1 0 VB6-30-10-02 GJL1211901R0102 5 0.355
0 1 VB6-30-01-02 GJL1211901R0012 5 0.355
48 48 1 0 VB6-30-10-03 GJL1211901R0103 5 0.355
0 1 VB6-30-01-03 GJL1211901R0013 5 0.355
110 … 127 110 … 127 1 0 VB6-30-10-84 GJL1211901R8104 5 0.355
0 1 VB6-30-01-84 GJL1211901R8014 5 0.355
220 … 240 220 … 240 1 0 VB6-30-10-80 GJL1211901R8100 5 0.355
0 1 VB6-30-01-80 GJL1211901R8010 5 0.355
380 … 415 380 … 415 1 0 VB6-30-10-85 GJL1211901R8105 5 0.355
0 1 VB6-30-01-85 GJL1211901R8015 5 0.355
VB7 mini reversing contactors
5.5 20 5 600 V / 24 24 1 0 VB7-30-10-01 GJL1311901R0101 5 0.355
16 A 0 1 VB7-30-01-01 GJL1311901R0011 5 0.355
42 42 1 0 VB7-30-10-02 GJL1311901R0102 5 0.355
0 1 VB7-30-01-02 GJL1311901R0012 5 0.355
48 48 1 0 VB7-30-10-03 GJL1311901R0103 5 0.355
0 1 VB7-30-01-03 GJL1311901R0013 5 0.355
110 … 127 110 … 127 1 0 VB7-30-10-84 GJL1311901R8104 5 0.355
0 1 VB7-30-01-84 GJL1311901R8014 5 0.355
220 … 240 220 … 240 1 0 VB7-30-10-80 GJL1311901R8100 5 0.355
0 1 VB7-30-01-80 GJL1311901R8010 5 0.355
380 … 415 380 … 415 1 0 VB7-30-10-85 GJL1311901R8105 5 0.355
0 1 VB7-30-01-85 GJL1311901R8015 5 0.355
2CDC212005F0011
2CDC102016C0201
4.5 0.18"
VB6, VB7
3/6 | ABB
VBC6, VBC7 3-pole mini reversing contactors – with screw terminals
4 to 5.5 kW
DC operated
Description
VBC6, VBC7 3-pole compact design reversing contactors are space optimized control products mainly
2CDC211042F0011
used for switching resistive or motor loads up to 690 V AC.
These reversing contactors are designed with:
– – built-in mechanical interlock. The coils must be mutually interlocked electrically and coils must be de-
energised for 50 ms at least to prevent phase to phase short circuit on the arc.
– – control circuit: DC operated
VBC6-30-10
– – low coil consumption (3.5 W at pull-in and at holding)
– – hum-free coil 3
–– add-on auxiliary contact blocks for front mounting
–– designed for rail or wall mounting
2CDC211001F0011
Ordering details
IEC UL/CSA Rated control Auxiliary Type Order code Pkg Weight
Rated operational 3-phase General circuit voltage contacts qty (1 pce)
power current motor use UC fitted
VBC7-30-10 θ ≤ 40 °C rating rating
400 V 480 V
AC-3 AC-1
kW A hp V DC kg
VBC6 mini reversing contactors
4 20 3 300 V / 12 1 0 VBC6-30-10-07 GJL1213901R0107 5 0.355
12 A 0 1 VBC6-30-01-07 GJL1213901R0017 5 0.355
24 1 0 VBC6-30-10-01 GJL1213901R0101 5 0.355
0 1 VBC6-30-01-01 GJL1213901R0011 5 0.355
48 1 0 VBC6-30-10-16 GJL1213901R1106 5 0.355
0 1 VBC6-30-01-16 GJL1213901R1016 5 0.355
60 1 0 VBC6-30-10-03 GJL1213901R0103 5 0.355
0 1 VBC6-30-01-03 GJL1213901R0013 5 0.355
110 ... 125 1 0 VBC6-30-10-04 GJL1213901R0104 5 0.355
0 1 VBC6-30-01-04 GJL1213901R0014 5 0.355
220 … 240 1 0 VBC6-30-10-05 GJL1213901R0105 5 0.355
0 1 VBC6-30-01-05 GJL1213901R0015 5 0.355
VBC7 mini reversing contactors
5.5 20 5 600 V / 12 1 0 VBC7-30-10-07 GJL1313901R0107 5 0.355
16 A 0 1 VBC7-30-01-07 GJL1313901R0017 5 0.355
24 1 0 VBC7-30-10-01 GJL1313901R0101 5 0.355
0 1 VBC7-30-01-01 GJL1313901R0011 5 0.355
48 1 0 VBC7-30-10-16 GJL1313901R1106 5 0.355
0 1 VBC7-30-01-16 GJL1313901R1016 5 0.355
60 1 0 VBC7-30-10-03 GJL1313901R0103 5 0.355
0 1 VBC7-30-01-03 GJL1313901R0013 5 0.355
110 ... 125 1 0 VBC7-30-10-04 GJL1313901R0104 5 0.355
0 1 VBC7-30-01-04 GJL1313901R0014 5 0.355
220 … 240 1 0 VBC7-30-10-05 GJL1313901R0105 5 0.355
0 1 VBC7-30-01-05 GJL1313901R0015 5 0.355
2CDC212005F0011
2CDC102017C0201
4.5 0.18"
VBC6, VBC7
ABB | 3/7
BC6, BC7 3-pole interface mini contactors – with screw terminals
4 to 5.5 kW
DC operated
Description
BC6, BC7 3-pole interface mini contactors are compact control products mainly used for switching resis-
tive or motor loads up to 690 V AC.
2CDC211040F0011
Ordering details
IEC UL/CSA Rated control Auxiliary Type Order code Pkg Weight
2CDC211013F0011
1.78"
1.66"
57.5
45.2
42.2
2CDC212001F0011
2CDC102010C0201
4.5 0.18"
BC6, BC7
3/8 | ABB
TBC7 3-pole mini contactors – with screw terminals
4 to 5.5 kW
DC operated – large coil voltage range
Description
TBC7 3-pole mini contactors are compact control products mainly used for switching resistive or motor
loads up to 690 V AC.
2CDC211015F0011
Ordering details
IEC UL/CSA Rated control Auxiliary Type Order code Pkg Weight
Rated operational 3-phase General circuit voltage contacts qty (1 pce)
power current motor use UCmin ... UCmax fitted
θ ≤ 40 °C rating rating
400 V 480 V
AC-3 AC-1
kW A hp V DC kg
TBC7 mini contactors
5.5 20 5 600 V / 17 ... 32 1 0 TBC7-30-10-51 GJL1313061R5101 10 0.185
16 A 0 1 TBC7-30-01-51 GJL1313061R5011 10 0.185
50 ... 90 1 0 TBC7-30-10-55 GJL1313061R5105 10 0.185
0 1 TBC7-30-01-55 GJL1313061R5015 10 0.185
77 ... 143 1 0 TBC7-30-10-62 GJL1313061R6102 10 0.185
0 1 TBC7-30-01-62 GJL1313061R6012 10 0.185
140 ... 260 1 0 TBC7-30-10-68 GJL1313061R6108 10 0.185
0 1 TBC7-30-01-68 GJL1313061R6018 10 0.185
Other types on request
1.78"
1.66"
57.5
45.2
42.2
2CDC212001F0011
2CDC102020C0201
4.5 0.18"
TBC7
ABB | 3/9
B6, B7 4-pole mini contactors – with screw terminals
4 to 5.5 kW
AC operated
Description
B6, B7 4-pole mini contactors are compact control products mainly used for switching resistive loads up
to 690 V AC.
2CDC211028F0011
Ordering details
IEC UL/CSA Rated control Auxiliary Type Order code Pkg Weight
Rated operational General use circuit voltage contacts qty (1 pce)
current rating UC fitted
θ ≤ 40 °C 50/60 Hz
AC-1
A V AC kg
4 N.O. main poles
20 300 V / 12 A 24 0 0 B6-40-00-01 GJL1211201R0001 10 0.175
42 0 0 B6-40-00-02 GJL1211201R0002 10 0.175
48 0 0 B6-40-00-03 GJL1211201R0003 10 0.175
110 ... 127 0 0 B6-40-00-84 GJL1211201R8004 10 0.175
220 ... 240 0 0 B6-40-00-80 GJL1211201R8000 10 0.175
20 600 V / 16 A 24 0 0 B7-40-00-01 GJL1311201R0001 10 0.175
42 0 0 B7-40-00-02 GJL1311201R0002 10 0.175
48 0 0 B7-40-00-03 GJL1311201R0003 10 0.175
110 ... 127 0 0 B7-40-00-84 GJL1311201R8004 10 0.175
220 ... 240 0 0 B7-40-00-80 GJL1311201R8000 10 0.175
2 N.O. + 2 N.C. main poles
20 300 V / 12 A 24 0 0 B6-22-00-01 GJL1211501R0001 10 0.175
42 0 0 B6-22-00-02 GJL1211501R0002 10 0.175
48 0 0 B6-22-00-03 GJL1211501R0003 10 0.175
110 ... 127 0 0 B6-22-00-84 GJL1211501R8004 10 0.175
220 ... 240 0 0 B6-22-00-80 GJL1211501R8000 10 0.175
20 600 V / 16 A 24 0 0 B7-22-00-01 GJL1311501R0001 10 0.175
42 0 0 B7-22-00-02 GJL1311501R0002 10 0.175
48 0 0 B7-22-00-03 GJL1311501R0003 10 0.175
110 ... 127 0 0 B7-22-00-84 GJL1311501R8004 10 0.175
220 ... 240 0 0 B7-22-00-80 GJL1311501R8000 10 0.175
1.78"
1.66"
57.5
45.2
42.2
2CDC212001F0011
2CDC102009C0201
4.5 0.18"
B6, B7
3/10 | ABB
BC6, B7D 4-pole mini contactors – with screw terminals
4 to 5.5 kW
DC operated
Description
BC6, B7D 4-pole mini contactors are compact control products mainly used for switching resistive loads
up to 690 V AC.
2CDC211032F0011
Ordering details
IEC UL/CSA Rated control Auxiliary Type Order code Pkg Weight
Rated General use circuit voltage contacts qty (1 pce)
operational rating UC fitted
current
θ ≤ 40 °C
AC-1
A V DC kg
4 N.O. main poles
20 600 V / 16 A 24 0 0 B7D-40-00-01 GJL1317201R0001 10 0.175
220 0 0 B7D-40-00-05 GJL1317201R0005 10 0.175
2 N.O. + 2 N.C. main poles
20 300 V / 12 A 12 0 0 BC6-22-00-07 GJL1213501R0007 10 0.175
24 0 0 BC6-22-00-01 GJL1213501R0001 10 0.175
42 0 0 BC6-22-00-02 GJL1213501R0002 10 0.175
48 0 0 BC6-22-00-16 GJL1213501R1006 10 0.175
60 0 0 BC6-22-00-03 GJL1213501R0003 10 0.175
110 ... 125 0 0 BC6-22-00-04 GJL1213501R0004 10 0.175
220 ... 240 0 0 BC6-22-00-05 GJL1213501R0005 10 0.175
1.78"
1.66"
57.5
45.2
42.2
2CDC212001F0011
2CDC102021C0201
4.5 0.18"
BC6, B7D
ABB | 3/11
TBC7 4-pole mini contactors – with screw terminals
4 to 5.5 kW
DC operated – large coil voltage range
Description
TBC7 4-pole mini contactors are compact control products mainly used for switching resistive or motor
loads up to 690 V AC.
2CDC211026F0011
Ordering details
IEC UL/CSA Rated control Auxiliary Type Order code Pkg Weight
Rated operational General use circuit voltage contacts qty (1 pce)
current rating UC min ... UC max fitted
θ ≤ 40 °C
AC-1
A V DC kg
3 N.O. + 1 N.C. main poles
20 600 V / 16 A 50 ... 90 0 0 TBC7-31-00-55 GJL1313461R5005 10 0.185
77 ... 143 0 0 TBC7-31-00-62 GJL1313461R6002 10 0.185
140 ... 260 0 0 TBC7-31-00-68 GJL1313461R6008 10 0.185
2 N.O. + 2 N.C. main poles
20 600 V / 16 A 50 ... 90 0 0 TBC7-22-00-55 GJL1313561R5005 10 0.185
77 ... 143 0 0 TBC7-22-00-62 GJL1313561R6002 10 0.185
140 ... 260 0 0 TBC7-22-00-68 GJL1313561R6008 10 0.185
1.78"
1.66"
57.5
45.2
42.2
2CDC212001F0011
2CDC102022C0201
4.5 0.18"
TBC7
3/12 | ABB
K6 4-pole mini contactor relays – with screw terminals
AC operated
Description
K6 4-pole mini-contactor relays are space optimized control products mainly used for control functions or
for small loads up to 4 A.
2CDC211012F0011
Ordering details
2CDC211004F0010
1.78"
1.66"
57.5
45.2
42.2
2CDC212001F0011
2CDC102011C0201
4.5 0.18"
K6
ABB | 3/13
KC6 4-pole mini contactor relays – with screw terminals
DC operated
Description
KC6 4-pole mini-contactor relays are space optimized control products mainly used for control functions
or for small loads up to 4 A.
2CDC211016F0011
Ordering details
Rated control circuit voltage Type Order code Pkg Weight
UC qty (1 pce)
V DC kg
KC6 4-pole mini contactor relays
12 KC6-22Z-07 GJH1213001R0227 10 0.175
24 KC6-22Z-01 GJH1213001R0221 10 0.175
48 KC6-22Z-16 GJH1213001R1226 10 0.175
60 KC6-22Z-03 GJH1213001R0223 10 0.175
110 ... 125 KC6-22Z-04 GJH1213001R0224 10 0.175
220 ... 240 KC6-22Z-05 GJH1213001R0225 10 0.175
12 KC6-31Z-07 GJH1213001R0317 10 0.175
24 KC6-31Z-01 GJH1213001R0311 10 0.175
48 KC6-31Z-16 GJH1213001R1316 10 0.175
60 KC6-31Z-03 GJH1213001R0313 10 0.175
110 ... 125 KC6-31Z-04 GJH1213001R0314 10 0.175
220 ... 240 KC6-31Z-05 GJH1213001R0315 10 0.175
12 KC6-40E-07 GJH1213001R0407 10 0.175
24 KC6-40E-01 GJH1213001R0401 10 0.175
48 KC6-40E-16 GJH1213001R1406 10 0.175
60 KC6-40E-03 GJH1213001R0403 10 0.175
110 ... 125 KC6-40E-04 GJH1213001R0404 10 0.175
220 ... 240 KC6-40E-05 GJH1213001R0405 10 0.175
1.78"
1.66"
57.5
45.2
42.2
2CDC212001F0011
2CDC102012C0201
4.5 0.18"
KC6
3/14 | ABB
KC6 4-pole interface mini contactor relays – with screw terminals
DC operated
Description
KC6 4-pole interface mini-contactor relays are space optimized control products mainly used for control
functions or for small loads up to 4 A.
2CDC211017F0011
Ordering details
Rated control circuit voltage Type Order code Pkg Weight
UC qty (1 pce)
V DC kg
DC operation 24 V / 1.4 W
24 KC6-31Z-1.4-81 GJH1213001R8311 10 0.175
24 KC6-40E-1.4-81 GJH1213001R8401 10 0.175
DC operation 17 ... 32 V / 2.4 W
17 ... 32 KC6-31Z-2.4-51 GJH1213001R5311 10 0.175
17 ... 32 KC6-40E-2.4-51 GJH1213001R5401 10 0.175
DC operation 24 V / 1.7 W
24 K6S-22Z-1.7-71 GJH1213001R7221 10 0.175
24 K6S-31Z-1.7-71 GJH1213001R7311 10 0.175
24 K6S-40E-1.7-71 GJH1213001R7401 10 0.175
DC operation 17 ... 32 V / 2.8 W
17 ... 32 K6S-22Z-2.8-72 GJH1213001R7222 10 0.175
17 ... 32 K6S-31Z-2.8-72 GJH1213001R7312 10 0.175
17 ... 32 K6S-40E-2.8-72 GJH1213001R7402 10 0.175
1.78"
1.66"
57.5
45.2
42.2
2CDC212001F0011
2CDC102013C0201
4.5 0.18"
KC6
ABB | 3/15
TKC6 4-pole mini contactor relays – with screw terminals
DC operated – large coil voltage range
Description
TKC6 4-pole mini contactors are space optimized control products mainly used for control functions or for
small loads up to 4 A.
2CDC211021F0011
Ordering details
Rated control circuit voltage Type Order code Pkg Weight
UC min ... UC max qty (1 pce)
V DC kg
17 ... 32 TKC6-22Z-51 GJH1213061R5221 10 0.180
50 ... 90 TKC6-22Z-55 GJH1213061R5225 10 0.180
77 ... 143 TKC6-22Z-62 GJH1213061R6222 10 0.180
140 ... 260 TKC6-22Z-68 GJH1213061R6228 10 0.180
17 ... 32 TKC6-31Z-51 GJH1213061R5311 10 0.180
50 ... 90 TKC6-31Z-55 GJH1213061R5315 10 0.180
77 ... 143 TKC6-31Z-62 GJH1213061R6312 10 0.180
140 ... 260 TKC6-31Z-68 GJH1213061R6318 10 0.180
17 ... 32 TKC6-40E-51 GJH1213061R5401 10 0.180
50 ... 90 TKC6-40E-55 GJH1213061R5405 10 0.180
77 ... 143 TKC6-40E-62 GJH1213061R6402 10 0.180
140 ... 260 TKC6-40E-68 GJH1213061R6408 10 0.180
1.78"
1.66"
57.5
45.2
42.2
2CDC212001F0011
2CDC102014C0201
4.5 0.18"
TKC6
3/16 | ABB
B6, B7, BC6, BC7 3 and 4-pole mini contactors
VB6, VB7, VBC6, VBC7 3-pole mini reversing contactors
Accessories
Odering details
2CDC211012S0010
kg
CAF6-11N Front-mounted instantaneous auxiliary contact blocks
(not allowed for mounting on TBC, B6S, B7S, interface contactors) (1)
B6-, B7-40-00, BC6-, BC7-40-00
VB6, VB7, VBC6, VBC7, VB6A, VB7A
1 1 CAF6-11E GJL1201330R0002 10 0.020 3
2 0 CAF6-20E GJL1201330R0006 10 0.020
2CDC211007S0010
For contactors Rated control Connection type Type Order code Pkg Weight
CA6-11E-P circuit voltage Uc qty (1 pce)
V DC kg
1SBC101635S0201 - Rev. A
T16
ABB | 3/17
K6, KC6 4-pole mini contactor relays
Accessories
Ordering details
2CDC211019S0011
kg
CAF6-11K
Front-mounted instantaneous auxiliary contact blocks (1)
K6, KC6 1 1 CAF6-11K GJL1201330R0001 10 0.020
3 2 0 CAF6-20K GJL1201330R0005 10 0.020
0 2 CAF6-02K GJL1201330R0009 10 0.020
For contactors Rated control Connection type Type Order code Pkg Weight
CA6-11K
circuit voltage Uc qty (1 pce)
V DC kg
LT6-B
2CDC211007S0010
RV-BC6/250
1SBC101635S0201 - Rev. A
3/18 | ABB
Notes
N2
ABB | 3/19
4
Summary_4
4/0 | ABB
AS 3-pole contactors and NS contactor relays
with screw terminals
Overview 4/2
3-pole contactors
AS09 ... AS16 AC operated 4/4
ASL09 ... ASL16 DC operated 4/5
AS09 ... AS16 AC operated - 2-stack 4/6
ASL09 ... ASL16 DC operated - 2-stack 4/7
Main accessories 4/8
4
Contactor relays
NS AC operated 4/10
NSL DC operated 4/11
Main accessories 4/12
For direct product details information, use product type or order code, ex:
Summary_4
www.abb.com/productdetails/AF09-30-10-13 or www.abb.com/productdetails/1SBL137001R1310
ABB | 4/1
Compact
Optimize your equipment dimensions!
Same dimensions
for AC and DC operated contactors with screw
or spring terminals
"Click"
1SBC101277S0201
4/2 | ABB
Simple
Choose reliable and time-saving solutions
ABB | 4/3
AS09 ... AS16 3-pole contactors
4 to 7.5 kW
AC operated
Description
AS09 ... AS16 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC and
220 V DC.
These contactors are of the block type design with:
–– 3 main poles and 1 built-in auxiliary contact
1SBC101007F0014
Ordering details
IEC UL/CSA Rated control circuit Auxiliary Type Order code Weight
AS09-30-10
Rated operational 3-phase General voltage contacts
power current motor use Uc fitted Pkg
4 θ ≤ 40 °C rating rating (1) (1 pce)
400 V 480 V 600 V AC
AC-3 AC-1
kW A hp A V 50 Hz V 60 Hz kg
4 22 5 20 24 24 1 0 AS09-30-10-20 1SBL101001R2010 0.220
0 1 AS09-30-01-20 1SBL101001R2001 0.220
- 120 1 0 AS09-30-10-16 1SBL101001R1610 0.220
0 1 AS09-30-01-16 1SBL101001R1601 0.220
230 230 1 0 AS09-30-10-26 1SBL101001R2610 0.220
0 1 AS09-30-01-26 1SBL101001R2601 0.220
400 400 1 0 AS09-30-10-28 1SBL101001R2810 0.220
0 1 AS09-30-01-28 1SBL101001R2801 0.220
5.5 24 7.5 20 24 24 1 0 AS12-30-10-20 1SBL111001R2010 0.220
0 1 AS12-30-01-20 1SBL111001R2001 0.220
- 120 1 0 AS12-30-10-16 1SBL111001R1610 0.220
0 1 AS12-30-01-16 1SBL111001R1601 0.220
230 230 1 0 AS12-30-10-26 1SBL111001R2610 0.220
0 1 AS12-30-01-26 1SBL111001R2601 0.220
400 400 1 0 AS12-30-10-28 1SBL111001R2810 0.220
0 1 AS12-30-01-28 1SBL111001R2801 0.220
7.5 24 10 20 24 24 1 0 AS16-30-10-20 1SBL121001R2010 0.220
0 1 AS16-30-01-20 1SBL121001R2001 0.220
- 120 1 0 AS16-30-10-16 1SBL121001R1610 0.220
0 1 AS16-30-01-16 1SBL121001R1601 0.220
230 230 1 0 AS16-30-10-26 1SBL121001R2610 0.220
0 1 AS16-30-01-26 1SBL121001R2601 0.220
400 400 1 0 AS16-30-10-28 1SBL121001R2810 0.220
0 1 AS16-30-01-28 1SBL121001R2801 0.220
Note: for multiple packaging, please contact your ABB local sales organization.
(1) Other control voltages see voltage code table.
72.5 2.85"
35 1.38"
45 1.77" 7 0.28" 10 0.39" 2x
M4 8-32 UNC ø 4.2 0.17"
35 mm EN/IEC 60715
5.5 0.22"
68 2.68"
50 1.97"
60 2.36"
1SBC101301S0201
4/4 | ABB
ASL09 ... ASL16 3-pole contactors
4 to 7.5 kW
DC operated
Description
ASL09 ... ASL16 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC
and 220 V DC.
These contactors are of the block type design with:
–– 3 main poles and 1 built-in auxiliary contact
1SBC101010F0014
–– control circuit: low consumption (3 W at pull-in and holding) DC operated with solid core magnet. Suitable for
direct control by PLC outputs (the polarity on the coil terminals A1+ and A2- must be respected)
–– add-on auxiliary contact blocks for front mounting and a comprehensive range of accessories.
Ordering details
ASL09-30-10
IEC UL/CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational
power current
3-phase
motor
General voltage
use Uc
contacts
fitted Pkg
4
θ ≤ 40 °C rating rating (1) (1 pce)
400 V 480 V 600 V AC
AC-3 AC-1
kW A hp A V DC kg
4 22 5 20 24 1 0 ASL09-30-10-81 1SBL103001R8110 0.280
0 1 ASL09-30-01-81 1SBL103001R8101 0.280
48 1 0 ASL09-30-10-83 1SBL103001R8310 0.280
0 1 ASL09-30-01-83 1SBL103001R8301 0.280
110 1 0 ASL09-30-10-86 1SBL103001R8610 0.280
0 1 ASL09-30-01-86 1SBL103001R8601 0.280
220 1 0 ASL09-30-10-88 1SBL103001R8810 0.280
0 1 ASL09-30-01-88 1SBL103001R8801 0.280
5.5 24 7.5 20 24 1 0 ASL12-30-10-81 1SBL113001R8110 0.280
0 1 ASL12-30-01-81 1SBL113001R8101 0.280
48 1 0 ASL12-30-10-83 1SBL113001R8310 0.280
0 1 ASL12-30-01-83 1SBL113001R8301 0.280
110 1 0 ASL12-30-10-86 1SBL113001R8610 0.280
0 1 ASL12-30-01-86 1SBL113001R8601 0.280
220 1 0 ASL12-30-10-88 1SBL113001R8810 0.280
0 1 ASL12-30-01-88 1SBL113001R8801 0.280
7.5 24 10 20 24 1 0 ASL16-30-10-81 1SBL123001R8110 0.280
0 1 ASL16-30-01-81 1SBL123001R8101 0.280
48 1 0 ASL16-30-10-83 1SBL123001R8310 0.280
0 1 ASL16-30-01-83 1SBL123001R8301 0.280
110 1 0 ASL16-30-10-86 1SBL123001R8610 0.280
0 1 ASL16-30-01-86 1SBL123001R8601 0.280
220 1 0 ASL16-30-10-88 1SBL123001R8810 0.280
0 1 ASL16-30-01-88 1SBL123001R8801 0.280
Note: for multiple packaging, please contact your ABB local sales organization.
(1) Other control voltages see voltage code table.
72.5 2.85"
35 1.38"
45 1.77" 7 0.28" 10 0.39" 2x
M4 8-32 UNC ø 4.2 0.17"
35 mm EN/IEC 60715
5.5 0.22"
68 2.68"
60 2.36"
1SBC101302S0201
ABB | 4/5
AS09 ... AS16 2-stack 3-pole contactors
4 to 7.5 kW
AC operated
Description
AS09 ... AS16 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC and
220 V DC.
These contactors are of the block type design with:
–– 1st stack with 3 main poles and 1 N.O. built-in auxiliary contact
1SBC101332F0014
–– 2nd stack with permanently fixed 2 N.O. + 2 N.C. auxiliary contact block. The auxiliary contact elements are
mechanically linked (side-marked symbol) and the N.C. auxiliary contacts are mirror contacts
–– control circuit: AC operated
–– a comprehensive range of accessories.
AS09-30-32
Ordering details
4 IEC UL/CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational 3-phase General voltage contacts
power current motor use Uc fitted Pkg
θ ≤ 40 °C rating rating (1) (1 pce)
400 V 480 V 600 V AC
AC-3 AC-1
kW A hp A V 50 Hz V 60 Hz kg
4 22 5 20 24 24 3 2 AS09-30-32-20 1SBL101001R2032 0.260
- 120 3 2 AS09-30-32-16 1SBL101001R1632 0.260
230 230 3 2 AS09-30-32-26 1SBL101001R2632 0.260
400 400 3 2 AS09-30-32-28 1SBL101001R2832 0.260
5.5 24 7.5 20 24 24 3 2 AS12-30-32-20 1SBL111001R2032 0.260
- 120 3 2 AS12-30-32-16 1SBL111001R1632 0.260
230 230 3 2 AS12-30-32-26 1SBL111001R2632 0.260
400 400 3 2 AS12-30-32-28 1SBL111001R2832 0.260
7.5 24 10 20 24 24 3 2 AS16-30-32-20 1SBL121001R2032 0.260
- 120 3 2 AS16-30-32-16 1SBL121001R1632 0.260
230 230 3 2 AS16-30-32-26 1SBL121001R2632 0.260
400 400 3 2 AS16-30-32-28 1SBL121001R2832 0.260
Note: for multiple packaging, please contact your ABB local sales organization.
(1) Other control voltages see voltage code table.
5.5 0.22"
44.2 1.74"
68 2.68"
1SBC101303S0201
4/6 | ABB
ASL09 ... ASL16 2-stack 3-pole contactors
4 to 7.5 kW
DC operated
Description
ASL09 ... ASL16 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC
and 220 V DC.
These contactors are of the block type design with:
–– 1st stack with 3 main poles and 1 N.O. built-in auxiliary contact
–– 2nd stack with permanently fixed 2 N.O. + 2 N.C. auxiliary contact block. The auxiliary contact elements are
1SBC101334F0014
mechanically linked (side-marked symbol) and the N.C. auxiliary contacts are mirror contacts
–– control circuit: low consumption (3 W at pull-in and holding) DC operated with solid core magnet. Suitable for
direct control by PLC outputs (the polarity on the coil terminals A1+ and A2- must be respected)
ASL09-30-32
–– a comprehensive range of accessories.
Ordering details 4
IEC UL/CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational 3-phase General voltage contacts
power current motor use Uc fitted Pkg
θ ≤ 40 °C rating rating (1) (1 pce)
400 V 480 V 600 V AC
AC-3 AC-1
kW A hp A V DC kg
4 22 5 20 24 3 2 ASL09-30-32-81 1SBL103001R8132 0.320
48 3 2 ASL09-30-32-83 1SBL103001R8332 0.320
110 3 2 ASL09-30-32-86 1SBL103001R8632 0.320
220 3 2 ASL09-30-32-88 1SBL103001R8832 0.320
5.5 24 7.5 20 24 3 2 ASL12-30-32-81 1SBL113001R8132 0.320
48 3 2 ASL12-30-32-83 1SBL113001R8332 0.320
110 3 2 ASL12-30-32-86 1SBL113001R8632 0.320
220 3 2 ASL12-30-32-88 1SBL113001R8832 0.320
7.5 24 10 20 24 3 2 ASL16-30-32-81 1SBL123001R8132 0.320
48 3 2 ASL16-30-32-83 1SBL123001R8332 0.320
110 3 2 ASL16-30-32-86 1SBL123001R8632 0.320
220 3 2 ASL16-30-32-88 1SBL123001R8832 0.320
Note: for multiple packaging, please contact your ABB local sales organization.
(1) Other control voltages see voltage code table.
5.5 0.22"
44.2 1.74"
68 2.68"
1SBC101453S0201
ABB | 4/7
AS09 ... AS16 and
ASL09 ... ASL16 3-pole contactors
Main accessories
Contactor and main accessories (other accessories available)
BEY16C-3
BER16C-3 VM3
(optional)
MS116
4
VM3
BEA16-3 AS
ASL
AS Contactors
RV5, RC5-1 or RT5 ASL
Contactors
T16
T16
AS
ASL TEF3
Contactors
CA3
4/8 | ABB
AS09 ... AS16 and
ASL09 ... ASL16 3-pole contactors
Main accessories
Front-mounted instantaneous auxiliary contact blocks
For contactors Auxiliary Type Order code Pkg Weight
1SBC101036F0014
kg
AS09 … AS16 1 0 CA3-10 1SBN011010T1010 10 0.011
CA3-10 ASL09 … ASL16 0 1 CA3-01 1SBN011010T1001 10 0.011
V kg 4
ON-delay
AS09 … AS16, ASL09 … ASL16 24...240 V AC/DC TEF3-ON 1SBN021012R1000 1 0.065
TEF3-ON
OFF-delay
AS09 … AS16, ASL09 … ASL16 24...240 V AC/DC TEF3-OFF 1SBN021014R1000 1 0.065
1SBC101069F0014
Surge suppressors
1SBC574001F0301
For contactors Rated control circuit Type Order code Pkg Weight
voltage - Uc qty (1 pce)
V AC DC kg
AS09 ... AS16, 24...50 ● ● RV5/50 1SBN050010R1000 2 0.015
RV5
ASL09 ... ASL16 50...133 ● ● RV5/133 1SBN050010R1001 2 0.015
110...250 ● ● RV5/250 1SBN050010R1002 2 0.015
250...440 ● ● RV5/440 1SBN050010R1003 2 0.015
AS09 ... AS16 24...50 ● – RC5-1/50 1SBN050100R1000 2 0.012
1SBC101034F0014
contactors
kg
AS09 … AS12, ASL09 … ASL12 with or without VM3 BEY16C-3 1SBN081018R2000 1 0.041
Note: BEY16C-3 connection set includes two BB3 fixing clips, and an electrical interlocking when fitted on Star and Delta contactors
BEY16C-3 with built-in N.C. auxiliary contacts. BEY16C-3 can be used with or without VM3 mechanical interlock unit.
ABB | 4/9
NS contactor relays
AC operated
Description
NS contactor relays are used for switching auxiliary and control circuits.
These contactor relays are designed with:
–– 4 poles or 8 poles. Contactor relays have mechanically linked auxiliary contact elements (side-marked symbol)
–– control circuit: AC operated
1SBC101012F0014
–– add-on auxiliary contact blocks for front mounting and a comprehensive range of accessories.
Ordering details
Number of contacts Rated control circuit Type Order code Weight
1st stack 2nd stack voltage
NS22E Uc
(1) Pkg
4 (1 pce)
V 50 Hz V 60 Hz kg
A1 13
NO
21
NC
31
NC
43
NO
24 24 NS22E-20 1SBH101001R2022 0.220
- 120 NS22E-16 1SBH101001R1622 0.220
NO NC NC NO
A2 14 22 32 44
230 230 NS22E-26 1SBH101001R2622 0.220
400 400 NS22E-28 1SBH101001R2822 0.220
A1 13
NO
21
NC
33
NO
43
NO
24 24 NS31E-20 1SBH101001R2031 0.220
- 120 NS31E-16 1SBH101001R1631 0.220
NO NC NO NO
A2 14 22 34 44
230 230 NS31E-26 1SBH101001R2631 0.220
400 400 NS31E-28 1SBH101001R2831 0.220
A1 13
NO
23
NO
33
NO
43
NO
24 24 NS40E-20 1SBH101001R2040 0.220
- 120 NS40E-16 1SBH101001R1640 0.220
NO NO NO NO
A2 14 24 34 44
230 230 NS40E-26 1SBH101001R2640 0.220
400 400 NS40E-28 1SBH101001R2840 0.220
A1 13
NO
23
NO
33
NO
43
NO
51
NC
61
NC
71
NC
81
NC
24 24 NS44E-20 1SBH101001R2044 0.260
- 120 NS44E-16 1SBH101001R1644 0.260
A2
NO
14
NO
24
NO
34
NO
44
NC
52
NC
62
NC
72
NC
82 230 230 NS44E-26 1SBH101001R2644 0.260
400 400 NS44E-28 1SBH101001R2844 0.260
A1 13
NO
23
NO
33
NO
43
NO
53
NO
61
NC
71
NC
81
NC 24 24 NS53E-20 1SBH101001R2053 0.260
- 120 NS53E-16 1SBH101001R1653 0.260
A2
NO
14
NO
24
NO
34
NO
44
NO
54
NC
62
NC
72
NC
82 230 230 NS53E-26 1SBH101001R2653 0.260
400 400 NS53E-28 1SBH101001R2853 0.260
A1 13
NO
23
NO
33
NO
43
NO
53
NO
61
NC
71
NC
83
NO 24 24 NS62E-20 1SBH101001R2062 0.260
- 120 NS62E-16 1SBH101001R1662 0.260
A2
NO
14
NO
24
NO
34
NO
44
NO
54
NC
62
NC
72
NO
84 230 230 NS62E-26 1SBH101001R2662 0.260
400 400 NS62E-28 1SBH101001R2862 0.260
A1 13
NO
23
NO
33
NO
43
NO
53
NO
61
NC
73
NO
83
NO 24 24 NS71E-20 1SBH101001R2071 0.260
- 120 NS71E-16 1SBH101001R1671 0.260
230 230 NS71E-26 1SBH101001R2671 0.260
NO NO NO NO NO NC NO NO
A2 14 24 34 44 54 62 74 84
35 mm EN/IEC 60715
68 2.68"
50 1.97"
60 2.36"
1SBC101475S0201
4/10 | ABB
NSL contactor relays
DC operated
Description
NSL contactor relays are used for switching auxiliary and control circuits.
These contactor relays are designed with:
–– 4 poles or 8 poles. Contactor relays have mechanically linked auxiliary contact elements (side-marked symbol)
–– control circuit: low coil consumption (3 W at pull-in and holding) DC operated with solid core magnet. Suitable
1SBC101018F0014
for direct control by PLC outputs (the polarity on the coil terminals A1+ and A2- must be respected)
–– add-on auxiliary contact blocks for front mounting and a comprehensive range of accessories.
Ordering details
Number of contacts Rated control circuit Type Order code Weight
NSL22E
1st stack 2nd stack voltage
Uc
(1)
Pkg
(1 pce) 4
V DC kg
A1+ 13
NO
21
NC
31
NC
43
NO
24 NSL22E-81 1SBH103001R8122 0.280
48 NSL22E-83 1SBH103001R8322 0.280
NO NC NC NO
A2- 14 22 32 44
110 NSL22E-86 1SBH103001R8622 0.280
220 NSL22E-88 1SBH103001R8822 0.280
A1+ 13
NO
21
NC
33
NO
43
NO
24 NSL31E-81 1SBH103001R8131 0.280
48 NSL31E-83 1SBH103001R8331 0.280
NO NC NO NO
A2- 14 22 34 44
110 NSL31E-86 1SBH103001R8631 0.280
220 NSL31E-88 1SBH103001R8831 0.280
A1+ 13
NO
23
NO
33
NO
43
NO
24 NSL40E-81 1SBH103001R8140 0.280
48 NSL40E-83 1SBH103001R8340 0.280
NO NO NO NO
A2- 14 24 34 44
110 NSL40E-86 1SBH103001R8640 0.280
220 NSL40E-88 1SBH103001R8840 0.280
A1+ 13
NO
23
NO
33
NO
43
NO
51
NC
61
NC
71
NC
81
NC
24 NSL44E-81 1SBH103001R8144 0.320
48 NSL44E-83 1SBH103001R8344 0.320
A2-
NO
14
NO
24
NO
34
NO
44
NC
52
NC
62
NC
72
NC
82 110 NSL44E-86 1SBH103001R8644 0.320
220 NSL44E-88 1SBH103001R8844 0.320
A1+ 13
NO
23
NO
33
NO
43
NO
53
NO
61
NC
71
NC
81
NC
24 NSL53E-81 1SBH103001R8153 0.320
48 NSL53E-83 1SBH103001R8353 0.320
A2-
NO
14
NO
24
NO
34
NO
44
NO
54
NC
62
NC
72
NC
82 110 NSL53E-86 1SBH103001R8653 0.320
220 NSL53E-88 1SBH103001R8853 0.320
A1+ 13
NO
23
NO
33
NO
43
NO
53
NO
61
NC
71
NC
83
NO 24 NSL62E-81 1SBH103001R8162 0.320
48 NSL62E-83 1SBH103001R8362 0.320
A2-
NO
14
NO
24
NO
34
NO
44
NO
54
NC
62
NC
72
NO
84 110 NSL62E-86 1SBH103001R8662 0.320
220 NSL62E-88 1SBH103001R8862 0.320
A1+ 13
NO
23
NO
33
NO
43
NO
53
NO
61
NC
73
NO
83
NO 24 NSL71E-81 1SBH103001R8171 0.320
48 NSL71E-83 1SBH103001R8371 0.320
A2-
NO
14
NO
24
NO
34
NO
44
NO
54
NC
62
NO
74
NO
84 110 NSL71E-86 1SBH103001R8671 0.320
220 NSL71E-88 1SBH103001R8871 0.320
A1+ 13
NO
23
NO
33
NO
43
NO
53
NO
63
NO
73
NO
83
NO
24 NSL80E-81 1SBH103001R8180 0.320
48 NSL80E-83 1SBH103001R8380 0.320
110 NSL80E-86 1SBH103001R8680 0.320
NO NO NO NO NO NO NO NO
A2- 14 24 34 44 54 64 74 84
35 mm EN/IEC 60715
68 2.68"
60 2.36"
1SBC101479S0201
ABB | 4/11
NS and NSL contactor relays
Main accessories
4 NS
CA3
NSL
Contactor relays
8-pole contactor relay
TEF3
NS
NSL
Contactor relays
4/12 | ABB
NS and NSL contactor relays
Main accessories
kg
NS, NSL 1 0 CA3-10 1SBN011010T1010 10 0.011
CA3-10 0 1 CA3-01 1SBN011010T1001 10 0.011
ON-delay
NS, NSL 24...240 V AC/DC TEF3-ON 1SBN021012R1000 1 0.065
TEF3-ON OFF-delay
NS, NSL 24...240 V AC/DC TEF3-OFF 1SBN021014R1000 1 0.065
Surge suppressors
1SBC574001F0301
For contactor relays Rated control circuit Type Order code Pkg Weight
voltage - Uc qty (1 pce)
V AC DC kg
NS, 24...50 ● ● RV5/50 1SBN050010R1000 2 0.015
RV5
NSL 50...133 ● ● RV5/133 1SBN050010R1001 2 0.015
110...250 ● ● RV5/250 1SBN050010R1002 2 0.015
250...440 ● ● RV5/440 1SBN050010R1003 2 0.015
NS 24...50 ● – RC5-1/50 1SBN050100R1000 2 0.012
50...133 ● – RC5-1/133 1SBN050100R1001 2 0.012
110...250 ● – RC5-1/250 1SBN050100R1002 2 0.012
250...440 ● – RC5-1/440 1SBN050100R1003 2 0.012
NSL 12...32 – ● RT5/32 1SBN050020R1000 2 0.015
25...65 – ● RT5/65 1SBN050020R1001 2 0.015
50...90 – ● RT5/90 1SBN050020R1002 2 0.015
77...150 – ● RT5/150 1SBN050020R1003 2 0.015
150...264 – ● RT5/264 1SBN050020R1004 2 0.015
1SBC101298S0201
ABB | 4/13
Voltage code table
The below tables indicate the available coil voltages and corresponding digits for order codes. When placing an order, please
give either type or order code. Select a standard contactor from ordering detail pages. Change the coil voltage code in the
type or in the order code according to the table below. Example: for contactor AS09-30-10 and coil 42 V 50/60 Hz, type is
AS09-30-10-21 and order code is 1SBL101001R2110.
3-pole contactors
AC coil code DC coil code
Auxiliary contacts 50 Hz 60 Hz 80 12 V
N.O. N.C. 20 24 V 24 V 81 24 V
Type Order code
21 42 V 42 V 83 48 V
AS16 - 30 - 10 - 26 1SBL121001R 26 10 22 48 V 48 V 84 60 V
23 110 V 110 V 86 110 V
4 24 115 V 115 V 87 125 V
16 – 120 V 88 220 V
N.O. N.C. 25 220 V 220 V 89 240 V
Main contacts
26 230 V 230 V
27 240 V 240 V
17 – 277 V
Contactor type
13 380 V –
AS AC operated
28 400 V 400 V
ASL DC operated
29 415 V 415 V
4/14 | ABB
DRAS09 … DRAS16 enclosed direct-on-line starters
4 to 7.5 kW, protected by thermal overload relays
AC or DC operated
Description
Enclosed direct-on-line (DOL) starters are used for controlling 3-phase asynchronous motors up to 690 V AC.
Each starter is delivered assembled and wired. It contains:
–– IP65 compact plastic enclosure with double insulation, equipped with:
-- 1 green flush "I" ON button and 1 red protruding "O" OFF/RESET button
-- 2 quarter-turn, quick fastening screws and a base with 6 cable inlets and outlets via knockouts.
–– 1 AS or ASL 3-pole contactor with holding contact
–– 1 PE and 1 neutral terminal.
3 versions of control supply wiring are available: phase-to-phase, separate supply or phase-to-neutral.
1SBC133003V0014
T16 thermal overload relay has to be ordered separately and choses according to motor's nominal current
(see table below).
DRAS, DRASL enclosed DOL starters
DRAS IEC - AC-3 Rated control circuit Control supply Type Order code Weight
+ T16 to be ordered separately Rated operational voltage wiring
power max. Uc Pkg 5
Other control (1 pce)
220 V 400 V 500 V current voltages see AS
230 V θ ≤ 40 °C voltage code table
240 V Ue=400 V
kW kW kW A V 50/60 Hz V DC kg
AC operated with AS 3-pole contactors
2.2 4 4 9 24 - Separate supply DRAS09-20S 1SBK104235R2000 0.650
230 - Phase-to-neutral DRAS09-26N 1SBK104135R2600 0.650
240 - Phase-to-neutral DRAS09-27N 1SBK104135R2700 0.650
400 - Phase-to-phase DRAS09-28P 1SBK104035R2800 0.650
415 - Phase-to-phase DRAS09-29P 1SBK104035R2900 0.650
3 5.5 5.5 12 24 - Separate supply DRAS12-20S 1SBK114235R2000 0.650
230 - Phase-to-neutral DRAS12-26N 1SBK114135R2600 0.650
240 - Phase-to-neutral DRAS12-27N 1SBK114135R2700 0.650
400 - Phase-to-phase DRAS12-28P 1SBK114035R2800 0.650
415 - Phase-to-phase DRAS12-29P 1SBK114035R2900 0.650
4 7.5 7.5 15.5 24 - Separate supply DRAS16-20S 1SBK124235R2000 0.650
230 - Phase-to-neutral DRAS16-26N 1SBK124135R2600 0.650
240 - Phase-to-neutral DRAS16-27N 1SBK124135R2700 0.650
400 - Phase-to-phase DRAS16-28P 1SBK124035R2800 0.650
415 - Phase-to-phase DRAS16-29P 1SBK124035R2900 0.650
DC operated with ASL 3-pole contactors
2.2 4 4 9 - 24 Separate supply DRASL09-81S 1SBK104335R8100 0.700
- 48 DRASL09-83S 1SBK104335R8300 0.700
3 5.5 5.5 12 - 24 Separate supply DRASL12-81S 1SBK114335R8100 0.700
- 48 DRASL12-83S 1SBK114335R8300 0.700
4 7.5 7.5 15.5 - 24 Separate supply DRASL16-81S 1SBK124335R8100 0.700
- 48 DRASL16-83S 1SBK124335R8300 0.700
ABB | 5/1
6
Summary_6
6/0 | ABB
AF, EK contactors and NF contactor relays
55 to 200 kW / 75 to 350 hp
AF116 ... AF146 AC / DC operated 6/34
AF190 ... AF370 AC / DC operated 6/36
Main accessories 6/38
6
NF contactor relays
NF AC / DC operated 6/60
NFZ AC / DC operated - low consumption 6/61
Main accessories 6/62
For direct product details information, use product type or order code, ex:
Summary_6
www.abb.com/productdetails/AF09-30-10-13 or www.abb.com/productdetails/1SBL137001R1310
ABB | 6/1
DOL and reversing starters protected by manual motor starters
With AF contactors - open type version in kit form
Application
Full voltage direct-on-line (DOL) starting and reversing starting for controlling three-phase asynchronous
motors is a simple and economic solution characterised by a high starting torque (1.9 to 2.1 times full-speed
torque) and a starting current 5.5 to 7 times nominal current.
I>
I/In C/Cn
6
I
5
I = current
4 C = torque
In = nominal current
3
Cn = nominal torque
2
C
1
1SFC101102V0001
0 10 30 60 80 100
Reversing starter
MS132-10 + BEA16-4 + BER16-4
+ VEM4 + AF09-30-10
Mounting positions
+30° -30° +30° -30°
Pos. 2 Pos. 2
Pos. 4 Pos. 4
Pos. 3 Pos. 3
Pos. 5 Pos. 5
6/2 | ABB
DOL and reversing starters protected by manual motor starters
With AF contactors - open type version in kit form
Direct-on-line starters
Description
You can easily assemble a direct-on-line starter by using the BEA..-4
connecting link 3-pole insulated. It is used to electrically and me-
I>
BEA
Connecting link
Reversing starters
Description
You can easily assemble reversing starter thanks to our complete range
I>
of accessories:
MS
–– BEA..-4 connecting link 3-pole insulated: it is used to electrically and
Manual motor starter mechanically connect MS116 or MS132 manual motor starter and
AF09 ... AF38 contactor, AC or DC operated
–– For AF09 ... AF38, use VEM4 mechanical and electrical interlock set
Fixing clip
for reversing starter in 90 mm width. It includes:
-- VM4 mechanical interlock unit including 2 fixing clips
-- VE4 electrical interlock block with A2-A2 connection.
–– For AF40 ... AF96, use VM96-4 mechanical interlock unit and ad-
ditional auxiliary contact blocks for electrical interlocking
BEA
–– BER..-4 connection set: it assures a safe and simple reversing con-
Connecting link nection between both contactor main terminals.
VM4
Mechanical
interlock unit
A2 BER..-4
Connection set
A2
Select now easily and quickly your starter in the following pages for coordination type 1 or 2 at 400 V, 50 / 60 Hz, Iq = 16 kA up to 18.5 kW
1SBC101917S0201
and Iq = 50 kA up to 45 kW.
ABB | 6/3
DOL starters protected by MS manual motor starters
Coordination type 1
I>
BEA..-4 CA4-10
IEC Type Order code Current Magnetic Rated control circuit Type Order code Allowed Type Order code
AC-3, 400 V (1) setting tripping voltage (3) setting
Rated range current Uc min. ... Uc max. current
operational (2)
power current
kW A A A V 50/60 Hz V DC A
0.06 0.2 MS132-0.25 1SAM350000R1002 0.16...0.25 2.44 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.25 BEA16-4 1SBN081306T1000
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.09 0.3 MS132-0.4 1SAM350000R1003 0.25...0.40 3.9 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.4
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.12 0.44 MS132-0.63 1SAM350000R1004 0.40...0.63 6.14 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.63
6 100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.18 0.6 MS132-0.63 1SAM350000R1004 0.40...0.63 6.14 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.63
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.25 0.85 MS132-1.0 1SAM350000R1005 0.63...1.00 11.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.37 1.1 MS132-1.6 1SAM350000R1006 1.00...1.60 18.4 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1.6
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.55 1.5 MS132-1.6 1SAM350000R1006 1.00...1.60 18.4 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1.6
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.75 1.9 MS132-2.5 1SAM350000R1007 1.60...2.50 28.75 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 2.5
100...250 100...250 AF09-30-10-13 1SBL137001R1310
1.1 2.7 MS132-4.0 1SAM350000R1008 2.50...4.00 50 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 4
100...250 100...250 AF09-30-10-13 1SBL137001R1310
1.5 3.6 MS132-4.0 1SAM350000R1008 2.50...4.00 50 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 4
100...250 100...250 AF09-30-10-13 1SBL137001R1310
2.2 4.9 MS132-6.3 1SAM350000R1009 4.00...6.30 78.75 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 6.3
100...250 100...250 AF09-30-10-13 1SBL137001R1310
3 6.5 MS132-10 1SAM350000R1010 6.30...10.0 150 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 9
100...250 100...250 AF09-30-10-13 1SBL137001R1310
4 8.5 MS132-10 1SAM350000R1010 6.30...10.0 150 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 9
100...250 100...250 AF09-30-10-13 1SBL137001R1310
5.5 11.5 MS132-12 1SAM350000R1012 8.00...12.0 180 24...60 20...60 AF12Z-30-10-21 1SBL156001R2110 12
100...250 100...250 AF12-30-10-13 1SBL157001R1310
7.5 15.5 MS132-16 1SAM350000R1011 10.0...16.0 240 24...60 20...60 AF16Z-30-10-21 1SBL176001R2110 16
100...250 100...250 AF16-30-10-13 1SBL177001R1310
11 22 MS132-25 1SAM350000R1014 20.0...25.0 375 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 25 BEA38-4 1SBN082306T2000
100...250 100...250 AF26-30-00-13 1SBL237001R1300 + CA4-10 1SBN010110R1010
15 29 MS132-32 1SAM350000R1015 25.0...32.0 480 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 32
100...250 100...250 AF30-30-00-13 1SBL277001R1300
18.5 35 MS450-40 1SAM450000R1005 28.0…40.0 520 24…60 20…60 AF38Z-30-00-21 1SBL296001R2100 38 CA4-10 1SBN010110R1010
100...250 100...250 AF38-30-00-13 1SBL297001R1300
22 41 MS450-50 1SAM450000R1007 36.0…50.0 650 24…60 20…60 AF52-30-00-11 1SBL367001R1100 50
100...250 100...250 AF52-30-00-13 1SBL367001R1300
30 55 MS495-63 1SAM550000R1007 45.0…63.0 819 24…60 20…60 AF65-30-00-11 1SBL387001R1100 63
100...250 100...250 AF65-30-00-13 1SBL387001R1300
37 66 MS495-75 1SAM550000R1008 57.0…75.0 975 24…60 20…60 AF80-30-00-11 1SBL397001R1100 75
100...250 100...250 AF80-30-00-13 1SBL397001R1300
45 80 MS495-90 1SAM550000R1009 70.0…90.0 1170 24…60 20…60 AF80-30-00-11 1SBL397001R1100 80
100...250 100...250 AF80-30-00-13 1SBL397001R1300
(1) MS116 manual motor starter can be selected according to the current setting range indicated on the coordination line, up to:
- 15 kW, 400 V - AC-3 at 16 kA
- 4 kW, 400 V - AC-3 at 50 kA.
(2) For other control voltages, see "Voltage code table".
(3) AF40 3-pole contactor can be selected for coordination type 1, 16 kA and 50 kA, 18.5 kW, 400 V - AC-3.
1SBC101913S0201 - Rev. A
6/4 | ABB
DOL starters protected by MS manual motor starters
Coordination type 2
I>
BEA..-4 CA4-10
IEC Type Order code Current Magnetic Rated control circuit Type Order code Allowed Type Order code
AC-3, 400 V (1) setting tripping voltage (3) setting (4)
Rated range current Uc min. ... Uc max. current
operational (2)
power current
kW A A A V 50/60 Hz V DC A
0.06 0.2 MS132-0.25 1SAM350000R1002 0.16...0.25 2.44 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.25 BEA16-4 1SBN081306T1000
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.09 0.3 MS132-0.4 1SAM350000R1003 0.25...0.40 3.9 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.4
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.12 0.44 MS132-0.63 1SAM350000R1004 0.40...0.63 6.14 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.63
100...250 100...250 AF09-30-10-13 1SBL137001R1310 6
0.18 0.6 MS132-0.63 1SAM350000R1004 0.40...0.63 6.14 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.63
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.25 0.85 MS132-1.0 1SAM350000R1005 0.63...1.00 11.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.37 1.1 MS132-1.6 1SAM350000R1006 1.00...1.60 18.4 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1.6
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.55 1.5 MS132-1.6 1SAM350000R1006 1.00...1.60 18.4 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1.6
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.75 1.9 MS132-2.5 1SAM350000R1007 1.60...2.50 28.75 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 2.5
100...250 100...250 AF09-30-10-13 1SBL137001R1310
1.1 2.7 MS132-4.0 1SAM350000R1008 2.50...4.00 50 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 4 BEA26-4 1SBN082306T1000
100...250 100...250 AF26-30-00-13 1SBL237001R1300 + CA4-10 1SBN010110R1010
1.5 3.6 MS132-4.0 1SAM350000R1008 2.50...4.00 50 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 4
100...250 100...250 AF26-30-00-13 1SBL237001R1300
2.2 4.9 MS132-6.3 1SAM350000R1009 4.00...6.30 78.75 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 6.3
100...250 100...250 AF26-30-00-13 1SBL237001R1300
3 6.5 MS132-10 1SAM350000R1010 6.30...10.0 150 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 10
100...250 100...250 AF26-30-00-13 1SBL237001R1300
4 8.5 MS132-10 1SAM350000R1010 6.30...10.0 150 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 10
100...250 100...250 AF26-30-00-13 1SBL237001R1300
5.5 11.5 MS132-12 1SAM350000R1012 8.00...12.0 180 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 12 BEA38-4 1SBN082306T2000
100...250 100...250 AF26-30-00-13 1SBL237001R1300 + CA4-10 1SBN010110R1010
7.5 15.5 MS132-16 1SAM350000R1011 10.0...16.0 240 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 16
100...250 100...250 AF30-30-00-13 1SBL277001R1300
11 22 MS132-25 1SAM350000R1014 20.0...25.0 375 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 25
100...250 100...250 AF30-30-00-13 1SBL277001R1300
15 29 MS132-32 1SAM350000R1015 25.0...32.0 480 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 32
100...250 100...250 AF30-30-00-13 1SBL277001R1300
18.5 35 MS450-40 1SAM450000R1005 28.0…40.0 520 24…60 20…60 AF38Z-30-00-21 1SBL296001R2100 40 CA4-10 1SBN010110R1010
100…250 100…250 AF38-30-00-13 1SBL297001R1300
22 41 MS450-50 1SAM450000R1007 36.0…50.0 650 24…60 20…60 AF52-30-00-11 1SBL367001R1100 50
100…250 100…250 AF52-30-00-13 1SBL367001R1300
30 55 MS495-63 1SAM550000R1007 45.0…63.0 819 24…60 20…60 AF65-30-00-11 1SBL387001R1100 63
100…250 100…250 AF65-30-00-13 1SBL387001R1300
37 66 MS495-75 1SAM550000R1008 57.0…75.0 975 24…60 20…60 AF80-30-00-11 1SBL397001R1100 75
100…250 100…250 AF80-30-00-13 1SBL397001R1300
45 80 MS495-90 1SAM550000R1009 70.0…90.0 1170 24…60 20…60 AF96-30-00-11 1SBL407001R1100 90
100…250 100…250 AF96-30-00-13 1SBL407001R1300
(1) MS116 manual motor starter can be selected according to the current setting range indicated on the coordination line, up to
- 15 kW 400V - AC-3 at 16 kA
- 4 kW, 400 V - AC-3 at 50 kA.
(2) For other control voltages, see "Voltage code table".
(3) AF26 3-pole contactor can be selected for coordination type 2, 16 kA, 7.5 kW, 400 V - AC-3.
1SBC101914S0201 - Rev. A
AF40 3-pole contactor can be selected for coordination type 2, 16 kA and 50 kA, 18.5 kW, 400 V - AC-3.
(4) BEA26-4 should be selected with MS116-12 … MS116-16 and AF26 … AF38.
BEA38-4 can only be selected with MS116-20 … MS116-32.
ABB | 6/5
Reversing starters protected by MS manual motor starters
Coordination type 1
+
I>
BEA..-4 BER..-4
VEM4 CA4-10
IEC Type Order code Current Magnetic Rated control circuit Type Order code Allowed Type Order code
AC-3, 400 V (1) setting tripping voltage (3) setting
Rated range current Uc min. ... Uc max. current
operational (2)
power current
kW A A A V 50/60 Hz V DC A
0.06 0.2 MS132-0.25 1SAM350000R1002 0.16...0.25 2.44 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.25 BEA16-4 1SBN081306T1000
100...250 100...250 AF09-30-10-13 1SBL137001R1310 + BER16-4 1SBN081311R1000
+ VEM4 1SBN030111R1000
6 0.09 0.3 MS132-0.4 1SAM350000R1003 0.25...0.40 3.9 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.4
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.12 0.44 MS132-0.63 1SAM350000R1004 0.40...0.63 6.14 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.63
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.18 0.6 MS132-0.63 1SAM350000R1004 0.40...0.63 6.14 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.63
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.25 0.85 MS132-1.0 1SAM350000R1005 0.63...1.00 11.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.37 1.1 MS132-1.6 1SAM350000R1006 1.00...1.60 18.4 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1.6
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.55 1.5 MS132-1.6 1SAM350000R1006 1.00...1.60 18.4 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1.6
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.75 1.9 MS132-2.5 1SAM350000R1007 1.60...2.50 28.75 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 2.5
100...250 100...250 AF09-30-10-13 1SBL137001R1310
1.1 2.7 MS132-4.0 1SAM350000R1008 2.50...4.00 50 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 4
100...250 100...250 AF09-30-10-13 1SBL137001R1310
1.5 3.6 MS132-4.0 1SAM350000R1008 2.50...4.00 50 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 4
100...250 100...250 AF09-30-10-13 1SBL137001R1310
2.2 4.9 MS132-6.3 1SAM350000R1009 4.00...6.30 78.75 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 6.3
100...250 100...250 AF09-30-10-13 1SBL137001R1310
3 6.5 MS132-10 1SAM350000R1010 6.30...10.0 150 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 9
100...250 100...250 AF09-30-10-13 1SBL137001R1310
4 8.5 MS132-10 1SAM350000R1010 6.30...10.0 150 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 9
100...250 100...250 AF09-30-10-13 1SBL137001R1310
5.5 11.5 MS132-12 1SAM350000R1012 8.00...12.0 180 24...60 20...60 AF12Z-30-10-21 1SBL156001R2110 12
100...250 100...250 AF12-30-10-13 1SBL157001R1310
7.5 15.5 MS132-16 1SAM350000R1011 10.0...16.0 240 24...60 20...60 AF16Z-30-10-21 1SBL176001R2110 16
100...250 100...250 AF16-30-10-13 1SBL177001R1310
11 22 MS132-25 1SAM350000R1014 20.0...25.0 375 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 25 BEA38-4 1SBN082306T2000
100...250 100...250 AF26-30-00-13 1SBL237001R1300 + BER38-4 1SBN082311R1000
15 29 MS132-32 1SAM350000R1015 25.0...32.0 480 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 32 + VEM4 1SBN030111R1000
100...250 100...250 AF30-30-00-13 1SBL277001R1300 + 2x CA4-10 1SBN010110R1010
18.5 35 MS450-40 1SAM450000R1005 28.0…40.0 520 24…60 20…60 AF38Z-30-00-21 1SBL296001R2100 38 BER38-4 1SBN082311R1000
+ VEM4 1SBN030111R1000
100…250 100…250 AF38-30-00-13 1SBL297001R1300 + 2x CA4-10 1SBN010110R1010
22 41 MS450-50 1SAM450000R1007 36.0…50.0 650 24…60 20…60 AF52-30-00-11 1SBL367001R1100 50 BER65-4 1SBN083411R1000
100…250 100…250 AF52-30-00-13 1SBL367001R1300 + VM96-4 1SBN033405T1000
30 55 MS495-63 1SAM550000R1007 45.0…63.0 819 24…60 20…60 AF65-30-00-11 1SBL387001R1100 63 + 2x CA4-10 1SBN010110R1010
100…250 100…250 AF65-30-00-13 1SBL387001R1300 + 2x CA4-01 1SBN010110R1001
37 66 MS495-75 1SAM550000R1008 57.0…75.0 975 24…60 20…60 AF80-30-00-11 1SBL397001R1100 75 BER96-4 1SBN083911R1000
100…250 100…250 AF80-30-00-13 1SBL397001R1300 + VM96-4 1SBN033405T1000
45 80 MS495-90 1SAM550000R1009 70.0…90.0 1170 24…60 20…60 AF80-30-00-11 1SBL397001R1100 80 + 2x CA4-10 1SBN010110R1010
+ 2x CA4-01 1SBN010110R1001
100…250 100…250 AF80-30-00-13 1SBL397001R1300
1SBC101915S0201 - Rev. A
(1) MS116 manual motor starter can be selected according to the current setting range indicated on the coordination line, up to:
- 15 kW, 400 V - AC-3 at 16 kA
- 4 kW, 400 V - AC-3 at 50 kA.
(2) For other control voltages, see "Voltage code table".
(3) AF40 3-pole contactor can be selected for coordination type 1, 16 kA and 50 kA, 18.5 kW, 400 V - AC-3.
6/6 | ABB
Reversing starters protected by MS manual motor starters
Coordination type 2
+
I>
BEA..-4 BER..-4
VEM4 CA4-10
IEC Type Order code Current Magnetic Rated control circuit Type Order code Allowed Type Order code
AC-3, 400 V (1) setting tripping voltage (3) setting (4)
Rated range current Uc min. ... Uc max. current
operational (2)
power current
kW A A A V 50/60 Hz V DC A
0.06 0.2 MS132-0.25 1SAM350000R1002 0.16...0.25 2.44 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.25 BEA16-4 1SBN081306T1000
100...250 100...250 AF09-30-10-13 1SBL137001R1310 + BER16-4 1SBN081311R1000
0.09 0.3 MS132-0.4 1SAM350000R1003 0.25...0.40 3.9 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.4 + VEM4 1SBN030111R1000
100...250 100...250 AF09-30-10-13 1SBL137001R1310
6
0.12 0.44 MS132-0.63 1SAM350000R1004 0.40...0.63 6.14 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.63
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.18 0.6 MS132-0.63 1SAM350000R1004 0.40...0.63 6.14 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.63
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.25 0.85 MS132-1.0 1SAM350000R1005 0.63...1.00 11.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.37 1.1 MS132-1.6 1SAM350000R1006 1.00...1.60 18.4 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1.6
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.55 1.5 MS132-1.6 1SAM350000R1006 1.00...1.60 18.4 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1.6
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.75 1.9 MS132-2.5 1SAM350000R1007 1.60...2.50 28.75 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 2.5
100...250 100...250 AF09-30-10-13 1SBL137001R1310
1.1 2.7 MS132-4.0 1SAM350000R1008 2.50...4.00 50 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 4 BEA26-4 1SBN082306T1000
100...250 100...250 AF26-30-00-13 1SBL237001R1300 + BER38-4 1SBN082311R1000
1.5 3.6 MS132-4.0 1SAM350000R1008 2.50...4.00 50 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 4 + VEM4 1SBN030111R1000
100...250 100...250 AF26-30-00-13 1SBL237001R1300 + 2x CA4-10 1SBN010110R1010
2.2 4.9 MS132-6.3 1SAM350000R1009 4.00...6.30 78.75 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 6.3
100...250 100...250 AF26-30-00-13 1SBL237001R1300
3 6.5 MS132-10 1SAM350000R1010 6.30...10.0 150 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 10
100...250 100...250 AF26-30-00-13 1SBL237001R1300
4 8.5 MS132-10 1SAM350000R1010 6.30...10.0 150 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 10
100...250 100...250 AF26-30-00-13 1SBL237001R1300
5.5 11.5 MS132-12 1SAM350000R1012 8.00...12.0 180 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 12 BEA38-4 1SBN082306T2000
100...250 100...250 AF26-30-00-13 1SBL237001R1300 + BER38-4 1SBN082311R1000
7.5 15.5 MS132-16 1SAM350000R1011 10.0...16.0 240 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 16 + VEM4 1SBN030111R1000
100...250 100...250 AF30-30-00-13 1SBL277001R1300 + 2x CA4-10 1SBN010110R1010
11 22 MS132-25 1SAM350000R1014 20.0...25.0 375 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 25
100...250 100...250 AF30-30-00-13 1SBL277001R1300
15 29 MS132-32 1SAM350000R1015 25.0...32.0 480 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 32
100...250 100...250 AF30-30-00-13 1SBL277001R1300
18.5 35 MS450-40 1SAM450000R1005 28.0…40.0 520 24…60 20…60 AF38Z-30-00-21 1SBL296001R2100 40 BER65-4 1SBN083411R1000
100...250 100...250 AF38-30-00-13 1SBL297001R1300 + VM96-4 1SBN033405T1000
22 41 MS450-50 1SAM450000R1007 36.0…50.0 650 24…60 20…60 AF52-30-00-11 1SBL367001R1100 50 + 2x CA4-10 1SBN010110R1010
100...250 100...250 AF52-30-00-13 1SBL367001R1300 + 2x CA4-01 1SBN010110R1001
30 55 MS495-63 1SAM550000R1007 45.0…63.0 819 24…60 20…60 AF65-30-00-11 1SBL387001R1100 63
100...250 100...250 AF65-30-00-13 1SBL387001R1300
37 66 MS495-75 1SAM550000R1008 57.0…75.0 975 24…60 20…60 AF80-30-00-11 1SBL397001R1100 75 BER96-4 1SBN083911R1000
100...250 100...250 AF80-30-00-13 1SBL397001R1300 + VM96-4 1SBN033405T1000
45 80 MS495-90 1SAM550000R1009 70.0…90.0 1170 24…60 20…60 AF96-30-00-11 1SBL407001R1100 90 + 2x CA4-10 1SBN010110R1010
100...250 100...250 AF96-30-00-13 1SBL407001R1300 + 2x CA4-01 1SBN010110R1001
(1) MS116 manual motor starter can be selected according to the current setting range indicated on the coordination line, up to
- 15 kW 400V - AC-3 at 16 kA
- 4 kW, 400 V - AC-3 at 50 kA.
1SBC101916S0201 - Rev. A
ABB | 6/7
DOL starters protected by moulded-case circuit-breakers and
overload relays
With AF contactors - Open type version in kit form
Application
Full voltage direct-on-line (DOL) starting for controlling three-phase asynchronous motors is a simple and
economic solution characterised by a high starting torque (1.9 to 2.1 times full-speed torque) and a starting
current 5.5 to 7 times nominal current.
I/In C/Cn
6
I
5
I = current
4 C = torque
In = nominal current
3
Cn = nominal torque
2
C
1
1SFC101191V0001
0 10 30 60 80 100
Mounting positions
Pos. 2 +30° -30°
XT2S 160 + BEA140/XT2 +
AF140-30-11 + EF146
Pos. 4
Pos. 3
Pos. 1
1SBC101973S0201
Pos. 5
Direct-on-line Direct-on-line
MCCB + AF MCCB + AF + OL
6/8 | ABB
DOL starters protected by moulded-case circuit-breakers and
overload relays
With AF contactors - Open type version in kit form
Description
MCCB MCCB You can easily assemble a direct-on-
Moulded-case circuit-breaker Moulded-case circuit-breaker
line starter by using the BEA connection
including motor protection (magnetic only)
bars. It is used to electrically connect
MCCB moulded-case circuit-breaker and
AF116 ... AF370 contactor, AC or DC
operated.
TF
Thermal overload relay
EF
Electronic overload relay
1SBC101973S0201
ABB | 6/9
DOL starters protected by MCCB including motor protection
Coordination type 1 or 2
+
IEC Magnetic Max. allowed Base Trip unit
AC-3, 400 V triping thermal setting Type Order code Type Order code
Rated Rated current
power current setting
kW A A
55 97 1440 116 XT2S 160 1SDA068164R1 + Ekip M-LIU In160 1SDA067355R1
75 132 1920 140 XT2S 160 1SDA068164R1 + Ekip M-LIU In160 1SDA067355R1
6
90 160 2400 190 T4S 250 PR222MP In200 1SDA054527R1 Included -
110 195 2880 205 T5S 400 PR222MP In320 1SDA054553R1 Included -
132 230 3600 265 T5S 400 PR222MP In400 1SDA054554R1 Included -
160 280 4400 305 T5S 400 PR222MP In400 1SDA054554R1 Included -
6/10 | ABB
Contactors Connection bars
V 50/60 Hz V DC
24...60 20...60 AF116-30-11-11 1SFL427001R1111 BEA140/XT2 1SFN084206R1000
100...250 100...250 AF116-30-11-13 1SFL427001R1311
24...60 20...60 AF140-30-11-11 1SFL447001R1111
100...250 100...250 AF140-30-11-13 1SFL447001R1311 6
24...60 20...60 AF190-30-11-11 1SFL487002R1111 BEA205/T4 1SFN084806R1001
100...250 100...250 AF190-30-11-13 1SFL487002R1311
24...60 20...60 AF205-30-11-11 1SFL527002R1111
100...250 100...250 AF205-30-11-13 1SFL527002R1311
24...60 20...60 AF265-30-11-11 1SFL547002R1111 BEA370/T5 1SFN085406R1000
100...250 100...250 AF265-30-11-13 1SFL547002R1311
24...60 20...60 AF305-30-11-11 1SFL587002R1111
100...250 100...250 AF305-30-11-13 1SFL587002R1311
1SBC101975S0201
ABB | 6/11
DOL starters protected by MCCB (magnetic only) and overload relays
Coordination type 1 or 2
6/12 | ABB
Overload relays Connection bars
A A
80...110 110 TF140DU-110 1SAZ431201R1002 BEA140/XT2 1SFN084206R1000
6
110...142 140 TF140DU-142 1SAZ431201R1004
1SBC101974S0201
ABB | 6/13
DOL and reversing starters protected by overload relays
With AF contactors - Open type version in kit form
Application
Full voltage direct-on-line and reversing starting for controlling three-phase asynchronous motors is a simple
and economic solution characterised by a high starting torque (1.9 to 2.1 times full-speed torque) and a
starting current 5.5 to 7 times nominal current.
I/In C/Cn
6
1SBC100058V0014
I
5
I = current
4 C = torque
In = nominal current
3
Cn = nominal torque
AF09-30-10 + TF42 2
C
0 10 30 60 80 100
6
Coordination Types
The contactor, the short-circuit protection device and the thermal overload relay control and protect motors
against overload and short-circuits according to coordination types 1 and 2 (IEC 60947-4-1 / EN 60947-4-1)
1SFC101153V0001
Mounting positions
1SFC101152V0001
1SBC101920S0201
6/14 | ABB
DOL and reversing starters protected by overload relays
With AF contactors - Open type version in kit form
Description
Direct-On-Line Reversing starters for AF09 ... AF38 You can easily assemble a direct-on-line
starters starter by connecting AF contactor and
Fixing clip
TF thermal overload relay or EF electronic
A2 overload relay.
AF09 ... AF96 You can also easily assemble reversing
Contactor AF09 ... AF38
A2
Contactors
starter thanks to our complete range of
accessories:
–– For AF09 ... AF38, use VEM4 me-
chanical and electrical interlock set for
reversing starter in 90 mm width.
VM4 It includes:
Mechanical -- VM4 mechanical interlock unit includ-
interlock unit ing 2 fixing clips
-- VE4 electrical interlock block with
A2-A2 connection.
–– For AF40 ... AF370, use VM mechani-
cal interlock unit and additional auxiliary
contact blocks for electrical interlocking.
VE4
Electrical –– BER..-4 connection set: it assures a 6
interlock safe and simple reversing connection
block between both contactor main terminals.
BER..-4 AF contactor
Connection set with built-in
cable clamps
VM
Mechanical
interlock
unit
AF contactor
with built-in
cable clamps
TF/TA
Thermal overload relay
1SBC101920S0201
BER..-4 EF
Connection set Electronic overload relay
ABB | 6/15
Direct-on-line starters protected by thermal overload relays
With AF contactors - Open type version in kit form
IEC Control voltage Type Order code Setting ranges Type Order code
AC-3, 400 V Uc min. ... Uc max.
(1)
Rated Rated
power current
kW A V 50/60 Hz V DC A
4 8.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 7.60...10.0 TF42-10 1SAZ721201R1043
100...250 100...250 AF09-30-10-13 1SBL137001R1310
5.5 11.5 24...60 20...60 AF12Z-30-10-21 1SBL156001R2110 10.0...13.0 TF42-13 1SAZ721201R1045
100...250 100...250 AF12-30-10-13 1SBL157001R1310
7.5 15.5 24...60 20...60 AF16Z-30-10-21 1SBL176001R2110 13.0...16.0 TF42-16 1SAZ721201R1047
100...250 100...250 AF16-30-10-13 1SBL177001R1310
6 11 22 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 20.0...24.0 TF42-24 1SAZ721201R1051
100...250 100...250 AF26-30-00-13 1SBL237001R1300
15 29 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 29.0...35.0 TF42-35 1SAZ721201R1053
100...250 100...250 AF30-30-00-13 1SBL277001R1300
18.5 35 24...60 20...60 AF38Z-30-00-21 1SBL296001R2100 35.0...38.0/40.0 TF42-38 1SAZ721201R1055
100...250 100...250 AF38-30-00-13 1SBL297001R1300
18.5 35 24...60 20...60 AF40-30-00-11 1SBL347001R1100 30.0...40.0 TF65-40 1SAZ811201R1003
100...250 100...250 AF40-30-00-13 1SBL347001R1300
22 41 24…60 20…60 AF52-30-00-11 1SBL367001R1100 36.00…47.0 TF65-47 1SAZ811201R1004
100-250 100-250 AF52-30-00-13 1SBL367001R1300
30 55 24…60 20…60 AF65-30-00-11 1SBL387001R1100 50.0…60.0 TF65-60 1SAZ811201R1006
100-250 100-250 AF65-30-00-13 1SBL387001R1300
37 66 24…60 20…60 AF80-30-00-11 1SBL397001R1100 57.0…68.0 TF96-68 1SAZ911201R1003
100-250 100-250 AF80-30-00-13 1SBL397001R1300
45 80 24…60 20…60 AF96-30-00-11 1SBL407001R1100 75.0..87.0 TF96-87 1SAZ911201R1005
100-250 100-250 AF96-30-00-13 1SBL407001R1300
55 97 24…60 20…60 AF116-30-11-11 1SFL427001R1111 80…110 TF140DU-110 1SAZ431201R1002
100-250 100-250 AF116-30-11-13 1SFL427001R1311
75 132 24…60 20…60 AF140-30-11-11 1SFL447001R1111 100…135 TF140DU-135 1SAZ431201R1003
100-250 100-250 AF140-30-11-13 1SFL447001R1311
90 160 24…60 20…60 AF190-30-11-11 1SFL487002R1111 130…175 TA200DU-175 1SAZ421201R1005
100-250 100-250 AF190-30-11-13 1SFL487002R1311
110 195 24…60 20…60 AF205-30-11-11 1SFL527002R1111 150…200 TA200DU-200 1SAZ421201R1006
100-250 100-250 AF205-30-11-13 1SFL527002R1311
(1) For other control voltages, see "Voltage code table".
Note : for rated power above 110 kW, refer to "Starters protected by electronic overload relays".
1SBC101921S0201
6/16 | ABB
Reversing starters protected by thermal overload relays
With AF contactors - Open type version in kit form
+
BER..-4
VEM4 CA4-10
IEC Control voltage Type Order code Setting ranges Type Order code Type Order code
AC-3, 400 V Uc min. ... Uc max.
(1)
Rated Rated
power current
kW A V 50/60 Hz V DC A
4 8.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 7.60...10.0 TF42-10 1SAZ721201R1043 BER16-4 1SBN081311R1000
100...250 100...250 AF09-30-10-13 1SBL137001R1310 + VEM4 1SBN030111R1000
5.5 11.5 24...60 20...60 AF12Z-30-10-21 1SBL156001R2110 10.0...13.0 TF42-13 1SAZ721201R1045
100...250 100...250 AF12-30-10-13 1SBL157001R1310
7.5 15.5 24...60 20...60 AF16Z-30-10-21 1SBL176001R2110 13.0...16.0 TF42-16 1SAZ721201R1047 6
100...250 100...250 AF16-30-10-13 1SBL177001R1310
11 22 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 20.0...24.0 TF42-24 1SAZ721201R1051 BER38-4 1SBN082311R1000
100...250 100...250 AF26-30-00-13 1SBL237001R1300 + VEM4 1SBN030111R1000
+ 2x CA4-10 1SBN010110R1010
15 29 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 29.0...35.0 TF42-35 1SAZ721201R1053
100...250 100...250 AF30-30-00-13 1SBL277001R1300
18.5 35 24...60 20...60 AF38Z-30-00-21 1SBL296001R2100 35.0...38.0/40.0 TF42-38 1SAZ721201R1055
100...250 100...250 AF38-30-00-13 1SBL297001R1300
18.5 35 24...60 20...60 AF40-30-00-11 1SBL347001R1100 30.0...40.0 TF65-40 1SAZ811201R1003 BER65-4 1SBN083411R1000
100...250 100...250 AF40-30-00-13 1SBL347001R1300 + VM96-4 1SBN033405T1000
+ 2x CA4-10 1SBN010110R1010
22 41 24...60 20...60 AF52-30-00-11 1SBL367001R1100 36.00…47.0 TF65-47 1SAZ811201R1004
+ 2x CA4-01 1SBN010110R1001
100...250 100...250 AF52-30-00-13 1SBL367001R1300
30 55 24...60 20...60 AF65-30-00-11 1SBL387001R1100 50.0…60.0 TF65-60 1SAZ811201R1006
100...250 100...250 AF65-30-00-13 1SBL387001R1300
37 66 24...60 20...60 AF80-30-00-11 1SBL397001R1100 57.0…68.0 TF96-68 1SAZ911201R1003 BER96-4 1SBN083911R1000
100...250 100...250 AF80-30-00-13 1SBL397001R1300 + VM96-4 1SBN033405T1000
+ 2x CA4-10 1SBN010110R1010
45 80 24...60 20...60 AF96-30-00-11 1SBL407001R1100 75.0..87.0 TF96-87 1SAZ911201R1005
+ 2x CA4-01 1SBN010110R1001
100...250 100...250 AF96-30-00-13 1SBL407001R1300
55 97 24...60 20...60 AF116-30-11-11 1SFL427001R1111 80…110 TF140DU-110 1SAZ431201R1002 BER140-4 1SFN084211R1000
100...250 100...250 AF116-30-11-13 1SFL427001R1311 + VM19 1SFN030300R1000
75 132 24...60 20...60 AF140-30-11-11 1SFL447001R1111 100…135 TF140DU-135 1SAZ431201R1003
100...250 100...250 AF140-30-11-13 1SFL447001R1311
90 160 24...60 20...60 AF190-30-11-11 1SFL487002R1111 130…175 TA200DU-175 1SAZ421201R1005 BER205-4 1SFN084811R1000
100...250 100...250 AF190-30-11-13 1SFL487002R1311 + VM19 1SFN030300R1000
110 195 24...60 20...60 AF205-30-11-11 1SFL527002R1111 150…200 TA200DU-200 1SAZ421201R1006
100...250 100...250 AF205-30-11-13 1SFL527002R1311
(1) For other control voltages, see "Voltage code table".
Note : for rated power above 110 kW, refer to "Starters protected by electronic overload relays".
1SBC101922S0201
ABB | 6/17
Direct-on-line starters protected by electronic overload relays
With AF contactors - Open type version in kit form
IEC Control voltage Type Order code Setting ranges Type Order code
AC-3, 400 V Uc min. ... Uc max.
(1)
Rated Rated
power current
kW A V 50/60 Hz V DC A
4 8.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 5.70…18.9 EF19-18.9 1SAX121001R1105
100...250 100...250 AF09-30-10-13 1SBL137001R1310
5.5 11.5 24...60 20...60 AF12Z-30-10-21 1SBL156001R2110 5.70…18.9 EF19-18.9 1SAX121001R1105
100...250 100...250 AF12-30-10-13 1SBL157001R1310
7.5 15.5 24...60 20...60 AF16Z-30-10-21 1SBL176001R2110 5.70…18.9 EF19-18.9 1SAX121001R1105
100...250 100...250 AF16-30-10-13 1SBL177001R1310
6 11 22 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 9.00…30.0 EF45-30 1SAX221001R1101
100...250 100...250 AF26-30-00-13 1SBL237001R1300
15 29 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 9.00…30.0 EF45-30 1SAX221001R1101
100...250 100...250 AF30-30-00-13 1SBL277001R1300
18.5 35 24...60 20...60 AF38Z-30-00-21 1SBL296001R2100 15.0…45.0 EF45-45 1SAX221001R1102
100...250 100...250 AF38-30-00-13 1SBL297001R1300
18.5 35 24...60 20...60 AF40-30-00-11 1SBL347001R1100 25.0...70.0 EF65-70 1SAX331001R1101
100...250 100...250 AF40-30-00-13 1SBL347001R1300
22 41 24…60 20…60 AF52-30-00-11 1SBL367001R1100 25.0…70.0 EF65-70 1SAX331001R1101
100-250 100-250 AF52-30-00-13 1SBL367001R1300
30 55 24…60 20…60 AF65-30-00-11 1SBL387001R1100 25.0…70.0 EF65-70 1SAX331001R1101
100-250 100-250 AF65-30-00-13 1SBL387001R1300
37 66 24…60 20…60 AF80-30-00-11 1SBL397001R1100 36…100 EF96-100 1SAX341001R1101
100-250 100-250 AF80-30-00-13 1SBL397001R1300
45 80 24…60 20…60 AF96-30-00-11 1SBL407001R1100 36…100 EF96-100 1SAX341001R1101
100-250 100-250 AF96-30-00-13 1SBL407001R1300
55 97 24…60 20…60 AF116-30-11-11 1SFL427001R1111 54…150 EF146-150 1SAX351001R1101
100-250 100-250 AF116-30-11-13 1SFL427001R1311
75 132 24…60 20…60 AF140-30-11-11 1SFL447001R1111 54…150 EF146-150 1SAX351001R1101
100-250 100-250 AF140-30-11-13 1SFL447001R1311
90 160 24…60 20…60 AF190-30-11-11 1SFL487002R1111 63…210 EF205-210 1SAX531001R1101
100-250 100-250 AF190-30-11-13 1SFL487002R1311
110 195 24…60 20…60 AF205-30-11-11 1SFL527002R1111 63…210 EF205-210 1SAX531001R1101
100-250 100-250 AF205-30-11-13 1SFL527002R1311
132 230 24…60 20…60 AF265-30-11-11 1SFL547002R1111 115…380 EF370-380 1SAX611001R1101
100-250 100-250 AF265-30-11-13 1SFL547002R1311
160 280 24…60 20…60 AF305-30-11-11 1SFL587002R1111 115…380 EF370-380 1SAX611001R1101
100-250 100-250 AF305-30-11-13 1SFL587002R1311
200 350 24…60 20…60 AF370-30-11-11 1SFL607002R1111 115…380 EF370-380 1SAX611001R1101
100-250 100-250 AF370-30-11-13 1SFL607002R1311
(1) For other control voltages, see "Voltage code table".
1SBC101948S0201
6/18 | ABB
Reversing starters protected by electronic overload relays
With AF contactors - Open type version in kit form
+
BER..-4
VEM4 CA4-10
IEC Control voltage Type Order code Setting ranges Type Order code Type Order code
AC-3, 400 V Uc min. ... Uc max.
(1)
Rated Rated
power current
kW A V 50/60 Hz V DC A
4 8.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 5.70…18.9 EF19-18.9 1SAX121001R1105 BER16-4 1SBN081311R1000
100...250 100...250 AF09-30-10-13 1SBL137001R1310 + VEM4 1SBN030111R1000
5.5 11.5 24...60 20...60 AF12Z-30-10-21 1SBL156001R2110 5.70…18.9 EF19-18.9 1SAX121001R1105
100...250 100...250 AF12-30-10-13 1SBL157001R1310
7.5 15.5 24...60 20...60 AF16Z-30-10-21 1SBL176001R2110 5.70…18.9 EF19-18.9 1SAX121001R1105 6
100...250 100...250 AF16-30-10-13 1SBL177001R1310
11 22 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 9.00…30.0 EF45-30 1SAX221001R1101 BER38-4 1SBN082311R1000
100...250 100...250 AF26-30-00-13 1SBL237001R1300 + VEM4 1SBN030111R1000
+ 2x CA4-10 1SBN010110R1010
15 29 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 9.00…30.0 EF45-30 1SAX221001R1101
100...250 100...250 AF30-30-00-13 1SBL277001R1300
18.5 35 24...60 20...60 AF38Z-30-00-21 1SBL296001R2100 15.0…45.0 EF45-45 1SAX221001R1102
100...250 100...250 AF38-30-00-13 1SBL297001R1300
18.5 35 24...60 20...60 AF40-30-00-11 1SBL347001R1100 25.0...70.0 EF65-70 1SAX331001R1101 BER65-4 1SBN083411R1000
100...250 100...250 AF40-30-00-13 1SBL347001R1300 + VM96-4 1SBN033405T1000
+ 2x CA4-10 1SBN010110R1010
22 41 24...60 20...60 AF52-30-00-11 1SBL367001R1100 25.0…70.0 EF65-70 1SAX331001R1101
+ 2x CA4-01 1SBN010110R1001
100...250 100...250 AF52-30-00-13 1SBL367001R1300
30 55 24...60 20...60 AF65-30-00-11 1SBL387001R1100 25.0…70.0 EF65-70 1SAX331001R1101
100...250 100...250 AF65-30-00-13 1SBL387001R1300
37 66 24...60 20...60 AF80-30-00-11 1SBL397001R1100 36…100 EF96-100 1SAX341001R1101 BER96-4 1SBN083911R1000
100...250 100...250 AF80-30-00-13 1SBL397001R1300 + VM96-4 1SBN033405T1000
+ 2x CA4-10 1SBN010110R1010
45 80 24...60 20...60 AF96-30-00-11 1SBL407001R1100 36…100 EF96-100 1SAX341001R1101
+ 2x CA4-01 1SBN010110R1001
100...250 100...250 AF96-30-00-13 1SBL407001R1300
55 97 24...60 20...60 AF116-30-11-11 1SFL427001R1111 54…150 EF146-150 1SAX351001R1101 BER140-4 1SFN084211R1000
100...250 100...250 AF116-30-11-13 1SFL427001R1311 + VM19 1SFN030300R1000
75 132 24...60 20...60 AF140-30-11-11 1SFL447001R1111 54…150 EF146-150 1SAX351001R1101
100...250 100...250 AF140-30-11-13 1SFL447001R1311
90 160 24...60 20...60 AF190-30-11-11 1SFL487002R1111 63…210 EF205-210 1SAX531001R1101 BER205-4 1SFN084811R1000
100...250 100...250 AF190-30-11-13 1SFL487002R1311 + VM19 1SFN030300R1000
110 195 24...60 20...60 AF205-30-11-11 1SFL527002R1111 63…210 EF205-210 1SAX531001R1101
100...250 100...250 AF205-30-11-13 1SFL527002R1311
132 230 24...60 20...60 AF265-30-11-11 1SFL547002R1111 115…380 EF370-380 1SAX611001R1101 BER370-4 1SFN085411R1000
100...250 100...250 AF265-30-11-13 1SFL547002R1311 + VM19 1SFN030300R1000
160 280 24...60 20...60 AF305-30-11-11 1SFL587002R1111 115…380 EF370-380 1SAX611001R1101
100...250 100...250 AF305-30-11-13 1SFL587002R1311
200 350 24...60 20...60 AF370-30-11-11 1SFL607002R1111 115…380 EF370-380 1SAX611001R1101
100...250 100...250 AF370-30-11-13 1SFL607002R1311
(1) For other control voltages, see "Voltage code table".
1SBC101949S0201
ABB | 6/19
Star-delta starters protected by overload relays
With AF contactors - Open type version in kit form
Application
Y Star-delta starting is the most common method to reduce the starting current of a motor.
L Δ
This system can be used on all the squirrel cage motors, which are normally used in delta connection. In this
type of starting, it is recommended to choose motors having high starting torque i.e. much higher than the
resistive torque in order to reach sufficient high speed when the motor is connected in star.
starting torque.
5
Transient current is generated when switching from star to
4 delta connection.
During the initial starting phase ("star" connection), the
3 resistive torque of the driven load must remain, irrespective
T∆ (motor)
of speed, less than the "star" motor torque until "star-delta"
2 switching occurs.
I (star)
6 AF16-30-10 + AF16-30-10 + 1 This starting mode is therefore ideal for machines having
T (motor) low starting torque such as pumps, centrifugal compres-
AF09-30-10 + BEY16-4 + VEM4 +
Tr (resistive torque)
TF42 sors, wood-working machines...
0 20 40 60 80 100
Motor speed (%)
Precaution
1SFC101104V0001
–– Motor nominal voltage in delta connection must be equal to that of the mains. Example: a motor for 400 V
star-delta starting must be designed for 400 V in "delta" connection. Its usual designation is "400 V /
690 V motor". The motor must be constructed with 6 terminal windings
–– In order to prevent a high current peak, at least 85 % of nominal speed must be reached before switching
from star to delta
Sequence
AF140-30-11 + AF140-30-11 + Starting is a three-stage process:
AF140-30-11 + BEY140-4 + VM19
+ EF146 1st stage: "Star" connection - Press the "On" button on the control circuit to close the KM2 "Star" contactor.
The KM1 "line" contactor then closes and the motor starts. Countdown of programmed starting time (6 to
10 s) then begins.
2nd stage: "Star" to "Delta" switching - when programmed starting time is over, the KM2 "Star" contactor opens.
3rd stage: "Delta" connection - Thanks to AF contactors, a transition time (or dwelling time) of 50 ms is
already integrated between the opening of the "star" contactor and closing of the "delta" contactor.
Conclusion: An on-delay timer without dwelling time (e.g.: CT-ERS.21S or TEF4-ON) is enough to count-
down the programmed starting time (6 to 10 s) during "Star connection". The use of a star-delta timer includ-
ing a dwelling time is not permitted.
Pos. 1
6/20 | ABB
Star-delta starters protected by overload relays
With AF contactors - Open type version in kit form
Description
Star-delta starters for AF09 ... AF38 You can easily assemble star-delta starter
L Δ
Y thanks to our complete range of acces-
A2
sories:
–– For AF09 ... AF38, use VEM4 mechani-
A2
cal and electrical interlock set without
increasing starter width. It includes:
2 -- VM4 mechanical interlock unit and 2
Fixing KM
clip fixing clips
-- VE4 electrical interlock block with
A2-A2 connection.
3 –– For AF40 ... AF370, use VM mechani-
KM cal interlock unit and additional auxiliary
1
KM contact blocks for electrical interlocking.
AF09 ... AF38 –– BEY..-4 connection set: it assures a
Contactors VM4 safe and simple connection between
Mechanical VE4
interlock Electrical both contactor main terminals.
unit interlock block
BEY..-4
Connection set For the full coordination tables:
www.abb.com/lowvoltage then go to the right
menu: "Support", select: "Online Product Selection
TF42 Tools" then select "Coordination Tables for motor
Thermal overload relay protection"
EF19, EF45
Electronic overload relay
2 AF contactor
KM with built-in
cable clamps
BEY..-4
Connection set
VM
Mechanical
3 interlock
KM unit
1
KM
AF contactor
with built-in
cable clamps
BEY..-4
Connection set
TF/TA
1SBC101956S0201
ABB | 6/21
Star-delta starters protected by thermal overload relays
With AF contactors - Open type version in kit form
Y
L Δ
IEC Control voltage Type Order code Type Order code Type Order code
AC-3 Uc min. ... Uc max.
Rated power Rated (1)
current
220 V 230/240 V 380 V 400 V 415 V 440 V 500 V 690 V 400 V
kW kW kW kW kW kW kW kW A V 50/60 Hz V DC
4 4 7.5 7.5 7.5 7.5 9 9 15.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 AF09Z-30-10-21 1SBL136001R2110 AF09Z-30-10-21 1SBL136001R2110
100...250 100...250 AF09-30-10-13 1SBL137001R1310 AF09-30-10-13 1SBL137001R1310 AF09-30-10-13 1SBL137001R1310
5.5 5.5 9 11 11 11 11 11 22 24...60 20...60 AF12Z-30-10-21 1SBL156001R2110 AF12Z-30-10-21 1SBL156001R2110 AF09Z-30-10-21 1SBL136001R2110
100...250 100...250 AF12-30-10-13 1SBL157001R1310 AF12-30-10-13 1SBL157001R1310 AF09-30-10-13 1SBL137001R1310
7.5 9 15 15 15 15 15 15 29 24...60 20...60 AF16Z-30-10-21 1SBL176001R2110 AF16Z-30-10-21 1SBL176001R2110 AF09Z-30-10-21 1SBL136001R2110
6 100...250 100...250 AF16-30-10-13 1SBL177001R1310 AF16-30-10-13 1SBL177001R1310 AF09-30-10-13 1SBL137001R1310
11 11 18.5 18.5 25 25 25 25 35 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 AF26Z-30-00-21 1SBL236001R2100 AF26Z-30-00-21 1SBL236001R2100
100...250 100...250 AF26-30-00-13 1SBL237001R1300 AF26-30-00-13 1SBL237001R1300 AF26-30-00-13 1SBL237001R1300
11 11 22 22 25 25 25 25 41 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 AF26Z-30-00-21 1SBL236001R2100 AF26Z-30-00-21 1SBL236001R2100
100...250 100...250 AF26-30-00-13 1SBL237001R1300 AF26-30-00-13 1SBL237001R1300 AF26-30-00-13 1SBL237001R1300
11 15 25 25 25 25 30 30 47 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 AF30Z-30-00-21 1SBL276001R2100 AF26Z-30-00-21 1SBL236001R2100
100...250 100...250 AF30-30-00-13 1SBL277001R1300 AF30-30-00-13 1SBL277001R1300 AF26-30-00-13 1SBL237001R1300
18.5 18.5 37 37 37 37 37 37 66 24...60 20...60 AF40-30-00-11 1SBL347001R1100 AF40-30-00-11 1SBL347001R1100 AF40-30-00-11 1SBL347001R1100
100...250 100...250 AF40-30-00-13 1SBL347001R1300 AF40-30-00-13 1SBL347001R1300 AF40-30-00-13 1SBL347001R1300
55 55 90 110 110 132 132 110 195 24...60 20...60 AF116-30-11-11 1SFL427001R1111 AF116-30-11-11 1SFL427001R1111 AF116-30-11-11 (4) 1SFL427001R1111
100...250 100...250 AF116-30-11-13 1SFL427001R1311 AF116-30-11-13 1SFL427001R1311 AF116-30-11-13 1SFL427001R1311
75 75 132 132 132 132 160 132 230 24...60 20...60 AF140-30-11-11 1SFL447001R1111 AF140-30-11-11 1SFL447001R1111 AF116-30-11-11 1SFL427001R1111
100...250 100...250 AF140-30-11-13 1SFL447001R1311 AF140-30-11-13 1SFL447001R1311 AF116-30-11-13 1SFL427001R1311
90 90 160 160 160 160 200 200 280 24...60 20...60 AF190-30-11-11 1SFL487002R1111 AF190-30-11-11 1SFL487002R1111 AF140-30-11-11 1SFL447001R1111
100...250 100...250 AF190-30-11-13 1SFL487002R1311 AF190-30-11-13 1SFL487002R1311 AF140-30-11-13 1SFL447001R1311
(1) AF09 ... AF190: ambient temperature ≤ 60 °C.
(2) The setting current value is: nominal motor current x 0.58. Overload relay type given for 400 V - AC-3.
For other voltage, select overload relay type according to required nominal motor current x 0.58.
(3) On-delay timer without dwelling-time (e.g.: side-mounted CT-ERS.21S or front-mounted TEF4-ON) is enough to countdown the programmed starting time during "Star connection".
In case of use of front-mounted TEF4-ON on-delay timer, mount on KM1 contactor AF26 ... AF96 a side-mounted CAL4-11 auxiliary contact block instead of CA4-10 auxiliary contact block.
(4) AF80 can also be used, but no connection set and mechanical interlock is available for this combination.
6/22 | ABB
Thermal overload relays (2) Electronic timers (3) Accessories
Mechanical
CT-ERS TEF4-ON
and electrical CA4
Uc = 24...240 V
50/60 Hz or DC interlock sets
VEM4
Setting Type Order code Type Order code Type Order code Type Order code
ranges
A
7.60...10.0 TF42-10 1SAZ721201R1043 CT-ERS.21S 1SVR730100R0300 BEY16-4 1SBN081313R2000 - -
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000
10.0...13.0 TF42-13 1SAZ721201R1045 CT-ERS.21S 1SVR730100R0300 BEY16-4 1SBN081313R2000 - -
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000
16.0...20.0 TF42-20 1SAZ721201R1049 CT-ERS.21S 1SVR730100R0300 BEY16-4 1SBN081313R2000 - -
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000 6
20.0...24.0 TF42-24 1SAZ721201R1051 CT-ERS.21S 1SVR730100R0300 BEY38-4 1SBN082713R2000 KM1 : 1 x CA4-10 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000 KM2 : 1 x CA4-10 1SBN010110R1010
20.0...24.0 TF42-24 1SAZ721201R1051 CT-ERS.21S 1SVR730100R0300 BEY38-4 1SBN082713R2000 KM1 : 1 x CA4-10 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000 KM2 : 1 x CA4-10 1SBN010110R1010
24.0...29.0 TF42-29 1SAZ721201R1052 CT-ERS.21S 1SVR730100R0300 BEY38-4 1SBN082713R2000 KM1 : 1 x CA4-10 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000 KM2 : 1 x CA4-10 1SBN010110R1010
30.0...40.0 TF65-40 1SAZ811201R1003 CT-ERS.21S 1SVR730100R0300 BEY65-4 1SBN083413R2000 KM1 : 1 x CA4-10 (3) 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VM96-4 1SBN033405T1000 KM2 : 1 x CA4-10 1SBN010110R1010
1 x CA4-01 1SBN010110R1001
KM3 : 1 x CA4-01 1SBN010110R1001
36.0...47.0 TF65-47 1SAZ811201R1004 CT-ERS.21S 1SVR730100R0300 BEY65-4 1SBN083413R2000 KM1 : 1 x CA4-10 (3) 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VM96-4 1SBN033405T1000 KM2 : 1 x CA4-10 1SBN010110R1010
1 x CA4-01 1SBN010110R1001
KM3 : 1 x CA4-01 1SBN010110R1001
50.0...60.0 TF65-60 1SAZ811201R1006 CT-ERS.21S 1SVR730100R0300 BEY65-4 1SBN083413R2000 KM1 : 1 x CA4-10 (3) 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VM96-4 1SBN033405T1000 KM2 : 1 x CA4-10 1SBN010110R1010
1 x CA4-01 1SBN010110R1001
KM3 : 1 x CA4-01 1SBN010110R1001
65.0...78.0 TF96-78 1SAZ911201R1004 CT-ERS.21S 1SVR730100R0300 BEY96-4 1SBN083913R2000 KM1 : 1 x CA4-10 (3) 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VM96-4 1SBN033405T1000 KM2 : 1 x CA4-10 1SBN010110R1010
1 x CA4-01 1SBN010110R1001
KM3 : 1 x CA4-01 1SBN010110R1001
84.0...96.0 TF96-96 1SAZ911201R1006 CT-ERS.21S 1SVR730100R0300 BEY96-4 1SBN083913R2000 KM1 : 1 x CA4-10 (3) 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VM96-4 1SBN033405T1000 KM2 : 1 x CA4-10 1SBN010110R1010
1 x CA4-01 1SBN010110R1001
KM3 : 1 x CA4-01 1SBN010110R1001
100...135 TF140DU-135 1SAZ431201R1003 CT-ERS.21S 1SVR730100R0300 BEY140-4 1SFN084413R1000 - -
+ VM19 1SFN030300R1000
100...135 TF140DU-135 1SAZ431201R1003 CT-ERS.21S 1SVR730100R0300 BEY140-4 1SFN084413R1000 - -
+ VM19 1SFN030300R1000
130...175 TA200DU-175 1SAZ421201R1005 CT-ERS.21S 1SVR730100R0300 BEY190-4 1SFN084813R1000 - -
+ VM140/190 1SFN034403R1000
1SBC101959S0201
ABB | 6/23
Star-delta starters protected by electronic overload relays
With AF contactors - Open type version in kit form
Y
L Δ
IEC Control voltage Type Order code Type Order code Type Order code
AC-3 Uc min. ... Uc max.
Rated power Rated (1)
current
220 V 230/240 V 380 V 400 V 415 V 440 V 500 V 690 V 400 V
kW kW kW kW kW kW kW kW A V 50/60 Hz V DC
4 4 7.5 7.5 7.5 7.5 9 9 15.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 AF09Z-30-10-21 1SBL136001R2110 AF09Z-30-10-21 1SBL136001R2110
100...250 100...250 AF09-30-10-13 1SBL137001R1310 AF09-30-10-13 1SBL137001R1310 AF09-30-10-13 1SBL137001R1310
5.5 5.5 9 11 11 11 11 11 22 24...60 20...60 AF12Z-30-10-21 1SBL156001R2110 AF12Z-30-10-21 1SBL156001R2110 AF09Z-30-10-21 1SBL136001R2110
100...250 100...250 AF12-30-10-13 1SBL157001R1310 AF12-30-10-13 1SBL157001R1310 AF09-30-10-13 1SBL137001R1310
7.5 9 15 15 15 15 15 15 29 24...60 20...60 AF16Z-30-10-21 1SBL176001R2110 AF16Z-30-10-21 1SBL176001R2110 AF09Z-30-10-21 1SBL136001R2110
6 100...250 100...250 AF16-30-10-13 1SBL177001R1310 AF16-30-10-13 1SBL177001R1310 AF09-30-10-13 1SBL137001R1310
11 11 18.5 18.5 25 25 25 25 35 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 AF26Z-30-00-21 1SBL236001R2100 AF26Z-30-00-21 1SBL236001R2100
100...250 100...250 AF26-30-00-13 1SBL237001R1300 AF26-30-00-13 1SBL237001R1300 AF26-30-00-13 1SBL237001R1300
11 11 22 22 25 25 25 25 41 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 AF26Z-30-00-21 1SBL236001R2100 AF26Z-30-00-21 1SBL236001R2100
100...250 100...250 AF26-30-00-13 1SBL237001R1300 AF26-30-00-13 1SBL237001R1300 AF26-30-00-13 1SBL237001R1300
11 15 25 25 25 25 30 30 47 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 AF30Z-30-00-21 1SBL276001R2100 AF26Z-30-00-21 1SBL236001R2100
100...250 100...250 AF30-30-00-13 1SBL277001R1300 AF30-30-00-13 1SBL277001R1300 AF26-30-00-13 1SBL237001R1300
18.5 18.5 37 37 37 37 37 37 66 24...60 20...60 AF40-30-00-11 1SBL347001R1100 AF40-30-00-11 1SBL347001R1100 AF40-30-00-11 1SBL347001R1100
100...250 100...250 AF40-30-00-13 1SBL347001R1300 AF40-30-00-13 1SBL347001R1300 AF40-30-00-13 1SBL347001R1300
55 55 90 110 110 132 132 110 195 24...60 20...60 AF116-30-11-11 1SFL427001R1111 AF116-30-11-11 1SFL427001R1111 AF116-30-11-11 (4) 1SFL427001R1111
100...250 100...250 AF116-30-11-13 1SFL427001R1311 AF116-30-11-13 1SFL427001R1311 AF116-30-11-13 1SFL427001R1311
75 75 132 132 132 132 160 132 230 24...60 20...60 AF140-30-11-11 1SFL447001R1111 AF140-30-11-11 1SFL447001R1111 AF116-30-11-11 1SFL427001R1111
100...250 100...250 AF140-30-11-13 1SFL447001R1311 AF140-30-11-13 1SFL447001R1311 AF116-30-11-13 1SFL427001R1311
90 90 160 160 160 160 200 200 280 24...60 20...60 AF190-30-11-11 1SFL487002R1111 AF190-30-11-11 1SFL487002R1111 AF140-30-11-11 1SFL447001R1111
100...250 100...250 AF190-30-11-13 1SFL487002R1311 AF190-30-11-13 1SFL487002R1311 AF140-30-11-13 1SFL447001R1311
110 110 160 200 200 200 250 250 350 24...60 20...60 AF205-30-11-11 1SFL527002R1111 AF205-30-11-11 1SFL527002R1111 AF190-30-11-11 1SFL487002R1111
100...250 100...250 AF205-30-11-13 1SFL527002R1311 AF205-30-11-13 1SFL527002R1311 AF190-30-11-13 1SFL487002R1311
132 132 250 250 250 250 315 355 430 24...60 20...60 AF265-30-11-11 1SFL547002R1111 AF265-30-11-11 1SFL547002R1111 AF205-30-11-11 1SFL527002R1111
100...250 100...250 AF265-30-11-13 1SFL547002R1311 AF265-30-11-13 1SFL547002R1311 AF205-30-11-13 1SFL527002R1311
160 160 315 315 315 355 400 400 540 24...60 20...60 AF370-30-11-11 1SFL607002R1111 AF370-30-11-11 1SFL607002R1111 AF265-30-11-11 1SFL547002R1111
100...250 100...250 AF370-30-11-13 1SFL607002R1311 AF370-30-11-13 1SFL607002R1311 AF265-30-11-13 1SFL547002R1311
200 200 315 355 355 400 400 500 610 24...60 20...60 AF370-30-11-11 1SFL607002R1111 AF370-30-11-11 1SFL607002R1111 AF305-30-11-11 1SFL587002R1111
100...250 100...250 AF370-30-11-13 1SFL607002R1311 AF370-30-11-13 1SFL607002R1311 AF305-30-11-13 1SFL587002R1311
(1) AF09 ... AF370: ambient temperature ≤ 60 °C.
(2) The setting current value is: nominal motor current x 0.58. Overload relay type given for 400 V - AC-3.
For other voltage, select overload relay type according to required nominal motor current x 0.58.
(3) On-delay timer without dwelling-time (e.g.: side-mounted CT-ERS.21S or front-mounted TEF4-ON) is enough to countdown the programmed starting time during "Star connection".
In case of use of front-mounted TEF4-ON on-delay timer, mount on KM1 contactor AF26 ... AF96 a side-mounted CAL4-11 auxiliary contact block instead of CA4-10 auxiliary contact block.
(4) AF80 can also be used, but no connection set and mechanical interlock is available for this combination.
6/24 | ABB
Electronic overload relays (2) Electronic timers (3) Accessories
Mechanical
CT-ERS TEF4-ON
and electrical CA4
Uc = 24...240 V
50/60 Hz or DC interlock sets
VEM4
Setting Type Order code Type Order code Type Order code Type Order code
ranges
A
5.70…18.9 EF19-18.9 1SAX121001R1105 CT-ERS.21S 1SVR730100R0300 BEY16-4 1SBN081313R2000 - -
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000
5.70…18.9 EF19-18.9 1SAX121001R1105 CT-ERS.21S 1SVR730100R0300 BEY16-4 1SBN081313R2000 - -
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000
5.70…18.9 EF19-18.9 1SAX121001R1105 CT-ERS.21S 1SVR730100R0300 BEY16-4 1SBN081313R2000 - -
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000 6
9.00…30.0 EF45-30 1SAX221001R1101 CT-ERS.21S 1SVR730100R0300 BEY38-4 1SBN082713R2000 KM1 : 1 x CA4-10 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000 KM2 : 1 x CA4-10 1SBN010110R1010
9.00…30.0 EF45-30 1SAX221001R1101 CT-ERS.21S 1SVR730100R0300 BEY38-4 1SBN082713R2000 KM1 : 1 x CA4-10 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000 KM2 : 1 x CA4-10 1SBN010110R1010
9.00…30.0 EF45-30 1SAX221001R1101 CT-ERS.21S 1SVR730100R0300 BEY38-4 1SBN082713R2000 KM1 : 1 x CA4-10 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VEM4 1SBN030111R1000 KM2 : 1 x CA4-10 1SBN010110R1010
25…70 EF65-70 1SAX331001R1101 CT-ERS.21S 1SVR730100R0300 BEY65-4 1SBN083413R2000 KM1 : 1 x CA4-10 (3) 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VM96-4 1SBN033405T1000 KM2 : 1 x CA4-10 1SBN010110R1010
1 x CA4-01 1SBN010110R1001
KM3 : 1 x CA4-01 1SBN010110R1001
25…70 EF65-70 1SAX331001R1101 CT-ERS.21S 1SVR730100R0300 BEY65-4 1SBN083413R2000 KM1 : 1 x CA4-10 (3) 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VM96-4 1SBN033405T1000 KM2 : 1 x CA4-10 1SBN010110R1010
1 x CA4-01 1SBN010110R1001
KM3 : 1 x CA4-01 1SBN010110R1001
25…70 EF65-70 1SAX331001R1101 CT-ERS.21S 1SVR730100R0300 BEY65-4 1SBN083413R2000 KM1 : 1 x CA4-10 (3) 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VM96-4 1SBN033405T1000 KM2 : 1 x CA4-10 1SBN010110R1010
1 x CA4-01 1SBN010110R1001
KM3 : 1 x CA4-01 1SBN010110R1001
36…100 EF96-100 1SAX341001R1101 CT-ERS.21S 1SVR730100R0300 BEY96-4 1SBN083913R2000 KM1 : 1 x CA4-10 (3) 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VM96-4 1SBN033405T1000 KM2 : 1 x CA4-10 1SBN010110R1010
1 x CA4-01 1SBN010110R1001
KM3 : 1 x CA4-01 1SBN010110R1001
36…100 EF96-100 1SAX341001R1101 CT-ERS.21S 1SVR730100R0300 BEY96-4 1SBN083913R2000 KM1 : 1 x CA4-10 (3) 1SBN010110R1010
or TEF4-ON 1SBN020112R1000 + VM96-4 1SBN033405T1000 KM2 : 1 x CA4-10 1SBN010110R1010
1 x CA4-01 1SBN010110R1001
KM3 : 1 x CA4-01 1SBN010110R1001
54…150 EF146-150 1SAX351001R1101 CT-ERS.21S 1SVR730100R0300 BEY140-4 1SFN084413R1000 - -
+ VM19 1SFN030300R1000
54…150 EF146-150 1SAX351001R1101 CT-ERS.21S 1SVR730100R0300 BEY140-4 1SFN084413R1000 - -
+ VM19 1SFN030300R1000
63…210 EF205-210 1SAX531001R1101 CT-ERS.21S 1SVR730100R0300 BEY190-4 1SFN084813R1000 - -
+ VM140/190 1SFN034403R1000
63…210 EF205-210 1SAX531001R1101 CT-ERS.21S 1SVR730100R0300 BEY205-4 1SFN085213R1000 - -
+ VM19 1SFN030300R1000
115…380 EF370-380 1SAX611001R1101 CT-ERS.21S 1SVR730100R0300 BEY265-4 1SFN085413R1000 - -
+ VM205/265 1SFN035203R1000
115…380 EF370-380 1SAX611001R1101 CT-ERS.21S 1SVR730100R0300 BEY370-4 1SFN085813R1000 - -
+ VM19 1SFN030300R1000
115…380 EF370-380 1SAX611001R1101 CT-ERS.21S 1SVR730100R0300 BEY370-4 1SFN085813R1000 - -
+ VM19 1SFN030300R1000
1SBC101960S0201
ABB | 6/25
3-pole contactors, for motor control and power switching
AC / DC Control supply Type AF09 AF12 AF16 AF26 AF30 AF38 AF40 AF52 AF65 AF80 AF96
IEC AC-3 Rated operational power 220 - 230 - 240 V kW 2.2 3 4 6.5 9 11 11 15 18.5 22 25
θ ≤ 60 °C for AF09 ... AF370 380 - 400 V kW 4 5.5 7.5 11 15 18.5 18.5 22 30 37 45
θ ≤ 55 °C for AF400 ... AF2650 415 V kW 4 5.5 9 11 15 18.5 22 30 37 45 55
440 V kW 4 5.5 9 15 18.5 22 22 30 37 45 55
500 V kW 5.5 7.5 9 15 18.5 22 22 30 37 45 55
6 690 V kW 5.5 7.5 9 15 18.5 22 22 30 37 45 55
1000 V kW — — — — — — — — — 35 40
Rated operational current 380 - 400 V A 9 12 18 26 32 38 40 53 65 80 96
AC-1 Rated operational current θ ≤ 40 °C, 690 V A 25 28 30 45 50 50 70 100 105 125 130
Main accessories
Auxiliary contact blocks Front mounting CA4-10 (1 x N.O.)
CA4-01 (1 x N.C.)
Side mounting CAL4-11 (1 x N.O. + 1 x N.C.)
Timers Electronic TEF4-ON
TEF4-OFF
Interlocking units Mechanical VM4 VM96-4
Overload relays
Thermal relays Class 10 TF42 (0.10…38 A) TF65 (22...67 A) TF96 (40...96 A)
(Class 10A for TF140, TA200DU)
Electronic relays Class 10E, 20E, 30E EF19 (0.10…18.9 A) EF19 (0.10…18.9 A) EF65 (20...70 A) EF96 (36...100 A)
EF45 (9…45 A)
6/26 | ABB
AF116 AF140 AF146 AF190 AF205 AF265 AF305 AF370 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050 AF2650
— — — — — — — — — — — — — — — — —
— — — — — — — — — — — — — — — — —
30 40 40 50 60 75 100 125 125 150 200 250 — — — — —
40 50 50 60 75 100 125 150 150 200 250 300 — 400 450 — —
75 100 100 125 150 200 250 300 350 400 500 600 — 800 900 — —
100 125 125 150 200 250 300 350 400 500 600 700 — 1000 1150 — —
160 200 200 250 300 350 400 520 550 650 750 900 1210 1350 1650 2100 2700
— 4 — — — 5 — — — 6 — 7 — — 8 — —
ABB | 6/27
AF09 ... AF38 3-pole contactors
4 to 18.5 kW
AC / DC operated
Description
AF09 ... AF38 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC
and 220 V DC. These contactors are of the block type design with 3 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage
range (e.g. 100...250 V AC and DC), only 4 control voltage ranges covering 24...500V 50/60 Hz and
1SBC101011V0014
20...500 V DC
-- can manage large control voltage variations
-- reduced panel energy consumption
-- very distinct closing and opening.
AF09-30-10 –– built-in surge suppression
–– add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Ordering details
IEC UL/CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational 3-phase General voltage contacts (1)
power current motor use Uc min. … Uc max. fitted Pkg
θ ≤ 40 °C rating rating (1 pce)
400 V 480 V 600 V AC
AC-3 AC-1
kW A hp A V 50/60 Hz V DC kg
1SBC101001V0014
35 mm EN/IEC 60715
35 mm EN/IEC 60715
1SBC101371S0201 - Rev. C
60 2.36"
3.15"
80 3.15"
5.5 0.22"
70 2.76"
60802.36"
5.5 0.22"
5 0.20"
10 0.39"
10 0.39" 5 0.20"
5 0.20"
AF09, AF12, AF16 AF26, AF30, AF38
6/28 | ABB
AF09Z ... AF38Z 3-pole contactors
4 to 18.5 kW
AC / DC operated - low consumption
Description
AF09Z ... AF38Z contactors are mainly used for controlling 3-phase motors and power circuits up to
690 V AC and 220 V DC. These contactors are of the block type design with 3 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage
range (e.g. 100...250 V AC and DC), only 4 control voltage ranges covering 24...250 V 50/60 Hz and
1SBC101011V0014
12...250 V DC
-- can manage large control voltage variations
-- allow direct control by PLC-output ≥ 24 V DC 500 mA
-- reduced panel energy consumption
AF09Z-30-10 -- very distinct closing and opening
-- can withstand short voltage dips and voltage sags (SEMI F47-0706 conditions of use on request).
–– built-in surge suppression
–– add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Ordering details
IEC UL/CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational 3-phase General voltage contacts (1)
power current motor use Uc min. … Uc max. fitted Pkg
θ ≤ 40 °C rating rating (1 pce)
1SBC101001V0014
35 mm EN/IEC 60715
35 mm EN/IEC 60715
1SBC101372S0201 - Rev. B
60 2.36"
3.15"
80 3.15"
5.5 0.22"
70 2.76"
60802.36"
5.5 0.22"
5 0.20"
10 0.39"
10 0.39" 5 0
5 0.20"
AF09Z, AF12Z, AF16Z AF26Z, AF30Z, AF38Z
ABB | 6/29
AF40 ... AF96 3-pole contactors
18.5 to 45 kW
AC / DC operated
Description
AF40 ... AF96 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC
and 220 V DC. These contactors are of the block type design with 3 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage
range (e.g. 100...250 V AC and DC), only 4 control voltage ranges covering 24...500 V 50/60 Hz and
20...500 V DC
-- can manage large control voltage variations
-- reduced panel energy consumption
1SBC101014V0014
AF40-30-00
Ordering details
IEC UL / CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational 3-phase General voltage contacts (1)
power current motor use Uc min. … Uc max. fitted Pkg
θ ≤ 40 °C rating rating (1 pce)
400 V 480 V 600 V AC
6 AC-3 AC-1
kW A hp A V 50/60 Hz V DC kg
18.5 70 30 60 24...60 - 0 0 AF40-30-00-41 1SBL347001R4100 0.970
24...60 20...60 (2) 0 0 AF40-30-00-11 1SBL347001R1100 0.970
48...130 48...130 0 0 AF40-30-00-12 1SBL347001R1200 0.970
100...250 100...250 0 0 AF40-30-00-13 1SBL347001R1300 0.950
1SBC101016V0014
6 0.24"
6 0.24"
6 0.24"
35 x 15 mm EN/IEC 60715
35 x 15 mm EN/IEC 60715
35 mm EN/IEC 60715
35 mm EN/IEC 60715
119.5 4.70"
119.5 4.70"
1SBC101740S0201 - Rev. A
119.5 4.70"
119.5 4.70"
5.5 0.22"
5.5 0.22"
5.5 0.22" 5.5 0.22"
10 0.39"
10 0.39" 10 0.39" 10 0.39"
6/30 | ABB
6
N1
ABB | 6/31
AF09 ... AF96 3-pole contactors
Main accessories
AF09 ... AF65 VEM4 mechanical and electrical interlock set including:
– VM4 mechanical interlock unit with 2 fixing clips
– VE4 electrical interlock block with A2-A2 connection
AF contactor
(without top mounted
coil terminal block)
TEF4
VM Electronic timer A2
6 BX4-CA A2
Protective cover
BX4-CA
AF09 ... AF38
CA4 Protective cover
4-pole auxiliary
contact block
CAL4-11
2-pole auxiliary CA4, CC4
contact block CA4, CC4
BX4 1-pole auxiliary
1-pole auxiliary
Protective cover contact block
contact block
TF
EF
Overload relay
VE4
CAL4-11
2-pole auxiliary
contact block CA4, CC4
1-pole auxiliary
contact block
TF42
EF
Overload relay
6/32 | ABB
AF09 ... AF96 3-pole contactors
Main accessories
CA4-22E Front-mounted auxiliary contact blocks with N.O. leading contact and N.C. lagging contact
AF09 ... AF96 – – 1 0 CC4-10 1SBN010111R1010 1 0.014
1SBC100002V0014
01 NC 01NC Note: - VEM4 includes a VM4 mechanical interlock unit with 2 fixing clips (BB4), a VE4 electrical interlock block. VE4 block must be used with A2-A2
connection to respect the electrical connection diagram.
- VEM4 not suitable for AF..Z contactors with DC control voltage 12...20 V DC.
KM1 KM2 For contactors Time delay Delay Auxiliary Type Order code Pkg Weight
A2 A2 range type contacts qty (1 pce)
VEM4 selected by
switch
kg
Electronic timers
AF09 ... AF96 0.1...1 s ON-delay 1 1 TEF4-ON 1SBN020112R1000 1 0.065
1...10 s
1SBC100004V0014
BER16-4 (1) For more information, refer to main catalog "Accessories" section.
ABB | 6/33
AF116 ... AF146 3-pole contactors
55 to 75 kW
AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts
Description
AF116 ... AF140 contactors are mainly used for controlling 3-phase motors and power circuits up to
690 V AC, AF146 up to 1000 V AC. These contactors are of the block type design with 3 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range
(e.g. 100...250 V AC and DC), only 4 coils to cover control voltages between 24...500 V 50/60 Hz and
20...500 V DC
-- can manage large control voltage variations
-- reduced panel energy consumption
1SFC101001V0001
D D D D
55.5 0.22"
55.5 2.18"
19.5 0.77"
19.5 4.96"
150 5.91"
150 5.91"
1SFC101090C0201 - Rev. C
30 1.18" 30 1.18"
6/34 | ABB
AF116 ... AF146 3-pole contactors with built-in PLC interface
55 to 75 kW
AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts
Description
AF116 ... AF140 contactors are mainly used for controlling 3-phase motors and power circuits up to
690 V AC, AF146 up to 1000 V AC. These contactors are of the block type design with 3 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range
(e.g. 100...250 V AC and DC), only 2 coils to cover control voltages between 100...500 V 50/60 Hz and
100...500 V DC
-- can manage large control voltage variations
-- reduced panel energy consumption
1SFC101083V0001
AF116 ... AF146 are equipped with low voltage inputs for control, for example by a PLC.
Control inputs
D D D
D
55.5 2.18"
55.5 0.22"
19.5 0.77"
19.5 4.96"
150 5.91"
150 5.91"
1SFC101166C0201
30 1.18" 30 1.18"
ABB | 6/35
AF190 ... AF370 3-pole contactors
90 to 200 kW
AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts
Description
AF190 ... AF370 contactors are mainly used for controlling 3-phase motors and power circuits up to
1000 V AC. These contactors are of the block type design with 3 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range
(e.g. 100...250 V AC and DC), only 4 coils to cover control voltages between 24...500 V 50/60 Hz and
20...500 V DC
1SFC101013V0001
225 8.86"
196 7.72"
1SFC101091C0201 - Rev. D
6/36 | ABB
AF190 ... AF370 3-pole contactors with built-in PLC interface
90 to 200 kW
AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts
Description
AF190 ... AF370 contactors are mainly used for controlling 3-phase motors and power circuits up to
1000 V AC. These contactors are of the block type design with 3 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range
(e.g. 100...250 V AC and DC), only 2 coils to cover control voltages between 100...500 V 50/60 Hz and
100...500 V DC
-- can manage large control voltage variations
-- reduced panel energy consumption
1SFC101165V0001
AF190 ... AF370 are equipped with low voltage inputs for control, for example by a PLC.
Control inputs
225 8.86"
196 7.72"
1SFC101167C0201
ABB | 6/37
AF116 ... AF370 3-pole contactors
with 1 N.O. + 1 N.C. auxiliary contacts
Main accessories
Main accessories (other accessories available)
CAL19-11B
2-pole auxiliary
contact block
LW
Terminal
enlargement
VM
Mechanical
interlock
AF contactor
6 with bar connections
LT
CAL19-11B Terminal shroud
2-pole auxiliary
contact block
AF contactor
with built-in cable clamps
TF/TA
Thermal overload relay
EF
Electronic overload relay
(1) Total number of auxiliary contact blocks for the two contactors. (2) Interlock type, according to the contactor ratings (see "Accessories").
6/38 | ABB
AF116 ... AF370 3-pole contactors
with 1 N.O. + 1 N.C. auxiliary contacts
Main accessories
Ordering details (1)
For contactors Auxiliary Type Order code Pkg Weight
contacts qty (1 pce)
kg
1SFC101071V0001
Terminal shrouds
AF116 ... AF146, with compression lugs LT140-30L 1SFN124203R1000 2 0.070
AF190, AF205, with cable clamps LT205-30C 1SFN124801R1000 2 0.050
AF190, AF205, with compression lugs LT205-30L 1SFN124803R1000 2 0.220
1SFC101035V0001
Terminal enlargements
AF116...AF146 6.5 13 x 3 LW140 1SFN074207R1000 1 0.115
AF190...AF205 10.5 17.5 x 5 LW205 1SFN074807R1000 1 0.260
AF265...AF370 10.5 20 x 5 LW370 1SFN075407R1000 1 0.340
Terminal extension
1SFC101049V0001
1SFC101138C0201
ABB | 6/39
AF400 ... AF750 3-pole contactors
200 to 400 kW
AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts
Description
AF400 ... AF750 contactors are mainly used for controlling 3-phase motors and power circuits up to
1000 V AC or 600 V DC (2). These contactors are of the block type design with 3 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range
(e.g. 100...250 V AC and DC), only 4 coils to cover control voltages between 48...500 V 50/60 Hz and
24...500 V DC
-- can manage large control voltage variations
-- reduced panel energy consumption
1SFC101022V0001
AF400 ... AF750 are equipped with low voltage inputs for control, for example by a PLC.
Control inputs
283 11.14"
268 10.55"
278 10.94"
1SFC101013C0201 - Rev. A
E1627D1
E1633D
E1626D1
E1632D
63 2.48" 72 2.83"
6/40 | ABB
AF1250 ... AF2650 3-pole contactors
475 to 560 kW and 1260 to 2650 A AC-1
AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts
Description
AF1250 ... AF2050 contactors are mainly used for controlling power circuits up to 1000 V AC or 850 V DC,
AF2650 for controlling power up to 1000 V AC. These contactors are of the block type design with 3 main
poles.
– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range
(e.g. 100...250 V AC and DC)
- only 4 coils for AF1250 to cover control voltages between 48...500 V 50/60 Hz and 24...500 V DC
- only 1 coil for AF1350 ... AF2650 to cover control voltages between 100...250 V 50/60 Hz and
100...250 V DC
1SFC101027V0001
AF1250 ... AF2650 are equipped with low voltage inputs for control, for example by a PLC
Control inputs
AF1350, AF1650, AF2050 AF2650
A 392 mm / 15.43" 422 mm / 16.61"
B 47 mm / 1.85" 53 mm / 2.09"
C 10 mm / 0.39" 25 mm / 0.98"
313 12.32"
263 10.35"
249 9.8"
312 12.3"
A
1SFC101125F0001
1SFC101094C0201 - Rev. A
1.57"
40
1SFC101124F0001
ABB | 6/41
AF400 ... AF2650 3-pole contactors
with 1 N.O. + 1 N.C. auxiliary contacts
Main accessories
Main accessories (other accessories available)
LW
Terminal
enlargement
LZ
Connector CAL18-11B
terminal 2-pole auxiliary
contact block
VM LT
Mechanical Terminal shroud
interlock
AF contactor
CAL18-11B
2-pole auxiliary
contact block
(1) Total number of auxiliary contact blocks for the two contactors. (2) Interlock type, according to the contactor ratings (see "Accessories").
(3) The CEL18-.. auxiliary contact blocks can replace the CAL18-11 and CAL18-11B. Though, no auxiliary contact block can be mounted outside the CEL18-..
6/42 | ABB
AF400 ... AF2650 3-pole contactors
with 1 N.O. + 1 N.C. auxiliary contacts
Main accessories
Ordering details (1)
For contactors Auxiliary Type Order code Pkg Weight
contacts qty (1 pce)
1SFC101082V0001
kg
Terminal shrouds
AF400, AF460 with connectors LT460-AC 1SFN125701R1000 2 0.100
AF400, AF460 with lugs LT460-AL 1SFN125703R1000 2 0.800
VM750H AF580 ... AF750 with connectors LT750-AC 1SFN126101R1000 2 0.120
AF580 ... AF750 with lugs LT750-AL 1SFN126103R1000 2 0.825
6
1SFC101089V0001
Terminal enlargements
AF400, AF460 10.5 25 x 5 LW460 1SFN075707R1000 1 0.730
AF580, AF750 13 40 x 6 LW750 1SFN076107R1000 1 1.230
AF1250 13 50 x 10 LW1250 1SFN076407R1000 1 2.000
Terminal extension
AF400, AF460 10.5 25 x 5 LX460 1SFN075710R1000 1 0.500
AF580, AF750 13 40 x 6 LX750 1SFN076110R1000 1 0.850
(1) For more information, refer to main catalog "Accessories" section.
1SFC101128C0201
ABB | 6/43
4-pole contactors
AC / DC Control supply Type AF09 AF16 AF26 AF38 AF40 AF52 AF80
AC Control supply Type AF09 AF16 AF26 AF38 AF40 AF52 AF80
DC Control supply Type AF09 AF16 AF26 AF38 AF40 AF52 AF80
Main accessories
Auxiliary contact blocks Front mounting CA4-10 (1 x N.O.), CA4-01 (1 x N.C.)
Side mounting CAL4-11 (1 x N.O. + 1 x N.C.)
Timers Electronic TEF4-ON
TEF4-OFF
Interlocking units Mechanical VM4 VM96-4
Mechanical / Electrical VEM4
Surge suppressors Varistor + RC (AC / DC) Built-in surge protection
6/44 | ABB
160 200 275 350 400 500 525 800 1000
160 175 230 250 300 350 420 540 —
RC-EH800
1SBC101569S0201 - Rev. E
ABB | 6/45
AF09 ... AF38 4-pole contactors
25 to 55 A AC-1
AC / DC operated
Description
AF09 ... AF38 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e.
resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. These
contactors are of the block type design with 4 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage
1SBC101095F0014
range (e.g. 100...250 V AC and DC), only 4 control voltage ranges covering 24...500 V 50/60 Hz and
20...500 V DC
-- can manage large control voltage variations
-- reduced panel energy consumption
AF09-40-00 -- very distinct closing and opening.
–– built-in surge suppression
–– add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Ordering details
IEC UL/CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational General use voltage contacts
current rating Uc min. … Uc max. fitted Pkg
θ ≤ 40 °C 600 V AC (1 pce)
AC-1
A A V 50/60 Hz V DC kg
6
1SBC101097F0014
6 0.24"
1SBC101375S0201 - Rev. B
35 mm EN/IEC 60715
35 mm EN/IEC 60715
60 2.36"
80 3.15"
80 3.15"
70 2.76"
70 2.76"
60 2.36"
5 0.20"
10 0.39" 10 0.39"
5 0.20" 5 0.20"
6/46 | ABB
AF09Z ... AF38Z 4-pole contactors
25 to 55 A AC-1
AC / DC operated - low consumption
Description
AF09Z ... AF38Z 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads
(i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. These
contactors are of the block type design with 4 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage
1SBC101095F0014
range (e.g. 100...250 V AC and DC), only 4 control voltage ranges covering 24...250 V 50/60 Hz and
12...250 V DC
-- can manage large control voltage variations
-- allow direct control by PLC-output ≥ 24 V DC 500 mA
AF09Z-40-00 -- reduced panel energy consumption
-- very distinct closing and opening
-- can withstand short voltage dips and voltage sags (SEMI F47-0706 conditions of use on request).
–– built-in surge suppression
–– add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Ordering details
IEC UL/CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational General use voltage contacts
current rating Uc min. … Uc max. fitted Pkg
θ ≤ 40 °C 600 V AC (1 pce)
6
1SBC101097F0014
AC-1
A A V 50/60 Hz V DC kg
4 N.O. main poles
25 25 - 12...20 0 0 AF09Z-40-00-20 1SBL136201R2000 0.310
AF26Z-40-00 24...60 20...60 0 0 AF09Z-40-00-21 1SBL136201R2100 0.310
48...130 48...130 0 0 AF09Z-40-00-22 1SBL136201R2200 0.310
100...250 100...250 0 0 AF09Z-40-00-23 1SBL136201R2300 0.310
30 30 - 12...20 0 0 AF16Z-40-00-20 1SBL176201R2000 0.310
24...60 20...60 0 0 AF16Z-40-00-21 1SBL176201R2100 0.310
48...130 48...130 0 0 AF16Z-40-00-22 1SBL176201R2200 0.310
100...250 100...250 0 0 AF16Z-40-00-23 1SBL176201R2300 0.310
45 45 - 12...20 0 0 AF26Z-40-00-20 1SBL236201R2000 0.400
24...60 20...60 0 0 AF26Z-40-00-21 1SBL236201R2100 0.400
48...130 48...130 0 0 AF26Z-40-00-22 1SBL236201R2200 0.400
100...250 100...250 0 0 AF26Z-40-00-23 1SBL236201R2300 0.400
55 55 - 12...20 0 0 AF38Z-40-00-20 1SBL296201R2000 0.400
24...60 20...60 0 0 AF38Z-40-00-21 1SBL296201R2100 0.400
48...130 48...130 0 0 AF38Z-40-00-22 1SBL296201R2200 0.400
100...250 100...250 0 0 AF38Z-40-00-23 1SBL296201R2300 0.400
2 N.O. + 2 N.C. main poles
25 25 - 12...20 0 0 AF09Z-22-00-20 1SBL136501R2000 0.310
24...60 20...60 0 0 AF09Z-22-00-21 1SBL136501R2100 0.310
48...130 48...130 0 0 AF09Z-22-00-22 1SBL136501R2200 0.310
100...250 100...250 0 0 AF09Z-22-00-23 1SBL136501R2300 0.310
30 30 - 12...20 0 0 AF16Z-22-00-20 1SBL176501R2000 0.310
24...60 20...60 0 0 AF16Z-22-00-21 1SBL176501R2100 0.310
48...130 48...130 0 0 AF16Z-22-00-22 1SBL176501R2200 0.310
100...250 100...250 0 0 AF16Z-22-00-23 1SBL176501R2300 0.310
45 45 - 12...20 0 0 AF26Z-22-00-20 1SBL236501R2000 0.400
24...60 20...60 0 0 AF26Z-22-00-21 1SBL236501R2100 0.400
48...130 48...130 0 0 AF26Z-22-00-22 1SBL236501R2200 0.400
100...250 100...250 0 0 AF26Z-22-00-23 1SBL236501R2300 0.400
55 55 - 12...20 0 0 AF38Z-22-00-20 1SBL296501R2000 0.400
24...60 20...60 0 0 AF38Z-22-00-21 1SBL296501R2100 0.400
48...130 48...130 0 0 AF38Z-22-00-22 1SBL296501R2200 0.400
100...250 100...250 0 0 AF38Z-22-00-23 1SBL296501R2300 0.400
Note: Only AF..Z contactors with DC control voltage 12...20 V DC need to respect the connection polarities indicated close to the
coil terminals: A1+ for the positive pole and A2- for the negative pole.
6 0.24"
1SBC101376S0201 - Rev. A
35 mm EN/IEC 60715
35 mm EN/IEC 60715
60 2.36"
80 3.15"
80 3.15"
70 2.76"
70 2.76"
60 2.36"
5 0.20"
10 0.39" 10 0.39"
5 0.20" 5 0.20"
ABB | 6/47
AF40 ... AF80 4-pole contactors
70 to 125 A AC-1
AC / DC operated
Description
AF40 ... AF80 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e.
resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC. These
contactors are of the block type design with 4 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage
1SBC101045V0014
range (e.g. 100...250 V AC and DC), only 4 control voltages ranges covering 24...500 V 50/60 Hz and
20...500 V DC
-- can manage large control voltage variations
-- reduced panel energy consumption
AF40-40-00 -- very distinct closing and opening.
–– built-in surge suppression
–– add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Ordering details
IEC UL/CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational General use voltage contacts (1)
current rating Uc min. … Uc max. fitted Pkg
θ ≤ 40 °C 600 V AC (1 pce)
AC-1
1SBC101048V0014
A A V 50/60 Hz V DC kg
6
4 N.O. Main Poles
70 60 24...60 - 0 0 AF40-40-00-41 1SBL347201R4100 1.210
24...60 20...60 (1) 0 0 AF40-40-00-11 1SBL347201R1100 1.210
AF80-40-00 48...130 48...130 0 0 AF40-40-00-12 1SBL347201R1200 1.210
100...250 100...250 0 0 AF40-40-00-13 1SBL347201R1300 1.160
(2) 250...500 250...500 0 0 AF40-40-00-14 1SBL347201R1400 1.160
100 80 24...60 - 0 0 AF52-40-00-41 1SBL367201R4100 1.210
24...60 20...60 (1) 0 0 AF52-40-00-11 1SBL367201R1100 1.210
48...130 48...130 0 0 AF52-40-00-12 1SBL367201R1200 1.210
100...250 100...250 0 0 AF52-40-00-13 1SBL367201R1300 1.160
(2) 250...500 250...500 0 0 AF52-40-00-14 1SBL367201R1400 1.160
125 105 24...60 - 0 0 AF80-40-00-41 1SBL397201R4100 1.490
24...60 20...60 (1) 0 0 AF80-40-00-11 1SBL397201R1100 1.490
48...130 48...130 0 0 AF80-40-00-12 1SBL397201R1200 1.490
100...250 100...250 0 0 AF80-40-00-13 1SBL397201R1300 1.440
(2) 250...500 250...500 0 0 AF80-40-00-14 1SBL397201R1400 1.440
2 N.O. + 2 N.C. Main Poles
70 60 24...60 - 0 0 AF40-22-00-41 1SBL347501R4100 1.210
24...60 20...60 (1) 0 0 AF40-22-00-11 1SBL347501R1100 1.210
48...130 48...130 0 0 AF40-22-00-12 1SBL347501R1200 1.210
100...250 100...250 0 0 AF40-22-00-13 1SBL347501R1300 1.160
(2) 250...500 250...500 0 0 AF40-22-00-14 1SBL347501R1400 1.160
125 105 24...60 - 0 0 AF80-22-00-41 1SBL397501R4100 1.490
24...60 20...60 (1) 0 0 AF80-22-00-11 1SBL397501R1100 1.490
48...130 48...130 0 0 AF80-22-00-12 1SBL397501R1200 1.490
100...250 100...250 0 0 AF80-22-00-13 1SBL397501R1300 1.440
(2) 250...500 250...500 0 0 AF80-22-00-14 1SBL397501R1400 1.440
(1) AF..-..-..-11 not suitable for direct control by PLC-output.
(2) In progress.
6 0.24"
1SBC101987S0201 - Rev. B
35 x 15 mm EN/IEC 60715
35 x 15 mm EN/IEC 60715
119.5 4.70"
119.5 4.70"
10 0.39" 10 0.39"
6/48 | ABB
6
N3
ABB | 6/49
AF09 ... AF80 4-pole contactors
Main accessories
AF contactor
(without top mounted
coil terminal block)
AF contactor
Fixing clips
CAT4-11
2-pole auxiliary contact
and A1/A2 coil terminal block
AF contactor
BX4-CA
Protective cover
TEF4
A2
Electronic timer
VM4
A2
6 BX4-CA
Protective cover
BX4-CA
CA4
Protective cover
4-pole auxiliary
contact block
CAL4-11
2-pole auxiliary CA4, CC4
contact block CA4, CC4 1-pole auxiliary
BX4 1-pole auxiliary contact block
Protective cover contact block
2 2 0 0 4 max. – or 1 or 1 – + 1 + 1
AF80 2 2 0 0 4 max. – or 1 or 1 – + 1 + 1
6/50 | ABB
AF09 ... AF80 4-pole contactors
Main accessories
qty (1 pce)
1SBC101112F0014
kg
Front-mounted auxiliary contact blocks with N.O. leading contact and N.C. lagging contact
AF09 ... AF80-40-00 – – 1 0 CC4-10 1SBN010111R1010 1 0.014
AF09 ... AF80-22-00 – – 0 1 CC4-01 1SBN010111R1001 1 0.014
CAT4-11E
6
Side-mounted instantaneous auxiliary contact blocks
AF09 ... AF80-40-00 1 1 – – CAL4-11 1SBN010120R1011 1 0.040
1SBC101130F0014
1SBC101129F0014
Note: CAT4 not suitable for AF..Z contactors with DC control voltage 12...20 V DC.
For contactors Time delay Delay Auxiliary Type Order code Pkg Weight
range type contacts qty (1 pce)
selected by
1SBC101392F0014
switch
kg
Electronic timers
AF09 ... AF80 0.1...1 s ON-delay 1 1 TEF4-ON 1SBN020112R1000 1 0.065
TEF4-ON 1...10 s
10...100 s OFF-delay 1 1 TEF4-OFF 1SBN020114R1000 1 0.065
ABB | 6/51
AF116 … AF140 4-pole contactors
160 to 200 A AC-1
AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts
Description
AF116 ... AF140 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads
(i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC. These contactors are
of the block type design with 4 main poles.
1SFC101154V0001
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range
(e.g. 100...250 V AC and DC), only 4 coils to cover control voltages between 24...500 V 50/60 Hz and
20...500 V DC
-- can manage large control voltage variations
-- reduced panel energy consumption
AF140-40-11 -- very distinct closing and opening
-- can withstand short voltage dips and voltage sags (SEMI F47 conditions of use on request).
–– built-in surge suppression
–– add-on auxiliary contact blocks for side mounting and a wide range of accessories.
Ordering details
IEC UL / CSA Rated control circuit Auxiliary Type Order code Weight
1SFC101192V0001
55.5 0.22"
55.5 2.18"
55.5 2.18"
19.5 4.96"
19.5 4.96"
19.5 0.77"
19.5 0.77"
150 5.91"
150 5.91"
150 5.91"
150 5.91"
1SFC101199C0201 - Rev. A
30 1.18"
30 1.18" 30 1.18"
30 1.18"
6/52 | ABB
AF190 … AF370 4-pole contactors
275 to 525 A AC-1
AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts
Description
AF190 ... AF370 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads
(i.e. resistance furnaces...) and generally for controlling power circuits up to 1000 V AC. These contactors
are of the block type design with 4 main poles.
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range
(e.g. 100...250 V AC and DC), only 4 coils to cover control voltages between 24...500 V 50/60 Hz and
1SFC101155V0001
20...500 V DC
-- can manage large control voltage variations
-- reduced panel energy consumption
-- very distinct closing and opening
-- can withstand short voltage dips and voltage sags (SEMI F47 conditions of use on request).
–– built-in surge suppression
AF205-40-11 –– add-on auxiliary contact blocks for side mounting and a wide range of accessories.
Ordering details
IEC UL / CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational General use voltage contacts (1)
current rating Uc min. ... Uc max. fitted Pkg
θ ≤ 40 °C 600 V AC (1 pce) 6
AC-1
A A V 50/60 Hz V DC kg
4 N.O. main poles
1SFC101195V0001
A 152.5 6.00"
225 8.86"
1SFC101200C0201 - Rev. A
196 7.72"
ABB | 6/53
AF116 ... AF370 4-pole contactors
with 1 N.O. + 1 N.C. auxiliary contacts
Main accessories
Main accessories (other accessories available)
CAL19-11B
2-pole auxiliary
contact block
VM
Mechanical
interlock
AF contactor
CAL19-11B with bar connections
2-pole auxiliary LT
contact block Terminal shroud
AF contactor
with built-in cable clamps
(1) Total number of auxiliary contact blocks for the two contactors. (2) Interlock type, according to the contactor ratings (see "Accessories").
1SFC101205C0201
6/54 | ABB
AF116 ... AF370 4-pole contactors
with 1 N.O. + 1 N.C. auxiliary contacts
Main accessories
Ordering details (1)
For contactors Auxiliary Type Order code Pkg Weight
contacts qty (1 pce)
1SFC101071V0001
kg
Terminal shrouds
AF116 … AF140, with compression lugs LT140-40L 1SFN124203R2000 2 0.090
1SFC101035V0001
Terminal enlargements
AF190 … AF205 10.5 20 x 5 LW205-40 1SFN074807R2000 1 0.306
AF265 … AF370 10.5 25 x 5 LW370-40 1SFN075407R2000 1 0.540
(1) For more information, refer to "Accessories" section.
1SFC101206C0201
ABB | 6/55
EK550, EK1000 4-pole contactors
800 to 1000 A AC-1
AC operated - with 1 N.O. + 1 N.C. auxiliary contacts
Description
EK550 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resist-
ance furnaces...) and generally for controlling power circuits up to 1000 V AC and 600 V DC, EK1000 up to
1000 V AC.
These contactors are of the block type design with:
–– 4 main poles
1SFC98099-069
Ordering details
EK1000-40-11 IEC UL/CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational General use voltage contacts
current rating Uc fitted Pkg
θ ≤ 40 °C 600 V AC (1) (1 pce)
AC-1
A A V 50 Hz V 60 Hz kg
800 540 48 - 1 1 EK550-40-11 SK827041-AD 17.200
110 110…120 1 1 EK550-40-11 SK827041-EF 17.200
110…115 115…127 1 1 EK550-40-11 SK827041-EG 17.200
6 220 220…240 1 1 EK550-40-11 SK827041-EL 17.200
220…230 230…255 1 1 EK550-40-11 SK827041-EM 17.200
380 380…415 1 1 EK550-40-11 SK827041-EP 17.200
380…400 400…440 1 1 EK550-40-11 SK827041-ER 17.200
400…415 - 1 1 EK550-40-11 SK827041-AR 17.200
1000 - 48 - 1 1 EK1000-40-11 SK827044-AD 17.500
110 110…120 1 1 EK1000-40-11 SK827044-EF 17.500
110…115 115…127 1 1 EK1000-40-11 SK827044-EG 17.500
220 220…240 1 1 EK1000-40-11 SK827044-EL 17.500
220…230 230…255 1 1 EK1000-40-11 SK827044-EM 17.500
380 380…415 1 1 EK1000-40-11 SK827044-EP 17.500
380…400 400…440 1 1 EK1000-40-11 SK827044-ER 17.500
400…415 - 1 1 EK1000-40-11 SK827044-AR 17.500
(1) Other control voltages see voltage code table.
23 0.91"4) (M10) 5)
223 8.78"
223 8.78"
3)
40
E1694D
1.57"
0.79"
20
E0263D6 11
E1692D 11
E0264D6
67 25 12.5 403) 67 40
2.64" 0.98" 0.49" 1.57" 2.64" 1.57"
EK550 EK1000
1SFC101217C0201
6/56 | ABB
EK550, EK1000 4-pole contactors
800 to 1000 A AC-1
DC operated - with 2 N.O. + 1 N.C. auxiliary contacts
Description
EK550 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads
(i.e. resistance furnaces...) and generally for controlling power circuits up to 1000 V AC and 600 V DC,
EK1000 up to 1000 V AC.
These contactors are of the block type design with:
–– 4 main poles
1SFC98099-069
Ordering details
EK1000-40-21 IEC UL / CSA Rated control circuit Auxiliary Type Order code Weight
Rated operational General use voltage contacts
current rating Uc fitted Pkg
θ ≤ 40 °C 600 V AC (1 pce)
AC-1
A A V DC kg
800 540 24 2 1 EK550-40-21 SK827041-DB 17.200
36 2 1 EK550-40-21 SK827041-DC 17.200
48 2 1 EK550-40-21 SK827041-DD 17.200
60 2 1 EK550-40-21 SK827041-DT 17.200 6
75 2 1 EK550-40-21 SK827041-DG 17.200
110 2 1 EK550-40-21 SK827041-DE 17.200
125 2 1 EK550-40-21 SK827041-DU 17.200
220 2 1 EK550-40-21 SK827041-DF 17.200
1000 - 24 2 1 EK1000-40-21 SK827044-DB 17.500
36 2 1 EK1000-40-21 SK827044-DC 17.500
48 2 1 EK1000-40-21 SK827044-DD 17.500
60 2 1 EK1000-40-21 SK827044-DT 17.500
75 2 1 EK1000-40-21 SK827044-DG 17.500
110 2 1 EK1000-40-21 SK827044-DE 17.500
125 2 1 EK1000-40-21 SK827044-DU 17.500
220 2 1 EK1000-40-21 SK827044-DF 17.500
23 0.91"4) (M10) 5)
223 8.78"
3)
40
E1694D
1.57"
E0264D6
E0263D8
E1693D
67 25 12.5 403) 67 40 20
2.64" 0.98" 0.49" 1.57" 2.64" 1.57" 0.79"
EK550 EK1000
1SFC101218C0201
ABB | 6/57
EK550, EK1000 4-pole contactors
with 1 N.O. + 1 N.C. auxiliary contacts
and 2 N.O. + 1 N.C. auxiliary contacts
Main accessory fitting details
Mounting positions of the auxiliary contact Auxiliary contact types and connecting diagrams
13 21 31 43 53 61 71 83 35 47
14 22 32 44 54 62 72 84 36 48
EK 4-pole contactors
Contactor Main Available
types poles auxiliary
contacts
Add-on auxiliary contact Mounting and positioning
blocks Factory mounted auxiliary contacts
2-pole CAL16-11 ... Add-on CAL16-11 auxiliary contacts
AC operated, 50 Hz, 60 Hz or 50/60 Hz
6 + 1 x CAL16-11B
EK550, EK1000 4 0 1 1 A + 1 x CAL16-11C CA BD
+ 1 x CAL16-11D
DC operated
EK 4-pole reversing contactors with VH800 mechanical and electrical interlock units
"Left hand" Interlocking "Right hand"
contactors contactors
1 x CAL16-11C
EK550, EK1000 VH800 EK550, EK1000 + CA BD
1 x CAL16-11D
DC operated
6/58 | ABB
EK550, EK1000 4-pole contactors
with 1 N.O. + 1 N.C. auxiliary contacts
and 2 N.O. + 1 N.C. auxiliary contacts
A1
1 3 5 7 7 5 3 1
A1 Ordering details (1)
2 4 6 8 8 6 4 2 For contactors Auxiliary Type Order code Pkg Weight
A2 A2
contacts qty (1 pce)
E0747D
kg
BSS550 ... BSS1000
Side-mounted auxiliary contact blocks
EK 1 1 CAL16-11B SK829002-B 1 0.050
1 1 CAL16-11C SK829002-C 1 0.050
1 1 CAL16-11D SK829002-D 1 0.050
1 1 CCL16-11E (2) SK829002-E 1 0.050
A078
1SFC101220C0201
ABB | 6/59
NF 4-pole contactor relays
AC / DC operated
Description
NF contactor relays are used for switching auxiliary and control circuits.
These contactor relays are of the block type design with:
–– 4 poles. Contactor relays have mechanically linked auxiliary contact elements (side-marked symbol)
1SBC101104F0014
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range
(e.g. 100...250 V AC and DC)
-- can manage large control voltage variations
-- only 4 control voltage ranges covering 24...500 V 50/60 Hz and 20...500 V DC
NF22E -- reduced panel energy consumption
-- very distinct closing and opening.
–– built-in surge suppression
–– add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Ordering details
Number of contacts Rated control circuit Type Order code Weight
voltage
Uc min. ... Uc max. Pkg
(1 pce)
V 50/60 Hz V DC kg
6 24...60 - (1) NF22E-41 1SBH137001R4122 0.270
A1 13 21 31 43
NO NC NC NO 48...130 48...130 NF22E-12 1SBH137001R1222 0.270
NO NC NC NO
100...250 100...250 NF22E-13 1SBH137001R1322 0.270
A2 14 22 32 44
250...500 250...500 NF22E-14 1SBH137001R1422 0.310
24...60 - (1) NF31E-41 1SBH137001R4131 0.270
A1 13 21 33 43
NO NC NO NO 48...130 48...130 NF31E-12 1SBH137001R1231 0.270
NO NC NO NO 100...250 100...250 NF31E-13 1SBH137001R1331 0.270
A2 14 22 34 44
250...500 250...500 NF31E-14 1SBH137001R1431 0.310
24...60 - (1) NF40E-41 1SBH137001R4140 0.270
48...130 48...130 NF40E-12 1SBH137001R1240 0.270
A1 13 23 33 43
NO NO NO NO
NO NO NO NO
100...250 100...250 NF40E-13 1SBH137001R1340 0.270
A2 14 24 34 44
250...500 250...500 NF40E-14 1SBH137001R1440 0.310
(1) For 24...60 V 50/60 Hz - 20...60 V DC, use NF..E-21.
35 mm EN/IEC 60715
1SBC101558S0201 - Rev. B
80 3.15"
70 2.76"
60 2.36"
5.5 0.22"
5 0.20"
10 0.39"
5 0.20"
6/60 | ABB
NFZ 4-pole contactor relays
AC / DC operated - low consumption
Description
NFZ contactor relays are used for switching auxiliary and control circuits.
These contactor relays are of the block type design with:
–– 4 poles. Contactor relays have mechanically linked auxiliary contact elements (side-marked symbol)
1SBC101104F0014
–– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range
(e.g. 100...250 V AC and DC)
-- can manage large control voltage variations
-- only 4 control voltage ranges covering 24...250 V 50/60 Hz and 12...250 V DC
NFZ22E -- allow direct control by PLC-output ≥ 24 V DC 500 mA
-- reduced panel energy consumption
-- very distinct closing and opening
-- can withstand short voltage dips and voltage sags (SEMI F47-0706 conditions of use on request).
–– built-in surge suppression
–– add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Ordering details
Number of contacts Rated control circuit Type Order code Weight
voltage
Uc min. ... Uc max. Pkg
(1 pce) 6
V 50/60 Hz V DC kg
– 12...20 NFZ22E-20 1SBH136001R2022 0.310
A1 13 21 31 43
NO NC NC NO 24...60 20...60 NFZ22E-21 1SBH136001R2122 0.310
NO NC NC NO
48...130 48...130 NFZ22E-22 1SBH136001R2222 0.310
A2 14 22 32 44
100...250 100...250 NFZ22E-23 1SBH136001R2322 0.310
– 12...20 NFZ31E-20 1SBH136001R2031 0.310
A1 13 21 33 43
NO NC NO NO 24...60 20...60 NFZ31E-21 1SBH136001R2131 0.310
NO NC NO NO 48...130 48...130 NFZ31E-22 1SBH136001R2231 0.310
A2 14 22 34 44
100...250 100...250 NFZ31E-23 1SBH136001R2331 0.310
– 12...20 NFZ40E-20 1SBH136001R2040 0.310
24...60 20...60 NFZ40E-21 1SBH136001R2140 0.310
A1 13 23 33 43
NO NO NO NO
NO NO NO NO
48...130 48...130 NFZ40E-22 1SBH136001R2240 0.310
A2 14 24 34 44
100...250 100...250 NFZ40E-23 1SBH136001R2340 0.310
Note: Only NFZ contactor relays with DC control voltage 12...20 V DC need to respect the connection polarities indicated close to the
coil terminals: A1+ for the positive pole and A2- for the negative pole.
35 mm EN/IEC 60715
1SBC101559S0201 - Rev. A
80 3.15"
70 2.76"
60 2.36"
5.5 0.22"
5 0.20"
10 0.39"
5 0.20"
ABB | 6/61
NF 4-pole contactor relays
Main accessories
NF contactor relay
TEF4
Electronic timer
BX4-CA
Protective cover
BX4-CA
CAL4-11 Protective cover
CA4
2-pole auxiliary
4-pole auxiliary
contact block
contact block
6
CA4, CC4
1-pole auxiliary
BX4 contact block
Protective cover
1SBC101518S0201 - Rev. A
6/62 | ABB
NF 4-pole contactor relays
Main accessories
qty (1 pce)
kg
Front-mounted auxiliary contact blocks with N.O. leading contact and N.C. lagging contact
4-pole NF – – 1 0 CC4-10 1SBN010111R1010 1 0.014
– – 0 1 CC4-01 1SBN010111R1001 1 0.014
6
Side-mounted instantaneous auxiliary contact blocks
NF 1 1 – – CAL4-11 1SBN010120R1011 1 0.040
1SBC101112F0014
For contactors Time delay Delay Auxiliary Type Order code Pkg Weight
CAL4-11 range type contacts qty (1 pce)
selected by
switch
kg
Electronic timers
NF 0.1...1 s ON-delay 1 1 TEF4-ON 1SBN020112R1000 1 0.065
1SBC101392F0014
1...10 s
10...100 s OFF-delay 1 1 TEF4-OFF 1SBN020114R1000 1 0.065
Protective covers
1SBC101133F0014
LDC4
1SBC101136F0014
BX4
1SBC101138F0014
1SBC101519S0201 - Rev. A
BX4-CA
ABB | 6/63
Voltage code table
The below tables indicate the available coil voltages and corresponding digits for order codes. When placing an order, please give
the order code. Select a standard contactor from ordering detail pages. Change the coil voltage code in the order code accord-
ing to the table below. Example: for contactor AF400-30-11 and coil 100...250 V 50/60 Hz, the order code is 1SFL577001R7011.
AF09 - 30 - 10 - 13 1SBL137001R 13 10
AC coil code DC coil code
50/60 Hz
N.O. N.C. 41 24...60 V -
Main contacts
11 24...60 V 20...60 V
12 48...130 V 48...130 V
13 100...250 V 100...250 V
Contactor type
14 250...500 V 250...500 V
AF.. AC / DC operated
6 Coil 41: not available for AF116 ... AF370
AF400 - 30 - 11 1SFL577001R 69 11
AC coil code DC coil code
50/60 Hz
N.O. N.C. 68 - 24...60 V
Main contacts
69 48...130 V 48...130 V
70 100...250 V 100...250 V
71 250...500 V 250...500 V
Contactor type
AF.. AC / DC operated Coil 68, 69, 71: not available for AF1350 ... AF2650
Auxiliary contacts
N.O. N.C.
Type Order code
AF09 Z - 30 - 10 - 21 1SBL136001R 21 10
1SBC101601S0201 - Rev. D
6/64 | ABB
Voltage code table
NF contactor relays
Type Order code
NF 22 E - 13 1SBH137001R 13 22
AC coil code DC coil code
50/60 Hz
N.O. N.C. 41 24...60 V -
Number contacts 11 24...60 V 20...60 V
12 48...130 V 48...130 V
13 100...250 V 100...250 V
Contactor type 14 250...500 V 250...500 V
NF AC / DC operated
6
NF contactor relays with overlapping of lagging / leading contacts
N.O. leading contacts
N.C. lagging contacts
Type Order code
NF 33 / 11 - 13 1SBH137001R 13 39
AC coil code DC coil code
50/60 Hz
N.O. N.C. 41 24...60 V -
Number contacts 11 24...60 V 20...60 V
12 48...130 V 48...130 V
13 100...250 V 100...250 V
Contactor type 14 250...500 V 250...500 V
NF AC / DC operated
NF Z 22 E - 21 1SBH136001R 21 22
AC coil code DC coil code
50/60 Hz
N.O. N.C. 20 - 12...20 V
Number contacts 21 24...60 V 20...60 V
22 48...130 V 48...130 V
Contactor type 23 100...250 V 100...250 V
NF AC / DC operated
NF Z 33 / 11 E - 21 1SBH136001R 21 39
1SBC101601S0201 - Rev. D
ABB | 6/65
Voltage code table
AU 500 V -
DC 36 V
AV - 600 V
DD 48 V
DT 60 V
DG 75 V
DE 110 V
DU 125 V
DF 220 V
6/66 | ABB
Voltage code table
GAF185 - 10 - 11 1SFL497025R 69 11
AC coil code DC coil code
50/60 Hz
N.O. N.C. 72 - 20...60 V
Main contacts
69 48...130 V 48...130 V
70 100...250 V 100...250 V
Contactor type
GAF AC / DC operated
GAF460 - 10 - 11 1SFL597025R 69 11
AC coil code DC coil code
50/60 Hz
N.O. N.C. 68 - 24...60 V
Main contacts
69 48...130 V 48...130 V
70 100...250 V 100...250 V
71 250...500 V 250...500 V
Contactor type
GAF AC / DC operated
GAF1650 - 10 - 11 1SFL677025R 70 11
AC coil code DC coil code
50/60 Hz
N.O. N.C.
70 100...250 V 100...250 V
Main contacts
Contactor type
GAF AC / DC operated
1SBC101601S0201 - Rev. D
ABB | 6/67
7
Summary_7
7/0 | ABB
Overload relays
Overview
Thermal and electronic overload relays 7/2
General accessories
7
WRH, WRB 7/16
For direct product details information, use product type or order code, ex:
Summary_7
www.abb.com/productdetails/AF09-30-10-13 or www.abb.com/productdetails/1SBL137001R1310
ABB | 7/1
Thermal and electronic overload relays
Thermal overload
relays
IEC: rated operational power AC-3 400 V 0.03 … 4.0 kW 0.03 … 4.0 kW 4.0 … 18.5 kW 18.5 … 30 kW
UL/CSA: 3-phase hp-ratings 480 V 1/2 … 5 hp 1/2 … 10 hp 5 … 20 hp 30 … 60 hp
Fitting to contactors B6, B7 AS09 … AS16 AF09 ... AF38 AF40, AF52, AF65
7 Electronic overload
relays
with integrated CT
IEC: rated operational power AC-3 400 V 4 … 7.5 kW 4 … 7.5 kW 4.0 … 18.5 kW 18.5 … 30 kW
UL/CSA: 3-phase hp-ratings 480 V 5 … 10 hp 5 … 10 hp 5 … 20 hp 30 … 60 hp
Fitting to contactors B6, B7, BC6, BC7, A09 AF09 … AF16 AF26 ... AF38 AF40, AF52, AF65
... A16, AL09 ... AL16,
VB6, VB7, VBC6, VBC7
Electronic overload
relays
with external separate CT
IEC: rated operational power AC-3 400 V 200 … 250 kW 315 … 400 kW
UL/CSA: 3-phase hp-ratings 480 V 350 … 400 hp 500 … 600 hp
Fitting to contactors AF400, AF460 AF580, AF750, AF1250
7/2 | ABB
37 … 45 kW 55 … 75 kW 90 … 110 kW
60 hp 75 … 100 hp 125 … 150 hp
AF80, AF96 AF116, AF140 AF190, AF205
475 … 560 kW
800 … 900 hp
AF1350, AF1650
2CDC106062C0201
E1250DU
375 … 1250 A
10E, 20E, 30E selectable
ABB | 7/3
T16 thermal overload relays
0.10 to 16.0 A
Description
The T16 thermal overload relays are economic electromechanical protection devices for the main circuit.
They offer reliable protection for motors in the event of overload or phase failure. The devices have trip
class 10.
The thermal overload relays are three pole relays with bimetal tripping elements. The motor current flows
2CDC231009F0013
through the bimetal tripping elements and heats them directly and indirectly. In case of an overload (over
current), the bimetal elements bent as a result of the heating. This leads to a release of the relay and a
change of the contacts switching position (95-96 / 97-98).
– – Manual or automatic reset selectable
– – Phase loss sensitive acc. to IEC/EN 60947-4-1
T16 – – TEST and STOP function – Trip indication on the front
– – Temperature compensation
– – Suitable for three- and single-phase applications
Ordering details
Setting range Short-circuit Trip class Type Order code Weight
protective device (1 pc)
A kg
2CDC231025F0013
2CDC106036C0201_1s4
2CDC232008F0008
T16
7/4 | ABB
TF42 thermal overload relays
0.10 to 38.0 A
Description
The TF42 thermal overload relays are economic electromechanical protection devices for the main circuit.
They offer reliable protection for motors in the event of overload or phase failure. The devices have trip
class 10.
The thermal overload relays are three pole relays with bimetal tripping elements. The motor current flows
through the bimetal tripping elements and heats them directly and indirectly. In case of an overload (over
2CDC231006F0013
current), the bimetal elements bent as a result of the heating. This leads to a release of the relay and a
change of the contacts switching position (95-96 / 97-98).
– – Manual or automatic reset selectable
– – Phase loss sensitive acc. to IEC/EN 60947-4-1
TF42 – – TEST and STOP function – Trip indication on the front
– – Temperature compensation
– – Suitable for three- and single-phase applications
Ordering details
Setting range Short-circuit Trip class Type Order code Weight
protective device (1 pc)
2CDC231001F0011
A kg
0.10 ... 0.13 0.5 A, fuse type T 10 TF42-0.13 1SAZ721201R1005 0.130
0.13 ... 0.17 1.0 A, fuse type T 10 TF42-0.17 1SAZ721201R1008 0.130
0.17 ... 0.23 1.0 A, fuse type T 10 TF42-0.23 1SAZ721201R1009 0.130
0.23 ... 0.31 1.0 A, fuse type T 10 TF42-0.31 1SAZ721201R1013 0.130
DB42 0.31 ... 0.41 2.0 A, fuse type gG 10 TF42-0.41 1SAZ721201R1014 0.130
0.41 ... 0.55 2.0 A, fuse type gG 10 TF42-0.55 1SAZ721201R1017 0.130 7
0.55 ... 0.74 4.0 A, fuse type gG 10 TF42-0.74 1SAZ721201R1021 0.130
0.74 ... 1.00 6.0 A, fuse type gG 10 TF42-1.0 1SAZ721201R1023 0.130
1.00 ... 1.30 6.0 A, fuse type gG 10 TF42-1.3 1SAZ721201R1025 0.130
1.30 ... 1.70 10.0 A, fuse type gG 10 TF42-1.7 1SAZ721201R1028 0.130
1.70 ... 2.30 10.0 A, fuse type gG 10 TF42-2.3 1SAZ721201R1031 0.130
2.30 ... 3.10 10.0 A, fuse type gG 10 TF42-3.1 1SAZ721201R1033 0.130
2CDC231026F0013
2CDC106046C0201_1s4
88.3
2CDC232005F0009
TF42
ABB | 7/5
TF65 thermal overload relays
22.0 to 67.0 A
Description
The TF65 thermal overload relays are economic electromechanical protection devices for the main circuit.
They offer reliable protection for motors in the event of overload or phase failure. The devices have trip
class 10.
The thermal overload relays are three pole relays with bimetal tripping elements. The motor current flows
through the bimetal tripping elements and heats them directly and indirectly. In case of an overload (over
current), the bimetal elements bent as a result of the heating. This leads to a release of the relay and a
change of the contacts switching position (95-96 / 97-98).
2CDC231004F0013
Ordering details
Setting range Short-circuit Trip class Type Order code Weight
1SFC151224F0002
7 0.28"
3.45"
16.6 0.65"
87.7 3.45"
46 1.81"
101.4
67.8 2.67"
65 2.56"
18.9 0.74"
2CDC106063C0201_1s4
106.9 4.21"
TF65
7/6 | ABB
TF96 thermal overload relays
40.0 to 96.0 A
Description
The TF96 thermal overload relays are economic electromechanical protection devices for the main circuit.
They offer reliable protection for motors in the event of overload or phase failure. The devices have trip
class 10.
The thermal overload relays are three pole relays with bimetal tripping elements. The motor current flows
through the bimetal tripping elements and heats them directly and indirectly. In case of an overload (over
current), the bimetal elements bent as a result of the heating. This leads to a release of the relay and a
change of the contacts switching position (95-96 / 97-98).
2CDC231005F0013
Ordering details
Setting range Short-circuit Trip class Type Order code Weight
1SFC151224F0002
16.6 0.65"
60.6 3.57"
46 1.81"
106.3
70.3 2.77"
67.5 2.66"
18.9 0.74"
TF96
ABB | 7/7
TF140DU thermal overload relays
66 to 142 A
Description
The TF140DU thermal overload relays are economic electromechanical protection devices for the main
circuit. They offer reliable protection for motors in the event of overload or phase failure. The devices have
trip class 10A.
The thermal overload relays are three pole relays with bimetal tripping elements. The motor current flows
2CDC231012F0012
through the bimetal tripping elements and heats them directly and indirectly. In case of an overload (over
current), the bimetal elements bent as a result of the heating. This leads to a release of the relay and a
change of the contacts switching position (95-96 / 97-98).
– – Manual or automatic reset selectable
TF140DU – – Phase loss sensitive acc. to IEC/EN 60947-4-1
– – TEST and STOP function – Trip indication on the front
– – Temperature compensation
– – Suitable for three- and single-phase applications
1SFC151224F0002
Ordering details
Setting range Short-circuit Trip class Type Order code Weight
protective device (1 pc)
KPR-101L A kg
66 ... 90 200 A, fuse type gG 10A TF140DU-90 1SAZ431201R1001 0.820
80 ... 110 224 A, fuse type gG 10A TF140DU-110 1SAZ431201R1002 0.820
100 ... 135 224 A, fuse type gG 10A TF140DU-135 1SAZ431201R1003 0.820
110 ... 142 250 A, fuse type gG 10A TF140DU-142 1SAZ431201R1004 0.820
89 3.5"
29.75 1.17" 29.75 1.17" 19.9 0.78" 37 1.46"
6.4 3.5" 4 0.16" 5.5 0.22"
51 2.01"
13.45 0.53"
5.51"
140
67.3 2.65"
98 97 96 95
82.3 3.24"
73.8 2.91"
TF140DU
7/8 | ABB
TA200DU thermal overload relays
66 to 200 A
Description
The TA200DU thermal overload relays are economic electromechanical protection devices for the main
circuit. They offer reliable protection for motors in the event of overload or phase failure. The devices have
trip class 10A.
The thermal overload relays are three pole relays with bimetal tripping elements. The motor current flows
through the bimetal tripping elements and heats them directly and indirectly. In case of an overload (over
2CDC231016F0013
current), the bimetal elements bent as a result of the heating. This leads to a release of the relay and a
change of the contacts switching position (95-96 / 97-98).
– – Manual or automatic reset selectable
– – Phase loss sensitive acc. to IEC/EN 60947-4-1
TA200DU – – TEST and STOP function – Trip indication on the front
– – Temperature compensation
– – Suitable for three- and single-phase applications
Ordering details
1SFC151224F0002
35 1.38" 35 1.38"
37 1.46"
23 0.91" 26 1.02"
5.5 0.22" 32 1.26" 3 0.12"
Ø8.5 Ø0.33"
2"
11 0.43"
30.9 1.22"
49.9
6 0.24"
10 0.39"
5.94"
4 0.16"
82.3 3.24"
68 2.68"
151
80 3.15"
2CDC106038C0201_1s4
2CDC232021F0011
22.1 0.87"
8 0.31" 6 0.24"
61 2.4" 4 0.16"
Ø 11 Ø 0.43" Ø 5.3 Ø 0.21"
126 4.96"
20 0.79"
50 1.97"
42 1.65" 42 1.65"
TA200DU
ABB | 7/9
E16DU electronic overload relays
0.10 to 18.9 A
Description
The E16DU is self-supplied electronic overload relays, which means no extra external supply is needed.
It offers reliable protection for motors in the event of overload or phase failure. Easy to use like a
thermal overload relay and compatible with standard motor applications, the electronic overload relay is
convincing, above all, due to its wide setting range, high accuracy, high operational temperature range and
2CDC231001F0007
the possibility to select a trip class (10E, 20E, 30E). Further features are the temperature compensation,
trip contact (N.C.), signal contact (N.O.), automatic or manual reset selectable, trip-free mechanism, STOP
and TEST function and a trip indication. The overload relays are connected directly to the contactors.
Ordering details
E16DU-1.0 Setting range Short-circuit Trip class Type Order code Weight
protective device (1 pc)
A kg
E16DU electronic overload relays
0.10 ... 0.32 1 A, fuse type gG 10E, 20E, 30E E16DU-0.32 1SAX111001R1101 0.150
0.30 ... 1.00 4 A, fuse type gG 10E, 20E, 30E E16DU-1.0 1SAX111001R1102 0.150
0.80 ... 2.70 10 A, fuse type gG 10E, 20E, 30E E16DU-2.7 1SAX111001R1103 0.150
2CDC231003F0010
2.00 ... 6.30 20 A, fuse type gG 10E, 20E, 30E E16DU-6.3 1SAX111001R1104 0.150
5.70 ... 18.9 50 A, fuse type gG 10E, 20E, 30E E16DU-18.9 1SAX111001R1105 0.150
DB16E
Ordering details accessories
Suitable for Description Type Order code Weight
7 (1 pc)
kg
E16DU Single mounting kit DB16E 1SAX101110R0001 0.035
E16DU Reset push button* KPR-101L 1SFA616162R1014 0.019
KPR-101L
2CDC107032C0201_1s4
2CDC232007F0011
E16DU
7/10 | ABB
EF19, EF45 electronic overload relays
0.10 to 45.0 A
Description
The EF19 and EF45 are self-supplied electronic overload relays, which means no extra external supply
is needed. It offers reliable protection for motors in the event of overload or phase failure. Easy to use
like a thermal overload relay and compatible with standard motor applications, the electronic overload
relay is convincing, above all, due to its wide setting range, high accuracy, high operational temperature
range and the possibility to select a trip class (10E, 20E, 30E). Further features are the temperature
1SBC101147F0010
compensation, trip contact (N.C.), signal contact (N.O.), automatic or manual reset selectable, trip-free
mechanism, STOP and TEST function and a trip indication. The overload relays are connected directly to
the contactors.
Ordering details
EF19-18.9
Setting range Short-circuit Trip class Type Order code Weight
protective device (1 pc)
A kg
EF19 electronic overload relays
0.10 … 0.32 1 A, fuse type gG 10E, 20E, 30E EF19-0.32 1SAX121001R1101 0.158
0.30 … 1.00 4 A, fuse type gG 10E, 20E, 30E EF19-1.0 1SAX121001R1102 0.158
0.80 … 2.70 10 A, fuse type gG 10E, 20E, 30E EF19-2.7 1SAX121001R1103 0.158
1SBC101148F0010
1.90 … 6.30 20 A, fuse type gG 10E, 20E, 30E EF19-6.3 1SAX121001R1104 0.158
5.70 … 18.9 50 A, fuse type gG 10E, 20E, 30E EF19-18.9 1SAX121001R1105 0.158
DB45EF
KPR-101L
104.7 4.12"
3.35"
85
2CDC107032C0201_1s4
2CDC232007F0009
2CDC232008F0009
10.3 0.41" 5.65 0.22" 37.5 1.48" 10.3 0.41" 5.65 0.22" 56.5 2.22"
8.2 0.32" 14 0.55" 55.4 2.18" 8.5 0.33" 14 0.55" 82.1 3.23"
44.4 1.75" 29.3 2.33" 45 1.77" 86 3.39"
EF19 EF45
ABB | 7/11
EF65, EF96, EF146 electronic overload relays
20 to 150 A
Description
The EF65, EF96 and EF146 are self-supplied electronic overload relays, which means no extra external
supply is needed. It offers reliable protection for motors in the event of overload or phase failure. Easy to
use like a thermal overload relay and compatible with standard motor applications, the electronic overload
relay is convincing, above all, due to its wide setting range, high accuracy, high operational temperature
2CDC231001F0012
range and the possibility to select a trip class (10E, 20E, 30E). Further features are the temperature
compensation, trip contact (N.C.), signal contact (N.O.), automatic or manual reset selectable, trip-free
mechanism, STOP and TEST function and a trip indication. The overload relays are connected directly to
the contactors.
54 ... 150 315 A, fuse type gG 10E, 20E, 30E EF146-150 1SAX351001R1101 0.879
EF146-150
Main dimensions mm, inches
55 2.17" 43.7 1.72"
34.65 1.36" 56.6 2.23" 3 0.12"
8 0.31"
8 0.31"
53.3 2.1" 3 0.12"
17.2 0.68"
17.2 0.68"
1SFC151224F0002
25.4 1"
25.4 1"
10 0.39"
10 0.39"
120.2 4.73"
121.7 4.79"
105.2 4.14"
38.4 1.51"
38.4 1.51"
105.2 4.14"
3.35"
4.06"
85.2 3.35"
KPR-101L
103.2 4.06"
2.92"
74.2 2.92"
85.2
103.2
74.2
11 0.43"
11 0.43"
2CDC232001F0012
2CDC232002F0012
3 0.12" 3 0.12"
16 0.63" 5.5 0.22" 74 2.91" 16 0.63" 5.5 0.22"
74 2.91"
37 1.46" 101.4 3.99" 37 1.46"
58 2.28" 58 2.28" 101.4 3.99"
105.2 4.14"
70 2.76" 70 2.76" 105.2 4.14"
89.05 3.51"
60.1 2.37"
13 0.5"
6.6 0.26" 15.5 0.61" 4 0.16"
10 0.39"
139.4 5.49"
4.69"
5"
117.4 4.62"
127
38.4 1.51"
119.25
88.9 3.5"
85.2 3.35"
4.08"
74.2 2.92"
103.7
11 0.43"
2CDC107038C0201_1s4
2CDC232003F0012
EF146-150
7/12 | ABB
EF205, EF370 electronic overload relays
63 to 380 A
Description
The EF205 and EF370 are self-supplied electronic overload relays, which means no extra external supply
is needed. It offers reliable protection for motors in the event of overload or phase failure. Easy to use like
a thermal overload relay and compatible with standard motor applications, the electronic overload relay is
convincing, above all, due to its wide setting range, high accuracy, high operational temperature range and
the possibility to select a trip class (10E, 20E, 30E). Further features are the temperature compensation,
2CDC231004F0012
trip contact (N.C.), signal contact (N.O.), automatic or manual reset selectable, trip-free mechanism, STOP
and TEST function and a trip indication. The overload relays are connected directly to the contactors.
Ordering details
Setting range Short-circuit Trip class Type Order code Weight
EF205-210 protective device (1 pc)
A kg
63 ... 210 1250 A, fuse type gG 10E, 20E, 30E EF205-210 1SAX531001R1101 1.210
115 ... 380 1600 A, fuse type gG 10E, 20E, 30E EF370-380 1SAX611001R1101 1.430
kg
EF205, EF370 Reset push button* KPR-101L 1SFA616162R1014 0.027
122.8 4.83"
KPR-101L
11 0.43"
5 0.2"
122 4.8"
151 5.9"
18.5 0.73"
2CDC232004F0012
10 0.39"
EF205-210
122.8 4.83"
11 0.43"
5 0.2"
6.4"
0.4'
163.6
122
0.9"
22.8
2CDC107040C0201_1s4
2CDC232005F0012
14 0.55"
EF370-380
ABB | 7/13
EF460, EF750 electronic overload relays
150 to 800 A
Description
2CDC231013F0013
The EF460 and EF750 are self-supplied electronic overload relays, which means no extra external supply
is needed. It offers reliable protection for motors in the event of overload or phase failure. Easy to use like
a thermal overload relay and compatible with standard motor applications, the electronic overload relay is
convincing, above all, due to its wide setting range, high accuracy, high operational temperature range and
the possibility to select a trip class (10E, 20E, 30E). Further features are the temperature compensation,
trip contact (N.C.), signal contact (N.O.), automatic or manual reset selectable, trip-free mechanism, STOP
and TEST function and a trip indication. Busbar kits are available as accessory for contactor mounting.
Ordering details
EF460-500
Setting Short-circuit Trip class Type Order code Weight
range protective device (1 pc)
A kg
2CDC231014F0013
48.04 1.89"
153.4 6.04"
149.9 5.9"
110.5 4.35"
152.3 6"
28.4 1.12"
103 4.06"
74 2.91"
76 2.99"
41.5 1.63"
21 0.83" 83 3.27" 83 3.27" 40.5 1.59"
58 2.28" 58 2.28" 32 1.26"
53.3 2.1" 82 3.23"
28 1.1"
30.9 1.22" 76 2.99"
5.6 0.22"
60 2.36"
80 3.15"
100 3.94"
55 2.17"
2CDC107045C0201_1s3
2CDC232008F0013
2CDC232009F0013
Ø5
.2
7 0.28"
13 0.51"
Ø7
19.5 0.77"
Ø0
25.5 1"
.2"
Ø0
.28
"
EF460-500 EF750-800
7/14 | ABB
E1250DU electronic overload relays
375 to 1250 A
Description
The E1250DU are self-supplied electronic overload relays, which means no extra external supply is
needed. It offers reliable protection for motors in the event of overload or phase failure. Easy to use like a
thermal overload relay and compatible with standard motor applications, the electronic overload relay is
convincing, above all, due to its wide setting range, high accuracy, high operational temperature range and
1SFC101025F0201
the possibility to select a trip class (10E, 20E, 30E). Further features are the temperature compensation,
trip contact (N.C.), signal contact (N.O.), automatic or manual reset selectable, trip-free mechanism, STOP
and TEST function and a trip indication. Busbar kits are available as accessory for contactor mounting.
Ordering details
Setting range Short-circuit Trip class Type Order code Weight
E1250DU-1250 protective device (1 pc)
A kg
E1250DU electronic overload relay
375 ... 1250 - 10E, 20E, 30E E1250DU-1250 1SFA739001R1000 12.181
2CDC107031C0201_1s3
ABB | 7/15
Thermal and electronic overload relays
General accessories
Description
The wire reset is a general accessory for thermal and electronic overloads relays. In installations which
2CDC231028F0013
are difficult to access, like a motor control centre or compact cubical, the accessory allows the user to
remotely reset the overload relays.
The wire reset consists of two parts, the bowden wire with actuator and the holder. The actuator should
be mounted into a door of a panel. The holder will be mounted on the overload relay. The actuator and
WRB-400 holder are connected via the bowden wire.
Ordering details
Suitable for Description Length Type Order code Weight
(1 pc)
mm kg
2CDC231027F0013
Holder
TF42, TF65, TF96, Holder for tool less direct mounting WRH-F 1SAZ701903R1001 0.006
EF19, EF45, EF65,
EF96, EF146,
EF205, EF370,
WRH-F EF460, EF750
7 IP54 gasket
WRB-400 IP54 Panel seal gasket WRBG 1SAZ701903R1030 0.037
WRB-600
WRB-1000
2CDC232015F0013
WRB-400/600/1000
TF42 ... TF96
WRH-F
2CDC131059C0201
7/16 | ABB
Notes
N4
ABB | 7/17
8
8/0 | ABB
R contactors
Presentation 8/2
Download
For additional information Questionnaire
Specification for R contactors
Customer .................................................................................................................
Contact person ...................................................... Date ..............................
ABB .............................................................................................................................
Contact person ....................................................................................................
Submit your request with the dedicated
refer to our main catalog. form. Our expert will define the right
Tel. .......................................................... e-mail .................................................. Tel. ...............................................................................................................................
or
DC switching
Application type
DC-1 (resistive load)
Main catalog DC-3 (shunt motors)
DC-5 (series motors)
Control of AC and DC power circuits Number of poles: N.O. ..................... N.C. .....................
Rated operational current Ie .................. A
up to 5000 A
Making current ........................................ A
Breaking current min. .......... A max. .......... A
Rated operational voltage Ue ............... V DC Control circuit (coil)
AC Voltage ..................... V ............... Hz
Operating conditions DC Voltage ..................... V DC
Switching frequency ............................................. cycles/h Options
Mech. durability required (millions of operating cycles) .............. Magnetical latching
Remarks .......................................................................................... Mechanical latching
Accessories
Summary_8
.............................................................................................................................................................................................................................................
Please add any other useful documents for further information e.g. technical specification, drawing, wiring diagram, etc.
Download Download
Brand ................................................................
Type ..................................................................
H
H = ............... mm F D
D = ............... mm W
Please photocopy and forward. Questionnaire also available on the ABB Website:
ABB | Questionnaire
ABB | 8/1
R contactors
Tailored to your needs
Reliability
Robust construction
Durability up to 5 millions of operating cycles
Experienced and proven for years.
8/2 | ABB
R contactors
Get the right product
Conventional applications
AC circuit switching DC circuit switching
Up to 500 V AC From 500 up to 1000 V AC Up to 1500 V DC with poles in series
IOR contactors IOR..MT contactors IOR..CC contactors
AC-1 Rated operational current up to 5000 A DC-1 Rated operational current up to 5000 A
AC-3 Rated power up to 1500 kW (1520 A - 440 V) DC-3 / DC-5 operational current up to 2000 A
Advanced applications
8
N.O./N.C. main poles combination Power circuit coupling Slip-ring motor control
AC circuit switching DC circuit switching Up to 1000 V AC / 1500 V DC Uer up to 5000 V AC
NOR..MT contactors NOR..CC contactors LOR couplers FOR contactors
ABB | 8/3
Coordination with short-circuit protection devices
In compliance with standards IEC 60947-4-1 and EN 60947-4-1, we define for the contactors and starters the type, rating
and characteristics of the short-circuit protection devices SCPD which allow selective protection against overloads and ensure
protection against short circuits.
Basic functions
Any starter is designed to:
–– start motors,
–– ensure continuous functioning of motors,
–– disconnect motors from the supply line,
–– guarantee protection of motors against overloads.
The starter is typically made up of a switching device (contactor) and an overload protection device (thermal overload relay or electronic overload
relay).
These two devices MUST be coordinated with equipment capable of providing protection against short circuit (SCPD: short circuit protective de-
vice): typically a circuit breaker with magnetic release only or a switch fuse. These are not necessarily part of the starter.
Applicable standards
IEC 60947-4-1 (EN 60947-4-1) precisely defines the different points to be considered in order to carry out correct coordination.
Complete coordination for a combination includes the following points:
–– Selectivity test between the overload relay and the short-circuit protection device SCPD.
–– Short-circuit condition tests:
-- at prospective "r" currents - These currents depend on the rated operational current of the starter (Ie AC-3) and are given by the standard
(Table 13). For example:
r = 1kA for Ie AC-3 < 16 A
r = 3 kA for 16 A < Ie AC-3 < 63 A
r = 5 kA for 63 A < Ie AC-3 < 125 A etc.
-- at the rated conditional short-circuit current "Iq" - This is the maximum prospective current that the combination can withstand, for example
50 kA.
9
Types of coordination
IEC 60947-4-1 (EN 60947-4-1) defines two types of coordination according to the expected level of service continuity. Acceptable extreme dam-
age for the switchgear is divided into two types.
Type 1: In short-circuit conditions, the contactor or starter does not endanger persons or installations and will not be able to then operate without
being repaired or having parts replaced.
Type 2: In short-circuit conditions, the contactor or starter does not endanger persons or installations and will be able to operate afterwards.
The risk of contacts light welding is acceptable. In this case, the manufacturer must stipulate the measures to be taken with respect to
maintenance of the equipment.
9/0 | ABB
Coordination with short-circuit protection devices
A complete data base of coordination tables, according to IEC 60947-4-1 (EN 60947-4-1) or UL 508 / UL 60947-4-1, is available on the ABB
Website: see below.
Selection
Simple or multiple selections all from the same screen.
Short-circuit protection devices
–– Air circuit breakers
–– Fuses "gG" or "aM"
–– Miniature circuit breaker
–– Moulded case circuit breaker
–– Manual motor starter
Starter type
–– Direct-on-line normal start
–– Direct-on-line heavy duty
–– Star-delta normal start
–– Soft starter normal start
Overload relay
–– TOL : thermal overload relay
–– EOL : electronic overload relay
–– UMC : Universal motor controller
Coordination
–– IEC type 1 or type 2
–– UL type A to Type F
Results
–– Search results displayed at the bottom of the selection page.
–– Only the most appropriate solutions to your application, will be displayed at the bottom of the page.
"Enable Smart Current Search" function featured for the short-circuit current where "near to" selected values also are included in the result.
–– Possible to print the page to a pdf file or from your printer.
–– "Clear selection" function to deselect all selected.
1SBC101591S0201 - Rev. B
Access
To find the coordination tables for motor protection, please see:
http://applications.it.abb.com/SOC/Page/Selection.aspx
ABB | 9/1
Index
Order code classification
Order code Type Page Order code Type Page Order code Type Page
1SAM101901R0001 HK-11 2/24 1SAM201906R1122 PS1-2-2-65 2/14 1SAM350005R1012 MS132-12.0-HKF1-11 2/7
1SAM101901R0002 HK-20 2/24 1SAM201906R1123 PS1-3-2-65 2/14 1SAM350005R1013 MS132-20-HKF1-11 2/7
1SAM101901R0003 HK-02 2/24 1SAM201906R1124 PS1-4-2-65 2/14 1SAM350005R1014 MS132-25-HKF1-11 2/7
1SAM101903R0024 UAF-24 2/24 1SAM201906R1125 PS1-5-2-65 2/14 1SAM350005R1015 MS132-32-HKF1-11 2/7
1SAM101903R0048 UAF-48 2/24 1SAM201907R1101 S1-M1-25 2/14 1SAM360000R1001 MO132-0.16 2/8
1SAM101903R0060 UAF-60 2/24 1SAM201907R1102 S1-M2-25 2/14 1SAM360000R1002 MO132-0.25 2/8
1SAM101903R0110 UAF-110 2/24 1SAM201907R1103 S1-M3-25 2/14 1SAM360000R1003 MO132-0.4 2/8
1SAM101903R0230 UAF-230 2/24 1SAM201908R1001 BS1-3 2/14 1SAM360000R1004 MO132-0.63 2/8
1SAM101903R0400 UAF-400 2/24 1SAM201909R1001 FS116 2/14 1SAM360000R1005 MO132-1.0 2/8
1SAM101903R0415 UAF-415 2/24 1SAM201909R1021 MSAH1 2/26 1SAM360000R1006 MO132-1.6 2/8
1SAM101903R0500 UAF-500 2/24 1SAM201910R1001 AA1-24 2/12 1SAM360000R1007 MO132-2.5 2/8
1SAM101904R0003 SK-11 2/24 1SAM201910R1002 AA1-110 2/12 1SAM360000R1008 MO132-4.0 2/8
1SAM101909R0001 AA-24 2/24 1SAM201910R1003 AA1-230 2/12 1SAM360000R1009 MO132-6.3 2/8
1SAM101909R0002 AA-230 2/24 1SAM201910R1004 AA1-400 2/12 1SAM360000R1010 MO132-10 2/8
1SAM101909R0003 AA-400 2/24 1SAM201911R1010 IB132-G 2/15 1SAM360000R1011 MO132-16 2/8
1SAM101923R0002 MSMN 3) 2/26 1SAM201911R1011 IB132-Y 2/15 1SAM360000R1012 MO132-12 2/8
1SAM101923R0012 MSMNO 4) 2/26 1SAM201912R1010 DMS132-G 2/15 1SAM360000R1013 MO132-20 2/8
1SAM101928R0001 HKF-11 2/24 1SAM201912R1011 DMS132-Y 2/15 1SAM360000R1014 MO132-25 2/8
1SAM101928R0002 HKF-20 2/24 1SAM201913R1103 S1-M3-35 2/14 1SAM360000R1015 MO132-32 2/8
1SAM101937R0012 PS3-2-0 2/23 1SAM201914R1001 PB1-1-32 2/14 1SAM401901R1001 HK4-11 2/19
1SAM101937R0013 PS3-3-0 2/23 1SAM201914R1002 S1-PB1-25 2/14 1SAM401901R1002 HK4-W 2/19
1SAM101937R0014 PS3-4-0 2/23 1SAM201916R1103 PS1-3-0-100 2/14 1SAM401902R1001 HKS4-11 2/19
1SAM101937R0015 PS3-5-0 2/23 1SAM201916R1104 PS1-4-0-100 2/14 1SAM401902R1002 HKS4-20 2/19
1SAM101937R0016 PS3-6-0 2/23 1SAM201916R1105 PS1-5-0-100 2/14 1SAM401902R1003 HKS4-02 2/19
1SAM101937R0022 PS3-2-1 2/23 1SAM201916R1113 PS1-3-1-100 2/14 1SAM401904R1001 SK4-11 2/19
1SAM101937R0023 PS3-3-1 2/23 1SAM201916R1114 PS1-4-1-100 2/14 1SAM401905R1001 UA4-110 2/19
1SAM101937R0024 PS3-4-1 2/23 1SAM201916R1115 PS1-5-1-100 2/14 1SAM401905R1002 UA4-230 2/19
1SAM101937R0025 PS3-5-1 2/23 1SAM201916R1123 PS1-3-2-100 2/14 1SAM401905R1003 UA4-400 2/19
1SAM101937R0032 PS3-2-2 2/23 1SAM201920R1000 MSH-AR 2/26 1SAM401905R1004 UA4-24 2/19
1SAM101937R0034 PS3-4-2 2/23 1SAM201920R1001 MSHD-LB 1) 2/26 1SAM401906R1001 UA4-HK-230 2/19
1SAM101938R0001 S3-M1 2/23 1SAM201920R1002 MSHD-LY 1) 2/26 1SAM401906R1002 UA4-HK-400 2/19
1SAM101938R0002 S3-M2 2/23 1SAM201920R1011 MSHD-LTB 2) 2/26 1SAM401907R1001 AA4-24 2/19
1SAM101938R0003 BS3-3 2/23 1SAM201920R1012 MSHD-LTY 2) 2/26 1SAM401907R1002 AA4-110 2/19
1SAM101938R0004 S3-M3 2/23 1SAM250000R1001 MS116-0.16 2/6 1SAM401907R1003 AA4-230 2/19
1SAM101940R1000 IB325-G 2/25 1SAM250000R1002 MS116-0.25 2/6 1SAM401907R1004 AA4-400 2/19
1SAM101940R1001 IB325-Y 2/25 1SAM250000R1003 MS116-0.4 2/6 1SAM401908R1001 KA450 2/20
1SAM101941R1000 DMS325-G 2/25 1SAM250000R1004 MS116-0.63 2/6 1SAM401910R1001 TB450 2/20
1SAM101941R1001 DMS325-Y 2/25 1SAM250000R1005 MS116-1.0 2/6 1SAM401911R1001 PS4-2-0 2/20
1SAM101943R0001 CK-11 2/24 1SAM250000R1006 MS116-1.6 2/6 1SAM401911R1002 PS4-3-0 2/20
1SAM150000R1001 MS325-0.16 2/21 1SAM250000R1007 MS116-2.5 2/6 1SAM401911R1003 PS4-4-0 2/20
1SAM150000R1002 MS325-0.25 2/21 1SAM250000R1008 MS116-4.0 2/6 1SAM401911R1004 PS4-2-2 2/20
1SAM150000R1003 MS325-0.4 2/21 1SAM250000R1009 MS116-6.3 2/6 1SAM401911R1005 PS4-3-2 2/20
1SAM150000R1004 MS325-0.63 2/21 1SAM250000R1010 MS116-10 2/6 1SAM401911R1006 PS4-4-2 2/20
1SAM150000R1005 MS325-1 2/21 1SAM250000R1011 MS116-16 2/6 1SAM401911R1007 S4-M1 2/20
1SAM150000R1006 MS325-1.6 2/21 1SAM250000R1012 MS116-12 2/6 1SAM401911R1008 BS4-3 2/20
1SAM150000R1007 MS325-2.5 2/21 1SAM250000R1013 MS116-20 2/6 1SAM401912R1001 DX495 2/20
1SAM150000R1008 MS325-4 2/21 1SAM250000R1014 MS116-25 2/6 1SAM450000R1005 MS450-40 2/16
1SAM150000R1009 MS325-6.3 2/21 1SAM250000R1015 MS116-32 2/6 1SAM450000R1006 MS450-45 2/16
1SAM150000R1010 MS325-9 2/21 1SAM250005R1001 MS116-0.16-HKF1-11 2/6 1SAM450000R1007 MS450-50 2/16
1SAM150000R1011 MS325-12.5 2/21 1SAM250005R1002 MS116-0.25-HKF1-11 2/6 1SAM460000R1005 MO450-40 2/17
1SAM150000R1012 MS325-16 2/21 1SAM250005R1003 MS116-0.4-HKF1-11 2/6 1SAM460000R1006 MO450-45 2/17
1SAM150000R1013 MS325-20 2/21 1SAM250005R1004 MS116-0.63-HKF1-11 2/6 1SAM460000R1007 MO450-50 2/17
1SAM150000R1014 MS325-25 2/21 1SAM250005R1005 MS116-1.0-HKF1-11 2/6 1SAM501901R1001 KA495 2/20
1SAM150005R0001 MS325-0.16-HKF11 2/21 1SAM250005R1006 MS116-1.6-HKF1-11 2/6 1SAM501902R1001 KA495C 1) 2/20
1SAM150005R0002 MS325-0.25-HKF11 2/21 1SAM250005R1007 MS116-2.5-HKF1-11 2/6 1SAM550000R1007 MS495-63 2/16
1SAM150005R0003 MS325-0.4-HKF11 2/21 1SAM250005R1008 MS116-4.0-HKF1-11 2/6 1SAM550000R1008 MS495-75 2/16
1SAM150005R0004 MS325-0.63-HKF11 2/21 1SAM250005R1009 MS116-6.3-HKF1-11 2/6 1SAM550000R1009 MS495-90 2/16
10 1SAM150005R0005
1SAM150005R0006
MS325-1-HKF11
MS325-1.6-HKF11
2/21
2/21
1SAM250005R1010
1SAM250005R1011
MS116-10.0-HKF1-11
MS116-16.0-HKF1-11
2/6
2/6
1SAM550000R1010
1SAM560000R1007
MS495-100
MO495-63
2/16
2/17
1SAM150005R0007 MS325-2.5-HKF11 2/21 1SAM250005R1012 MS116-12.0-HKF1-11 2/6 1SAM560000R1008 MO495-75 2/17
1SAM150005R0008 MS325-4-HKF11 2/21 1SAM250005R1013 MS116-20-HKF1-11 2/6 1SAM560000R1009 MO495-90 2/17
1SAM150005R0009 MS325-6.3-HKF11 2/21 1SAM250005R1014 MS116-25-HKF1-11 2/6 1SAM560000R1010 MO495-100 2/17
1SAM150005R0010 MS325-9-HKF11 2/21 1SAM250005R1015 MS116-32-HKF1-11 2/6 1SAM580000R1004 MS497-32 2/16
1SAM150005R0011 MS325-12.5-HKF11 2/21 1SAM301901R1001 CK1-11 2/11 1SAM580000R1005 MS497-40 2/16
1SAM150005R0012 MS325-16-HKF11 2/21 1SAM301901R1002 CK1-20 2/11 1SAM580000R1006 MS497-50 2/16
1SAM150005R0013 MS325-20-HKF11 2/21 1SAM301901R1003 CK1-02 2/11 1SAM580000R1007 MS497-63 2/16
1SAM150005R0014 MS325-25-HKF11 2/21 1SAM340000R1001 MS132-0.16T 2/9 1SAM580000R1008 MS497-75 2/16
1SAM160000R1003 MO325-0.4 2/22 1SAM340000R1002 MS132-0.25T 2/9 1SAM580000R1009 MS497-90 2/16
1SAM160000R1004 MO325-0.63 2/22 1SAM340000R1003 MS132-0.4T 2/9 1SAM580000R1010 MS497-100 2/16
1SAM160000R1005 MO325-1 2/22 1SAM340000R1004 MS132-0.63T 2/9 1SAM590000R1004 MO496-32 2/17
1SAM160000R1006 MO325-1.6 2/22 1SAM340000R1005 MS132-1.0T 2/9 1SAM590000R1005 MO496-40 2/17
1SAM160000R1007 MO325-2.5 2/22 1SAM340000R1006 MS132-1.6T 2/9 1SAM590000R1006 MO496-50 2/17
1SAM160000R1008 MO325-4 2/22 1SAM340000R1007 MS132-2.5T 2/9 1SAM590000R1007 MO496-63 2/17
1SAM160000R1009 MO325-6.3 2/22 1SAM340000R1008 MS132-4.0T 2/9 1SAM590000R1008 MO496-75 2/17
1SAM160000R1010 MO325-9 2/22 1SAM340000R1009 MS132-6.3T 2/9 1SAM590000R1009 MO496-90 2/17
1SAM160000R1011 MO325-12.5 2/22 1SAM340000R1010 MS132-10T 2/9 1SAM590000R1010 MO496-100 2/17
1SAM160000R1012 MO325-16 2/22 1SAM340000R1011 MS132-16T 2/9 1SAX101110R0001 DB16E 7/10
1SAM160000R1013 MO325-20 2/22 1SAM340000R1012 MS132-12T 2/9 1SAX101910R1001 DB19EF 7/11
1SAM160000R1014 MO325-25 2/22 1SAM340000R1013 MS132-20T 2/9 1SAX111001R1101 E16DU-0.32 7/10
1SAM201901R1001 HKF1-11 2/11 1SAM340000R1014 MS132-25T 2/9 1SAX111001R1102 E16DU-1.0 7/10
1SAM201901R1002 HKF1-20 2/11 1SAM350000R1001 MS132-0.16 2/7 1SAX111001R1103 E16DU-2.7 7/10
1SAM201902R1001 HK1-11 2/11 1SAM350000R1002 MS132-0.25 2/7 1SAX111001R1104 E16DU-6.3 7/10
1SAM201902R1002 HK1-20 2/11 1SAM350000R1003 MS132-0.4 2/7 1SAX111001R1105 E16DU-18.9 7/10
1SAM201902R1003 HK1-02 2/11 1SAM350000R1004 MS132-0.63 2/7 1SAX121001R1101 EF19-0.32 7/11
1SAM201902R1004 HK1-20L 2/11 1SAM350000R1005 MS132-1.0 2/7 1SAX121001R1102 EF19-1.0 7/11
1SAM201903R1001 SK1-11 2/11 1SAM350000R1006 MS132-1.6 2/7 1SAX121001R1103 EF19-2.7 7/11
1SAM201903R1002 SK1-20 2/11 1SAM350000R1007 MS132-2.5 2/7 1SAX121001R1104 EF19-6.3 7/11
1SAM201903R1003 SK1-02 2/11 1SAM350000R1008 MS132-4.0 2/7 1SAX121001R1105 EF19-18.9 7/11
1SAM201904R1001 UA1-24 2/12 1SAM350000R1009 MS132-6.3 2/7 1SAX201910R0001 DB45EF 7/11
1SAM201904R1002 UA1-48 2/12 1SAM350000R1010 MS132-10 2/7 1SAX221001R1101 EF45-30 7/11
1SAM201904R1003 UA1-60 2/12 1SAM350000R1011 MS132-16 2/7 1SAX221001R1102 EF45-45 7/11
1SAM201904R1004 UA1-110 2/12 1SAM350000R1012 MS132-12 2/7 1SAX331001R1101 EF65-70 7/12
1SAM201904R1005 UA1-230 2/12 1SAM350000R1013 MS132-20 2/7 1SAX331001R1102 EF65-56 7/12
1SAM201904R1006 UA1-400 2/12 1SAM350000R1014 MS132-25 2/7 1SAX341001R1101 EF96-100 7/12
1SAM201904R1007 UA1-415 2/12 1SAM350000R1015 MS132-32 2/7 1SAX351001R1101 EF146-150 7/12
1SAM201904R1008 UA1-208 2/12 1SAM350005R1001 MS132-0.16-HKF1-11 2/7 1SAX531001R1101 EF205-210 7/13
1SAM201904R1009 UA1-575 2/12 1SAM350005R1002 MS132-0.25-HKF1-11 2/7 1SAX611001R1101 EF370-380 7/13
1SAM201904R1010 UA1-20 2/12 1SAM350005R1003 MS132-0.4-HKF1-11 2/7 1SAX721001R1101 EF460-500 7/14
1SAM201906R1102 PS1-2-0-65 2/14 1SAM350005R1004 MS132-0.63-HKF1-11 2/7 1SAX821001R1101 EF750-800 7/14
1SAM201906R1103 PS1-3-0-65 2/14 1SAM350005R1005 MS132-1.0-HKF1-11 2/7 1SAZ401110R0001 DB200 7/9
1SAM201906R1104 PS1-4-0-65 2/14 1SAM350005R1006 MS132-1.6-HKF1-11 2/7 1SAZ401901R1001 LT200/A 7/9
1SAM201906R1105 PS1-5-0-65 2/14 1SAM350005R1007 MS132-2.5-HKF1-11 2/7 1SAZ421201R1001 TA200DU-90 7/9
1SAM201906R1112 PS1-2-1-65 2/14 1SAM350005R1008 MS132-4.0-HKF1-11 2/7 1SAZ421201R1002 TA200DU-110 7/9
1SAM201906R1113 PS1-3-1-65 2/14 1SAM350005R1009 MS132-6.3-HKF1-11 2/7 1SAZ421201R1003 TA200DU-135 7/9
Index
10/0 | ABB
Index
Order code classification
Order code Type Page Order code Type Page Order code Type Page
1SAZ421201R1006 TA200DU-200 7/9 1SBH103001R8322 NSL22E-83 4/11 1SBL113001R8110 ASL12-30-10-81 4/5
1SAZ431201R1001 TF140DU-90 7/8 1SBH103001R8331 NSL31E-83 4/11 1SBL113001R8132 ASL12-30-32-81 4/7
1SAZ431201R1002 TF140DU-110 7/8 1SBH103001R8340 NSL40E-83 4/11 1SBL113001R8301 ASL12-30-01-83 4/5
1SAZ431201R1003 TF140DU-135 7/8 1SBH103001R8344 NSL44E-83 4/11 1SBL113001R8310 ASL12-30-10-83 4/5
1SAZ431201R1004 TF140DU-142 7/8 1SBH103001R8353 NSL53E-83 4/11 1SBL113001R8332 ASL12-30-32-83 4/7
1SAZ701901R0001 DB16 7/4 1SBH103001R8362 NSL62E-83 4/11 1SBL113001R8601 ASL12-30-01-86 4/5
1SAZ701902R0001 DB42 7/5 1SBH103001R8371 NSL71E-83 4/11 1SBL113001R8610 ASL12-30-10-86 4/5
1SAZ701903R1001 WRH-F 7/16 1SBH103001R8380 NSL80E-83 4/11 1SBL113001R8632 ASL12-30-32-86 4/7
1SAZ701903R1011 WRB-400 7/16 1SBH103001R8622 NSL22E-86 4/11 1SBL113001R8801 ASL12-30-01-88 4/5
1SAZ701903R1012 WRB-600 7/16 1SBH103001R8631 NSL31E-86 4/11 1SBL113001R8810 ASL12-30-10-88 4/5
1SAZ701903R1013 WRB-1000 7/16 1SBH103001R8640 NSL40E-86 4/11 1SBL113001R8832 ASL12-30-32-88 4/7
1SAZ701903R1030 WRBG 7/16 1SBH103001R8644 NSL44E-86 4/11 1SBL121001R1601 AS16-30-01-16 4/4
1SAZ711201R1005 T16-0.13 5/1 1SBH103001R8653 NSL53E-86 4/11 1SBL121001R1610 AS16-30-10-16 4/4
1SAZ711201R1008 T16-0.17 5/1 1SBH103001R8662 NSL62E-86 4/11 1SBL121001R1632 AS16-30-32-16 4/6
1SAZ711201R1009 T16-0.23 5/1 1SBH103001R8671 NSL71E-86 4/11 1SBL121001R2001 AS16-30-01-20 4/4
1SAZ711201R1013 T16-0.31 5/1 1SBH103001R8680 NSL80E-86 4/11 1SBL121001R2010 AS16-30-10-20 4/4
1SAZ711201R1014 T16-0.41 5/1 1SBH103001R8822 NSL22E-88 4/11 1SBL121001R2032 AS16-30-32-20 4/6
1SAZ711201R1017 T16-0.55 5/1 1SBH103001R8831 NSL31E-88 4/11 1SBL121001R2601 AS16-30-01-26 4/4
1SAZ711201R1021 T16-0.74 5/1 1SBH103001R8840 NSL40E-88 4/11 1SBL121001R2610 AS16-30-10-26 4/4
1SAZ711201R1023 T16-1.0 5/1 1SBH103001R8844 NSL44E-88 4/11 1SBL121001R2632 AS16-30-32-26 4/6
1SAZ711201R1025 T16-1.3 5/1 1SBH103001R8853 NSL53E-88 4/11 1SBL121001R2801 AS16-30-01-28 4/4
1SAZ711201R1028 T16-1.7 5/1 1SBH103001R8862 NSL62E-88 4/11 1SBL121001R2810 AS16-30-10-28 4/4
1SAZ711201R1031 T16-2.3 5/1 1SBH103001R8871 NSL71E-88 4/11 1SBL121001R2832 AS16-30-32-28 4/6
1SAZ711201R1033 T16-3.1 5/1 1SBH103001R8880 NSL80E-88 4/11 1SBL123001R8101 ASL16-30-01-81 4/5
1SAZ711201R1035 T16-4.2 5/1 1SBH136001R2022 NFZ22E-20 6/61 1SBL123001R8110 ASL16-30-10-81 4/5
1SAZ711201R1038 T16-5.7 5/1 1SBH136001R2031 NFZ31E-20 6/61 1SBL123001R8132 ASL16-30-32-81 4/7
1SAZ711201R1040 T16-7.6 5/1 1SBH136001R2040 NFZ40E-20 6/61 1SBL123001R8301 ASL16-30-01-83 4/5
1SAZ711201R1043 T16-10 5/1 1SBH136001R2122 NFZ22E-21 6/61 1SBL123001R8310 ASL16-30-10-83 4/5
1SAZ711201R1045 T16-13 5/1 1SBH136001R2131 NFZ31E-21 6/61 1SBL123001R8332 ASL16-30-32-83 4/7
1SAZ711201R1047 T16-16 5/1 1SBH136001R2140 NFZ40E-21 6/61 1SBL123001R8601 ASL16-30-01-86 4/5
1SAZ721201R1005 TF42-0.13 7/5 1SBH136001R2222 NFZ22E-22 6/61 1SBL123001R8610 ASL16-30-10-86 4/5
1SAZ721201R1008 TF42-0.17 7/5 1SBH136001R2231 NFZ31E-22 6/61 1SBL123001R8632 ASL16-30-32-86 4/7
1SAZ721201R1009 TF42-0.23 7/5 1SBH136001R2240 NFZ40E-22 6/61 1SBL123001R8801 ASL16-30-01-88 4/5
1SAZ721201R1013 TF42-0.31 7/5 1SBH136001R2322 NFZ22E-23 6/61 1SBL123001R8810 ASL16-30-10-88 4/5
1SAZ721201R1014 TF42-0.41 7/5 1SBH136001R2331 NFZ31E-23 6/61 1SBL123001R8832 ASL16-30-32-88 4/7
1SAZ721201R1017 TF42-0.55 7/5 1SBH136001R2340 NFZ40E-23 6/61 1SBL136001R2001 AF09Z-30-01-20 6/29
1SAZ721201R1021 TF42-0.74 7/5 1SBH137001R1222 NF22E-12 6/60 1SBL136001R2010 AF09Z-30-10-20 6/29
1SAZ721201R1023 TF42-1.0 7/5 1SBH137001R1231 NF31E-12 6/60 1SBL136001R2101 AF09Z-30-01-21 6/29
1SAZ721201R1025 TF42-1.3 7/5 1SBH137001R1240 NF40E-12 6/60 1SBL136001R2110 AF09Z-30-10-21 6/29
1SAZ721201R1028 TF42-1.7 7/5 1SBH137001R1322 NF22E-13 6/60 1SBL136001R2201 AF09Z-30-01-22 6/29
1SAZ721201R1031 TF42-2.3 7/5 1SBH137001R1331 NF31E-13 6/60 1SBL136001R2210 AF09Z-30-10-22 6/29
1SAZ721201R1033 TF42-3.1 7/5 1SBH137001R1340 NF40E-13 6/60 1SBL136001R2301 AF09Z-30-01-23 6/29
1SAZ721201R1035 TF42-4.2 7/5 1SBH137001R1422 NF22E-14 6/60 1SBL136001R2310 AF09Z-30-10-23 6/29
1SAZ721201R1038 TF42-5.7 7/5 1SBH137001R1431 NF31E-14 6/60 1SBL136201R2000 AF09Z-40-00-20 6/47
1SAZ721201R1040 TF42-7.6 7/5 1SBH137001R1440 NF40E-14 6/60 1SBL136201R2100 AF09Z-40-00-21 6/47
1SAZ721201R1043 TF42-10 7/5 1SBH137001R4122 NF22E-41 6/60 1SBL136201R2200 AF09Z-40-00-22 6/47
1SAZ721201R1045 TF42-13 7/5 1SBH137001R4131 NF31E-41 6/60 1SBL136201R2300 AF09Z-40-00-23 6/47
1SAZ721201R1047 TF42-16 7/5 1SBH137001R4140 NF40E-41 6/60 1SBL136501R2000 AF09Z-22-00-20 6/47
1SAZ721201R1049 TF42-20 7/5 1SBK104035R2800 DRAS09-28P 5/1 1SBL136501R2100 AF09Z-22-00-21 6/47
1SAZ721201R1051 TF42-24 7/5 1SBK104035R2900 DRAS09-29P 5/1 1SBL136501R2200 AF09Z-22-00-22 6/47
1SAZ721201R1052 TF42-29 7/5 1SBK104135R2600 DRAS09-26N 5/1 1SBL136501R2300 AF09Z-22-00-23 6/47
1SAZ721201R1053 TF42-35 7/5 1SBK104135R2700 DRAS09-27N 5/1 1SBL137001R1201 AF09-30-01-12 6/28
1SAZ721201R1055 TF42-38 7/5 1SBK104235R2000 DRAS09-20S 5/1 1SBL137001R1210 AF09-30-10-12 6/28
1SAZ811201R1001 TF65-28 7/6 1SBK104335R8100 DRASL09-81S 5/1 1SBL137001R1301 AF09-30-01-13 6/28
1SAZ811201R1002 TF65-33 7/6 1SBK104335R8300 DRASL09-83S 5/1 1SBL137001R1310 AF09-30-10-13 6/28
1SAZ811201R1003 TF65-40 7/6 1SBK114035R2800 DRAS12-28P 5/1 1SBL137001R1401 AF09-30-01-14 6/28
1SAZ811201R1004 TF65-47 7/6 1SBK114035R2900 DRAS12-29P 5/1 1SBL137001R1410 AF09-30-10-14 6/28
1SAZ811201R1005
1SAZ811201R1006
TF65-53
TF65-60
7/6
7/6
1SBK114135R2600
1SBK114135R2700
DRAS12-26N
DRAS12-27N
5/1
5/1
1SBL137001R4101
1SBL137001R4110
AF09-30-01-41
AF09-30-10-41
6/28
6/28 10
1SAZ811201R1007 TF65-67 7/6 1SBK114235R2000 DRAS12-20S 5/1 1SBL137201R1200 AF09-40-00-12 6/46
1SAZ911201R1001 TF96-51 7/7 1SBK114335R8100 DRASL12-81S 5/1 1SBL137201R1300 AF09-40-00-13 6/46
1SAZ911201R1002 TF96-60 7/7 1SBK114335R8300 DRASL12-83S 5/1 1SBL137201R1400 AF09-40-00-14 6/46
1SAZ911201R1003 TF96-68 7/7 1SBK124035R2800 DRAS16-28P 5/1 1SBL137201R4100 AF09-40-00-41 6/46
1SAZ911201R1004 TF96-78 7/7 1SBK124035R2900 DRAS16-29P 5/1 1SBL137501R1200 AF09-22-00-12 6/46
1SAZ911201R1005 TF96-87 7/7 1SBK124135R2600 DRAS16-26N 5/1 1SBL137501R1300 AF09-22-00-13 6/46
1SAZ911201R1006 TF96-96 7/7 1SBK124135R2700 DRAS16-27N 5/1 1SBL137501R1400 AF09-22-00-14 6/46
1SBH101001R1622 NS22E-16 4/10 1SBK124235R2000 DRAS16-20S 5/1 1SBL137501R4100 AF09-22-00-41 6/46
1SBH101001R1631 NS31E-16 4/10 1SBK124335R8100 DRASL16-81S 5/1 1SBL156001R2001 AF12Z-30-01-20 6/29
1SBH101001R1640 NS40E-16 4/10 1SBK124335R8300 DRASL16-83S 5/1 1SBL156001R2010 AF12Z-30-10-20 6/29
1SBH101001R1644 NS44E-16 4/10 1SBL101001R1601 AS09-30-01-16 4/4 1SBL156001R2101 AF12Z-30-01-21 6/29
1SBH101001R1653 NS53E-16 4/10 1SBL101001R1610 AS09-30-10-16 4/4 1SBL156001R2110 AF12Z-30-10-21 6/29
1SBH101001R1662 NS62E-16 4/10 1SBL101001R1632 AS09-30-32-16 4/6 1SBL156001R2201 AF12Z-30-01-22 6/29
1SBH101001R1671 NS71E-16 4/10 1SBL101001R2001 AS09-30-01-20 4/4 1SBL156001R2210 AF12Z-30-10-22 6/29
1SBH101001R1680 NS80E-16 4/10 1SBL101001R2010 AS09-30-10-20 4/4 1SBL156001R2301 AF12Z-30-01-23 6/29
1SBH101001R2022 NS22E-20 4/10 1SBL101001R2032 AS09-30-32-20 4/6 1SBL156001R2310 AF12Z-30-10-23 6/29
1SBH101001R2031 NS31E-20 4/10 1SBL101001R2601 AS09-30-01-26 4/4 1SBL157001R1201 AF12-30-01-12 6/28
1SBH101001R2040 NS40E-20 4/10 1SBL101001R2610 AS09-30-10-26 4/4 1SBL157001R1210 AF12-30-10-12 6/28
1SBH101001R2044 NS44E-20 4/10 1SBL101001R2632 AS09-30-32-26 4/6 1SBL157001R1301 AF12-30-01-13 6/28
1SBH101001R2053 NS53E-20 4/10 1SBL101001R2801 AS09-30-01-28 4/4 1SBL157001R1310 AF12-30-10-13 6/28
1SBH101001R2062 NS62E-20 4/10 1SBL101001R2810 AS09-30-10-28 4/4 1SBL157001R1401 AF12-30-01-14 6/28
1SBH101001R2071 NS71E-20 4/10 1SBL101001R2832 AS09-30-32-28 4/6 1SBL157001R1410 AF12-30-10-14 6/28
1SBH101001R2080 NS80E-20 4/10 1SBL103001R8101 ASL09-30-01-81 4/5 1SBL157001R4101 AF12-30-01-41 6/28
1SBH101001R2622 NS22E-26 4/10 1SBL103001R8110 ASL09-30-10-81 4/5 1SBL157001R4110 AF12-30-10-41 6/28
1SBH101001R2631 NS31E-26 4/10 1SBL103001R8132 ASL09-30-32-81 4/7 1SBL176001R2001 AF16Z-30-01-20 6/29
1SBH101001R2640 NS40E-26 4/10 1SBL103001R8301 ASL09-30-01-83 4/5 1SBL176001R2010 AF16Z-30-10-20 6/29
1SBH101001R2644 NS44E-26 4/10 1SBL103001R8310 ASL09-30-10-83 4/5 1SBL176001R2101 AF16Z-30-01-21 6/29
1SBH101001R2653 NS53E-26 4/10 1SBL103001R8332 ASL09-30-32-83 4/7 1SBL176001R2110 AF16Z-30-10-21 6/29
1SBH101001R2662 NS62E-26 4/10 1SBL103001R8601 ASL09-30-01-86 4/5 1SBL176001R2201 AF16Z-30-01-22 6/29
1SBH101001R2671 NS71E-26 4/10 1SBL103001R8610 ASL09-30-10-86 4/5 1SBL176001R2210 AF16Z-30-10-22 6/29
1SBH101001R2680 NS80E-26 4/10 1SBL103001R8632 ASL09-30-32-86 4/7 1SBL176001R2301 AF16Z-30-01-23 6/29
1SBH101001R2822 NS22E-28 4/10 1SBL103001R8801 ASL09-30-01-88 4/5 1SBL176001R2310 AF16Z-30-10-23 6/29
1SBH101001R2831 NS31E-28 4/10 1SBL103001R8810 ASL09-30-10-88 4/5 1SBL176201R2000 AF16Z-40-00-20 6/47
1SBH101001R2840 NS40E-28 4/10 1SBL103001R8832 ASL09-30-32-88 4/7 1SBL176201R2100 AF16Z-40-00-21 6/47
1SBH101001R2844 NS44E-28 4/10 1SBL111001R1601 AS12-30-01-16 4/4 1SBL176201R2200 AF16Z-40-00-22 6/47
1SBH101001R2853 NS53E-28 4/10 1SBL111001R1610 AS12-30-10-16 4/4 1SBL176201R2300 AF16Z-40-00-23 6/47
1SBH101001R2862 NS62E-28 4/10 1SBL111001R1632 AS12-30-32-16 4/6 1SBL176501R2000 AF16Z-22-00-20 6/47
1SBH101001R2871 NS71E-28 4/10 1SBL111001R2001 AS12-30-01-20 4/4 1SBL176501R2100 AF16Z-22-00-21 6/47
1SBH101001R2880 NS80E-28 4/10 1SBL111001R2010 AS12-30-10-20 4/4 1SBL176501R2200 AF16Z-22-00-22 6/47
1SBH103001R8122 NSL22E-81 4/11 1SBL111001R2032 AS12-30-32-20 4/6 1SBL176501R2300 AF16Z-22-00-23 6/47
1SBH103001R8131 NSL31E-81 4/11 1SBL111001R2601 AS12-30-01-26 4/4 1SBL177001R1201 AF16-30-01-12 6/28
1SBH103001R8140 NSL40E-81 4/11 1SBL111001R2610 AS12-30-10-26 4/4 1SBL177001R1210 AF16-30-10-12 6/28
1SBH103001R8144 NSL44E-81 4/11 1SBL111001R2632 AS12-30-32-26 4/6 1SBL177001R1301 AF16-30-01-13 6/28
1SBH103001R8153 NSL53E-81 4/11 1SBL111001R2801 AS12-30-01-28 4/4 1SBL177001R1310 AF16-30-10-13 6/28
1SBH103001R8162 NSL62E-81 4/11 1SBL111001R2810 AS12-30-10-28 4/4 1SBL177001R1401 AF16-30-01-14 6/28
Index
ABB | 10/1
Index
Order code classification
Order code Type Page Order code Type Page Order code Type Page
1SBL177001R4110 AF16-30-10-41 6/28 1SBL397501R1200 AF80-22-00-12 6/48 1SFL447002R1111 AF140-30-11B-11 6/34
1SBL177201R1200 AF16-40-00-12 6/46 1SBL397501R1300 AF80-22-00-13 6/48 1SFL447002R1211 AF140-30-11B-12 6/34
1SBL177201R1300 AF16-40-00-13 6/46 1SBL397501R1400 AF80-22-00-14 6/48 1SFL447002R1311 AF140-30-11B-13 6/34
1SBL177201R1400 AF16-40-00-14 6/46 1SBL397501R4100 AF80-22-00-41 6/48 1SFL447002R1411 AF140-30-11B-14 6/34
1SBL177201R4100 AF16-40-00-41 6/46 1SBL407001R1100 AF96-30-00-11 6/30 1SFL447002R3311 AF140-30-11B-33 6/35
1SBL177501R1200 AF16-22-00-12 6/46 1SBL407001R1200 AF96-30-00-12 6/30 1SFL447002R3411 AF140-30-11B-34 6/35
1SBL177501R1300 AF16-22-00-13 6/46 1SBL407001R1300 AF96-30-00-13 6/30 1SFL447101R1111 AF140-40-11-11 6/52
1SBL177501R1400 AF16-22-00-14 6/46 1SBL407001R1400 AF96-30-00-14 6/30 1SFL447101R1211 AF140-40-11-12 6/52
1SBL177501R4100 AF16-22-00-41 6/46 1SBL407001R4100 AF96-30-00-41 6/30 1SFL447101R1311 AF140-40-11-13 6/52
1SBL236001R2000 AF26Z-30-00-20 6/29 1SBN010110R1001 CA4-01 6/33 1SFL447101R1411 AF140-40-11-14 6/52
1SBL236001R2100 AF26Z-30-00-21 6/29 1SBN010110R1010 CA4-10 6/33 1SFL447102R1111 AF140-40-11B-11 6/52
1SBL236001R2200 AF26Z-30-00-22 6/29 1SBN010110T1001 CA4-01-T 6/33 1SFL447102R1211 AF140-40-11B-12 6/52
1SBL236001R2300 AF26Z-30-00-23 6/29 1SBN010110T1010 CA4-10-T 6/33 1SFL447102R1311 AF140-40-11B-13 6/52
1SBL236201R2000 AF26Z-40-00-20 6/47 1SBN010111R1001 CC4-01 6/33 1SFL447102R1411 AF140-40-11B-14 6/52
1SBL236201R2100 AF26Z-40-00-21 6/47 1SBN010111R1010 CC4-10 6/33 1SFL467001R1111 AF146-30-11-11 6/34
1SBL236201R2200 AF26Z-40-00-22 6/47 1SBN010120R1011 CAL4-11 6/33 1SFL467001R1211 AF146-30-11-12 6/34
1SBL236201R2300 AF26Z-40-00-23 6/47 1SBN010120T1011 CAL4-11-T 6/33 1SFL467001R1311 AF146-30-11-13 6/34
1SBL236501R2000 AF26Z-22-00-20 6/47 1SBN010140R1004 CA4-04E 6/51 1SFL467001R1411 AF146-30-11-14 6/34
1SBL236501R2100 AF26Z-22-00-21 6/47 1SBN010140R1022 CA4-22E 6/33 1SFL467001R3311 AF146-30-11-33 6/35
1SBL236501R2200 AF26Z-22-00-22 6/47 1SBN010140R1031 CA4-31E 6/51 1SFL467001R3411 AF146-30-11-34 6/35
1SBL236501R2300 AF26Z-22-00-23 6/47 1SBN010140R1040 CA4-40E 6/51 1SFL467002R1111 AF146-30-11B-11 6/34
1SBL237001R1200 AF26-30-00-12 6/28 1SBN010140R1122 CA4-22M 6/33 1SFL467002R1211 AF146-30-11B-12 6/34
1SBL237001R1300 AF26-30-00-13 6/28 1SBN010140R1204 CA4-04N 6/63 1SFL467002R1311 AF146-30-11B-13 6/34
1SBL237001R1400 AF26-30-00-14 6/28 1SBN010140R1213 CA4-13N 6/63 1SFL467002R1411 AF146-30-11B-14 6/34
1SBL237001R4100 AF26-30-00-41 6/28 1SBN010140R1222 CA4-22N 6/63 1SFL467002R3311 AF146-30-11B-33 6/35
1SBL237201R1200 AF26-40-00-12 6/46 1SBN010140R1231 CA4-31N 6/63 1SFL487002R1111 AF190-30-11-11 6/36
1SBL237201R1300 AF26-40-00-13 6/46 1SBN010140R1240 CA4-40N 6/63 1SFL487002R1211 AF190-30-11-12 6/36
1SBL237201R1400 AF26-40-00-14 6/46 1SBN010140R1322 CA4-22U 6/33 1SFL487002R1311 AF190-30-11-13 6/36
1SBL237201R4100 AF26-40-00-41 6/46 1SBN010151R1011 CAT4-11E 6/33 1SFL487002R1411 AF190-30-11-14 6/36
1SBL237501R1200 AF26-22-00-12 6/46 1SBN010151R1111 CAT4-11M 6/33 1SFL487002R3311 AF190-30-11-33 6/37
1SBL237501R1300 AF26-22-00-13 6/46 1SBN010151R1311 CAT4-11U 6/33 1SFL487002R3411 AF190-30-11-34 6/37
1SBL237501R1400 AF26-22-00-14 6/46 1SBN011010T1001 CA3-01 4/9 1SFL487102R1111 AF190-40-11-11 6/53
1SBL237501R4100 AF26-22-00-41 6/46 1SBN011010T1010 CA3-10 4/9 1SFL487102R1211 AF190-40-11-12 6/53
1SBL276001R2000 AF30Z-30-00-20 6/29 1SBN020112R1000 TEF4-ON 6/33 1SFL487102R1311 AF190-40-11-13 6/53
1SBL276001R2100 AF30Z-30-00-21 6/29 1SBN020114R1000 TEF4-OFF 6/33 1SFL487102R1411 AF190-40-11-14 6/53
1SBL276001R2200 AF30Z-30-00-22 6/29 1SBN021012R1000 TEF3-ON 4/9 1SFL527002R1111 AF205-30-11-11 6/36
1SBL276001R2300 AF30Z-30-00-23 6/29 1SBN021014R1000 TEF3-OFF 4/9 1SFL527002R1211 AF205-30-11-12 6/36
1SBL277001R1200 AF30-30-00-12 6/28 1SBN030105T1000 VM4 6/33 1SFL527002R1311 AF205-30-11-13 6/36
1SBL277001R1300 AF30-30-00-13 6/28 1SBN030111R1000 VEM4 6/33 1SFL527002R1411 AF205-30-11-14 6/36
1SBL277001R1400 AF30-30-00-14 6/28 1SBN031005T1000 VM3 4/9 1SFL527002R3311 AF205-30-11-33 6/37
1SBL277001R4100 AF30-30-00-41 6/28 1SBN033405T1000 VM96-4 6/33 1SFL527002R3411 AF205-30-11-34 6/37
1SBL296001R2000 AF38Z-30-00-20 6/29 1SBN050010R1000 RV5/50 4/9 1SFL527102R1111 AF205-40-11-11 6/53
1SBL296001R2100 AF38Z-30-00-21 6/29 1SBN050010R1001 RV5/133 4/9 1SFL527102R1211 AF205-40-11-12 6/53
1SBL296001R2200 AF38Z-30-00-22 6/29 1SBN050010R1002 RV5/250 4/9 1SFL527102R1311 AF205-40-11-13 6/53
1SBL296001R2300 AF38Z-30-00-23 6/29 1SBN050010R1003 RV5/440 4/9 1SFL527102R1411 AF205-40-11-14 6/53
1SBL296201R2000 AF38Z-40-00-20 6/47 1SBN050020R1000 RT5/32 4/9 1SFL547002R1111 AF265-30-11-11 6/36
1SBL296201R2100 AF38Z-40-00-21 6/47 1SBN050020R1001 RT5/65 4/9 1SFL547002R1211 AF265-30-11-12 6/36
1SBL296201R2200 AF38Z-40-00-22 6/47 1SBN050020R1002 RT5/90 4/9 1SFL547002R1311 AF265-30-11-13 6/36
1SBL296201R2300 AF38Z-40-00-23 6/47 1SBN050020R1003 RT5/150 4/9 1SFL547002R1411 AF265-30-11-14 6/36
1SBL296501R2000 AF38Z-22-00-20 6/47 1SBN050020R1004 RT5/264 4/9 1SFL547002R3311 AF265-30-11-33 6/37
1SBL296501R2100 AF38Z-22-00-21 6/47 1SBN050100R1000 RC5-1/50 4/9 1SFL547002R3411 AF265-30-11-34 6/37
1SBL296501R2200 AF38Z-22-00-22 6/47 1SBN050100R1001 RC5-1/133 4/9 1SFL547102R1111 AF265-40-11-11 6/53
1SBL296501R2300 AF38Z-22-00-23 6/47 1SBN050100R1002 RC5-1/250 4/9 1SFL547102R1211 AF265-40-11-12 6/53
1SBL297001R1200 AF38-30-00-12 6/28 1SBN050100R1003 RC5-1/440 4/9 1SFL547102R1311 AF265-40-11-13 6/53
1SBL297001R1300 AF38-30-00-13 6/28 1SBN070156T1000 LDC4 6/63 1SFL547102R1411 AF265-40-11-14 6/53
1SBL297001R1400 AF38-30-00-14 6/28 1SBN080906R1001 BEA7/325 3/17 1SFL577001R6811 AF400-30-11 6/40
1SBL297001R4100 AF38-30-00-41 6/28 1SBN080906R1002 BEA7/132 3/17 1SFL577001R6911 AF400-30-11 6/40
10 1SBL297201R1200
1SBL297201R1300
AF38-40-00-12
AF38-40-00-13
6/46
6/46
1SBN081006T1000
1SBN081012R1000
BEA16-3
BER16C-3
4/9
4/9
1SFL577001R7011
1SFL577001R7111
AF400-30-11
AF400-30-11
6/40
6/40
1SBL297201R1400 AF38-40-00-14 6/46 1SBN081018R2000 BEY16C-3 4/9 1SFL587002R1111 AF305-30-11-11 6/36
1SBL297201R4100 AF38-40-00-41 6/46 1SBN081306T1000 BEA16-4 6/33 1SFL587002R1211 AF305-30-11-12 6/36
1SBL297501R1200 AF38-22-00-12 6/46 1SBN081311R1000 BER16-4 6/33 1SFL587002R1311 AF305-30-11-13 6/36
1SBL297501R1300 AF38-22-00-13 6/46 1SBN081313R2000 BEY16-4 6/33 1SFL587002R1411 AF305-30-11-14 6/36
1SBL297501R1400 AF38-22-00-14 6/46 1SBN082306T1000 BEA26-4 6/33 1SFL587002R3311 AF305-30-11-33 6/37
1SBL297501R4100 AF38-22-00-41 6/46 1SBN082306T2000 BEA38-4 6/33 1SFL587002R3411 AF305-30-11-34 6/37
1SBL347001R1100 AF40-30-00-11 6/30 1SBN082311R1000 BER38-4 6/33 1SFL587102R1111 AF305-40-11-11 6/53
1SBL347001R1200 AF40-30-00-12 6/30 1SBN082713R2000 BEY38-4 6/33 1SFL587102R1211 AF305-40-11-12 6/53
1SBL347001R1300 AF40-30-00-13 6/30 1SBN083411R1000 BER65-4 6/33 1SFL587102R1311 AF305-40-11-13 6/53
1SBL347001R1400 AF40-30-00-14 6/30 1SBN083413R2000 BEY65-4 6/33 1SFL587102R1411 AF305-40-11-14 6/53
1SBL347001R4100 AF40-30-00-41 6/30 1SBN083911R1000 BER96-4 6/33 1SFL597001R6811 AF460-30-11 6/40
1SBL347201R1100 AF40-40-00-11 6/48 1SBN083913R2000 BEY96-4 6/33 1SFL597001R6911 AF460-30-11 6/40
1SBL347201R1200 AF40-40-00-12 6/48 1SBN101035R1000 FR16AS-12VARS 5/1 1SFL597001R7011 AF460-30-11 6/40
1SBL347201R1300 AF40-40-00-13 6/48 1SBN110108T1000 BX4 6/63 1SFL597001R7111 AF460-30-11 6/40
1SBL347201R1400 AF40-40-00-14 6/48 1SBN110109W1000 BX4-CA 6/63 1SFL607002R1111 AF370-30-11-11 6/36
1SBL347201R4100 AF40-40-00-41 6/48 1SCA101647R1001 OXS6X85 2/26 1SFL607002R1211 AF370-30-11-12 6/36
1SBL347501R1100 AF40-22-00-11 6/48 1SCA101655R1001 OXS6X130 2/26 1SFL607002R1311 AF370-30-11-13 6/36
1SBL347501R1200 AF40-22-00-12 6/48 1SCA101659R1001 OXS6X180 2/26 1SFL607002R1411 AF370-30-11-14 6/36
1SBL347501R1300 AF40-22-00-13 6/48 1SCA108043R1001 OXS6X105 2/26 1SFL607002R3311 AF370-30-11-33 6/37
1SBL347501R1400 AF40-22-00-14 6/48 1SFA616162R1014 KPR-101L 7/4 1SFL607002R3411 AF370-30-11-34 6/37
1SBL347501R4100 AF40-22-00-41 6/48 1SFA739001R1000 E1250DU-1250 7/15 1SFL607102R1111 AF370-40-11-11 6/53
1SBL367001R1100 AF52-30-00-11 6/30 1SFL427001R1111 AF116-30-11-11 6/34 1SFL607102R1211 AF370-40-11-12 6/53
1SBL367001R1200 AF52-30-00-12 6/30 1SFL427001R1211 AF116-30-11-12 6/34 1SFL607102R1311 AF370-40-11-13 6/53
1SBL367001R1300 AF52-30-00-13 6/30 1SFL427001R1311 AF116-30-11-13 6/34 1SFL607102R1411 AF370-40-11-14 6/53
1SBL367001R1400 AF52-30-00-14 6/30 1SFL427001R1411 AF116-30-11-14 6/34 1SFL617001R6811 AF580-30-11 6/40
1SBL367001R4100 AF52-30-00-41 6/30 1SFL427001R3311 AF116-30-11-33 6/35 1SFL617001R6911 AF580-30-11 6/40
1SBL367201R1100 AF52-40-00-11 6/48 1SFL427001R3411 AF116-30-11-34 6/35 1SFL617001R7011 AF580-30-11 6/40
1SBL367201R1200 AF52-40-00-12 6/48 1SFL427002R1111 AF116-30-11B-11 6/34 1SFL617001R7111 AF580-30-11 6/40
1SBL367201R1300 AF52-40-00-13 6/48 1SFL427002R1211 AF116-30-11B-12 6/34 1SFL637001R6811 AF750-30-11 6/40
1SBL367201R1400 AF52-40-00-14 6/48 1SFL427002R1311 AF116-30-11B-13 6/34 1SFL637001R6911 AF750-30-11 6/40
1SBL367201R4100 AF52-40-00-41 6/48 1SFL427002R1411 AF116-30-11B-14 6/34 1SFL637001R7011 AF750-30-11 6/40
1SBL387001R1100 AF65-30-00-11 6/30 1SFL427002R3311 AF116-30-11B-33 6/35 1SFL637001R7111 AF750-30-11 6/40
1SBL387001R1200 AF65-30-00-12 6/30 1SFL427002R3411 AF116-30-11B-34 6/35 1SFL647001R6811 AF1250-30-11 6/41
1SBL387001R1300 AF65-30-00-13 6/30 1SFL427101R1111 AF116-40-11-11 6/52 1SFL647001R6911 AF1250-30-11 6/41
1SBL387001R1400 AF65-30-00-14 6/30 1SFL427101R1211 AF116-40-11-12 6/52 1SFL647001R7011 AF1250-30-11 6/41
1SBL387001R4100 AF65-30-00-41 6/30 1SFL427101R1311 AF116-40-11-13 6/52 1SFL647001R7111 AF1250-30-11 6/41
1SBL397001R1100 AF80-30-00-11 6/30 1SFL427101R1411 AF116-40-11-14 6/52 1SFL657001R7011 AF1350-30-11 6/41
1SBL397001R1200 AF80-30-00-12 6/30 1SFL427102R1111 AF116-40-11B-11 6/52 1SFL667001R7011 AF2650-30-11 6/41
1SBL397001R1300 AF80-30-00-13 6/30 1SFL427102R1211 AF116-40-11B-12 6/52 1SFL677001R7011 AF1650-30-11 6/41
1SBL397001R1400 AF80-30-00-14 6/30 1SFL427102R1311 AF116-40-11B-13 6/52 1SFL707001R7011 AF2050-30-11 6/41
1SBL397001R4100 AF80-30-00-41 6/30 1SFL427102R1411 AF116-40-11B-14 6/52 1SFN010720R1011 CAL18-11 6/43
1SBL397201R1100 AF80-40-00-11 6/48 1SFL447001R1111 AF140-30-11-11 6/34 1SFN010720R3311 CAL18-11B 6/43
1SBL397201R1200 AF80-40-00-12 6/48 1SFL447001R1211 AF140-30-11-12 6/34 1SFN010820R1011 CAL19-11 6/39
1SBL397201R1300 AF80-40-00-13 6/48 1SFL447001R1311 AF140-30-11-13 6/34 1SFN010820R3311 CAL19-11B 6/39
1SBL397201R1400 AF80-40-00-14 6/48 1SFL447001R1411 AF140-30-11-14 6/34 1SFN030300R1000 VM19 6/39
Index
10/2 | ABB
Index
Order code classification
Order code Type Page Order code Type Page Order code Type Page
1SFN035700R1000 VM750H 6/43 GJL1201330R0004 CAF6-11N 3/17 GJL1311501R8004 B7-22-00-84 3/10
1SFN036503R1000 VM1650H 6/43 GJL1201330R0005 CAF6-20K 3/18 GJL1311901R0011 VB7-30-01-01 3/6
1SFN074207R1000 LW140 6/39 GJL1201330R0006 CAF6-20E 3/17 GJL1311901R0012 VB7-30-01-02 3/6
1SFN074210R1000 LX140 6/39 GJL1201330R0007 CAF6-20M 3/17 GJL1311901R0013 VB7-30-01-03 3/6
1SFN074807R1000 LW205 6/39 GJL1201330R0008 CAF6-20N 3/17 GJL1311901R0101 VB7-30-10-01 3/6
1SFN074807R2000 LW205-40 6/55 GJL1201330R0009 CAF6-02K 3/18 GJL1311901R0102 VB7-30-10-02 3/6
1SFN074810R1000 LX205 6/39 GJL1201330R0010 CAF6-02E 3/17 GJL1311901R0103 VB7-30-10-03 3/6
1SFN075407R1000 LW370 6/39 GJL1201330R0011 CAF6-02M 3/17 GJL1311901R8010 VB7-30-01-80 3/6
1SFN075407R2000 LW370-40 6/55 GJL1201330R0012 CAF6-02N 3/17 GJL1311901R8014 VB7-30-01-84 3/6
1SFN075410R1000 LX370 6/39 GJL1201906R0001 LT6-B 3/17 GJL1311901R8015 VB7-30-01-85 3/6
1SFN075707R1000 LW460 6/43 GJL1201907R0001 LP6 3/17 GJL1311901R8100 VB7-30-10-80 3/6
1SFN075710R1000 LX460 6/43 GJL1201908R0001 BSM6-30 3/17 GJL1311901R8104 VB7-30-10-84 3/6
1SFN076107R1000 LW750 6/43 GJL1211001R0011 B6-30-01-01 3/4 GJL1311901R8105 VB7-30-10-85 3/6
1SFN076110R1000 LX750 6/43 GJL1211001R0012 B6-30-01-02 3/4 GJL1313001R0011 BC7-30-01-01 3/5
1SFN076407R1000 LW1250 6/43 GJL1211001R0013 B6-30-01-03 3/4 GJL1313001R0013 BC7-30-01-03 3/5
1SFN124203R1000 LT140-30L 6/39 GJL1211001R0101 B6-30-10-01 3/4 GJL1313001R0014 BC7-30-01-04 3/5
1SFN124203R2000 LT140-40L 6/55 GJL1211001R0102 B6-30-10-02 3/4 GJL1313001R0015 BC7-30-01-05 3/5
1SFN124801R1000 LT205-30C 6/39 GJL1211001R0103 B6-30-10-03 3/4 GJL1313001R0017 BC7-30-01-07 3/5
1SFN124801R2000 LT205-40C 6/55 GJL1211001R8010 B6-30-01-80 3/4 GJL1313001R0101 BC7-30-10-01 3/5
1SFN124803R1000 LT205-30L 6/39 GJL1211001R8014 B6-30-01-84 3/4 GJL1313001R0104 BC7-30-10-04 3/5
1SFN124803R2000 LT205-40L 6/55 GJL1211001R8015 B6-30-01-85 3/4 GJL1313001R0105 BC7-30-10-05 3/5
1SFN124804R1000 LT205-30Y 6/39 GJL1211001R8100 B6-30-10-80 3/4 GJL1313001R0107 BC7-30-10-07 3/5
1SFN125401R1000 LT370-30C 6/39 GJL1211001R8104 B6-30-10-84 3/4 GJL1313001R1016 BC7-30-01-16 3/5
1SFN125401R2000 LT370-40C 6/55 GJL1211001R8105 B6-30-10-85 3/4 GJL1313001R1103 BC7-30-10-03 3/5
1SFN125403R1000 LT370-30L 6/39 GJL1211201R0001 B6-40-00-01 3/10 GJL1313001R1106 BC7-30-10-16 3/5
1SFN125403R2000 LT370-40L 6/55 GJL1211201R0002 B6-40-00-02 3/10 GJL1313001R5011 BC7-30-01-2.4-51 3/8
1SFN125404R1000 LT370-30Y 6/39 GJL1211201R0003 B6-40-00-03 3/10 GJL1313001R5101 BC7-30-10-2.4-51 3/8
1SFN125406R1000 LT370-30D 6/39 GJL1211201R8000 B6-40-00-80 3/10 GJL1313001R7011 B7S-30-01-1.7-71 3/8
1SFN125701R1000 LT460-AC 6/43 GJL1211201R8004 B6-40-00-84 3/10 GJL1313001R7012 B7S-30-01-2.8-72 3/8
1SFN125703R1000 LT460-AL 6/43 GJL1211501R0001 B6-22-00-01 3/10 GJL1313001R7101 B7S-30-10-1.7-71 3/8
1SFN126101R1000 LT750-AC 6/43 GJL1211501R0002 B6-22-00-02 3/10 GJL1313001R7102 B7S-30-10-2.8-72 3/8
1SFN126103R1000 LT750-AL 6/43 GJL1211501R0003 B6-22-00-03 3/10 GJL1313001R8011 BC7-30-01-1.4-81 3/8
GHV2501902R0002 RV-BC6/60 3/17 GJL1211501R8000 B6-22-00-80 3/10 GJL1313001R8101 BC7-30-10-1.4-81 3/8
GHV2501902R0003 RV-BC6-F/60 3/17 GJL1211501R8004 B6-22-00-84 3/10 GJL1313061R5011 TBC7-30-01-51 3/9
GHV2501903R0002 RV-BC6/250 3/17 GJL1211901R0011 VB6-30-01-01 3/6 GJL1313061R5015 TBC7-30-01-55 3/9
GHV2501903R0003 RV-BC6-F/250 3/17 GJL1211901R0012 VB6-30-01-02 3/6 GJL1313061R5101 TBC7-30-10-51 3/9
GHV2501904R0002 RV-BC6/380 3/17 GJL1211901R0013 VB6-30-01-03 3/6 GJL1313061R5105 TBC7-30-10-55 3/9
GHV2501904R0003 RV-BC6-F/380 3/17 GJL1211901R0101 VB6-30-10-01 3/6 GJL1313061R6012 TBC7-30-01-62 3/9
GJF1101903R0001 SA1 2/14 GJL1211901R0102 VB6-30-10-02 3/6 GJL1313061R6018 TBC7-30-01-68 3/9
GJF1101903R0002 SA2 2/14 GJL1211901R0103 VB6-30-10-03 3/6 GJL1313061R6102 TBC7-30-10-62 3/9
GJF1101903R0003 SA3 2/14 GJL1211901R8010 VB6-30-01-80 3/6 GJL1313061R6108 TBC7-30-10-68 3/9
GJH1211001R0221 K6-22Z-01 3/13 GJL1211901R8014 VB6-30-01-84 3/6 GJL1313461R5005 TBC7-31-00-55 3/12
GJH1211001R0222 K6-22Z-02 3/13 GJL1211901R8015 VB6-30-01-85 3/6 GJL1313461R6002 TBC7-31-00-62 3/12
GJH1211001R0223 K6-22Z-03 3/13 GJL1211901R8100 VB6-30-10-80 3/6 GJL1313461R6008 TBC7-31-00-68 3/12
GJH1211001R0311 K6-31Z-01 3/13 GJL1211901R8104 VB6-30-10-84 3/6 GJL1313561R5005 TBC7-22-00-55 3/12
GJH1211001R0312 K6-31Z-02 3/13 GJL1211901R8105 VB6-30-10-85 3/6 GJL1313561R6002 TBC7-22-00-62 3/12
GJH1211001R0313 K6-31Z-03 3/13 GJL1213001R0011 BC6-30-01-01 3/5 GJL1313561R6008 TBC7-22-00-68 3/12
GJH1211001R0401 K6-40E-01 3/13 GJL1213001R0013 BC6-30-01-03 3/5 GJL1313901R0011 VBC7-30-01-01 3/7
GJH1211001R0402 K6-40E-02 3/13 GJL1213001R0014 BC6-30-01-04 3/5 GJL1313901R0013 VBC7-30-01-03 3/7
GJH1211001R0403 K6-40E-03 3/13 GJL1213001R0015 BC6-30-01-05 3/5 GJL1313901R0014 VBC7-30-01-04 3/7
GJH1211001R8220 K6-22Z-80 3/13 GJL1213001R0017 BC6-30-01-07 3/5 GJL1313901R0015 VBC7-30-01-05 3/7
GJH1211001R8224 K6-22Z-84 3/13 GJL1213001R0101 BC6-30-10-01 3/5 GJL1313901R0017 VBC7-30-01-07 3/7
GJH1211001R8225 K6-22Z-85 3/13 GJL1213001R0103 BC6-30-10-03 3/5 GJL1313901R0101 VBC7-30-10-01 3/7
GJH1211001R8310 K6-31Z-80 3/13 GJL1213001R0104 BC6-30-10-04 3/5 GJL1313901R0103 VBC7-30-10-03 3/7
GJH1211001R8314 K6-31Z-84 3/13 GJL1213001R0105 BC6-30-10-05 3/5 GJL1313901R0104 VBC7-30-10-04 3/7
GJH1211001R8315 K6-31Z-85 3/13 GJL1213001R0107 BC6-30-10-07 3/5 GJL1313901R0105 VBC7-30-10-05 3/7
GJH1211001R8400 K6-40E-80 3/13 GJL1213001R1016 BC6-30-01-16 3/5 GJL1313901R0107 VBC7-30-10-07 3/7
GJH1211001R8404
GJH1211001R8405
K6-40E-84
K6-40E-85
3/13
3/13
GJL1213001R1106
GJL1213001R5011
BC6-30-10-16
BC6-30-01-2.4-51
3/5
3/8
GJL1313901R1016
GJL1313901R1106
VBC7-30-01-16
VBC7-30-10-16
3/7
3/7 10
GJH1213001R0221 KC6-22Z-01 3/14 GJL1213001R5101 BC6-30-10-2.4-51 3/8 GJL1317001R0011 B7D-30-01-01 3/5
GJH1213001R0223 KC6-22Z-03 3/14 GJL1213001R7011 B6S-30-01-1.7-71 3/8 GJL1317001R0015 B7D-30-01-05 3/5
GJH1213001R0224 KC6-22Z-04 3/14 GJL1213001R7012 B6S-30-01-2.8-72 3/8 GJL1317001R0101 B7D-30-10-01 3/5
GJH1213001R0225 KC6-22Z-05 3/14 GJL1213001R7101 B6S-30-10-1.7-71 3/8 GJL1317001R0105 B7D-30-10-05 3/5
GJH1213001R0227 KC6-22Z-07 3/14 GJL1213001R7102 B6S-30-10-2.8-72 3/8 GJL1317201R0001 B7D-40-00-01 3/11
GJH1213001R0311 KC6-31Z-01 3/14 GJL1213001R8011 BC6-30-01-1.4-81 3/8 GJL1317201R0005 B7D-40-00-05 3/11
GJH1213001R0313 KC6-31Z-03 3/14 GJL1213001R8101 BC6-30-10-1.4-81 3/8
GJH1213001R0314 KC6-31Z-04 3/14 GJL1213501R0001 BC6-22-00-01 3/11
GJH1213001R0315 KC6-31Z-05 3/14 GJL1213501R0002 BC6-22-00-02 3/11
GJH1213001R0317 KC6-31Z-07 3/14 GJL1213501R0003 BC6-22-00-03 3/11
GJH1213001R0401 KC6-40E-01 3/14 GJL1213501R0004 BC6-22-00-04 3/11
GJH1213001R0403 KC6-40E-03 3/14 GJL1213501R0005 BC6-22-00-05 3/11
GJH1213001R0404 KC6-40E-04 3/14 GJL1213501R0007 BC6-22-00-07 3/11
GJH1213001R0405 KC6-40E-05 3/14 GJL1213501R1006 BC6-22-00-16 3/11
GJH1213001R0407 KC6-40E-07 3/14 GJL1213901R0011 VBC6-30-01-01 3/7
GJH1213001R1226 KC6-22Z-16 3/14 GJL1213901R0013 VBC6-30-01-03 3/7
GJH1213001R1316 KC6-31Z-16 3/14 GJL1213901R0014 VBC6-30-01-04 3/7
GJH1213001R1406 KC6-40E-16 3/14 GJL1213901R0015 VBC6-30-01-05 3/7
GJH1213001R5311 KC6-31Z-2.4-51 3/15 GJL1213901R0017 VBC6-30-01-07 3/7
GJH1213001R5401 KC6-40E-2.4-51 3/15 GJL1213901R0101 VBC6-30-10-01 3/7
GJH1213001R7221 K6S-22Z-1.7-71 3/15 GJL1213901R0103 VBC6-30-10-03 3/7
GJH1213001R7222 K6S-22Z-2.8-72 3/15 GJL1213901R0104 VBC6-30-10-04 3/7
GJH1213001R7311 K6S-31Z-1.7-71 3/15 GJL1213901R0105 VBC6-30-10-05 3/7
GJH1213001R7312 K6S-31Z-2.8-72 3/15 GJL1213901R0107 VBC6-30-10-07 3/7
GJH1213001R7401 K6S-40E-1.7-71 3/15 GJL1213901R1016 VBC6-30-01-16 3/7
GJH1213001R7402 K6S-40E-2.8-72 3/15 GJL1213901R1106 VBC6-30-10-16 3/7
GJH1213001R8311 KC6-31Z-1.4-81 3/15 GJL1311001R0011 B7-30-01-01 3/4
GJH1213001R8401 KC6-40E-1.4-81 3/15 GJL1311001R0012 B7-30-01-02 3/4
GJH1213061R5221 TKC6-22Z-51 3/16 GJL1311001R0013 B7-30-01-03 3/4
GJH1213061R5225 TKC6-22Z-55 3/16 GJL1311001R0101 B7-30-10-01 3/4
GJH1213061R5311 TKC6-31Z-51 3/16 GJL1311001R0102 B7-30-10-02 3/4
GJH1213061R5315 TKC6-31Z-55 3/16 GJL1311001R0103 B7-30-10-03 3/4
GJH1213061R5401 TKC6-40E-51 3/16 GJL1311001R8010 B7-30-01-80 3/4
GJH1213061R5405 TKC6-40E-55 3/16 GJL1311001R8014 B7-30-01-84 3/4
GJH1213061R6222 TKC6-22Z-62 3/16 GJL1311001R8015 B7-30-01-85 3/4
GJH1213061R6228 TKC6-22Z-68 3/16 GJL1311001R8100 B7-30-10-80 3/4
GJH1213061R6312 TKC6-31Z-62 3/16 GJL1311001R8104 B7-30-10-84 3/4
GJH1213061R6318 TKC6-31Z-68 3/16 GJL1311001R8105 B7-30-10-85 3/4
GJH1213061R6402 TKC6-40E-62 3/16 GJL1311201R0001 B7-40-00-01 3/10
GJH1213061R6408 TKC6-40E-68 3/16 GJL1311201R0002 B7-40-00-02 3/10
GJL1201317R0001 CA6-11K 3/18 GJL1311201R0003 B7-40-00-03 3/10
GJL1201317R0002 CA6-11E 3/17 GJL1311201R8000 B7-40-00-80 3/10
GJL1201317R0003 CA6-11M 3/17 GJL1311201R8004 B7-40-00-84 3/10
GJL1201317R0004 CA6-11N 3/17 GJL1311501R0001 B7-22-00-01 3/10
GJL1201330R0001 CAF6-11K 3/18 GJL1311501R0002 B7-22-00-02 3/10
Index
ABB | 10/3
Index
Type classification
Type Order code Page Type Order code Page Type Order code Page
AA1-110 1SAM201910R1002 2/12 AF146-30-11-13 1SFL467001R1311 6/34 AF305-30-11-33 1SFL587002R3311 6/37
AA1-230 1SAM201910R1003 2/12 AF146-30-11-14 1SFL467001R1411 6/34 AF305-30-11-34 1SFL587002R3411 6/37
AA1-24 1SAM201910R1001 2/12 AF146-30-11-33 1SFL467001R3311 6/35 AF305-40-11-11 1SFL587102R1111 6/53
AA1-400 1SAM201910R1004 2/12 AF146-30-11-34 1SFL467001R3411 6/35 AF305-40-11-12 1SFL587102R1211 6/53
AA-230 1SAM101909R0002 2/24 AF146-30-11B-11 1SFL467002R1111 6/34 AF305-40-11-13 1SFL587102R1311 6/53
AA-24 1SAM101909R0001 2/24 AF146-30-11B-12 1SFL467002R1211 6/34 AF305-40-11-14 1SFL587102R1411 6/53
AA-400 1SAM101909R0003 2/24 AF146-30-11B-13 1SFL467002R1311 6/34 AF30Z-30-00-20 1SBL276001R2000 6/29
AA4-110 1SAM401907R1002 2/19 AF146-30-11B-14 1SFL467002R1411 6/34 AF30Z-30-00-21 1SBL276001R2100 6/29
AA4-230 1SAM401907R1003 2/19 AF146-30-11B-33 1SFL467002R3311 6/35 AF30Z-30-00-22 1SBL276001R2200 6/29
AA4-24 1SAM401907R1001 2/19 AF16-22-00-12 1SBL177501R1200 6/46 AF30Z-30-00-23 1SBL276001R2300 6/29
AA4-400 1SAM401907R1004 2/19 AF16-22-00-13 1SBL177501R1300 6/46 AF370-30-11-11 1SFL607002R1111 6/36
AF09-22-00-12 1SBL137501R1200 6/46 AF16-22-00-14 1SBL177501R1400 6/46 AF370-30-11-12 1SFL607002R1211 6/36
AF09-22-00-13 1SBL137501R1300 6/46 AF16-22-00-41 1SBL177501R4100 6/46 AF370-30-11-13 1SFL607002R1311 6/36
AF09-22-00-14 1SBL137501R1400 6/46 AF16-30-01-12 1SBL177001R1201 6/28 AF370-30-11-14 1SFL607002R1411 6/36
AF09-22-00-41 1SBL137501R4100 6/46 AF16-30-01-13 1SBL177001R1301 6/28 AF370-30-11-33 1SFL607002R3311 6/37
AF09-30-01-12 1SBL137001R1201 6/28 AF16-30-01-14 1SBL177001R1401 6/28 AF370-30-11-34 1SFL607002R3411 6/37
AF09-30-01-13 1SBL137001R1301 6/28 AF16-30-01-41 1SBL177001R4101 6/28 AF370-40-11-11 1SFL607102R1111 6/53
AF09-30-01-14 1SBL137001R1401 6/28 AF16-30-10-12 1SBL177001R1210 6/28 AF370-40-11-12 1SFL607102R1211 6/53
AF09-30-01-41 1SBL137001R4101 6/28 AF16-30-10-13 1SBL177001R1310 6/28 AF370-40-11-13 1SFL607102R1311 6/53
AF09-30-10-12 1SBL137001R1210 6/28 AF16-30-10-14 1SBL177001R1410 6/28 AF370-40-11-14 1SFL607102R1411 6/53
AF09-30-10-13 1SBL137001R1310 6/28 AF16-30-10-41 1SBL177001R4110 6/28 AF38-22-00-12 1SBL297501R1200 6/46
AF09-30-10-14 1SBL137001R1410 6/28 AF16-40-00-12 1SBL177201R1200 6/46 AF38-22-00-13 1SBL297501R1300 6/46
AF09-30-10-41 1SBL137001R4110 6/28 AF16-40-00-13 1SBL177201R1300 6/46 AF38-22-00-14 1SBL297501R1400 6/46
AF09-40-00-12 1SBL137201R1200 6/46 AF16-40-00-14 1SBL177201R1400 6/46 AF38-22-00-41 1SBL297501R4100 6/46
AF09-40-00-13 1SBL137201R1300 6/46 AF16-40-00-41 1SBL177201R4100 6/46 AF38-30-00-12 1SBL297001R1200 6/28
AF09-40-00-14 1SBL137201R1400 6/46 AF1650-30-11 1SFL677001R7011 6/41 AF38-30-00-13 1SBL297001R1300 6/28
AF09-40-00-41 1SBL137201R4100 6/46 AF16Z-22-00-20 1SBL176501R2000 6/47 AF38-30-00-14 1SBL297001R1400 6/28
AF09Z-22-00-20 1SBL136501R2000 6/47 AF16Z-22-00-21 1SBL176501R2100 6/47 AF38-30-00-41 1SBL297001R4100 6/28
AF09Z-22-00-21 1SBL136501R2100 6/47 AF16Z-22-00-22 1SBL176501R2200 6/47 AF38-40-00-12 1SBL297201R1200 6/46
AF09Z-22-00-22 1SBL136501R2200 6/47 AF16Z-22-00-23 1SBL176501R2300 6/47 AF38-40-00-13 1SBL297201R1300 6/46
AF09Z-22-00-23 1SBL136501R2300 6/47 AF16Z-30-01-20 1SBL176001R2001 6/29 AF38-40-00-14 1SBL297201R1400 6/46
AF09Z-30-01-20 1SBL136001R2001 6/29 AF16Z-30-01-21 1SBL176001R2101 6/29 AF38-40-00-41 1SBL297201R4100 6/46
AF09Z-30-01-21 1SBL136001R2101 6/29 AF16Z-30-01-22 1SBL176001R2201 6/29 AF38Z-22-00-20 1SBL296501R2000 6/47
AF09Z-30-01-22 1SBL136001R2201 6/29 AF16Z-30-01-23 1SBL176001R2301 6/29 AF38Z-22-00-21 1SBL296501R2100 6/47
AF09Z-30-01-23 1SBL136001R2301 6/29 AF16Z-30-10-20 1SBL176001R2010 6/29 AF38Z-22-00-22 1SBL296501R2200 6/47
AF09Z-30-10-20 1SBL136001R2010 6/29 AF16Z-30-10-21 1SBL176001R2110 6/29 AF38Z-22-00-23 1SBL296501R2300 6/47
AF09Z-30-10-21 1SBL136001R2110 6/29 AF16Z-30-10-22 1SBL176001R2210 6/29 AF38Z-30-00-20 1SBL296001R2000 6/29
AF09Z-30-10-22 1SBL136001R2210 6/29 AF16Z-30-10-23 1SBL176001R2310 6/29 AF38Z-30-00-21 1SBL296001R2100 6/29
AF09Z-30-10-23 1SBL136001R2310 6/29 AF16Z-40-00-20 1SBL176201R2000 6/47 AF38Z-30-00-22 1SBL296001R2200 6/29
AF09Z-40-00-20 1SBL136201R2000 6/47 AF16Z-40-00-21 1SBL176201R2100 6/47 AF38Z-30-00-23 1SBL296001R2300 6/29
AF09Z-40-00-21 1SBL136201R2100 6/47 AF16Z-40-00-22 1SBL176201R2200 6/47 AF38Z-40-00-20 1SBL296201R2000 6/47
AF09Z-40-00-22 1SBL136201R2200 6/47 AF16Z-40-00-23 1SBL176201R2300 6/47 AF38Z-40-00-21 1SBL296201R2100 6/47
AF09Z-40-00-23 1SBL136201R2300 6/47 AF190-30-11-11 1SFL487002R1111 6/36 AF38Z-40-00-22 1SBL296201R2200 6/47
AF116-30-11-11 1SFL427001R1111 6/34 AF190-30-11-12 1SFL487002R1211 6/36 AF38Z-40-00-23 1SBL296201R2300 6/47
AF116-30-11-12 1SFL427001R1211 6/34 AF190-30-11-13 1SFL487002R1311 6/36 AF400-30-11 1SFL577001R6811 6/40
AF116-30-11-13 1SFL427001R1311 6/34 AF190-30-11-14 1SFL487002R1411 6/36 1SFL577001R6911 6/40
AF116-30-11-14 1SFL427001R1411 6/34 AF190-30-11-33 1SFL487002R3311 6/37 1SFL577001R7011 6/40
AF116-30-11-33 1SFL427001R3311 6/35 AF190-30-11-34 1SFL487002R3411 6/37 1SFL577001R7111 6/40
AF116-30-11-34 1SFL427001R3411 6/35 AF190-40-11-11 1SFL487102R1111 6/53 AF40-22-00-11 1SBL347501R1100 6/48
AF116-30-11B-11 1SFL427002R1111 6/34 AF190-40-11-12 1SFL487102R1211 6/53 AF40-22-00-12 1SBL347501R1200 6/48
AF116-30-11B-12 1SFL427002R1211 6/34 AF190-40-11-13 1SFL487102R1311 6/53 AF40-22-00-13 1SBL347501R1300 6/48
AF116-30-11B-13 1SFL427002R1311 6/34 AF190-40-11-14 1SFL487102R1411 6/53 AF40-22-00-14 1SBL347501R1400 6/48
AF116-30-11B-14 1SFL427002R1411 6/34 AF2050-30-11 1SFL707001R7011 6/41 AF40-22-00-41 1SBL347501R4100 6/48
AF116-30-11B-33 1SFL427002R3311 6/35 AF205-30-11-11 1SFL527002R1111 6/36 AF40-30-00-11 1SBL347001R1100 6/30
AF116-30-11B-34 1SFL427002R3411 6/35 AF205-30-11-12 1SFL527002R1211 6/36 AF40-30-00-12 1SBL347001R1200 6/30
AF116-40-11-11 1SFL427101R1111 6/52 AF205-30-11-13 1SFL527002R1311 6/36 AF40-30-00-13 1SBL347001R1300 6/30
AF116-40-11-12 1SFL427101R1211 6/52 AF205-30-11-14 1SFL527002R1411 6/36 AF40-30-00-14 1SBL347001R1400 6/30
10 AF116-40-11-13
AF116-40-11-14
1SFL427101R1311
1SFL427101R1411
6/52
6/52
AF205-30-11-33
AF205-30-11-34
1SFL527002R3311
1SFL527002R3411
6/37
6/37
AF40-30-00-41
AF40-40-00-11
1SBL347001R4100
1SBL347201R1100
6/30
6/48
AF116-40-11B-11 1SFL427102R1111 6/52 AF205-40-11-11 1SFL527102R1111 6/53 AF40-40-00-12 1SBL347201R1200 6/48
AF116-40-11B-12 1SFL427102R1211 6/52 AF205-40-11-12 1SFL527102R1211 6/53 AF40-40-00-13 1SBL347201R1300 6/48
AF116-40-11B-13 1SFL427102R1311 6/52 AF205-40-11-13 1SFL527102R1311 6/53 AF40-40-00-14 1SBL347201R1400 6/48
AF116-40-11B-14 1SFL427102R1411 6/52 AF205-40-11-14 1SFL527102R1411 6/53 AF40-40-00-41 1SBL347201R4100 6/48
AF12-30-01-12 1SBL157001R1201 6/28 AF26-22-00-12 1SBL237501R1200 6/46 AF460-30-11 1SFL597001R6811 6/40
AF12-30-01-13 1SBL157001R1301 6/28 AF26-22-00-13 1SBL237501R1300 6/46 1SFL597001R6911 6/40
AF12-30-01-14 1SBL157001R1401 6/28 AF26-22-00-14 1SBL237501R1400 6/46 1SFL597001R7011 6/40
AF12-30-01-41 1SBL157001R4101 6/28 AF26-22-00-41 1SBL237501R4100 6/46 1SFL597001R7111 6/40
AF12-30-10-12 1SBL157001R1210 6/28 AF26-30-00-12 1SBL237001R1200 6/28 AF52-30-00-11 1SBL367001R1100 6/30
AF12-30-10-13 1SBL157001R1310 6/28 AF26-30-00-13 1SBL237001R1300 6/28 AF52-30-00-12 1SBL367001R1200 6/30
AF12-30-10-14 1SBL157001R1410 6/28 AF26-30-00-14 1SBL237001R1400 6/28 AF52-30-00-13 1SBL367001R1300 6/30
AF12-30-10-41 1SBL157001R4110 6/28 AF26-30-00-41 1SBL237001R4100 6/28 AF52-30-00-14 1SBL367001R1400 6/30
AF1250-30-11 1SFL647001R6811 6/41 AF26-40-00-12 1SBL237201R1200 6/46 AF52-30-00-41 1SBL367001R4100 6/30
1SFL647001R6911 6/41 AF26-40-00-13 1SBL237201R1300 6/46 AF52-40-00-11 1SBL367201R1100 6/48
1SFL647001R7011 6/41 AF26-40-00-14 1SBL237201R1400 6/46 AF52-40-00-12 1SBL367201R1200 6/48
1SFL647001R7111 6/41 AF26-40-00-41 1SBL237201R4100 6/46 AF52-40-00-13 1SBL367201R1300 6/48
AF12Z-30-01-20 1SBL156001R2001 6/29 AF2650-30-11 1SFL667001R7011 6/41 AF52-40-00-14 1SBL367201R1400 6/48
AF12Z-30-01-21 1SBL156001R2101 6/29 AF265-30-11-11 1SFL547002R1111 6/36 AF52-40-00-41 1SBL367201R4100 6/48
AF12Z-30-01-22 1SBL156001R2201 6/29 AF265-30-11-12 1SFL547002R1211 6/36 AF580-30-11 1SFL617001R6811 6/40
AF12Z-30-01-23 1SBL156001R2301 6/29 AF265-30-11-13 1SFL547002R1311 6/36 1SFL617001R6911 6/40
AF12Z-30-10-20 1SBL156001R2010 6/29 AF265-30-11-14 1SFL547002R1411 6/36 1SFL617001R7011 6/40
AF12Z-30-10-21 1SBL156001R2110 6/29 AF265-30-11-33 1SFL547002R3311 6/37 1SFL617001R7111 6/40
AF12Z-30-10-22 1SBL156001R2210 6/29 AF265-30-11-34 1SFL547002R3411 6/37 AF65-30-00-11 1SBL387001R1100 6/30
AF12Z-30-10-23 1SBL156001R2310 6/29 AF265-40-11-11 1SFL547102R1111 6/53 AF65-30-00-12 1SBL387001R1200 6/30
AF1350-30-11 1SFL657001R7011 6/41 AF265-40-11-12 1SFL547102R1211 6/53 AF65-30-00-13 1SBL387001R1300 6/30
AF140-30-11-11 1SFL447001R1111 6/34 AF265-40-11-13 1SFL547102R1311 6/53 AF65-30-00-14 1SBL387001R1400 6/30
AF140-30-11-12 1SFL447001R1211 6/34 AF265-40-11-14 1SFL547102R1411 6/53 AF65-30-00-41 1SBL387001R4100 6/30
AF140-30-11-13 1SFL447001R1311 6/34 AF26Z-22-00-20 1SBL236501R2000 6/47 AF750-30-11 1SFL637001R6811 6/40
AF140-30-11-14 1SFL447001R1411 6/34 AF26Z-22-00-21 1SBL236501R2100 6/47 1SFL637001R6911 6/40
AF140-30-11-33 1SFL447001R3311 6/35 AF26Z-22-00-22 1SBL236501R2200 6/47 1SFL637001R7011 6/40
AF140-30-11-34 1SFL447001R3411 6/35 AF26Z-22-00-23 1SBL236501R2300 6/47 1SFL637001R7111 6/40
AF140-30-11B-11 1SFL447002R1111 6/34 AF26Z-30-00-20 1SBL236001R2000 6/29 AF80-22-00-11 1SBL397501R1100 6/48
AF140-30-11B-12 1SFL447002R1211 6/34 AF26Z-30-00-21 1SBL236001R2100 6/29 AF80-22-00-12 1SBL397501R1200 6/48
AF140-30-11B-13 1SFL447002R1311 6/34 AF26Z-30-00-22 1SBL236001R2200 6/29 AF80-22-00-13 1SBL397501R1300 6/48
AF140-30-11B-14 1SFL447002R1411 6/34 AF26Z-30-00-23 1SBL236001R2300 6/29 AF80-22-00-14 1SBL397501R1400 6/48
AF140-30-11B-33 1SFL447002R3311 6/35 AF26Z-40-00-20 1SBL236201R2000 6/47 AF80-22-00-41 1SBL397501R4100 6/48
AF140-30-11B-34 1SFL447002R3411 6/35 AF26Z-40-00-21 1SBL236201R2100 6/47 AF80-30-00-11 1SBL397001R1100 6/30
AF140-40-11-11 1SFL447101R1111 6/52 AF26Z-40-00-22 1SBL236201R2200 6/47 AF80-30-00-12 1SBL397001R1200 6/30
AF140-40-11-12 1SFL447101R1211 6/52 AF26Z-40-00-23 1SBL236201R2300 6/47 AF80-30-00-13 1SBL397001R1300 6/30
AF140-40-11-13 1SFL447101R1311 6/52 AF30-30-00-12 1SBL277001R1200 6/28 AF80-30-00-14 1SBL397001R1400 6/30
AF140-40-11-14 1SFL447101R1411 6/52 AF30-30-00-13 1SBL277001R1300 6/28 AF80-30-00-41 1SBL397001R4100 6/30
AF140-40-11B-11 1SFL447102R1111 6/52 AF30-30-00-14 1SBL277001R1400 6/28 AF80-40-00-11 1SBL397201R1100 6/48
AF140-40-11B-12 1SFL447102R1211 6/52 AF30-30-00-41 1SBL277001R4100 6/28 AF80-40-00-12 1SBL397201R1200 6/48
AF140-40-11B-13 1SFL447102R1311 6/52 AF305-30-11-11 1SFL587002R1111 6/36 AF80-40-00-13 1SBL397201R1300 6/48
AF140-40-11B-14 1SFL447102R1411 6/52 AF305-30-11-12 1SFL587002R1211 6/36 AF80-40-00-14 1SBL397201R1400 6/48
Index
10/4 | ABB
Index
Type classification
Type Order code Page Type Order code Page Type Order code Page
AF96-30-00-12 1SBL407001R1200 6/30 B7-22-00-84 GJL1311501R8004 3/10 CA6-11E GJL1201317R0002 3/17
AF96-30-00-13 1SBL407001R1300 6/30 B7-30-01-01 GJL1311001R0011 3/4 CA6-11K GJL1201317R0001 3/18
AF96-30-00-14 1SBL407001R1400 6/30 B7-30-01-02 GJL1311001R0012 3/4 CA6-11M GJL1201317R0003 3/17
AF96-30-00-41 1SBL407001R4100 6/30 B7-30-01-03 GJL1311001R0013 3/4 CA6-11N GJL1201317R0004 3/17
AS09-30-01-16 1SBL101001R1601 4/4 B7-30-01-80 GJL1311001R8010 3/4 CAF6-02E GJL1201330R0010 3/17
AS09-30-01-20 1SBL101001R2001 4/4 B7-30-01-84 GJL1311001R8014 3/4 CAF6-02K GJL1201330R0009 3/18
AS09-30-01-26 1SBL101001R2601 4/4 B7-30-01-85 GJL1311001R8015 3/4 CAF6-02M GJL1201330R0011 3/17
AS09-30-01-28 1SBL101001R2801 4/4 B7-30-10-01 GJL1311001R0101 3/4 CAF6-02N GJL1201330R0012 3/17
AS09-30-10-16 1SBL101001R1610 4/4 B7-30-10-02 GJL1311001R0102 3/4 CAF6-11E GJL1201330R0002 3/17
AS09-30-10-20 1SBL101001R2010 4/4 B7-30-10-03 GJL1311001R0103 3/4 CAF6-11K GJL1201330R0001 3/18
AS09-30-10-26 1SBL101001R2610 4/4 B7-30-10-80 GJL1311001R8100 3/4 CAF6-11M GJL1201330R0003 3/17
AS09-30-10-28 1SBL101001R2810 4/4 B7-30-10-84 GJL1311001R8104 3/4 CAF6-11N GJL1201330R0004 3/17
AS09-30-32-16 1SBL101001R1632 4/6 B7-30-10-85 GJL1311001R8105 3/4 CAF6-20E GJL1201330R0006 3/17
AS09-30-32-20 1SBL101001R2032 4/6 B7-40-00-01 GJL1311201R0001 3/10 CAF6-20K GJL1201330R0005 3/18
AS09-30-32-26 1SBL101001R2632 4/6 B7-40-00-02 GJL1311201R0002 3/10 CAF6-20M GJL1201330R0007 3/17
AS09-30-32-28 1SBL101001R2832 4/6 B7-40-00-03 GJL1311201R0003 3/10 CAF6-20N GJL1201330R0008 3/17
AS12-30-01-16 1SBL111001R1601 4/4 B7-40-00-80 GJL1311201R8000 3/10 CAL18-11 1SFN010720R1011 6/43
AS12-30-01-20 1SBL111001R2001 4/4 B7-40-00-84 GJL1311201R8004 3/10 CAL18-11B 1SFN010720R3311 6/43
AS12-30-01-26 1SBL111001R2601 4/4 B7D-30-01-01 GJL1317001R0011 3/5 CAL19-11 1SFN010820R1011 6/39
AS12-30-01-28 1SBL111001R2801 4/4 B7D-30-01-05 GJL1317001R0015 3/5 CAL19-11B 1SFN010820R3311 6/39
AS12-30-10-16 1SBL111001R1610 4/4 B7D-30-10-01 GJL1317001R0101 3/5 CAL4-11 1SBN010120R1011 6/33
AS12-30-10-20 1SBL111001R2010 4/4 B7D-30-10-05 GJL1317001R0105 3/5 CAL4-11-T 1SBN010120T1011 6/33
AS12-30-10-26 1SBL111001R2610 4/4 B7D-40-00-01 GJL1317201R0001 3/11 CAT4-11E 1SBN010151R1011 6/33
AS12-30-10-28 1SBL111001R2810 4/4 B7D-40-00-05 GJL1317201R0005 3/11 CAT4-11M 1SBN010151R1111 6/33
AS12-30-32-16 1SBL111001R1632 4/6 B7S-30-01-1.7-71 GJL1313001R7011 3/8 CAT4-11U 1SBN010151R1311 6/33
AS12-30-32-20 1SBL111001R2032 4/6 B7S-30-01-2.8-72 GJL1313001R7012 3/8 CC4-01 1SBN010111R1001 6/33
AS12-30-32-26 1SBL111001R2632 4/6 B7S-30-10-1.7-71 GJL1313001R7101 3/8 CC4-10 1SBN010111R1010 6/33
AS12-30-32-28 1SBL111001R2832 4/6 B7S-30-10-2.8-72 GJL1313001R7102 3/8 CK1-02 1SAM301901R1003 2/11
AS16-30-01-16 1SBL121001R1601 4/4 BC6-22-00-01 GJL1213501R0001 3/11 CK-11 1SAM101943R0001 2/24
AS16-30-01-20 1SBL121001R2001 4/4 BC6-22-00-02 GJL1213501R0002 3/11 CK1-11 1SAM301901R1001 2/11
AS16-30-01-26 1SBL121001R2601 4/4 BC6-22-00-03 GJL1213501R0003 3/11 CK1-20 1SAM301901R1002 2/11
AS16-30-01-28 1SBL121001R2801 4/4 BC6-22-00-04 GJL1213501R0004 3/11 DB16 1SAZ701901R0001 7/4
AS16-30-10-16 1SBL121001R1610 4/4 BC6-22-00-05 GJL1213501R0005 3/11 DB16E 1SAX101110R0001 7/10
AS16-30-10-20 1SBL121001R2010 4/4 BC6-22-00-07 GJL1213501R0007 3/11 DB19EF 1SAX101910R1001 7/11
AS16-30-10-26 1SBL121001R2610 4/4 BC6-22-00-16 GJL1213501R1006 3/11 DB200 1SAZ401110R0001 7/9
AS16-30-10-28 1SBL121001R2810 4/4 BC6-30-01-01 GJL1213001R0011 3/5 DB42 1SAZ701902R0001 7/5
AS16-30-32-16 1SBL121001R1632 4/6 BC6-30-01-03 GJL1213001R0013 3/5 DB45EF 1SAX201910R0001 7/11
AS16-30-32-20 1SBL121001R2032 4/6 BC6-30-01-04 GJL1213001R0014 3/5 DMS132-G 1SAM201912R1010 2/15
AS16-30-32-26 1SBL121001R2632 4/6 BC6-30-01-05 GJL1213001R0015 3/5 DMS132-Y 1SAM201912R1011 2/15
AS16-30-32-28 1SBL121001R2832 4/6 BC6-30-01-07 GJL1213001R0017 3/5 DMS325-G 1SAM101941R1000 2/25
ASL09-30-01-81 1SBL103001R8101 4/5 BC6-30-01-1.4-81 GJL1213001R8011 3/8 DMS325-Y 1SAM101941R1001 2/25
ASL09-30-01-83 1SBL103001R8301 4/5 BC6-30-01-16 GJL1213001R1016 3/5 DRAS09-20S 1SBK104235R2000 5/1
ASL09-30-01-86 1SBL103001R8601 4/5 BC6-30-01-2.4-51 GJL1213001R5011 3/8 DRAS09-26N 1SBK104135R2600 5/1
ASL09-30-01-88 1SBL103001R8801 4/5 BC6-30-10-01 GJL1213001R0101 3/5 DRAS09-27N 1SBK104135R2700 5/1
ASL09-30-10-81 1SBL103001R8110 4/5 BC6-30-10-03 GJL1213001R0103 3/5 DRAS09-28P 1SBK104035R2800 5/1
ASL09-30-10-83 1SBL103001R8310 4/5 BC6-30-10-04 GJL1213001R0104 3/5 DRAS09-29P 1SBK104035R2900 5/1
ASL09-30-10-86 1SBL103001R8610 4/5 BC6-30-10-05 GJL1213001R0105 3/5 DRAS12-20S 1SBK114235R2000 5/1
ASL09-30-10-88 1SBL103001R8810 4/5 BC6-30-10-07 GJL1213001R0107 3/5 DRAS12-26N 1SBK114135R2600 5/1
ASL09-30-32-81 1SBL103001R8132 4/7 BC6-30-10-1.4-81 GJL1213001R8101 3/8 DRAS12-27N 1SBK114135R2700 5/1
ASL09-30-32-83 1SBL103001R8332 4/7 BC6-30-10-16 GJL1213001R1106 3/5 DRAS12-28P 1SBK114035R2800 5/1
ASL09-30-32-86 1SBL103001R8632 4/7 BC6-30-10-2.4-51 GJL1213001R5101 3/8 DRAS12-29P 1SBK114035R2900 5/1
ASL09-30-32-88 1SBL103001R8832 4/7 BC7-30-01-01 GJL1313001R0011 3/5 DRAS16-20S 1SBK124235R2000 5/1
ASL12-30-01-81 1SBL113001R8101 4/5 BC7-30-01-03 GJL1313001R0013 3/5 DRAS16-26N 1SBK124135R2600 5/1
ASL12-30-01-83 1SBL113001R8301 4/5 BC7-30-01-04 GJL1313001R0014 3/5 DRAS16-27N 1SBK124135R2700 5/1
ASL12-30-01-86 1SBL113001R8601 4/5 BC7-30-01-05 GJL1313001R0015 3/5 DRAS16-28P 1SBK124035R2800 5/1
ASL12-30-01-88 1SBL113001R8801 4/5 BC7-30-01-07 GJL1313001R0017 3/5 DRAS16-29P 1SBK124035R2900 5/1
ASL12-30-10-81 1SBL113001R8110 4/5 BC7-30-01-1.4-81 GJL1313001R8011 3/8 DRASL09-81S 1SBK104335R8100 5/1
ASL12-30-10-83
ASL12-30-10-86
1SBL113001R8310
1SBL113001R8610
4/5
4/5
BC7-30-01-16
BC7-30-01-2.4-51
GJL1313001R1016
GJL1313001R5011
3/5
3/8
DRASL09-83S
DRASL12-81S
1SBK104335R8300
1SBK114335R8100
5/1
5/1 10
ASL12-30-10-88 1SBL113001R8810 4/5 BC7-30-10-01 GJL1313001R0101 3/5 DRASL12-83S 1SBK114335R8300 5/1
ASL12-30-32-81 1SBL113001R8132 4/7 BC7-30-10-03 GJL1313001R1103 3/5 DRASL16-81S 1SBK124335R8100 5/1
ASL12-30-32-83 1SBL113001R8332 4/7 BC7-30-10-04 GJL1313001R0104 3/5 DRASL16-83S 1SBK124335R8300 5/1
ASL12-30-32-86 1SBL113001R8632 4/7 BC7-30-10-05 GJL1313001R0105 3/5 DX495 1SAM401912R1001 2/20
ASL12-30-32-88 1SBL113001R8832 4/7 BC7-30-10-07 GJL1313001R0107 3/5 E1250DU-1250 1SFA739001R1000 7/15
ASL16-30-01-81 1SBL123001R8101 4/5 BC7-30-10-1.4-81 GJL1313001R8101 3/8 E16DU-0.32 1SAX111001R1101 7/10
ASL16-30-01-83 1SBL123001R8301 4/5 BC7-30-10-16 GJL1313001R1106 3/5 E16DU-1.0 1SAX111001R1102 7/10
ASL16-30-01-86 1SBL123001R8601 4/5 BC7-30-10-2.4-51 GJL1313001R5101 3/8 E16DU-18.9 1SAX111001R1105 7/10
ASL16-30-01-88 1SBL123001R8801 4/5 BEA16-3 1SBN081006T1000 4/9 E16DU-2.7 1SAX111001R1103 7/10
ASL16-30-10-81 1SBL123001R8110 4/5 BEA16-4 1SBN081306T1000 6/33 E16DU-6.3 1SAX111001R1104 7/10
ASL16-30-10-83 1SBL123001R8310 4/5 BEA26-4 1SBN082306T1000 6/33 EF146-150 1SAX351001R1101 7/12
ASL16-30-10-86 1SBL123001R8610 4/5 BEA38-4 1SBN082306T2000 6/33 EF19-0.32 1SAX121001R1101 7/11
ASL16-30-10-88 1SBL123001R8810 4/5 BEA7/132 1SBN080906R1002 3/17 EF19-1.0 1SAX121001R1102 7/11
ASL16-30-32-81 1SBL123001R8132 4/7 BEA7/325 1SBN080906R1001 3/17 EF19-18.9 1SAX121001R1105 7/11
ASL16-30-32-83 1SBL123001R8332 4/7 BER16-4 1SBN081311R1000 6/33 EF19-2.7 1SAX121001R1103 7/11
ASL16-30-32-86 1SBL123001R8632 4/7 BER16C-3 1SBN081012R1000 4/9 EF19-6.3 1SAX121001R1104 7/11
ASL16-30-32-88 1SBL123001R8832 4/7 BER38-4 1SBN082311R1000 6/33 EF205-210 1SAX531001R1101 7/13
B6-22-00-01 GJL1211501R0001 3/10 BER65-4 1SBN083411R1000 6/33 EF370-380 1SAX611001R1101 7/13
B6-22-00-02 GJL1211501R0002 3/10 BER96-4 1SBN083911R1000 6/33 EF45-30 1SAX221001R1101 7/11
B6-22-00-03 GJL1211501R0003 3/10 BEY16-4 1SBN081313R2000 6/33 EF45-45 1SAX221001R1102 7/11
B6-22-00-80 GJL1211501R8000 3/10 BEY16C-3 1SBN081018R2000 4/9 EF460-500 1SAX721001R1101 7/14
B6-22-00-84 GJL1211501R8004 3/10 BEY38-4 1SBN082713R2000 6/33 EF65-56 1SAX331001R1102 7/12
B6-30-01-01 GJL1211001R0011 3/4 BEY65-4 1SBN083413R2000 6/33 EF65-70 1SAX331001R1101 7/12
B6-30-01-02 GJL1211001R0012 3/4 BEY96-4 1SBN083913R2000 6/33 EF750-800 1SAX821001R1101 7/14
B6-30-01-03 GJL1211001R0013 3/4 BS1-3 1SAM201908R1001 2/14 EF96-100 1SAX341001R1101 7/12
B6-30-01-80 GJL1211001R8010 3/4 BS3-3 1SAM101938R0003 2/23 FR16AS-12VARS 1SBN101035R1000 5/1
B6-30-01-84 GJL1211001R8014 3/4 BS4-3 1SAM401911R1008 2/20 FS116 1SAM201909R1001 2/14
B6-30-01-85 GJL1211001R8015 3/4 BSM6-30 GJL1201908R0001 3/17 HK-02 1SAM101901R0003 2/24
B6-30-10-01 GJL1211001R0101 3/4 BX4 1SBN110108T1000 6/63 HK1-02 1SAM201902R1003 2/11
B6-30-10-02 GJL1211001R0102 3/4 BX4-CA 1SBN110109W1000 6/63 HK-11 1SAM101901R0001 2/24
B6-30-10-03 GJL1211001R0103 3/4 CA3-01 1SBN011010T1001 4/9 HK1-11 1SAM201902R1001 2/11
B6-30-10-80 GJL1211001R8100 3/4 CA3-10 1SBN011010T1010 4/9 HK1-20 1SAM201902R1002 2/11
B6-30-10-84 GJL1211001R8104 3/4 CA4-01 1SBN010110R1001 6/33 HK1-20L 1SAM201902R1004 2/11
B6-30-10-85 GJL1211001R8105 3/4 CA4-01-T 1SBN010110T1001 6/33 HK-20 1SAM101901R0002 2/24
B6-40-00-01 GJL1211201R0001 3/10 CA4-04E 1SBN010140R1004 6/51 HK4-11 1SAM401901R1001 2/19
B6-40-00-02 GJL1211201R0002 3/10 CA4-04N 1SBN010140R1204 6/63 HK4-W 1SAM401901R1002 2/19
B6-40-00-03 GJL1211201R0003 3/10 CA4-10 1SBN010110R1010 6/33 HKF-11 1SAM101928R0001 2/24
B6-40-00-80 GJL1211201R8000 3/10 CA4-10-T 1SBN010110T1010 6/33 HKF1-11 1SAM201901R1001 2/11
B6-40-00-84 GJL1211201R8004 3/10 CA4-13N 1SBN010140R1213 6/63 HKF1-20 1SAM201901R1002 2/11
B6S-30-01-1.7-71 GJL1213001R7011 3/8 CA4-22E 1SBN010140R1022 6/33 HKF-20 1SAM101928R0002 2/24
B6S-30-01-2.8-72 GJL1213001R7012 3/8 CA4-22M 1SBN010140R1122 6/33 HKS4-02 1SAM401902R1003 2/19
B6S-30-10-1.7-71 GJL1213001R7101 3/8 CA4-22N 1SBN010140R1222 6/63 HKS4-11 1SAM401902R1001 2/19
B6S-30-10-2.8-72 GJL1213001R7102 3/8 CA4-22U 1SBN010140R1322 6/33 HKS4-20 1SAM401902R1002 2/19
B7-22-00-01 GJL1311501R0001 3/10 CA4-31E 1SBN010140R1031 6/51 IB132-G 1SAM201911R1010 2/15
B7-22-00-02 GJL1311501R0002 3/10 CA4-31N 1SBN010140R1231 6/63 IB132-Y 1SAM201911R1011 2/15
Index
ABB | 10/5
Index
Type classification
Type Order code Page Type Order code Page Type Order code Page
K6-22Z-01 GJH1211001R0221 3/13 MO325-25 1SAM160000R1014 2/22 MS325-1-HKF11 1SAM150005R0005 2/21
K6-22Z-02 GJH1211001R0222 3/13 MO325-4 1SAM160000R1008 2/22 MS325-2.5 1SAM150000R1007 2/21
K6-22Z-03 GJH1211001R0223 3/13 MO325-6.3 1SAM160000R1009 2/22 MS325-2.5-HKF11 1SAM150005R0007 2/21
K6-22Z-80 GJH1211001R8220 3/13 MO325-9 1SAM160000R1010 2/22 MS325-20 1SAM150000R1013 2/21
K6-22Z-84 GJH1211001R8224 3/13 MO450-40 1SAM460000R1005 2/17 MS325-20-HKF11 1SAM150005R0013 2/21
K6-22Z-85 GJH1211001R8225 3/13 MO450-45 1SAM460000R1006 2/17 MS325-25 1SAM150000R1014 2/21
K6-31Z-01 GJH1211001R0311 3/13 MO450-50 1SAM460000R1007 2/17 MS325-25-HKF11 1SAM150005R0014 2/21
K6-31Z-02 GJH1211001R0312 3/13 MO495-100 1SAM560000R1010 2/17 MS325-4 1SAM150000R1008 2/21
K6-31Z-03 GJH1211001R0313 3/13 MO495-63 1SAM560000R1007 2/17 MS325-4-HKF11 1SAM150005R0008 2/21
K6-31Z-80 GJH1211001R8310 3/13 MO495-75 1SAM560000R1008 2/17 MS325-6.3 1SAM150000R1009 2/21
K6-31Z-84 GJH1211001R8314 3/13 MO495-90 1SAM560000R1009 2/17 MS325-6.3-HKF11 1SAM150005R0009 2/21
K6-31Z-85 GJH1211001R8315 3/13 MO496-100 1SAM590000R1010 2/17 MS325-9 1SAM150000R1010 2/21
K6-40E-01 GJH1211001R0401 3/13 MO496-32 1SAM590000R1004 2/17 MS325-9-HKF11 1SAM150005R0010 2/21
K6-40E-02 GJH1211001R0402 3/13 MO496-40 1SAM590000R1005 2/17 MS450-40 1SAM450000R1005 2/16
K6-40E-03 GJH1211001R0403 3/13 MO496-50 1SAM590000R1006 2/17 MS450-45 1SAM450000R1006 2/16
K6-40E-80 GJH1211001R8400 3/13 MO496-63 1SAM590000R1007 2/17 MS450-50 1SAM450000R1007 2/16
K6-40E-84 GJH1211001R8404 3/13 MO496-75 1SAM590000R1008 2/17 MS495-100 1SAM550000R1010 2/16
K6-40E-85 GJH1211001R8405 3/13 MO496-90 1SAM590000R1009 2/17 MS495-63 1SAM550000R1007 2/16
K6S-22Z-1.7-71 GJH1213001R7221 3/15 MS116-0.16 1SAM250000R1001 2/6 MS495-75 1SAM550000R1008 2/16
K6S-22Z-2.8-72 GJH1213001R7222 3/15 MS116-0.16-HKF1-11 1SAM250005R1001 2/6 MS495-90 1SAM550000R1009 2/16
K6S-31Z-1.7-71 GJH1213001R7311 3/15 MS116-0.25 1SAM250000R1002 2/6 MS497-100 1SAM580000R1010 2/16
K6S-31Z-2.8-72 GJH1213001R7312 3/15 MS116-0.25-HKF1-11 1SAM250005R1002 2/6 MS497-32 1SAM580000R1004 2/16
K6S-40E-1.7-71 GJH1213001R7401 3/15 MS116-0.4 1SAM250000R1003 2/6 MS497-40 1SAM580000R1005 2/16
K6S-40E-2.8-72 GJH1213001R7402 3/15 MS116-0.4-HKF1-11 1SAM250005R1003 2/6 MS497-50 1SAM580000R1006 2/16
KA450 1SAM401908R1001 2/20 MS116-0.63 1SAM250000R1004 2/6 MS497-63 1SAM580000R1007 2/16
KA495 1SAM501901R1001 2/20 MS116-0.63-HKF1-11 1SAM250005R1004 2/6 MS497-75 1SAM580000R1008 2/16
KA495C 1) 1SAM501902R1001 2/20 MS116-1.0 1SAM250000R1005 2/6 MS497-90 1SAM580000R1009 2/16
KC6-22Z-01 GJH1213001R0221 3/14 MS116-1.0-HKF1-11 1SAM250005R1005 2/6 MSAH1 1SAM201909R1021 2/26
KC6-22Z-03 GJH1213001R0223 3/14 MS116-1.6 1SAM250000R1006 2/6 MSH-AR 1SAM201920R1000 2/26
KC6-22Z-04 GJH1213001R0224 3/14 MS116-1.6-HKF1-11 1SAM250005R1006 2/6 MSHD-LB 1) 1SAM201920R1001 2/26
KC6-22Z-05 GJH1213001R0225 3/14 MS116-10 1SAM250000R1010 2/6 MSHD-LTB 2) 1SAM201920R1011 2/26
KC6-22Z-07 GJH1213001R0227 3/14 MS116-10.0-HKF1-11 1SAM250005R1010 2/6 MSHD-LTY 2) 1SAM201920R1012 2/26
KC6-22Z-16 GJH1213001R1226 3/14 MS116-12 1SAM250000R1012 2/6 MSHD-LY 1) 1SAM201920R1002 2/26
KC6-31Z-01 GJH1213001R0311 3/14 MS116-12.0-HKF1-11 1SAM250005R1012 2/6 MSMN 3) 1SAM101923R0002 2/26
KC6-31Z-03 GJH1213001R0313 3/14 MS116-16 1SAM250000R1011 2/6 MSMNO 4) 1SAM101923R0012 2/26
KC6-31Z-04 GJH1213001R0314 3/14 MS116-16.0-HKF1-11 1SAM250005R1011 2/6 NF22E-12 1SBH137001R1222 6/60
KC6-31Z-05 GJH1213001R0315 3/14 MS116-2.5 1SAM250000R1007 2/6 NF22E-13 1SBH137001R1322 6/60
KC6-31Z-07 GJH1213001R0317 3/14 MS116-2.5-HKF1-11 1SAM250005R1007 2/6 NF22E-14 1SBH137001R1422 6/60
KC6-31Z-1.4-81 GJH1213001R8311 3/15 MS116-20 1SAM250000R1013 2/6 NF22E-41 1SBH137001R4122 6/60
KC6-31Z-16 GJH1213001R1316 3/14 MS116-20-HKF1-11 1SAM250005R1013 2/6 NF31E-12 1SBH137001R1231 6/60
KC6-31Z-2.4-51 GJH1213001R5311 3/15 MS116-25 1SAM250000R1014 2/6 NF31E-13 1SBH137001R1331 6/60
KC6-40E-01 GJH1213001R0401 3/14 MS116-25-HKF1-11 1SAM250005R1014 2/6 NF31E-14 1SBH137001R1431 6/60
KC6-40E-03 GJH1213001R0403 3/14 MS116-32 1SAM250000R1015 2/6 NF31E-41 1SBH137001R4131 6/60
KC6-40E-04 GJH1213001R0404 3/14 MS116-32-HKF1-11 1SAM250005R1015 2/6 NF40E-12 1SBH137001R1240 6/60
KC6-40E-05 GJH1213001R0405 3/14 MS116-4.0 1SAM250000R1008 2/6 NF40E-13 1SBH137001R1340 6/60
KC6-40E-07 GJH1213001R0407 3/14 MS116-4.0-HKF1-11 1SAM250005R1008 2/6 NF40E-14 1SBH137001R1440 6/60
KC6-40E-1.4-81 GJH1213001R8401 3/15 MS116-6.3 1SAM250000R1009 2/6 NF40E-41 1SBH137001R4140 6/60
KC6-40E-16 GJH1213001R1406 3/14 MS116-6.3-HKF1-11 1SAM250005R1009 2/6 NFZ22E-20 1SBH136001R2022 6/61
KC6-40E-2.4-51 GJH1213001R5401 3/15 MS132-0.16 1SAM350000R1001 2/7 NFZ22E-21 1SBH136001R2122 6/61
KPR-101L 1SFA616162R1014 7/4 MS132-0.16-HKF1-11 1SAM350005R1001 2/7 NFZ22E-22 1SBH136001R2222 6/61
LDC4 1SBN070156T1000 6/63 MS132-0.16T 1SAM340000R1001 2/9 NFZ22E-23 1SBH136001R2322 6/61
LP6 GJL1201907R0001 3/17 MS132-0.25 1SAM350000R1002 2/7 NFZ31E-20 1SBH136001R2031 6/61
LT140-30L 1SFN124203R1000 6/39 MS132-0.25-HKF1-11 1SAM350005R1002 2/7 NFZ31E-21 1SBH136001R2131 6/61
LT140-40L 1SFN124203R2000 6/55 MS132-0.25T 1SAM340000R1002 2/9 NFZ31E-22 1SBH136001R2231 6/61
LT200/A 1SAZ401901R1001 7/9 MS132-0.4 1SAM350000R1003 2/7 NFZ31E-23 1SBH136001R2331 6/61
LT205-30C 1SFN124801R1000 6/39 MS132-0.4-HKF1-11 1SAM350005R1003 2/7 NFZ40E-20 1SBH136001R2040 6/61
LT205-30L 1SFN124803R1000 6/39 MS132-0.4T 1SAM340000R1003 2/9 NFZ40E-21 1SBH136001R2140 6/61
10 LT205-30Y
LT205-40C
1SFN124804R1000
1SFN124801R2000
6/39
6/55
MS132-0.63
MS132-0.63-HKF1-11
1SAM350000R1004
1SAM350005R1004
2/7
2/7
NFZ40E-22
NFZ40E-23
1SBH136001R2240
1SBH136001R2340
6/61
6/61
LT205-40L 1SFN124803R2000 6/55 MS132-0.63T 1SAM340000R1004 2/9 NS22E-16 1SBH101001R1622 4/10
LT370-30C 1SFN125401R1000 6/39 MS132-1.0 1SAM350000R1005 2/7 NS22E-20 1SBH101001R2022 4/10
LT370-30D 1SFN125406R1000 6/39 MS132-1.0-HKF1-11 1SAM350005R1005 2/7 NS22E-26 1SBH101001R2622 4/10
LT370-30L 1SFN125403R1000 6/39 MS132-1.0T 1SAM340000R1005 2/9 NS22E-28 1SBH101001R2822 4/10
LT370-30Y 1SFN125404R1000 6/39 MS132-1.6 1SAM350000R1006 2/7 NS31E-16 1SBH101001R1631 4/10
LT370-40C 1SFN125401R2000 6/55 MS132-1.6-HKF1-11 1SAM350005R1006 2/7 NS31E-20 1SBH101001R2031 4/10
LT370-40L 1SFN125403R2000 6/55 MS132-1.6T 1SAM340000R1006 2/9 NS31E-26 1SBH101001R2631 4/10
LT460-AC 1SFN125701R1000 6/43 MS132-10 1SAM350000R1010 2/7 NS31E-28 1SBH101001R2831 4/10
LT460-AL 1SFN125703R1000 6/43 MS132-10.0-HKF1-11 1SAM350005R1010 2/7 NS40E-16 1SBH101001R1640 4/10
LT6-B GJL1201906R0001 3/17 MS132-10T 1SAM340000R1010 2/9 NS40E-20 1SBH101001R2040 4/10
LT750-AC 1SFN126101R1000 6/43 MS132-12 1SAM350000R1012 2/7 NS40E-26 1SBH101001R2640 4/10
LT750-AL 1SFN126103R1000 6/43 MS132-12.0-HKF1-11 1SAM350005R1012 2/7 NS40E-28 1SBH101001R2840 4/10
LW1250 1SFN076407R1000 6/43 MS132-12T 1SAM340000R1012 2/9 NS44E-16 1SBH101001R1644 4/10
LW140 1SFN074207R1000 6/39 MS132-16 1SAM350000R1011 2/7 NS44E-20 1SBH101001R2044 4/10
LW205 1SFN074807R1000 6/39 MS132-16.0-HKF1-11 1SAM350005R1011 2/7 NS44E-26 1SBH101001R2644 4/10
LW205-40 1SFN074807R2000 6/55 MS132-16T 1SAM340000R1011 2/9 NS44E-28 1SBH101001R2844 4/10
LW370 1SFN075407R1000 6/39 MS132-2.5 1SAM350000R1007 2/7 NS53E-16 1SBH101001R1653 4/10
LW370-40 1SFN075407R2000 6/55 MS132-2.5-HKF1-11 1SAM350005R1007 2/7 NS53E-20 1SBH101001R2053 4/10
LW460 1SFN075707R1000 6/43 MS132-2.5T 1SAM340000R1007 2/9 NS53E-26 1SBH101001R2653 4/10
LW750 1SFN076107R1000 6/43 MS132-20 1SAM350000R1013 2/7 NS53E-28 1SBH101001R2853 4/10
LX140 1SFN074210R1000 6/39 MS132-20-HKF1-11 1SAM350005R1013 2/7 NS62E-16 1SBH101001R1662 4/10
LX205 1SFN074810R1000 6/39 MS132-20T 1SAM340000R1013 2/9 NS62E-20 1SBH101001R2062 4/10
LX370 1SFN075410R1000 6/39 MS132-25 1SAM350000R1014 2/7 NS62E-26 1SBH101001R2662 4/10
LX460 1SFN075710R1000 6/43 MS132-25-HKF1-11 1SAM350005R1014 2/7 NS62E-28 1SBH101001R2862 4/10
LX750 1SFN076110R1000 6/43 MS132-25T 1SAM340000R1014 2/9 NS71E-16 1SBH101001R1671 4/10
MO132-0.16 1SAM360000R1001 2/8 MS132-32 1SAM350000R1015 2/7 NS71E-20 1SBH101001R2071 4/10
MO132-0.25 1SAM360000R1002 2/8 MS132-32-HKF1-11 1SAM350005R1015 2/7 NS71E-26 1SBH101001R2671 4/10
MO132-0.4 1SAM360000R1003 2/8 MS132-4.0 1SAM350000R1008 2/7 NS71E-28 1SBH101001R2871 4/10
MO132-0.63 1SAM360000R1004 2/8 MS132-4.0-HKF1-11 1SAM350005R1008 2/7 NS80E-16 1SBH101001R1680 4/10
MO132-1.0 1SAM360000R1005 2/8 MS132-4.0T 1SAM340000R1008 2/9 NS80E-20 1SBH101001R2080 4/10
MO132-1.6 1SAM360000R1006 2/8 MS132-6.3 1SAM350000R1009 2/7 NS80E-26 1SBH101001R2680 4/10
MO132-10 1SAM360000R1010 2/8 MS132-6.3-HKF1-11 1SAM350005R1009 2/7 NS80E-28 1SBH101001R2880 4/10
MO132-12 1SAM360000R1012 2/8 MS132-6.3T 1SAM340000R1009 2/9 NSL22E-81 1SBH103001R8122 4/11
MO132-16 1SAM360000R1011 2/8 MS325-0.16 1SAM150000R1001 2/21 NSL22E-83 1SBH103001R8322 4/11
MO132-2.5 1SAM360000R1007 2/8 MS325-0.16-HKF11 1SAM150005R0001 2/21 NSL22E-86 1SBH103001R8622 4/11
MO132-20 1SAM360000R1013 2/8 MS325-0.25 1SAM150000R1002 2/21 NSL22E-88 1SBH103001R8822 4/11
MO132-25 1SAM360000R1014 2/8 MS325-0.25-HKF11 1SAM150005R0002 2/21 NSL31E-81 1SBH103001R8131 4/11
MO132-32 1SAM360000R1015 2/8 MS325-0.4 1SAM150000R1003 2/21 NSL31E-83 1SBH103001R8331 4/11
MO132-4.0 1SAM360000R1008 2/8 MS325-0.4-HKF11 1SAM150005R0003 2/21 NSL31E-86 1SBH103001R8631 4/11
MO132-6.3 1SAM360000R1009 2/8 MS325-0.63 1SAM150000R1004 2/21 NSL31E-88 1SBH103001R8831 4/11
MO325-0.4 1SAM160000R1003 2/22 MS325-0.63-HKF11 1SAM150005R0004 2/21 NSL40E-81 1SBH103001R8140 4/11
MO325-0.63 1SAM160000R1004 2/22 MS325-1 1SAM150000R1005 2/21 NSL40E-83 1SBH103001R8340 4/11
MO325-1 1SAM160000R1005 2/22 MS325-1.6 1SAM150000R1006 2/21 NSL40E-86 1SBH103001R8640 4/11
MO325-1.6 1SAM160000R1006 2/22 MS325-1.6-HKF11 1SAM150005R0006 2/21 NSL40E-88 1SBH103001R8840 4/11
MO325-12.5 1SAM160000R1011 2/22 MS325-12.5 1SAM150000R1011 2/21 NSL44E-81 1SBH103001R8144 4/11
Index
10/6 | ABB
Index
Type classification
Type Order code Page Type Order code Page Type Order code Page
NSL53E-81 1SBH103001R8153 4/11 T16-2.3 1SAZ711201R1031 5/1 VB6-30-01-01 GJL1211901R0011 3/6
NSL53E-83 1SBH103001R8353 4/11 T16-3.1 1SAZ711201R1033 5/1 VB6-30-01-02 GJL1211901R0012 3/6
NSL53E-86 1SBH103001R8653 4/11 T16-4.2 1SAZ711201R1035 5/1 VB6-30-01-03 GJL1211901R0013 3/6
NSL53E-88 1SBH103001R8853 4/11 T16-5.7 1SAZ711201R1038 5/1 VB6-30-01-80 GJL1211901R8010 3/6
NSL62E-81 1SBH103001R8162 4/11 T16-7.6 1SAZ711201R1040 5/1 VB6-30-01-84 GJL1211901R8014 3/6
NSL62E-83 1SBH103001R8362 4/11 TA200DU-110 1SAZ421201R1002 7/9 VB6-30-01-85 GJL1211901R8015 3/6
NSL62E-86 1SBH103001R8662 4/11 TA200DU-135 1SAZ421201R1003 7/9 VB6-30-10-01 GJL1211901R0101 3/6
NSL62E-88 1SBH103001R8862 4/11 TA200DU-150 1SAZ421201R1004 7/9 VB6-30-10-02 GJL1211901R0102 3/6
NSL71E-81 1SBH103001R8171 4/11 TA200DU-175 1SAZ421201R1005 7/9 VB6-30-10-03 GJL1211901R0103 3/6
NSL71E-83 1SBH103001R8371 4/11 TA200DU-200 1SAZ421201R1006 7/9 VB6-30-10-80 GJL1211901R8100 3/6
NSL71E-86 1SBH103001R8671 4/11 TA200DU-90 1SAZ421201R1001 7/9 VB6-30-10-84 GJL1211901R8104 3/6
NSL71E-88 1SBH103001R8871 4/11 TB450 1SAM401910R1001 2/20 VB6-30-10-85 GJL1211901R8105 3/6
NSL80E-81 1SBH103001R8180 4/11 TBC7-22-00-55 GJL1313561R5005 3/12 VB7-30-01-01 GJL1311901R0011 3/6
NSL80E-83 1SBH103001R8380 4/11 TBC7-22-00-62 GJL1313561R6002 3/12 VB7-30-01-02 GJL1311901R0012 3/6
NSL80E-86 1SBH103001R8680 4/11 TBC7-22-00-68 GJL1313561R6008 3/12 VB7-30-01-03 GJL1311901R0013 3/6
NSL80E-88 1SBH103001R8880 4/11 TBC7-30-01-51 GJL1313061R5011 3/9 VB7-30-01-80 GJL1311901R8010 3/6
OXS6X105 1SCA108043R1001 2/26 TBC7-30-01-55 GJL1313061R5015 3/9 VB7-30-01-84 GJL1311901R8014 3/6
OXS6X130 1SCA101655R1001 2/26 TBC7-30-01-62 GJL1313061R6012 3/9 VB7-30-01-85 GJL1311901R8015 3/6
OXS6X180 1SCA101659R1001 2/26 TBC7-30-01-68 GJL1313061R6018 3/9 VB7-30-10-01 GJL1311901R0101 3/6
OXS6X85 1SCA101647R1001 2/26 TBC7-30-10-51 GJL1313061R5101 3/9 VB7-30-10-02 GJL1311901R0102 3/6
PB1-1-32 1SAM201914R1001 2/14 TBC7-30-10-55 GJL1313061R5105 3/9 VB7-30-10-03 GJL1311901R0103 3/6
PS1-2-0-65 1SAM201906R1102 2/14 TBC7-30-10-62 GJL1313061R6102 3/9 VB7-30-10-80 GJL1311901R8100 3/6
PS1-2-1-65 1SAM201906R1112 2/14 TBC7-30-10-68 GJL1313061R6108 3/9 VB7-30-10-84 GJL1311901R8104 3/6
PS1-2-2-65 1SAM201906R1122 2/14 TBC7-31-00-55 GJL1313461R5005 3/12 VB7-30-10-85 GJL1311901R8105 3/6
PS1-3-0-100 1SAM201916R1103 2/14 TBC7-31-00-62 GJL1313461R6002 3/12 VBC6-30-01-01 GJL1213901R0011 3/7
PS1-3-0-65 1SAM201906R1103 2/14 TBC7-31-00-68 GJL1313461R6008 3/12 VBC6-30-01-03 GJL1213901R0013 3/7
PS1-3-1-100 1SAM201916R1113 2/14 TEF3-OFF 1SBN021014R1000 4/9 VBC6-30-01-04 GJL1213901R0014 3/7
PS1-3-1-65 1SAM201906R1113 2/14 TEF3-ON 1SBN021012R1000 4/9 VBC6-30-01-05 GJL1213901R0015 3/7
PS1-3-2-100 1SAM201916R1123 2/14 TEF4-OFF 1SBN020114R1000 6/33 VBC6-30-01-07 GJL1213901R0017 3/7
PS1-3-2-65 1SAM201906R1123 2/14 TEF4-ON 1SBN020112R1000 6/33 VBC6-30-01-16 GJL1213901R1016 3/7
PS1-4-0-100 1SAM201916R1104 2/14 TF140DU-110 1SAZ431201R1002 7/8 VBC6-30-10-01 GJL1213901R0101 3/7
PS1-4-0-65 1SAM201906R1104 2/14 TF140DU-135 1SAZ431201R1003 7/8 VBC6-30-10-03 GJL1213901R0103 3/7
PS1-4-1-100 1SAM201916R1114 2/14 TF140DU-142 1SAZ431201R1004 7/8 VBC6-30-10-04 GJL1213901R0104 3/7
PS1-4-1-65 1SAM201906R1114 2/14 TF140DU-90 1SAZ431201R1001 7/8 VBC6-30-10-05 GJL1213901R0105 3/7
PS1-4-2-65 1SAM201906R1124 2/14 TF42-0.13 1SAZ721201R1005 7/5 VBC6-30-10-07 GJL1213901R0107 3/7
PS1-5-0-100 1SAM201916R1105 2/14 TF42-0.17 1SAZ721201R1008 7/5 VBC6-30-10-16 GJL1213901R1106 3/7
PS1-5-0-65 1SAM201906R1105 2/14 TF42-0.23 1SAZ721201R1009 7/5 VBC7-30-01-01 GJL1313901R0011 3/7
PS1-5-1-100 1SAM201916R1115 2/14 TF42-0.31 1SAZ721201R1013 7/5 VBC7-30-01-03 GJL1313901R0013 3/7
PS1-5-1-65 1SAM201906R1115 2/14 TF42-0.41 1SAZ721201R1014 7/5 VBC7-30-01-04 GJL1313901R0014 3/7
PS1-5-2-65 1SAM201906R1125 2/14 TF42-0.55 1SAZ721201R1017 7/5 VBC7-30-01-05 GJL1313901R0015 3/7
PS3-2-0 1SAM101937R0012 2/23 TF42-0.74 1SAZ721201R1021 7/5 VBC7-30-01-07 GJL1313901R0017 3/7
PS3-2-1 1SAM101937R0022 2/23 TF42-1.0 1SAZ721201R1023 7/5 VBC7-30-01-16 GJL1313901R1016 3/7
PS3-2-2 1SAM101937R0032 2/23 TF42-1.3 1SAZ721201R1025 7/5 VBC7-30-10-01 GJL1313901R0101 3/7
PS3-3-0 1SAM101937R0013 2/23 TF42-1.7 1SAZ721201R1028 7/5 VBC7-30-10-03 GJL1313901R0103 3/7
PS3-3-1 1SAM101937R0023 2/23 TF42-10 1SAZ721201R1043 7/5 VBC7-30-10-04 GJL1313901R0104 3/7
PS3-4-0 1SAM101937R0014 2/23 TF42-13 1SAZ721201R1045 7/5 VBC7-30-10-05 GJL1313901R0105 3/7
PS3-4-1 1SAM101937R0024 2/23 TF42-16 1SAZ721201R1047 7/5 VBC7-30-10-07 GJL1313901R0107 3/7
PS3-4-2 1SAM101937R0034 2/23 TF42-2.3 1SAZ721201R1031 7/5 VBC7-30-10-16 GJL1313901R1106 3/7
PS3-5-0 1SAM101937R0015 2/23 TF42-20 1SAZ721201R1049 7/5 VEM4 1SBN030111R1000 6/33
PS3-5-1 1SAM101937R0025 2/23 TF42-24 1SAZ721201R1051 7/5 VM140/190 1SFN034403R1000 6/39
PS3-6-0 1SAM101937R0016 2/23 TF42-29 1SAZ721201R1052 7/5 VM1650H 1SFN036503R1000 6/43
PS4-2-0 1SAM401911R1001 2/20 TF42-3.1 1SAZ721201R1033 7/5 VM19 1SFN030300R1000 6/39
PS4-2-2 1SAM401911R1004 2/20 TF42-35 1SAZ721201R1053 7/5 VM205/265 1SFN035203R1000 6/39
PS4-3-0 1SAM401911R1002 2/20 TF42-38 1SAZ721201R1055 7/5 VM3 1SBN031005T1000 4/9
PS4-3-2 1SAM401911R1005 2/20 TF42-4.2 1SAZ721201R1035 7/5 VM4 1SBN030105T1000 6/33
PS4-4-0 1SAM401911R1003 2/20 TF42-5.7 1SAZ721201R1038 7/5 VM750H 1SFN035700R1000 6/43
PS4-4-2 1SAM401911R1006 2/20 TF42-7.6 1SAZ721201R1040 7/5 VM96-4 1SBN033405T1000 6/33
RC5-1/133
RC5-1/250
1SBN050100R1001
1SBN050100R1002
4/9
4/9
TF65-28
TF65-33
1SAZ811201R1001
1SAZ811201R1002
7/6
7/6
WRB-1000
WRB-400
1SAZ701903R1013
1SAZ701903R1011
7/16
7/16 10
RC5-1/440 1SBN050100R1003 4/9 TF65-40 1SAZ811201R1003 7/6 WRB-600 1SAZ701903R1012 7/16
RC5-1/50 1SBN050100R1000 4/9 TF65-47 1SAZ811201R1004 7/6 WRBG 1SAZ701903R1030 7/16
RT5/150 1SBN050020R1003 4/9 TF65-53 1SAZ811201R1005 7/6 WRH-F 1SAZ701903R1001 7/16
RT5/264 1SBN050020R1004 4/9 TF65-60 1SAZ811201R1006 7/6
RT5/32 1SBN050020R1000 4/9 TF65-67 1SAZ811201R1007 7/6
RT5/65 1SBN050020R1001 4/9 TF96-51 1SAZ911201R1001 7/7
RT5/90 1SBN050020R1002 4/9 TF96-60 1SAZ911201R1002 7/7
RV5/133 1SBN050010R1001 4/9 TF96-68 1SAZ911201R1003 7/7
RV5/250 1SBN050010R1002 4/9 TF96-78 1SAZ911201R1004 7/7
RV5/440 1SBN050010R1003 4/9 TF96-87 1SAZ911201R1005 7/7
RV5/50 1SBN050010R1000 4/9 TF96-96 1SAZ911201R1006 7/7
RV-BC6/250 GHV2501903R0002 3/17 TKC6-22Z-51 GJH1213061R5221 3/16
RV-BC6/380 GHV2501904R0002 3/17 TKC6-22Z-55 GJH1213061R5225 3/16
RV-BC6/60 GHV2501902R0002 3/17 TKC6-22Z-62 GJH1213061R6222 3/16
RV-BC6-F/250 GHV2501903R0003 3/17 TKC6-22Z-68 GJH1213061R6228 3/16
RV-BC6-F/380 GHV2501904R0003 3/17 TKC6-31Z-51 GJH1213061R5311 3/16
RV-BC6-F/60 GHV2501902R0003 3/17 TKC6-31Z-55 GJH1213061R5315 3/16
S1-M1-25 1SAM201907R1101 2/14 TKC6-31Z-62 GJH1213061R6312 3/16
S1-M2-25 1SAM201907R1102 2/14 TKC6-31Z-68 GJH1213061R6318 3/16
S1-M3-25 1SAM201907R1103 2/14 TKC6-40E-51 GJH1213061R5401 3/16
S1-M3-35 1SAM201913R1103 2/14 TKC6-40E-55 GJH1213061R5405 3/16
S1-PB1-25 1SAM201914R1002 2/14 TKC6-40E-62 GJH1213061R6402 3/16
S3-M1 1SAM101938R0001 2/23 TKC6-40E-68 GJH1213061R6408 3/16
S3-M2 1SAM101938R0002 2/23 UA1-110 1SAM201904R1004 2/12
S3-M3 1SAM101938R0004 2/23 UA1-20 1SAM201904R1010 2/12
S4-M1 1SAM401911R1007 2/20 UA1-208 1SAM201904R1008 2/12
SA1 GJF1101903R0001 2/14 UA1-230 1SAM201904R1005 2/12
SA2 GJF1101903R0002 2/14 UA1-24 1SAM201904R1001 2/12
SA3 GJF1101903R0003 2/14 UA1-400 1SAM201904R1006 2/12
SK1-02 1SAM201903R1003 2/11 UA1-415 1SAM201904R1007 2/12
SK-11 1SAM101904R0003 2/24 UA1-48 1SAM201904R1002 2/12
SK1-11 1SAM201903R1001 2/11 UA1-575 1SAM201904R1009 2/12
SK1-20 1SAM201903R1002 2/11 UA1-60 1SAM201904R1003 2/12
SK4-11 1SAM401904R1001 2/19 UA4-110 1SAM401905R1001 2/19
T16-0.13 1SAZ711201R1005 5/1 UA4-230 1SAM401905R1002 2/19
T16-0.17 1SAZ711201R1008 5/1 UA4-24 1SAM401905R1004 2/19
T16-0.23 1SAZ711201R1009 5/1 UA4-400 1SAM401905R1003 2/19
T16-0.31 1SAZ711201R1013 5/1 UA4-HK-230 1SAM401906R1001 2/19
T16-0.41 1SAZ711201R1014 5/1 UA4-HK-400 1SAM401906R1002 2/19
T16-0.55 1SAZ711201R1017 5/1 UAF-110 1SAM101903R0110 2/24
T16-0.74 1SAZ711201R1021 5/1 UAF-230 1SAM101903R0230 2/24
T16-1.0 1SAZ711201R1023 5/1 UAF-24 1SAM101903R0024 2/24
T16-1.3 1SAZ711201R1025 5/1 UAF-400 1SAM101903R0400 2/24
T16-1.7 1SAZ711201R1028 5/1 UAF-415 1SAM101903R0415 2/24
T16-10 1SAZ711201R1043 5/1 UAF-48 1SAM101903R0048 2/24
Index
ABB | 10/7
Marketing material
http://new.abb.com/low-voltage/products/motor-protection
11
11/0 | ABB
Videos, prints, technical presentations and more Userfriendly web design
Videos
DemacLenko
Fabricant de canons à neige
Prolonger la saison
Distributeur
Réduire les stocks pour une meilleure productivité
1SFC101008L0301
SSAB
Production d’acier
1SFC101011L0301
Une belle réussite entraîne son lot de contraintes. Grâce à sa bobine électronique, le contacteur AF fonctionne
infrastructures, les stations de pompage et le stockage de été impressionné par la qualité globale du produit, capable
Une clientèle plus nombreuse implique des stocks sur une plage de tension élargie, sur les réseaux 50 et 60 Hz,
l'eau. Ses canons à neige haute capacité peuvent générer de résister aux vibrations et au climat rigoureux, qui lui a
plus importants, des stocks plus importants impliquent en AC ou en DC. En outre, le limiteur de surtension est
jusqu'à 105 m3 de neige par heure. Sauf en cas de coupure permis de réaliser des économies substantielles de temps
une logistique plus complexe et une logistique intégré au contacteur. En combinant autant de fonctionnalités
de courant, bien entendu… et d'argent en termes d'entretien et de gestion. Autre
complexe engendre des délais de livraison et des coûts dans un seul et même contacteur, la gamme AF offre non
avantage : un fabricant unique pour une gamme complète
supplémentaires. Les grands distributeurs de composants seulement des performances techniques exceptionnelles,
d'équipements de démarrage moteur, ce qui simplifie la
électriques doivent stocker, distribuer et gérer des quantités mais permet également une réduction considérable, jusqu'à
Le défi maintenance et rationalise l'assemblage. Compatibles à
considérables de produits, notamment des dizaines de 90 %, du nombre de variantes nécessaires. L'offre est passée
Tools
C'est ce qui est arrivé bien trop souvent à la station de ski la fois avec le courant AC et DC, sur réseau 50 ou 60 Hz,
milliers de contacteurs. Ils doivent ainsi composer avec de 45 références de bobines Le client
pour couvrir toute la plage La solution d'ABB
suédoise Funäsdal. Les conditions hivernales rigoureuses les contacteurs AF peuvent être utilisés partout dans le
de fortes contraintes en termes d'espace et de logistique, de tension à seulement 4Bonneavec lanouvelle
gammepour les OEM du secteur CVC (chauffage,
de contacteurs Intégrant la toute dernière technologie de contrôle moteurs issue
exercent évidemment des contraintes extrêmes sur les monde. Leur plage de tension de commande plus large et
pour garantir une distribution rapide et efficace. ventilation,
AF. Ces contacteurs permettent uneclimatisation).
réduction desEnfraisRussie, l'un de nos principaux de notre expérience de leader du secteur de l'énergie et de
équipements d'enneigement : taux d'humidité élevé, leurs valeurs d'accrochage et de décrochage plus franches
marchés,
d'administration et de logistique la profite
qui croissance rapide
à la fois auxdu secteur entraîne des l'automatisation, la nouvelle gamme de contacteurs AF redéfinit
températures très basses et vibrations constantes. De plus, garantissent un fonctionnement stable, même en cas de
Le défi conséquences
distributeurs et aux utilisateurs difficiles à maîtriser
finaux. L'extension de la : explosion du niveau des la norme en termes de contrôle industriel. Compatible à la fois
la longueur démesurée de certains câbles provoquaitLe client
des fluctuations de tension. La solution
Pour les distributeurs de produits électriques, les livraisons stocks et des
clientèle n'est ainsi plus synonyme coûts administratifs.
d'augmentation C'est le problème auquel ont
ingérable avec les alimentations AC et DC, le contacteur AF fonctionne
La division Produits Basse Tension d'ABB dispose de plus
fluctuations de tension endommageant les contacteurs, Les tableaux MNS d'ABB intègrent les technologies
doivent absolument être rapides et efficaces. Le succès est et coûteuse des stocks. Plusété confrontés
besoin de ADL et Freedes
proposer Tech, deux fournisseurs moscovites sur une plage de tension de commande considérablement
ce qui engendrait des interruptions de service et dedes
40 ans d'expérience
arrêts dans lacool,
Pour rester construction
prenez ledecontrôle.
tableaux de tableaux les plus avancées du marché. La réduction des
basse tension. Une collaboration étroite avec un large éventail pertes d'énergie au sein des tableaux peut atteindre jusqu'à source d'expansion, d'élargissement de la clientèle et de produits spécifiques pourdu lessecteur
tensionsCVC.
non standard : avec plus large que les contacteurs classiques. Grâce à sa bobine
coûteux pour la station. Que faire ?
électronique (limiteur de surtension intégré), un seul contacteur
de clients nous a permis de concevoir une solution adaptée
ABB France 28 %. Le contacteur AF, doté d'une bobine à commande croissance exponentielle des commandes. Une bonne chose, seulement quatre bobines, la technologie AF gère toutes les
Le20 défi est capable de fonctionner sur une plage de 100-250 V. Il est
à tous les besoins.Division
Les nouveaux
Produitstableaux MNS, équipés
Basse Tension électronique, a démontré ses nombreux avantages par certes, mais également un défi à relever. La grande variété tensions de commande de à 500 V AC/DC.
de la gamme de contacteurs AF, permettent une réduction rapport aux technologies de contacteurs classiques. Ces de contacteurs disponibles implique en effet une gestion plus Avec leur technologie de Au fil de et
bobine la leur
croissance
gammedu marché CVC russe, les entreprises
complète en outre compatible avec les réseaux 50 et 60 Hz. En 2011, en
Activité Basse Tension
lourde, une logistique plus complexe et une augmentation comme
d’accessoires, les contacteurs AFADL et Free dans
se situent Tech ontuneété contraintes de gonfler adoptant les contacteurs AF d'ABB, ADL et Free Tech ont pu
des pertes d'énergie pouvant atteindre 28 %, tout en offrant avantages se traduisent par une fonctionnalité accrue
Le client La solution d'ABB considérablement
aux besoins deleurs tousstocks afin de pouvoir répondre à réduire leurs stocks de contacteurs de plus de 60 % et les frais
des fonctionnalitéswww.abb.fr
et une durée de vie accrues. du système MNS comparé aux technologies équivalentes des stocks. À ces nombreux produits viennent s’ajouter catégorie à part, répondant les clients.
Important producteur d'acier, SSAB est leader sur le marché SSAB cherchait à disposer d'une alimentation constante la forte demande. L'accroissement et la diversification de la de gestion associés de 40 %. Le respect de délais de livraison
disponibles aujourd'hui. La réduction des pertes d'énergieles accessoires supplémentaires, participant à leur tour à
de niche de l'acier haute résistance. Avec des usines en Suède et stable, sans devoir recourir à des systèmes d'alimentation l’augmentation des stocks. Tous ces paramètres peuvent Besoin de plus d'espaceclientèle ont par ailleurs
et de simplicité, prenez entraîné la nécessité de proposer
le contrôle. n'est pour eux désormais plus un problème, ce qui a permis
Le défi entraîne une prolongation de la durée de vie et de la
et aux États-Unis, ainsi que des opérations de finition en sans interruption (UPS) ou de secours sur batterie. Il arrivait toujours plus de produits. Il est donc devenu de plus en plus à ces deux entreprises de rester en tête du marché en pleine
Dans l'industrie, le temps, c'est de l'argent. Les tendances disponibilité de tous les composants du système MNS. compromettre l'efficacité des distributeurs en termes de
Chine, l'entreprise compte plus de 9 000 employés, répartis que les contacteurs classiques restent soudés en position difficile d'assurer les livraisons sous 48 heures. L'augmentation croissance. La gamme AF offre de nombreux avantages, des
récentes sur le marché des tableaux basse tension indiquent En résumé, le système MNS, équipé de contacteurs AF, délais de livraison. Les contacteurs AF d'ABB contribuent à ABB France
dans 45 pays. Les hauts fourneaux et les fourneaux électriques fermée suite à des coupures de tension résultant de l'instabilité résoudre ce problème. des stocks a, en outre, été accompagnée d'une augmentation
Division Produits Basse Tension années de recherche et de développement ont permis à ABB
une orientation vers des complexes industriels plus vastes. permet d'économiser de l'énergie, du temps, et donc,
de SSAB consomment énormément d'électricité et imposent du réseau électrique. Ne pouvant s'affranchir des coupures Activité Basse Tension des frais administratifs. Pour pouvoir continuer à servir de réduire le nombre de variantes de produits de 90 %, tout en
L'efficacité énergétique est importante pour rester compétitif de l'argent.
des contraintes extrêmes sur la fourniture d'énergie en termes elles-mêmes, SSAB s'est tournée vers ABB, qui lui a efficacement leur large clientèle, ADL et Free Tech ont ainsi continuant à proposer un contacteur pour chaque application.
tout en se développant. Les clients d'ABB cherchent ainsi
de performance et de fiabilité. Pour garantir la continuité du proposé une solution en conformité avec la norme SEMI-F47 www.abb.fr dû résoudre le problème posé par leurs stocks excessivement Grâce à cette technologie, les fluctuations de tension ou les
à améliorer l'efficacité énergétique de chaque aspect de leur Pour mieux gérer votre énergie, prenez le contrôle.
fonctionnement de ses générateurs, SSAB exige que ses d'immunité à ces coupures de tension : les contacteurs AF à volumineux. La solution d'ABB : le contacteur AF. tensions de commande non standard ne sont plus un problème.
activité. ABB a identifié qu'il était possible d'économiser une
équipements de commande moteur soient certifiés SEMI-F47 commande électronique.
quantité importante d'énergie, et donc d'argent, en réduisant ABB France
(résistance aux coupures de tension). ABB est l'un des rares Vous avez besoin de plus de flexibilité, prenez le contrôle.
les pertes directement au sein des tableaux. C'est dans cette Division Produits Basse Tension
fournisseurs capables de satisfaire les exigences strictes de
optique qu'a été développé le nouveau tableau MNS, équipé Activité Basse Tension
cette norme. Pour une alimentation sans interruption, prenez le contrôle. ABB France
du contacteur AF.
Division Produits Basse Tension
www.abb.fr
Le défi ABB France Activité Basse Tension
La défaillance des contacteurs suite à des coupures de tension Division Produits Basse Tension
(contacteur soudé en position fermée) engendrait des temps Activité Basse Tension www.abb.fr
d'arrêt non planifiés, des pertes de production et des coûts
importants liés à leur remplacement. Cela mettait en danger www.abb.fr
la production ainsi que la sécurité des opérateurs. En effet,
la transformation du minerai en fusion à une température
d'environ 1 300 °C rend toute interruption potentiellement
dangereuse et un arrêt trop long risque de figer la matière à
l'intérieur des fours. SSAB devait trouver une solution offrant
des performances constantes et flexibles, y compris dans ces
conditions extrêmes.
Success stories
Mini contactors 3-pole contactors for motor control and power switching 4-pole contactors
3-pole or 4-pole
11
IEC (1) (1) AC-3
IEC AC-3
Rated
Rated
operational
operational powerθ ≤θ60
power ≤ 60
°C °C
(2),(2), V VkWkW
400400 4 4 5.55.5 4 4 5.55.5 7.57.5 4 4 5.55.5 7.57.5 1111 1515 18.5
18.5 18.5
18.5 2222 3030 3737 4545 5555 7575 7575 9090 110110 132
132 160
160 200
200 200
200 250
250 315315 400
400 —— 475
475 560
560 —— —— IEC AC-1 Rated operational current θ ≤ 40 °C, 690 V A 25 30 45 55 70 100 125 160 200 275 350 400 500 525 800 1000
UL/CSA
UL/CSA3-phase
3-phase
motor
motor
rating
rating 480480
V V hphp 3 3 5 5 5 5 7.57.5 1010 5 5 7.57.5 1010 1515 2020 2525 3030 4040 5050 6060 6060 7575 100
100 100
100 125
125 150
150 200
200 250
250 300
300 350
350 400
400 500
500 600
600 —— 800
800 900
900 —— —— UL/CSA General use rating 600 V A 25 30 45 55 60 80 105 160 175 230 250 300 350 420 540 —
ACAC
/ DC
/ DC
Control
Control
supply
supply Type
Type —— —— —— —— —— AF09
AF09 AF12
AF12 AF16
AF16 AF26
AF26 AF30
AF30 AF38
AF38 AF40
AF40 AF52
AF52 AF65
AF65 AF80
AF80 AF96
AF96 AF116 AF140
AF116 AF140 AF146
AF146 AF190
AF190 AF205
AF205 AF265
AF265 AF305 AF370 AF400
AF305 AF370 AF400 AF460
AF460 AF580
AF580 AF750
AF750 AF1250
AF1250 AF1350
AF1350 AF1650
AF1650 AF2050
AF2050 AF2650
AF2650 AC / DC Control supply Type AF09 AF16 AF26 AF38 AF40 AF52 AF80 AF116 AF140 AF190 AF205 AF265 AF305 AF370 — —
ACAC
Control
Control
supply
supply Type
Type B6B6 B7B7 AS09
AS09 AS12
AS12 AS16
AS16 AF09
AF09 AF12
AF12 AF16
AF16 AF26
AF26 AF30
AF30 AF38
AF38 AF40
AF40 AF52
AF52 AF65
AF65 AF80
AF80 AF96
AF96 AF116
AF116 AF140
AF140 AF146
AF146 AF190
AF190 AF205
AF205 AF265
AF265 AF305 AF370 AF400
AF305 AF370 AF400 AF460
AF460 AF580
AF580 AF750
AF750 AF1250
AF1250 AF1350
AF1350 AF1650
AF1650 AF2050
AF2050 AF2650
AF2650 AC Control supply Type AF09 AF16 AF26 AF38 AF40 AF52 AF80 AF116 AF140 AF190 AF205 AF265 AF305 AF370 EK550 EK1000
DCDC
Control
Control
supply
supply Type
Type BC6
BC6 BC7
BC7 ASL09
ASL09 ASL12 ASL16 AF09
ASL12 ASL16 AF09 AF12
AF12 AF16
AF16 AF26
AF26 AF30
AF30 AF38
AF38 AF40
AF40 AF52
AF52 AF65
AF65 AF80
AF80 AF96
AF96 AF116 AF140
AF116 AF140 AF146
AF146 AF190
AF190 AF205
AF205 AF265
AF265 AF305
AF305 AF370
AF370 AF400
AF400 AF460
AF460 AF580
AF580 AF750
AF750 AF1250
AF1250 AF1350
AF1350 AF1650
AF1650 AF2050
AF2050 AF2650
AF2650 DC Control supply Type AF09 AF16 AF26 AF38 AF40 AF52 AF80 AF116 AF140 AF190 AF205 AF265 AF305 AF370 EK550 EK1000
IEC
IEC AC-3
AC-3
Rated
Rated
operational
operational currentθ ≤θ60
current ≤ 60
°C °C
(2), (2), V VA A
400400 8.58.5 11.5
11.5 9 9 1212 15.5
15.5 9 9 1212 1818 2626 3232 3838 4040 5353 6565 8080 9696 116116 140
140 146
146 190
190 205
205 265
265 305
305 370
370 400
400 460
460 580
580 750
750 —— 860
860 1060
1060 —— ——
AC-1
AC-1
Rated
Rated
operational
operational currentθ ≤θ40
current ≤ 40
°C,°C,
690690
V V A A 2020 2020 2222 2424 2424 2525 2828 3030 4545 5050 5050 7070 100
100 105
105 125
125 130
130 160
160 200
200 225
225 275
275 350
350 400
400 500
500 600
600 600
600 700
700 800
800 1050
1050 1260
1260 1350
1350 1650
1650 2050
2050 2650
2650
Mini contactor relays Contactor relays
(400
(400(400
V)
V) V) (400
(400(400
V)
V) V)
UL/CSA
UL/CSAGeneral
General
useuse
rating
rating 600600
V V A A 1212
(300
(300(300
V)
V) V) 1616 2020 2020 2020 2525 2828 3030 4545 5050 5050 6060 8080 9090 105
105 115
115 160
160 200
200 200
200 250
250 300
300 350
350 400
400 520
520 550
550 650
650 750
750 900
900 1210
1210 1350
1350 1650
1650 2100
2100 2700
2700
NEMA
NEMA NEMA
NEMA
Size
Size —— —— 0000 0000 0 0 0000 0 0 —— 1 1 —— —— 2 2 —— —— 3 3 —— —— 4 4 —— —— —— 5 5 —— —— —— 6 6 —— 7 7 —— —— 8 8 —— ——
(1)
(1) (1)
1000
10001000
VV IEC
IEC
V IEC
ratings
ratings
ratings
available
available
available
for
forfor
AF80,
AF80,
AF80,
AF96
AF96
AF96 and
andand
AF146
AF146
AF146
…
…… AF2650
AF2650
AF2650
contactors.
contactors.
contactors.
(2) θ ≤≤θ55
(2) (2) 55
≤ 55
°C
°C°C
for
forfor
mini
mini
mini
contactors
contactors
contactors
and
andand
AF400
AF400
AF400
...
... AF2650
...
AF2650
AF2650
contactors.
contactors.
contactors.
(3)
(3) (3)
See
SeeSee
available
available
available
reversing
reversing
reversing
contactors
contactors
contactors
VB6,
VB6,
VB6,
VB7
VB7
VB7
and
and
and
VAS09
VAS09
VAS09
...
... VAS16.
...
VAS16.
VAS16.
R contactors
DC Circuit switching AC Circuit switching Special versions
Overload
Overloadrelays
relays DC-1 Rated current up to 5000 A AC-1 Rated current up to 5000 A AC / DC Coupling: LOR.. contactors
DC-3/DC-5 Rated current up to 2000 A AC-3 Rated power up to 1500 kW Slip ring motor control: FOR .. contactors
Thermal
Thermal
relays
relays Class
Class
10 10 T16
T16
(0.10…16
(0.10…16
(0.10…16
A)
A) A) T16
T16
(0.10…16
(0.10…16
(0.10…16
A)
A) A) TF42
TF42
(0.10…38
(0.10…38
(0.10…38
A)
A) A) TF65
TF65
(22...67
(22...67
(22...67
A)
A) A) TF96
TF96
(40...96
(40...96
(40...96
A)
A) A) TF140DU
TF140DU
(66...142
(66...142
(66...142
A)
A) A) TA200DU
TA200DU
(66...200
(66...200
(66...200
A)
A) A)
1500 V with poles in series (1520 A - 440 V)
(Class
(Class
(Class
10A
10A10A
for
for TF140,
for
TF140,
TF140,
TA200DU)
TA200DU)
TA200DU) θθ ≤≤θ55
55≤ °C
°C
55 °C θθ ≤≤θ55
55≤ °C
°C
55 °C Field discharge: AM(F)-CC-JORE contactors
Electronic
Electronic
relays
relays Class
Class
10E,
10E,
20E,
20E,
30E30E E16DU
E16DU
(0.10…18.9
(0.10…18.9
(0.10…18.9
A)
A) A) EF19
EF19
(0.10…18.9
(0.10…18.9
(0.10…18.9
A)
A) A) EF19
EF19
(0.10…18.9
(0.10…18.9
(0.10…18.9
A)
A) A) EF65
EF65
(20...70
(20...70
(20...70
A)
A) A) EF96
EF96
(36...100
(36...100
(36...100
A)
A) A) EF146
EF146
(54...150
(54...150
(54...150
A)
A) A) EF205
EF205
(63...210
(63...210
(63...210
A)
A) A) EF370
EF370
(115...380
(115...380
(115...380
A)
A) A) EF460
EF460
(150…500
(150…500
(150…500
A)
A) A) EF750
EF750
(250…800
(250…800
(250…800
A)
A) A) E1250DU
E1250DU
(375…1250
(375…1250
(375…1250
A)
A) A) AC / DC Switching (N.C./N.O. main poles):
IOR.. 63-..-CC to IOR.. 5100-..-CC IOR.. 63-..-MT to IOR.. 5100-..-MT
EF45
EF45
(9…45
(9…45
(9…45
A)
A) A) NOR & JOR contactors
Latching contactors for energy saving
and safety requirements: AMA or AME contactors
Manual
Manualmotor
motorstarters
starters Short-circuit
Short-circuitprotection
protection
devices
devices
control
(0.10…32
(0.10…32
(0.10…32
A)
A) A) (0.10...32
(0.10...32
(0.10...32
A)
A) A) (45…100
(45…100
(45…100
A)
A) A)
Ics
Ics up
Ics
up to
to
up100
100
to 100
kA
kA kA lcs
lcs up
lcs
up to
to
up100
100
to 100
kA
kA kA Ics
Ics up
Ics
up to
to
up50
50
to kA
kA
50 kA Capacitor switching DC Circuit switching
tactors
Ics
Ics up
Ics
up to
to
up100
100
to 100
kA
kA kA 12.5 to 80 kvar 100 A, 440 V, DC-1 275 to 2050 A, 1000 V, DC-1
Main catalog
Manual mo d relays
Accessories
Accessories ForFor
contactor
contactor
mounting
mounting BEA7/132
BEA7/132 BEA16-3
BEA16-3 BEA16-4
BEA16-4 BEA38-4
BEA38-4
and ove
ABB | 11/1
Contact us
ABB AB
Control Products
Low Voltage Products
SE-721 61 Västerås / Sweden
http://new.abb.com/low-voltage/products/motor-protection
http://www.abb.com/lowvoltage