Orion
Orion
E5@C Series That Pursues Greater Visibility with Large White PV Display.
Added new models with Push-In Plus Terminal that Reduce Wiring Work.
Digital Temperature Controllers: E5@C Series
page 16
Plug-in Models E5CC-U
page 36
Models with Screw Terminal E5EC
48 × 96 mm
page 36
Models with Push-In Plus Terminal E5EC-B
page 68
48 × 48 mm Models with Screw Terminal E5CC-T
page 84
48 × 96 mm Models with Screw Terminal E5EC-T
page 84
96 × 96 mm Models with Screw Terminal E5AC-T
1
Digital Temperature Controller
Sampling Period
• 50 ms
Auxiliary Outputs
• None
• PF (shift) Key
Event Inputs • Temperature status display •1
• None • Simple programming •2
•1 • Independent heating and
•2 cooling PID control
• Changed parameter display
• Display brightness setting
Serial Communications
• Simple transfer output (only on
• None models with liner current outputs)
• RS-485 • Work Bit Message
2
E5GC
Model Number Legend and Standard Models
Model Number Legend
E5GC-@@ @ @ @ M-@@@ (Example: E5GC-RX1A6M-015)
A B C D E F
A B C D E F
Model Control No. of Power Meaning
Terminal Input
outputs 1 auxiliary supply Options
type type
and 2 outputs voltage
E5GC 48 24 mm
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*1 CX Linear current output None
*2 0 None
1 1
2 2
A 100 to 240 VAC
D 24 VAC/DC
6 Screw terminal (with cover)
C Screwless clamp terminal *6
M Universal input
HB alarm and HS alarm Communications Event inputs
000 --- --- ---
015 --- RS-485 ---
*3 016 --- --- 1
*3, *4 023 1 --- ---
*5 024 --- --- 2
*1. The control output can be used as a simple transfer output.
*2. Only option 000 can be selected if an auxiliary output is zero.
*3. Option 016 and 023 can be selected only if two auxiliary outputs are selected.
*4. Option with HB and HS alarms (023) cannot be selected if a linear current output is selected for the control output.
*5. Option 024 can be selected only if one auxiliary output is selected.
*6. The specifications are different for Temperature Controllers with Push-In Plus terminal. Refer to Precautions when Wiring on page 114.
3
E5GC
4
E5GC
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85 to 110% of rated supply voltage
Power consumption 5.9 VA max. at 100 to 240 VAC, and 3.2 VA max. at 24 VAC or 1.8 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70C, 60 to 120C, 115 to 165C, or 140 to 260C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 M min. (Use a 1:1 connection when connecting the ES2-HB/
Input impedance
THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5
Relay output
V, 10 mA (reference value)
Control
Voltage output
output Output voltage 12 VDC 20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: Approx. 10,000
Number of outputs 1 or 2 (depends on model)
Auxiliary
output SPST-NO relay outputs, 250 VAC, 2 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
Number of inputs 1 or 2 (depends on model)
Event Contact input ON: 1 k max., OFF: 100 k min.
input External contact input
Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.
specifications
Current flow: approx. 7 mA per contact
Setting method Digital setting using front panel keys
11-segment digital displays and individual indicators
Indication method
Character height: PV: 10.5 mm, SV: 5.0 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or
Multi SP
serial communications. *
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter,
Other functions self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV
change rate limit, logic operations, temperature status display, simple programming, moving average of
input value, display brightness setting, simple transfer output, and work bit message
10 to 55C (with no condensation or icing), For 3-year warranty: 10 to 50C with standard mounting (with
Ambient operating temperature
no condensation or icing)
Ambient operating humidity 25 to 85%
Storage temperature 25 to 65C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)
* There are up to four event inputs.
5
E5GC
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor 10 to 60 to 115 to 140 to
Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
specification
2300
2300
1800
1800
1700 1700
1700
1600
1500
1400
1300 1300 1300
1300
Temperature range (°C)
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 -199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.
Analog input
Input type Current Voltage
Input specification 4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29
6
E5GC
Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.)
Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
Absolute-value upper- ON
X
ON
X The alarm will turn ON if the process value is larger than the
8
limit OFF
0
PV OFF
0
PV alarm value (X) regardless of the set point.
ON
X
ON
X The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF
0
PV OFF
0
PV alarm value (X) regardless of the set point.
Absolute-value upper-
ON
X
ON
X A standby sequence is added to the absolute-value upper-
10 limit with standby OFF
0
PV OFF
0
PV limit alarm (8). *6
sequence
Absolute-value lower-limit ON
X
ON
X A standby sequence is added to the absolute-value lower-
11
with standby sequence OFF
0
PV OFF
0
PV limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
SP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the set point (SP)
14
upper-limit alarm OFF
0
SP OFF
0
SP is higher than the alarm value (X).
SP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the set point (SP)
15
lower-limit alarm OFF
0
SP OFF
0
SP is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
7
E5GC
*1. With set values 1, 4, and 5, the upper- and lower-limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence
be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above at *2
“L” and “H.” • In cases 1 and 2 above, the alarm is always OFF if the upper-
*2. Set value: 1, Upper- and lower-limit alarm and lower-limit hysteresis overlaps.
Case 1 Case 2 Case 3 (Always OFF) • In case 3, the alarm is always OFF.
H<0, L<0 *5. Set value: 5, Upper- and lower-limit alarm with standby sequence
L H SP SP L H H SP L The alarm is always OFF if upper- and lower-limit hysteresis
H<0, L>0 overlaps.
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| *6. Refer to the E5@C Digital Temperature Controllers User’s Manual
|H| < |L| |H| > |L|
H>0, L<0 (Cat. No. H174) for information on the operation of the standby
SP H L |H| ≤ |L| sequence.
*3. Set value: 4, Upper- and lower-limit range *7. Refer to the E5@C Digital Temperature Controllers User’s Manual
Case 1 Case 2 Case 3 (Always ON) (Cat. No. H174) for information on the LBA.
H<0, L<0 *8. Refer to the E5@C Digital Temperature Controllers User’s Manual
L H SP SP L H H SP L (Cat. No. H174) for information on the PV change rate alarm.
H<0, L>0 H>0, L<0
H<0, L>0 *9. When heating/cooling control is performed, the MV absolute-
H L SP |H| ≥ |L| value upper-limit alarm functions only for the heating operation
|H| < |L| |H| > |L|
H>0, L<0 and the MV absolute-value lower-limit alarm functions only for the
SP H L |H| ≤ |L| cooling operation.
8
E5GC
Characteristics
Thermocouple: (0.3 % of indication value or 1C, whichever is greater) 1 digit max.*1
Indication accuracy Platinum resistance thermometer: (0.2 % of indication value or 0.8C, whichever is greater) 1 digit max.
(at the temperature of 23C) Analog input: 0.2% FS 1 digit max.
CT input: 5% FS 1 digit max.
Simple transfer output accuracy 0.3% FS max.*2
Influence of temperature *3 Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10C, whichever is greater) 1 digit max.
Other thermocouple input: (1% of indication value or 4C, whichever is greater) 1 digit max. *4
Influence of voltage *3 Platinum resistance thermometer: (1% of indication value or 2C, whichever is greater) 1 digit max.
Influence of EMS. Analog input: 1% FS 1 digit max.
(at EN 61326-1) CT input: 5% FS 1 digit max.
Input sampling period 50 ms
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range 1,999 to 9,999 (decimal point position depends on input type)
Influence of signal source
Thermocouple: 0.1C/ max. (100 max.), Platinum resistance thermometer: 0.1C/ max. (10 max.)
resistance
Insulation resistance 20 M min. (at 500 VDC)
100 to 240 VAC: 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Dielectric strength
24 VAC/DC: 2,300 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hr each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
Weight Controller: Approx. 80 g, Adapter: Approx. 4 g 2
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.62 or higher
E5GC side panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the
computer. *6
Setup Tool port
E5GC bottom panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable
are used together to connect a USB port on the computer. *6
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some
Approved standards
Standards models only.) *7
Conformed standards EN 61010-1 (IEC 61010-1)
EMI: EN61326-1 *8
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A
Noise Terminal Voltage: EN55011 Group 1, class A
EMS: EN61326-1 *8
ESD Immunity: EN61000-4-2
EMC
Electromagnetic Field Immunity: EN61000-4-3
Burst Noise Immunity: EN61000-4-4
Conducted Disturbance Immunity: EN61000-4-6
Surge Immunity: EN61000-4-5
Voltage Dip/Interrupting Immunity: EN61000-4-11
*1. The indication accuracy of K thermocouples in the 200 to 1,300C range, T and N thermocouples at a temperature of 100C max., and U
and L thermocouples at any temperature is 2C 1 digit max. The indication accuracy of B thermocouples at a temperature of 400C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800C is 3C max.
The indication accuracy of R and S thermocouples at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W
thermocouples is (0.3% of PV or 3C, whichever is greater) 1 digit max.
The indication accuracy of PLII thermocouples is (0.3% of PV or 2C, whichever is greater) 1 digit max.
*2. However, the precision between 0 and 4 mA for a 0 to 20 mA output is 1% FS max.
*3. Ambient temperature: 10C to 23C to 55C, Voltage range: 15% to 10% of rated voltage
*4. K thermocouple at 100C max.: 10C max.
*5. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6. External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time.
*7. Refer to your OMRON website for the most recent information on applicable models.
*8. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
9
E5GC
Communications 0 to 99 ms 300
response wait time Default: 20 ms 200
* The baud rate, data bit length, stop bit length, and vertical parity can
100
be individually set using the Communications Setting Level. E5GC
250 VAC, 30 VDC
50
Communications Functions 30
(resistive load)
cosφ = 1
You can use the memory in the PLC to read and write 20
E5@C parameters, start and stop operation, etc.
10
The E5@C automatically performs communications with
PLCs. No communications programming is required. 5
Number of connected Digital Temperature
3
Programless Controllers: 32 max. (Up to 16 for the FX Series)
2
communica- Applicable PLCs: OMRON PLCs
tions CS Series, CJ Series, or CP Series 1
0.1 0.2 0.3 0.5 1 2 3 5 10
Mitsubishi Electric PLCs
MELSEC Q Series, L Series, or FX Series Switching current (A)
(compatible with the FX2 or FX3 (excluding the FX1S))
KEYENCE PLCs
KEYENCE KV Series
10
E5GC
External Connections
E5GC
Control Outputs
(6) Options
Use no-voltage inputs for the event inputs.
015 016 023 024 The polarity for non-contact inputs is given in parentheses.
Communications Event input 1 CT input Event inputs 1 and 2
(RS-485) (−)
EV2
(−)
RS-485 EV1 CT EV1
B(+) A(−)
7 8 9 7 8 9 7 8 9 7 8 9
(5) Sensor (Temperature/Analog) Input
− + + mA −
5 6 5 6
3 4 3 4 3 4 Auxiliary Auxiliary
output 1 output 1
Relay output
: Reinforced insulation
: Functional isolation
11
E5GC
Terminal Block Appearance
E5GC-@6 E5GC-@C
Controllers with Screw Terminal (M3 Screws) Controllers with Screwless Clamp Terminal
5.8 mm max.
8 to 12 mm 8 to 12 mm
5.8 mm max.
Wires:AWG24 to AWG18 (equal to a cross-sectional area of 0.21 to 0.82 mm2) braided or solid wires
Note: Refer to Precautions When Wiring E5GC (Controllers with Screwless Clamp Terminal) on page 115 for information on wiring Controllers
with screwless clamp terminal.
Nomenclature
E5GC
Front panel Left Side View of the E5GC
No.2 display
SP or specified parameter value Bottom View of E5GC
Operation indicators
12
E5GC
Dimensions (Unit: mm)
Controllers
E5GC-@6 Waterproof Packing (Accessory)
Controllers with Screw Mounting Adapter (Accessory)
63.6 Terminal Cover (Accessory)
Terminal 4 90
48 44.8
1
24 40.8 22 22
• Use two Mounting Adapters, either on the top and bottom or on the right and left.
• Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58-
CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the side panel. The E58-CIFQ2 USB-Serial Conversion Cable
and E58-CIFQ2-E Communications Conversion Cable are required to connect to the port on the bottom panel. (You cannot leave either
port connected constantly during operation.)
L1
22.2+0.3
0
To mount the Temperature Controller so that it is waterproof,
insert the Waterproof Packing onto the Temperature Controller.
40 min +1.0
45+0.60 L1=(48×n-2.5) +0 Group mounting does not allow waterproofing.
n: Number of mounted Controllers (2 ≤ n ≤ 6)
22.2+0.3
0
• To install the Temperature Controller, insert it into a square hole in a panel with a thickness of 1 to 8 mm, and then insert the enclosed
adapter so that it locks into the grooves on the top and bottom or on the left and right of the rear case.
• Tighten the two mounting screws on the top and bottom or on the right and left of the Mounting Adapters alternately little by little to main-
tain a balance, and tighten them to a torque of between 0.29 and 0.39 N·m.
• When two or more Temperature Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable
operating temperature range given below.
Horizontal group mounting: 10 to 55C
• Use Temperature Controllers with Screwless Clamp Terminal for vertical group mounting.
24 40.8 22 22
• Use two Mounting Adapters, either on the top and bottom or on the right and left.
• Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58-
CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the side panel. The E58-CIFQ2 USB-Serial Conversion Cable
and E58-CIFQ2-E Communications Conversion Cable are required to connect to the port on the bottom panel. (You cannot leave either
port connected constantly during operation.)
22.2+0.3
0 To mount the Temperature Controller so
40 min
that it is waterproof, insert the Waterproof
+1.0
45+0.60 L1=(48×n-2.5) +0 Packing onto the Temperature Controller.
n: Number of mounted Controllers (2 ≤ n ≤ 6) L2 Group mounting does not allow waterproof-
22.2+0.3
0 ing.
L2=(24×n-1.5) +1.0
+0
• To install the Temperature Controller, insert it into a square hole in a panel with a thickness of 1 to 8 mm, and then insert the enclosed
adapter so that it locks into the grooves on the top and bottom or on the left and right of the rear case.
• Tighten the two mounting screws on the top and bottom or on the right and left of the Mounting Adapters alternately little by little to main-
tain a balance, and tighten them to a torque of between 0.29 and 0.39 N·m.
• When two or more Temperature Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable
operating temperature range given below.
Horizontal group mounting: 10 to 55C
Vertical group mounting of two Controllers: 10 to 45C
Vertical group mounting of three or more Controllers: 10 to 40C
• If you use vertical group mounting, you cannot draw out the interior body of the Controller.
13
E5GC
Accessories (Order Separately)
USB-Serial Conversion Cable (2110)
LED (RD)
USB connector
(type A plug)
LED (PWR) Serial connector
LED (SD)
Conversion Cable
E58-CIFQ2-E
Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510) 250 263 1510
Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
15
2.8 (Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 4002
25 3
Winding resistance: 182
10.5 100V
Output voltage (Eo) V (r.m.s.)
Frequency: 50 Hz
40 10 ∞
Distortion
Two, 3.5 dia. 1kΩ factor
10%
1
10 3%
1%
100mV
30
100μV
40 × 40
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
Armature Frequency: 50 Hz
Approx. 3 dia. Plug Distortion
∞
10 factor
1kΩ
Lead 10%
500Ω 3%
1 1%
18 100mV
100Ω
• Plug 10
50Ω
RL=10Ω
Approx. 6 dia. 1
(22) 100μV
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
14
E5GC
Mounting Adapter
Y92F-53 (Two provided.)
One pair is provided with the Temperature
34.7
Controller. Order this Adapter separately if it
becomes lost or damaged.
12
11.8 9.4
Waterproof Packing
Y92S-P12
Draw-out Jig
Y92F-55
Use this Draw-out Jig to remove the interior
body of the Digital Temperature Controller
from the case to perform maintenance
without removing the terminal wiring.
32.9
15 1.4
30.5
27.4
22
28.7
20
23
15
Digital Temperature Controller
16
E5CC/E5CC-B/E5CC-U
Model Number Legend and Standard Models
Model Number Legend
Models with Screw Terminal
E5CC-@@ 3 @ 5 M -@@@ (Example: E5CC-RX3A5M-000)
A B C D E F
A B C D E F
Model No. of Power Meaning
Control outputs Terminal Input
auxiliary supply Options
1 and 2 type type
outputs voltage
E5CC 48 48 mm
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*1 *3 CX Linear current output *2 None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
CQ Linear current output *2
(for driving SSR)
3 3 (one common)
A 100 to 240 VAC
D 24 VAC/DC
5 Screw terminal (with cover)
M Universal input
HB alarm and Event Remote Transfer
Communications
HS alarm inputs SP Input output
000 --- --- --- --- ---
*1 001 1 --- 2 --- ---
2
*1 003 (for 3-phase RS-485 --- --- ---
heaters)
*3 004 --- RS-485 2 --- ---
005 --- --- 4 --- ---
006 --- --- 2 Provided.
007 --- --- 2 Provided. ---
*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output.
*2. The control output cannot be used as a transfer output.
*3. Option 004 can be selected only when "CX" is selected for the control outputs.
Note: Draw-out-type models of the E5CC are available. Ask your OMRON representative for details.
17
E5CC/E5CC-B/E5CC-U
A B C D E F
Model No. of Power Meaning
Control outputs Terminal Input
auxiliary supply Options
1 and 2 type type
outputs voltage
E5CC 48 48 mm
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
2 2 (one common)
A 100 to 240 VAC
D 24 VAC/DC
B Push-in plus terminal
M Universal input
HB alarm and Event Remote Transfer
Communications
HS alarm inputs SP Input output
000 --- --- --- --- ---
001 1 --- 2 --- ---
002 1 RS-485 --- --- ---
004 --- RS-485 2 --- ---
006 --- --- 2 --- Provided.
18
E5CC/E5CC-B/E5CC-U
A B C D E F
Model Control No. of Power Meaning
Terminal Input
outputs auxiliary supply Options
type type
1 and 2 outputs voltage
E5CC 48 48 mm
Control output 1 Control output 2
RW Relay output (SPDT) None
QX Voltage output (for driving SSR) None
CX Linear current output * None
0 None
1 1
2 2 (one common)
A 100 to 240 VAC
D 24 VAC/DC
U Plug-in model
M Universal input
HB alarm and HS Communi- Remote SP Transfer
Event inputs
alarm cations Input output
000 --- --- --- --- ---
* The control output can be used as a simple transfer output for the Digital Temperature Controllers manufactured in May 2014 or later.
List of Models
Options Model Model
No. of auxiliary Power supply voltage Power supply voltage
Control output HB alarm and No. of event
outputs Communications
HS alarm inputs
100 to 240 VAC 24 VAC/DC
19
E5CC/E5CC-B/E5CC-U
Adapter
Model
Y92F-45
Note: Use this Adapter when the panel has already been prepared for
an E5B@ Controller.
Waterproof Cover
Model
Y92A-48N
Mounting Adapter
Model
Y92F-49
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
20
E5CC/E5CC-B/E5CC-U
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or
Power consumption 1.6 W max. at 24 VDC
All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Sensor input
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V,or 0 to 50 mV (The 0 to 50 mV range applies to the
E5CC-U only for those manufactured in May 2014 or later.)
Current input: 150 max., Voltage input: 1 M min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
E5CC/E5CC-B: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,
minimum applicable load: 5 V, 10 mA (reference value)
Relay output
E5CC-U: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,
Control minimum applicable load: 5 V, 10 mA (reference value)
output
Voltage output
Output voltage: 12 VDC 20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Linear current output *2 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: approx. 10,000
E5CC: 3
Number of outputs E5CC-B: 2
E5CC-U: 1 or 2 (depends on model)
Auxiliary
output SPST-NO relay outputs, 250 VAC, Models with 1 output: 3 A (resistive load), E5CC-U models with 2
outputs: 3 A (resistive load), E5CC-B models with 2 outputs: 2 A (resistive load), Models with 3
Output specifications
outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at
5 V (reference value)
E5CC: 2 or 4 (depends on model)
Number of inputs
E5CC-B: 2 (depends on model)
Event Contact input: ON: 1 k max., OFF: 100 k min.
input *1 External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output *1 Current output: 4 to 20 mA DC, load: 500 max., resolution: approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 k min., resolution: Approx. 10,000
Setting method Digital setting using front panel keys
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 max.)
Remote SP input *1 *2
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 M min.)
11-segment digital display and individual indicators
Indication method
Character height: PV: 15.2 mm, SV: 7.1 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations,
Multi SP *3
or serial communications.
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital
Other functions filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, logic operations, temperature status display, simple programming, moving
average of input value, and display brightness setting
10 to 55C (with no condensation or icing), For 3-year warranty: 10 to 50C with standard mounting
Ambient operating temperature
(with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)
*1. There are no optional functions for the E5CC-U. Refer to Model Number Legend and List of Models on page 19.
*2. This function is not supported by the E5CC-B. Refer to Model Number Legend on page 18.
*3. With the E5CC-B, there can be up to four set points if event inputs are used to select them.
21
E5CC/E5CC-B/E5CC-U
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor 10 to 60 to 115 to 140 to
Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
specification
2300
2300
1800
1800
1700 1700
1700
1600
1500
1400
1300 1300 1300
1300
Temperature range (°C)
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.
Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V 0 to 50 mV*
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29 30
* The range applies to the E5CC-U only for those manufactured in May 2014 or later.
22
E5CC/E5CC-B/E5CC-U
Alarm Types
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
Absolute-value upper- ON
X
ON
X The alarm will turn ON if the process value is larger than the
8
limit OFF
0
PV OFF
0
PV alarm value (X) regardless of the set point.
ON
X
ON
X The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF
0
PV OFF
0
PV alarm value (X) regardless of the set point.
Absolute-value upper-
ON
X
ON
X A standby sequence is added to the absolute-value upper-
10 limit with standby OFF
0
PV OFF
0
PV limit alarm (8). *6
sequence
Absolute-value lower-limit ON
X
ON
X A standby sequence is added to the absolute-value lower-
11
with standby sequence OFF
0
PV OFF
0
PV limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
SP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the set point (SP)
14
upper-limit alarm OFF
0
SP OFF
0
SP is higher than the alarm value (X).
SP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the set point (SP)
15
lower-limit alarm OFF
0
SP OFF
0
SP is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
X
RSP absolute-value ON
X ON This alarm type turns ON the alarm when the remote SP
18 OFF RSP
upper-limit alarm *10 OFF
0
RSP
0 (RSP) is higher than the alarm value (X).
RSP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the remote SP
19
lower-limit alarm *10 OFF
0
RSP OFF
0
RSP (RSP) is lower than the alarm value (X).
23
E5CC/E5CC-B/E5CC-U
*1. With set values 1, 4 and 5, the upper and lower limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence
be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above *2
“L” and “H.” • Case 1 and 2
*2. Set value: 1, Upper- and lower-limit alarm Always OFF when the upper-limit and lower-limit hysteresis overlaps.
Case 1 Case 2 Case 3 (Always ON)
• Case 3: Always OFF
H<0, L<0
L H SP SP L H H SP L *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 Always OFF when the upper-limit and lower-limit hysteresis
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| overlaps.
|H| < |L| |H| > |L|
H>0, L<0 *6. Refer to the E5@C Digital Temperature Controllers User's Manual
SP H L |H| ≤ |L| (Cat. No. H174) for information on the operation of the standby
*3. Set value: 4, Upper- and lower-limit range sequence.
Case 1 Case 2 Case 3 (Always OFF)
*7. Refer to the E5@C Digital Temperature Controllers User's Manual
H<0, L<0 (Cat. No.H174) for information on the loop burnout alarm (LBA).
L H SP SP L H H SP L *8. Refer to the E5@C Digital Temperature Controllers User's Manual
H<0, L>0 H>0, L<0 H<0, L>0 (Cat. No. H174) for information on the PV change rate alarm.
|H| < |L| |H| > |L| H L SP |H| ≥ |L| *9. When heating/cooling control is performed, the MV absolute
H>0, L<0
upper limit alarm functions only for the heating operation and the
SP H L |H| ≤ |L| MV absolute lower limit alarm functions only for the cooling
operation.
*10.This value is displayed only when a remote SP input is used. It
functions in both Local SP Mode and Remote SP Mode.
Remote SP input is supported only for the E5CC.
24
E5CC/E5CC-B/E5CC-U
Characteristics
E5CC/E5CC-B
Thermocouple: (0.3% of indication value or 1°C, whichever is greater) 1 digit max. *1
Platinum resistance thermometer: (0.2% of indication value or 0.8°C, whichever is greater) 1 digit max.
Analog input: 0.2% FS 1 digit max.
Indication accuracy
CT input: 5% FS 1 digit max.
(at the ambient temperature of 23°C)
E5CC-U
Thermocouple: (1% of indication value or 2°C, whichever is greater) 1 digit max. *1
Platinum resistance thermometer: (0.2% of indication value or 0.8°C, whichever is greater) 1 digit max.
Analog input: 0.2% FS 1 digit max.
Transfer output accuracy 0.3% FS max.
Simple transfer output accuracy 0.3% FS max.*2
Remote SP Input Type 0.2% FS 1 digit max.
Influence of temperature *3 Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10°C, whichever is greater) 1 digit max.
Other thermocouple input: (1% of indication value or 4°C, whichever is greater) 1 digit max. *4
Influence of voltage *3 Platinum resistance thermometer: (1% of indication value or 2°C, whichever is greater) 1 digit max.
Analog input: 1%FS 1 digit max.
Influence of EMS. CT input: 5% FS 1 digit max.
(at EN 61326-1) Remote SP input: 1% FS 1 digit max.
Input sampling period 50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1°C/ max. (100 max.)
Influence of signal source resistance
Platinum resistance thermometer: 0.1°C/ max. (10 max.)
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
E5CC/E5CC-B: Controller: Approx. 120 g, Adapter: Approx. 10 g
Weight
E5CC-U: Controller: Approx. 100 g, Adapter: Approx. 10 g
E5CC/E5CC-B: Front panel: IP66, Rear case: IP20, Terminals: IP00
Degree of protection
E5CC-U: Front panel: IP50, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
E5CC: CX-Thermo version 4.5 or higher
Setup Tool E5CC-B: CX-Thermo version 4.65 or higher
E5CC-U: CX-Thermo version 4.61 or higher
E5CC/E5CC-B/E5CC-U top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect
Setup Tool port
to a USB port on the computer. *6
*1. The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and
L thermocouples at any temperatures is 2°C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is 3°C max. The indication accuracy of the R and
S thermocouples at a temperature of 200°C max. is 3°C 1 digit max. The indication accuracy of W thermocouples is (0.3% of PV or 3°C,
whichever is greater) 1 digit max. The indication accuracy of PL II thermocouples is (0.3% of PV or 2°C, whichever is greater) 1 digit max.
*2. However, the precision between 0 and 4 mA for a 0 to 20 mA output is 1% FS max.
*3. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*4. K thermocouple at -100°C max.: 10°C max.
*5. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
25
E5CC/E5CC-B/E5CC-U
cULus: UL 61010-1/CSA C22.2 No.61010-1 *7, KOSHA (S Mark) certification (Some models only.) *8,
Approved standards
Standards Korean wireless regulations (Radio law: KC Mark) (Some models only.) *8, Lloyd's standards *9
Conformed standards EN 61010-1 (IEC 61010-1)
EMI: EN 61326-1 *10
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326-1 *10
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*7. The E5CC-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11
is not certified for UL listing.
*8. Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html
*9. Refer to information on maritime standards in Shipping Standards on page 110 for compliance with Lloyd's Standards.
*10.Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
26
E5CC/E5CC-B/E5CC-U
27
E5CC/E5CC-B/E5CC-U
External Connections
E5CC (Screw Terminal)
Control output 1
Relay output
250 VAC, 3A
E5CC-@@ 3 @ 5 M - @ @ @
(resistive load) (1) (2) (3) (4) (5) (6)
Voltage output ↑
(for driving SSR) Auxiliary outputs 1, 2, 3 Terminal type
12 VDC, 21 mA Control output 2 Relay outputs
Linear current output Models with 3 auxiliary
0 to 20 mA DC Voltage output The E5CC is set for a K-type thermocouple (input type = 5) by
(for driving SSR) outputs: 250 VAC, 2 A default. An input error (s.err) will occur if the input type setting does
4 to 20 mA DC
Load: 500 Ω max. 12 VDC, 21 mA (resistive load) not agree with the temperature sensor. Check the input type.
1 13 7
2 14 8
3 15 9
(5) Sensor (Temperature/Analog) Input (3) Input Power Supply
4 16 10
TC Pt I V 100 to 240 VAC 24 VAC/DC
A + 4 5 17 11
4 4 4
B mA 6 18 12 11 11
- 5 5 5 - 5
B - V 12 12
+ 6 6 6
+
6
(no polarity)
(6) Options
001 003 004 005 006 007
Event Inputs 1 Communications Communications Event Inputs Event Inputs Event Inputs
and 2, and CT1 (RS-485), CT1, (RS-485), and 1 to 4 1 and 2, and 1 and 2, and
and CT2 Event Inputs 3 and 4 Transfer Output Remote SP Input
(-) B(+) B(+)
13 13 13 (-) 13 (-) 13 (-) 13
RS-485 RS-485
EV1
14 14 14 14 14 14
A(-) A(-) EV1 EV1 EV1
EV2 15 15 15 EV2
15 EV2
15 EV2
15
16 16 (-) 16 (-) 16 16 + + 16
CT1 CT1 + V V +
17 COM 17 EV3
17 17 17 mA 17
CT2 EV3 I
18 18 EV4 18 EV4
18 18 - - 18
28
E5CC/E5CC-B/E5CC-U
1 OUT1 1 OUT1 1 17 9
+
R - Q 9
2 2 2 18 10 Auxiliary output 2
3 19 11 10
*
4 20 12
11
(5) Sensor (Temperature/Analog) Input 5 21 13 Auxiliary output 1
TC Pt I V 6 22 14 12
A + 6
6 6 6 7 23 15
- 7 B mA - 7
7 7 8 24 16
B - V (3) Input Power Supply
+ 8 8 8
+
8
100 to 240 VAC 24 VAC/DC
(6) Options 13 13
* *
001 002 004 006 14 14
Event Inputs 1 Communications Communications Event Inputs
and 2, and CT1 (RS-485), CT1 (RS-485), and 1 and 2, and 15 15
Event Inputs 3 and 4 Transfer Output * *
16 16
(-) B(+) B(+) (-)
17 17 17 17 (no polarity)
(-) * * * (-) *
18 RS-485 18 RS-485 18 18
EV1
19 19 19 EV1
19
A(-) * A(-) *
20 20 20 20
EV2 EV2
(-)
21 21 21 21
CT1 CT1 (-) * +
22 22 22 22
+ V Transfer
23 23 23 23
EV3 I Output
24 24 24 24 -
EV4
Wiring Example:
13
14
15
16
To another E5@C
29
E5CC/E5CC-B/E5CC-U
Control output 1
Auxiliary output 1
I Auxiliary output 2:
Pt
+ A Control output (cooling
mA V TC
− − B
− V
+ + Input power supply
B
Auxiliary outputs 1, 2, 3
: Reinforced insulation
: Functional isolation
: Reinforced insulation
: Functional isolation
E5CC-B
Models with 2 Auxiliary Outputs
Relay output
Auxiliary outputs 1, 2
: Reinforced insulation
: Functional isolation
30
E5CC/E5CC-B/E5CC-U
Nomenclature
E5CC Front panel
E5CC-B Temperature unit Top View of E5CC Top View of E5CC-B Top View of E5CC-U
PV or specified parameter
No. 2 display
Controllers
E5CC
73.1
4
60
48 × 48 1 44.8 × 44.8
E5CC-B (71.4)
4
67.4
(1)
48 × 48 44.8 × 44.8
44.8 × 44.8 58
Panel Cutout
Mounted Separately Group Mounted
(48 × number of units - 2.5)+1.0
0
31
E5CC/E5CC-B/E5CC-U
E5CC-U 76.8
4 14.2
48 × 48 58.6
44.8 × 44.8
58
Mounting Adapter
(Accessory)
LED (RD)
USB connector
(type A plug) Serial connector
LED (PWR)
LED (SD)
10
Terminal Cover
(E53-COV23)
22 44.8
9.1
34 Y92A-48G
UP 47.7×47.7 48×48
P C
16.5
24.6 27.6
Note: You can attach the P3GA-11 Back-connecting Socket for finger protection.
47.4
32
E5CC/E5CC-B/E5CC-U
Waterproof Packing The Waterproof Packing is provided only with the E5CC/E5CC-B.
Y92S-P8 (for DIN 48 48) It is not included with the E5CC-U.
Order the Waterproof Packing separately if it becomes lost or damaged.
The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site.
Consider three years as a rough standard.)
The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached.
Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15 (Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 4002
25 3
Winding resistance: 182
10.5
100V
10 100Ω
E54-CT3
2.36 dia.
30 RL=10Ω
1
12 dia.
9
100μV
10
40 × 40 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
Frequency: 50 Hz
Armature Distortion
Approx. 3 dia. Plug ∞
10 factor
1kΩ
10%
Lead 500Ω 3%
1 1%
100mV
18
100Ω
50Ω
• Plug 10
RL=10Ω
1
Approx. 6 dia.
100μV
(22)
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
33
E5CC/E5CC-B/E5CC-U
Adapter
Y92F-45 Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@.
2. Only black is available.
3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial
Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel.
4. You cannot use it together with the Y92F-49 Adapter that is enclosed with the Controller.
Fixture (Accessory)
4.7 76
69.6 to 77.6
72 × 72
67 × 67 87
48 × 48
2.2 4.7
62.8
To back of the E5CC
Mounted to E5CC
48
80.5
34
E5CC/E5CC-B/E5CC-U
87.7 69
79.2
12
67.6
8 7 6 5 Mounting Holes
4
Two, 4.5 dia. mounting holes
70 max. 35.4
Two,
4.5-dia. 9 3 40±0.2
holes
10 11 1 2 Note: Can also be mounted
to a DIN track
4 50 max. 31.2 max.
Note: 1. A model with finger protection (P2CF-11-E) is also available.
2. You cannot use the P2CF-11 or P2CF-11-E together with the Y92F-45.
Back-connecting Socket
P3GA-11
Eleven, M3.5 Terminal Layout/Internal Connections
sems screws
27dia. 4 7 3 (Bottom View)
5 6 7 8
4
45 25.6
3 9
2 1 11 10
45
4.5 16.3 6.2
6
8.7
Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets.
2. A Protective Cover for finger protection (Y92A-48G) is also available.
3. You cannot use the P3GA-11 together with the Y92F-45.
35
Digital Temperature Controller
Sensor Input
E5EC/E5EC-B E5AC
Universal input
• Thermocouple
• Pt
• Analog current/voltage Three-level Display
PV, SV, and MV displayed 4-digit
at the same time. displays
Indication Accuracy
• Thermocouple input: Control Output 1
±0.3% of PV <E5EC/E5AC> <E5EC-B>
• Pt input: ±0.2% of PV • Relay output • Relay output
• Analog input: ±0.2% of FS • Voltage output • Voltage output
(for driving SSR) (for driving SSR)
Sampling Period • Linear current output
• 50 ms
Control Output 2
<E5EC/E5AC> <E5EC-B>
Event Inputs • Voltage output • None
(for driving SSR)
• None • Relay output
• PF (shift) Key
•2 • Linear current output
• Setup Tool port on front panel
•4
• Temperature status display
•6
• Simple programming Auxiliary Outputs
Remote SP Input • Independent heating and <E5EC/E5AC> <E5EC-B>
cooling PID control •4 •2
• None • Changed parameter display •4
•1 • Display brightness setting
Transfer Output
Serial Communications
• None
• None
•1
• RS-485
36
E5EC/E5EC-B/E5AC
Model Number Legend and Standard Models
Model Number Legend
Models with Screw Terminal
E5EC-@@ 4 @ 5 M -@@@ (Example: E5EC-RX4A5M-000)
A B C D E F
E5AC-@@ 4 @ 5 M -@@@ (Example: E5AC-RX4A5M-000)
A B C D E F
A B C D E F
Model No. of Power Meaning
Control outputs Terminal Input
auxiliary supply Options
1 and 2 type type
outputs voltage
E5EC 48 96 mm
E5AC 96 96 mm
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*2 CX Linear current output None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
QR Relay output
(for driving SSR)
RR Relay output Relay output
Linear current
*2 CC Linear current output
output
Voltage output
*2 CQ Linear current output
(for driving SSR)
Position-
PR Position-proportional relay output proportional relay
output
4 (auxiliary outputs 1 and 2 with same common and
*3 4
auxiliary outputs 3 and 4 with same common)
A 100 to 240 VAC
D 24 VAC/DC
5 Screw terminal (with cover)
Control outputs 1 and 2 M Universal input
For RX,
QX, QQ, For CX or HB alarm
For PR Event Remote Transfer
QR, RR, or CC and Communications
inputs SP Input output
CQ HS alarm
Selectable Selectable Selectable 000 --- --- --- --- ---
Option Selectable Selectable 004 --- RS-485 2 --- ---
selection Selectable 005 --- --- 4 --- ---
conditions 2
*1 Selectable 009 (for 3-phase RS-485 2 --- ---
heaters)
Selectable 010 1 --- 4 --- ---
Selectable 011 1 --- 6 Provided. Provided.
Selectable 013 --- --- 6 Provided. Provided.
Selectable Selectable 014 --- RS-485 4 Provided. Provided.
*1. The options that can be selected depend on the type of control output.
*2. The control output cannot be used as a transfer output.
*3. A model with four auxiliary outputs must be selected.
Note: Draw-out-type models of the E5EC and E5AC are available. Ask your OMRON representative for details.
37
E5EC/E5EC-B/E5AC
A B C D E F
Model Control No. of Power Meaning
Terminal
outputs auxiliary supply Input type Options
type
1 and 2 outputs voltage
E5EC 48 96 mm
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
2 2 independent points
4 (auxiliary outputs 1 and 2 with same common and auxiliary
4
outputs 3 and 4 with same common)
A 100 to 240 VAC
D 24 VAC/DC
B Push-in plus terminal
M Universal input
HB alarm
Event Remote Transfer
and Communications
inputs SP Input output
HS alarm
000 --- --- --- --- ---
008 1 RS-485 2 --- ---
010 1 --- 4 --- ---
011 1 --- 6 Provided. Provided.
38
E5EC/E5EC-B/E5AC
Waterproof Cover
Applicable Controller Model
E5EC/E5EC-B Y92A-49N
E5AC Y92A-96N
Mounting Adapter
Model
Y92F-51 (2pcs)
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
39
E5EC/E5EC-B/E5AC
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85 to 110% of rated supply voltage
Models with option selection of 000: 6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or
E5EC/
2.3 W max. at 24 VDC
E5EC-B
All other models: 8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC
Power consumption
Models with option selection of 000: 7.0 VA max. at 100 to 240 VAC, and 4.2 VA max. at 24 VAC or
E5AC 2.4 W max. at 24 VDC
All other models: 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 M min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,
Relay output
minimum applicable load: 5 V, 10 mA (reference value)
Control
Voltage output Output voltage: 12 VDC 20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
output
(for driving SSR) (The maximum load current is 21 mA for models with two control outputs.)
Linear current output * 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: approx. 10,000
E5EC/E5AC: 4
Number of outputs
E5EC-B: 2 or 4 (depends on model)
Auxiliary
output SPST-NO. relay outputs, 250 VAC, Models with 2 outputs: 3 A (resistive load),
Output specifications Models with 4 outputs: 2 A (resistive load),
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
Number of inputs 2, 4 or 6 (depends on model)
Contact input: ON: 1 k max., OFF: 100 k min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output Current output: 4 to 20 mA DC, Load: 500 max., Resolution: Approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 k min., Resolution: Approx. 10,000
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 max.)
Remote SP input
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 M min.)
Potentiometer input * 100 to 10 k
Setting method Digital setting using front panel keys
11-segment digital display and individual indicators
Character height: E5EC/E5EC-B: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm
Indication method E5AC: PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm
Three displays Contents: PV/SV/MV, PV/SV/Multi-SP, or PV/SV/Remaining soak time, etc
Numbers of digits: 4 digits each for PM, SV, and MV displays
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations,
Multi SP
or serial communications.
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital
Other functions filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, logic operations, temperature status display, simple programming, moving
average of input value, and display brightness setting
10 to 55C (with no condensation or icing), For 3-year warranty: 10 to 50C with standard mounting
Ambient operating temperature
(with no condensation or icing)
Ambient operating humidity 25 to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)
* This function is not supported by the E5EC-B. Refer to Model Number Legend on page 38.
40
E5EC/E5EC-B/E5AC
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor 10 to 60 to 115 to 140 to
Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
specification
2300
2300
1800
1800
1700 1700
1700
1600
1500
1400
Temperature range (°C)
Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29
41
E5EC/E5EC-B/E5AC
Alarm Types
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP
X X
Absolute-value upper- ON ON The alarm will turn ON if the process value is larger than the
8 OFF PV OFF PV
limit 0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
Absolute-value upper- X X
ON ON A standby sequence is added to the absolute-value upper-
10 limit with standby OFF PV OFF PV
0 0 limit alarm (8). *6
sequence
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-
11 OFF PV OFF PV
with standby sequence 0 0 limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
14 OFF SP OFF SP
upper-limit alarm 0 0 is higher than the alarm value (X).
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
15 OFF SP OFF SP
lower-limit alarm 0 0 is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
X X
RSP absolute-value ON ON This alarm type turns ON the alarm when the remote SP
18 OFF RSP OFF RSP
upper-limit alarm *10 0 0 (RSP) is higher than the alarm value (X).
X X
RSP absolute-value ON ON This alarm type turns ON the alarm when the remote SP
19 OFF RSP OFF RSP
lower-limit alarm *10 0 0 (RSP) is lower than the alarm value (X).
42
E5EC/E5EC-B/E5AC
*1. With set values 1, 4 and 5, the upper and lower limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence
be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above *2
“L” and “H.” • Case 1 and 2
*2. Set value: 1, Upper- and lower-limit alarm Always OFF when the upper-limit and lower-limit hysteresis overlaps.
Case 1 Case 2 Case 3 (Always ON) • Case 3: Always OFF
H<0, L<0
H SP L
*5. Set value: 5, Upper- and lower-limit with standby sequence
L H SP SP L H
H<0, L>0
Always OFF when the upper-limit and lower-limit hysteresis
H<0, L>0 H>0, L<0 overlaps.
H L SP |H| ≥ |L|
|H| < |L| |H| > |L| *6. Refer to the E5@C Digital Temperature Controllers User's Manual
H>0, L<0
SP H L |H| ≤ |L|
(Cat. No. H174) for information on the operation of the standby
sequence.
*3. Set value: 4, Upper- and lower-limit range
*7. Refer to the E5@C Digital Temperature Controllers User's Manual
Case 1 Case 2 Case 3 (Always OFF)
(Cat. No. H174) for information on the loop burnout alarm (LBA).
H<0, L<0
L H SP H SP L This setting cannot be used with a position-proportional model.
SP L H
H<0, L>0 *8. Refer to the E5@C Digital Temperature Controllers User's Manual
H<0, L>0 H>0, L<0
|H| < |L| |H| > |L| H L SP |H| ≥ |L| (Cat. No. H174) for information on the PV change rate alarm.
*9. When heating/cooling control is performed, the MV absolute
H>0, L<0
|H| ≤ |L|
upper limit alarm functions only for the heating operation and the
SP H L
MV absolute lower limit alarm functions only for the cooling
operation.
*10.This value is displayed only when a remote SP input is used. It
functions in both Local SP Mode and Remote SP Mode.
43
E5EC/E5EC-B/E5AC
Characteristics
Thermocouple: (0.3% of indication value or 1°C, whichever is greater) 1 digit max. *1
Indication accuracy Platinum resistance thermometer: (0.2% of indication value or 0.8°C, whichever is greater) 1 digit max.
(at the ambient temperature of Analog input: 0.2% FS 1 digit max.
23°C) CT input: 5% FS 1 digit max.
Potentiometer input: 5% FS 1 digit max.
Transfer output accuracy 0.3% FS max.
Remote SP Input Type 0.2% FS 1 digit max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10°C, whichever is greater) 1 digit max.
Other thermocouple input: (1% of indication value or 4°C, whichever is greater) 1 digit max. *3
Influence of voltage *2 Platinum resistance thermometer: (1% of indication value or 2°C, whichever is greater) 1 digit max.
Analog input: 1%FS 1 digit max.
Influence of EMS. CT input: 5% FS 1 digit max.
(at EN 61326-1) Remote SP input: 1% FS 1 digit max.
Input sampling period 50ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or°F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Standard, heating/cooling, or Position-proportional (Close): 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)
Integral time (I)
Position-proportional (Floating): 1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s)*4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Influence of signal source Thermocouple: 0.1°C/ max. (100 max.)
resistance Platinum resistance thermometer: 0.1°C/ max. (10 max.)
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
E5EC/E5EC-B: Controller: Approx. 210 g, Adapter: Approx. 4 g 2
Weight
E5AC: Controller: Approx. 250 g, Adapter: Approx. 4 g 2
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
E5EC/E5AC: CX-Thermo version 4.5 or higher
Setup Tool
E5EC-B: CX-Thermo version 4.65 or higher
E5EC/E5EC-B/E5AC top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a
USB port on the computer.*5
Setup Tool port
E5EC/E5EC-B/E5AC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion
Cable are used together to connect to a USB port on the computer.*5
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some
Approved standards
Standards models only.) *6, Lloyd's standards *7
Conformed standards EN 61010-1 (IEC 61010-1)
EMI EN 61326-1 *8
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326-1 *8
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1. The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and
L thermocouples at any temperatures is 2°C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is 3°C max. The indication accuracy of the R
and S thermocouples at a temperature of 200°C max. is 3°C 1 digit max. The indication accuracy of W thermocouples is (0.3% of PV or 3C,
whichever is greater) 1 digit max. The indication accuracy of PL II thermocouples is (0.3% of PV or 2°C, whichever is greater) 1 digit max.
*2. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3. K thermocouple at -100°C max.: 10°C max.
*4. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6. Refer to your OMRON website for the most recent information on applicable models.
*7. Refer to information on maritime standards in Shipping Standards on page 110 for compliance with Lloyd's Standards.
*8. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
44
E5EC/E5EC-B/E5AC
500
be individually set using the Communications Setting Level. 300
45
E5EC/E5EC-B/E5AC
External Connections
E5EC/E5AC (Screw Terminal)
E5EC-@@ 4 @ 5 M - @ @ @ E5AC-@@ 4 @ 5 M - @ @ @
(1) (2) (3) (4) (5) (6) (1) (2) (3) (4) (5) (6) The E5EC is set for a K-type thermocouple (input
↑ ↑ type = 5) by default. An input error (s.err) will occur
if the input type setting does not agree with the
Terminal type Terminal type temperature sensor. Check the input type.
Control output 1 Control output 2 Auxiliary outputs 1, 2, 3, 4 (6) Options
Relay output Relay output Relay output 004 005 009 010
250 VAC, 5 A 250 VAC, 5 A Models with 4 auxiliary Communications 4 event inputs Communications, 2 event 4 event inputs
(resistive load) (resistive load) outputs: 250 VAC, 2 A and 2 event inputs inputs, and 2 CT inputs and 1 CT input
Voltage output Voltage output (resistive load) B(+) B(+)
(for driving SSR) 13 (-) 13 13 (-) 13
(for driving SSR) RS-485 RS-485
12 VDC, 40 mA 12 VDC, 21 mA 14 14 14 14
A(-) EV3 A(-) EV3
When There Is a Linear current output 15 15 15 15
EV4 EV4
Control Output 2: 0 to 20 mA DC (-) 16 (-) 16 (-) 16 (-) 16
21 mA 4 to 20 mA DC 17 17 17 17
Linear current output Load: 500 Ω max. EV1 EV1 EV1 EV1
0 to 20 mA DC 18 18 18 18
EV2 EV2 EV2 EV2
4 to 20 mA DC 19 19 19 19
CT1 CT1
Load: 500 Ω max. 20 20 COM 20 20
CT2
21 21 21 21
(1) Control output
RX QX CX
011
Models with Models with 1 Models with 1
1 Relay Output
6 event Inputs, 1 CT input,
Voltage Output Linear Current Output
(for Driving SSR) transfer output, and remote SP input
46
E5EC/E5EC-B/E5AC
E5EC-@@ @ @ B M - @ @ @
(1) (2) (3) (4) (5) (6)
↑
Terminal type
To another E5@C
47
E5EC/E5EC-B/E5AC
Isolation/Insulation Block Diagrams
Models with 2 Auxiliary Outputs Models with 4 Auxiliary Outputs
Sensor input, CT inputs, and remote SP input Sensor input, CT inputs, potentiometer input, and remote SP input
Voltage output (for driving SSR) and transfer output Voltage output (for driving SSR),
Power Power linear current output, and transfer output
Supply Supply
Relay output
Relay output
Auxiliary output 1
Auxiliary outputs 1, 2
Auxiliary output 2
Auxiliary outputs 3, 4
Nomenclature
E5EC/E5EC-B
Front panel
No. 1 display
Top View of E5EC Top View of E5EC-B
PV or specified parameter
Temperature unit
No. 2 display
Operation indicators
SP or specified parameter value
No. 3 display
Front-panel Setup Tool port Manipulated value or other value
E5AC
Front Panel
No. 2 display
Top-panel
Press the U or D Key to set the parameter.
Setup
Tool port
48
E5EC/E5EC-B/E5AC
Dimensions (Unit: mm)
Controllers
E5EC
(64)
4
48 60 44
1
96 110 91
Waterproof
Packing (Accessory) Mounting Adapter
(Accessory)
E5EC-B 4
(71.4)
67.4
(1)
48 44
96 110 91
• Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58-
CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the top panel. The E58-CIFQ2 USB-Serial Conversion Cable and
E58-CIFQ2-E Communications Conversion Cable are required to connect to the port on the front panel. (You cannot leave either port
connected constantly during operation.)
60 min.
45-0.6
0
92+0.8
0
92-0.8
0
120 min.
49
E5EC/E5EC-B/E5AC
E5AC (64)
4
60
96 x 96 1 91 x 91
110 91
Waterproof
Packing (Accessory) Mounting Adapter
(Accessory)
• Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the
Digital Temperature Controller. The E58-CIFQ2 USB-Serial Conversion Cable is required to
connect to the port on the top panel. The E58-CIFQ2 USB-Serial Conversion Cable and E58-
CIFQ2-E Communications Conversion Cable are required to connect to the port on the front panel.
(You cannot leave either port connected constantly during operation.)
92+0.8
0
50
E5EC/E5EC-B/E5AC
LED (RD)
USB connector
(type A plug)
LED (PWR) Serial connector
LED (SD)
Conversion Cable
E58-CIFQ2-E
Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510) 250 263 1510
51
E5EC/E5EC-B/E5AC
21.9 21.9
(2) (2)
131.7 131.7
Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15
(Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 4002
25 3
Winding resistance: 182
10.5 100V
40 10 ∞ Distortion
1kΩ factor
Two, 3.5 dia.
10%
1
10 3%
1%
100mV
30
10 100Ω
E54-CT3
2.36 dia. 1 RL=10Ω
30
12 dia.
9 100μV
10
1 10 100mA 1 10 100 1,000A
40 × 40
Thru-current (Io) A (r.m.s.)
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
Two, M3 (depth: 4) E54-CT3
Maximum continuous heater current: 120 A (50/60 Hz)
15
(Maximum continuous heater current for an OMRON Digital
Temperature Controller is 50 A.)
30
Number of windings: 4002
Winding resistance: 80.8
E54-CT3 Accessories 100V
Output voltage (Eo) V (r.m.s.)
Frequency: 50 Hz
• Armature Connection Example Distortion
∞
10 factor
Armature 1kΩ
10%
Approx. 3 dia. Plug 500Ω 3%
1 1%
Lead
100mV
100Ω
18 50Ω
10
RL=10Ω
• Plug
1
(22) 10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
52
MEMO
53
Digital Temperature Controller
• A white PV display (height: 8.5 mm) is easy to read when setting up,
checking alarms, and making settings in a control panel.
Event Inputs
• None
• PF (shift) Key
•1
• Temperature status display
• Simple programming
Serial Communications
• Independent heating and
• None cooling PID control
• RS-485 • Changed parameter display
• Display brightness setting
54
E5DC
Model Number Legend and Standard Models
Model Number Legend
Models with Screw Terminal
E5DC-@@ @ @ @ M-@@@ (Example: E5DC-RX0ASM-015)
A B C D E F
A B C D E F
Model No. of Power Meaning
Control Terminal Input
auxiliary supply Options
output 1 type type
outputs voltage
E5DC 22.5 mm wide and mounts to DIN Track
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*1 CX Linear current output *1 None
0 None
2 2 (one common)
A 100 to 240 VAC
D 24 VAC/DC
S Screw terminal (Main Unit and Terminal Unit together)
U Main Unit only (no Terminal Unit)
M Universal input
HB alarm and HS alarm Communications Event input
*2 000 --- --- ---
*3 002 1 RS-485 ---
*4 015 --- RS-485 ---
*5 016 --- --- 1
*3 017 1 --- 1
*1. The control output can be used as a simple transfer output for the Digital Temperature Controllers manufactured in July 2014 or later.
*2. Option 000 can be selected only if two auxiliary outputs are selected.
*3. Options 002 and 017 can be selected only if the control output is a relay output or voltage output and two auxiliary outputs are selected.
*4. Option 015 cannot be selected if the control output is a relay output or voltage output and two auxiliary outputs are selected.
*5. Options 016 can be selected only if the control output is a linear current output and two auxiliary outputs are selected.
List of Models
Options Model Model
No. of auxiliary
Control output HB alarm and HS Power supply voltage Power supply voltage
outputs No. of event inputs Communications
alarm 100 to 240 VAC 24 VAC/DC
E5DC-RX0ASM-015 E5DC-RX0DSM-015
--- RS-485
E5DC-RX0AUM-015 E5DC-RX0DUM-015
---
E5DC-RX2ASM-000 E5DC-RX2DSM-000
--- ---
E5DC-RX2AUM-000 E5DC-RX2DUM-000
Relay output
E5DC-RX2ASM-002 E5DC-RX2DSM-002
2 RS-485
Detection for single- E5DC-RX2AUM-002 E5DC-RX2DUM-002
phase heater E5DC-RX2ASM-017 E5DC-RX2DSM-017
1 ---
E5DC-RX2AUM-017 E5DC-RX2DUM-017
E5DC-QX0ASM-015 E5DC-QX0DSM-015
--- RS-485
E5DC-QX0AUM-015 E5DC-QX0DUM-015
---
E5DC-QX2ASM-000 E5DC-QX2DSM-000
--- ---
Voltage output E5DC-QX2AUM-000 E5DC-QX2DUM-000
(for driving SSR) E5DC-QX2ASM-002 E5DC-QX2DSM-002
2 RS-485
Detection for single- E5DC-QX2AUM-002 E5DC-QX2DUM-002
phase heater E5DC-QX2ASM-017 E5DC-QX2DSM-017
1 ---
E5DC-QX2AUM-017 E5DC-QX2DUM-017
E5DC-CX0ASM-015 E5DC-CX0DSM-015
--- RS-485
E5DC-CX0AUM-015 E5DC-CX0DUM-015
E5DC-CX2ASM-000 E5DC-CX2DSM-000
--- ---
Linear current E5DC-CX2AUM-000 E5DC-CX2DUM-000
---
output E5DC-CX2ASM-015 E5DC-CX2DSM-015
2 RS-485
E5DC-CX2AUM-015 E5DC-CX2DUM-015
E5DC-CX2ASM-016 E5DC-CX2DSM-016
1 ---
E5DC-CX2AUM-016 E5DC-CX2DUM-016
55
E5DC
Short Bars
Model
Y92S-P11 (4 pcs)
56
E5DC
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85 to 110% of rated supply voltage
Power consumption 4.9 VA max. at 100 to 240 VAC, and 2.8 VA max. at 24 VDC or 1.5 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70C, 60 to 120C, 115 to 165C, or 140 to 260C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 M min. (Use a 1:1 connection when connecting the ES2-HB/
Input impedance
THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5
Relay output
V, 10 mA (reference value)
Control
Voltage output
output Output voltage 12 VDC 20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: Approx. 10,000
Number of outputs 2 (depends on model)
Auxiliary
output SPST-NO relay outputs: 250 VAC, 2 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
Number of inputs 1 (depends on model)
Event Contact input ON: 1 k max., OFF: 100 k min.
input External contact input
Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.
specifications
Current flow: approx. 7 mA per contact
Setting method Digital setting using front panel keys
11-segment digital displays and individual indicators
Indication method
Character height: PV: 8.5 mm, SV: 8.0 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or
Multi SP
serial communications. *1
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter,
Other functions self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV
change rate limit, logic operations, temperature status display, simple programming, moving average of
input value, display brightness setting, simple transfer output, *2 and work bit message *2
10 to 55C (with no condensation or icing), For 3-year warranty: 10 to 50C with standard mounting (with
Ambient operating temperature
no condensation or icing)
Ambient operating humidity 25 to 85%
Storage temperature 25 to 65C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)
*1. Only two set points are selectable for event inputs.
*2. Usage is possible for the Digital Temperature Controllers manufactured in July 2014 or later.
57
E5DC
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor 10 to 60 to 115 to 140 to
Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
specification
2300
2300
1800
1800
1700 1700
1700
1600
1500
1400
1300 1300 1300
1300
Temperature range (°C)
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 -199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.
Analog input
Input type Current Voltage
Input specification 4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29
58
E5DC
Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.)
Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
Absolute-value upper- ON
X
ON
X The alarm will turn ON if the process value is larger than the
8
limit OFF
0
PV OFF
0
PV alarm value (X) regardless of the set point.
ON
X
ON
X The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF
0
PV OFF
0
PV alarm value (X) regardless of the set point.
Absolute-value upper-
ON
X
ON
X A standby sequence is added to the absolute-value upper-
10 limit with standby OFF
0
PV OFF
0
PV limit alarm (8). *6
sequence
Absolute-value lower-limit ON
X
ON
X A standby sequence is added to the absolute-value lower-
11
with standby sequence OFF
0
PV OFF
0
PV limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
SP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the set point (SP)
14
upper-limit alarm OFF
0
SP OFF
0
SP is higher than the alarm value (X).
SP absolute-value ON
X
ON
X This alarm type turns ON the alarm when the set point (SP)
15
lower-limit alarm OFF
0
SP OFF
0
SP is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
59
E5DC
*1. With set values 1, 4, and 5, the upper- and lower-limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence
be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above at *2
“L” and “H.” • In cases 1 and 2 above, the alarm is always OFF if the upper-
*2. Set value: 1, Upper- and lower-limit alarm and lower-limit hysteresis overlaps.
Case 1 Case 2 Case 3 (Always OFF) • In case 3, the alarm is always OFF.
H<0, L<0 *5. Set value: 5, Upper- and lower-limit alarm with standby sequence
L H SP SP L H H SP L The alarm is always OFF if upper- and lower-limit hysteresis
H<0, L>0 overlaps.
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| *6. Refer to the E5@C Digital Temperature Controllers User’s Manual
|H| < |L| |H| > |L|
H>0, L<0 (Cat. No. H174) for information on the operation of the standby
SP H L |H| ≤ |L| sequence.
*3. Set value: 4, Upper- and lower-limit range *7. Refer to the E5@C Digital Temperature Controllers User’s Manual
Case 1 Case 2 Case 3 (Always ON) (Cat. No. H174) for information on the LBA.
H<0, L<0 *8. Refer to the E5@C Digital Temperature Controllers User’s Manual
L H SP SP L H H SP L (Cat. No. H174) for information on the PV change rate alarm.
H<0, L>0 H>0, L<0
H<0, L>0 *9. When heating/cooling control is performed, the MV absolute-
H L SP |H| ≥ |L| value upper-limit alarm functions only for the heating operation
|H| < |L| |H| > |L|
H>0, L<0 and the MV absolute-value lower-limit alarm functions only for the
SP H L |H| ≤ |L| cooling operation.
60
E5DC
Characteristics
Thermocouple: (0.3 % of indication value or 1C, whichever is greater) 1 digit max.*1
Indication accuracy
Platinum resistance thermometer: (0.2 % of indication value or 0.8C, whichever is greater) 1 digit max.
(when mounted individually,
Analog input: 0.2% FS 1 digit max.
ambient temperature of 23C)
CT input: 5% FS 1 digit max.
Simple transfer output accuracy 0.3% FS max.*2
Influence of temperature *3 Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10C, whichever is greater) 1 digit
max.
Influence of voltage *3 Other thermocouple input: (1% of indication value or 4C, whichever is greater) 1 digit max. *4
Platinum resistance thermometer: (1% of indication value or 2C, whichever is greater) 1 digit max.
Influence of EMS. Analog input: 1% FS 1 digit max.
(at EN 61326-1) CT input: 5% FS 1 digit max.
R, S, B, W, or PLII thermocouple: (1% of PV or 10C, whichever is greater) 1 digit max.
Installation influence (E5DC only)
Other thermocouple: (1% of PV or 4C, whichever is greater) 1 digit max. *4
Input sampling period 50 ms
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range 1,999 to 9,999 (decimal point position depends on input type)
Influence of signal source
Thermocouple: 0.1C/ max. (100 max.), Platinum resistance thermometer: 0.1C/ max. (10 max.)
resistance
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hr each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
Weight Main unit: Approx. 80 g, Terminal unit: Approx. 40 g
Degree of protection Main unit: IP20, Terminal unit: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.6 or higher
E5DC bottom panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the
computer. *6
Setup Tool port
E5DC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable are
used together to connect a USB port on the computer.*6
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some
Approved standards
Standards models only.) *7, Lloyd's standards *8
Conformed standards EN 61010-1 (IEC 61010-1)
EMI: EN61326-1 *9
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A
Noise Terminal Voltage: EN55011 Group 1, class A
EMS: EN61326-1 *9
ESD Immunity: EN61000-4-2
EMC
Electromagnetic Field Immunity: EN61000-4-3
Burst Noise Immunity: EN61000-4-4
Conducted Disturbance Immunity: EN61000-4-6
Surge Immunity: EN61000-4-5
Voltage Dip/Interrupting Immunity: EN61000-4-11
*1. The indication accuracy of K thermocouples in the 200 to 1,300C range, T and N thermocouples at a temperature of 100C max., and U
and L thermocouples at any temperature is 2C 1 digit max. The indication accuracy of B thermocouples at a temperature of 400C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800C is 3C max.
The indication accuracy of R and S thermocouples at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W
thermocouples is (0.3% of PV or 3C, whichever is greater) 1 digit max.
The indication accuracy of PLII thermocouples is (0.3% of PV or 2C, whichever is greater) 1 digit max.
*2. However, the precision between 0 and 4 mA for a 0 to 20 mA output is 1% FS max.
*3. Ambient temperature: 10C to 23C to 55C, Voltage range: 15% to 10% of rated voltage
*4. K thermocouple at 100C max.: 10C max.
*5. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6. External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time.
*7. Refer to your OMRON website for the most recent information on applicable models.
*8. Refer to information on maritime standards in Shipping Standards on page 110 for compliance with Lloyd's Standards.
*9. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
61
E5DC
500
response wait time Default: 20 ms
300
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
100
Communications Functions
50
You can use the memory in the PLC to read and write
E5@C parameters, start and stop operation, etc. 30
62
E5DC
External Connections
E5DC
Control output Auxiliary outputs 1, 2
The E5DC is set for a K-type thermocouple (input type = 5) by default.
Relay output Relay outputs An input error (s.err) will occur if the input type setting does not agree
250 VAC, 3 A (resistive load) 250 VAC: 2 A (resistive load) with the temperature sensor. Check the input type.
Voltage output (for driving SSR)
12 VDC, 21 mA
Linear current output E5DC M
0 to 20 mA DC Control output Options
4 to 20 mA DC
Load: 500 Ω max. Input Power Supply Control Output
100 to 240 VAC 24 VAC/DC RX QX CX
1 relay 1 voltage output 1 linear
1 1 output (for driving SSR) current output
2 2 5 5 +Q 5 + C
R
6 6 - 6 -
(no polarity)
1 5 9
2 6 10 Auxiliary Outputs
Options
9
002 11 Auxiliary output 2
10
Communications and 1 CT Auxiliary output 1
B(+) 11
3 7
RS-485 CT1
4 8
A(-)
016 4 8 14
One event input
(-) 3 7
4 8
EV1
017
One event input and 1 CT
(-) 3 7
CT1
4 8
EV1
Relay output
: Reinforced insulation
: Functional isolation
63
E5DC
Nomenclature
E5DC Front panel
Use S Key to change the digit (default setting). Front-panel Setup Tool port
Controllers
E5DC (85)
4 81
22.5 22.5
96 35 110 91
Mounting Adapter
(Accessory: Sold separately)
The above figure shows the
Terminal Unit attached to
• Setup Tool ports are provided as standard feature. Use these ports to connect a computer to
the Main Unit. the Digital Temperature Controller. The E58-CIFQ2 USB-Serial Conversion Cable is required
to connect to the port on the bottom panel. The E58-CIFQ2 USB-Serial Conversion Cable and
E58-CIFQ2-E Communications Conversion Cable are required to connect to the port on the
front panel. (You cannot leave either port connected constantly during operation.)
92 +0.8
0 92 +0.8 92 +0.8
0 0
120 min
64
E5DC
Accessories (Order Separately)
Terminal Unit
E5DC-SCT1S
22.5 30.7
91 35
LED (RD)
USB connector
(type A plug)
LED (PWR) Serial connector
LED (SD)
Conversion Cable
E58-CIFQ2-E
Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510) 250 263 1510
65
E5DC
● Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
15
2.8 (Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 4002
25 3
Winding resistance: 182
10.5 100V
40 ∞
10 Distortion
Two, 3.5 dia. 1kΩ factor
10%
1
10 3%
1%
100mV
30
100μV
40 × 40
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
Frequency: 50 Hz
Distortion
Lead ∞
10 factor
1kΩ
10%
500Ω 3%
1 1%
18
100mV
• Plug 100Ω
50Ω
10
RL=10Ω
Approx. 6 dia.
1
(22)
100μV
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
66
E5DC
12
24.8
11.5
7.3±0.15
10 1.3
4.5
M4 spring washer 4.8
35±0.3 27±0.15
15 25 25 25 25 15 (5) * 1
10 10
1000 (500) *
16.5
End Cover
Y92F-54 (Two included.)
3.9 5.3
67
Programmable Temperature Controller (Digital Controller)
the computer with a Communications Conversion Cable (sold Refer to your OMRON website for the most recent
information on applicable safety standards.
separately). Setup is easy with the CX-Thermo (sold separately).
• Easy connections to a PLC with programless communications. Use Refer to Safety Precautions on page 108.
68
E5CC-T
Model Number Legend and Standard Models
Model Number Legend
Models with Screw Terminal
E5CC-T @@3 @5 M -@@@ (Example: E5CC-TRX3A5M-000)
A BC D E F
A B C D E F
Model No. of Power Meaning
Control outputs Terminal Input
auxiliary supply Options
1 and 2 type type
outputs voltage
E5CC-T 48 48 mm Programmable Type
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*1 CX Linear current output *2 None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
CQ Linear current output *2
(for driving SSR)
3 3 (one common)
A 100 to 240 VAC
D 24 VAC/DC
5 Screw terminal (with cover)
M Universal input
HB alarm
Communica- Event Transfer
and HS
tions inputs output
alarm
000 --- --- --- ---
*1 001 1 --- 2 ---
2 (for 3-
*1 003 phase RS-485 --- ---
heaters)
*3 004 --- RS-485 2 ---
005 --- --- 4 ---
006 --- --- 2 Provided.
*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output.
*2. The linear current output cannot be used as a transfer output.
*3. Option 004 can be selected only when “CX” is selected for the control outputs.
69
E5CC-T
Adapter
Model
Y92F-45
Note: Use this Adapter when the panel has already been prepared for
an E5B@ Controller.
Waterproof Cover
Model
Y92A-48N
Mounting Adapter
Model
Y92F-49
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
70
E5CC-T
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85 to 110% of rated supply voltage
Power consumption 7.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 M min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method 2-PID control (with auto-tuning) or ON/OFF control
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:
Relay output
5 V, 10 mA (reference value)
Control
Voltage output
output Output voltage: 12 VDC 20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: approx. 10,000
Number of outputs 3
Auxiliary
output SPST-NO relay outputs, 250 VAC, Models with 3 outputs: 2 A (resistive load), Electrical life: 100,000
Output specifications
operations, Minimum applicable load: 10 mA at 5 V (reference value)
Number of inputs 2 or 4 (depends on model)
Contact input: ON: 1 k max., OFF: 100 k min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output Current output: 4 to 20 mA DC, load: 500 max., resolution: approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 k min., resolution: Approx. 10,000
Setting method Digital setting using front panel keys
11-segment digital display and individual indicators
Indication method
Character height: PV: 15.2 mm, SV: 7.1 mm
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout (HB)
alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust
Other functions
tuning, PV input shift, protection functions, extraction of square root, MV change rate limit, logic
operations, temperature status display, moving average of input value, and display brightness setting
10 to 55C (with no condensation or icing), For 3-year warranty: 10 to 50C with standard mounting
Ambient operating temperature
(with no condensation or icing)
Ambient operating humidity 25 to 85%
Storage temperature 25 to 65C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)
71
E5CC-T
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor 10 to 60 to 115 to 140 to
Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
specification
2300
2300
1800
1800
1700 1700
1700
1600
1500
Temperature range (°C)
1400
1300 1300 1300
1300
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.
Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29
72
E5CC-T
Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP
X X
Absolute-value upper- ON ON The alarm will turn ON if the process value is larger than the
8 OFF PV OFF PV
limit 0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
Absolute-value upper- X X
ON ON A standby sequence is added to the absolute-value upper-
10 limit with standby OFF PV OFF PV
0 0 limit alarm (8). *6
sequence
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-
11 OFF PV OFF PV
with standby sequence 0 0 limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
14 OFF SP OFF SP
upper-limit alarm 0 0 is higher than the alarm value (X).
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
15 OFF SP OFF SP
lower-limit alarm 0 0 is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
73
E5CC-T
*1. With set values 1, 4 and 5, the upper and lower limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence
be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above *2
“L” and “H.” • Case 1 and 2
*2. Set value: 1, Upper- and lower-limit alarm Always OFF when the upper-limit and lower-limit hysteresis overlaps.
Case 1 Case 2 Case 3 (Always ON)
H<0, L<0
• Case 3: Always OFF
L H SP SP L H H SP L *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 Always OFF when the upper-limit and lower-limit hysteresis
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| overlaps.
|H| < |L| |H| > |L|
H>0, L<0 *6. Refer to the E5@C-T Digital Temperature Controllers
SP H L |H| ≤ |L| Programmable Type User's Manual (Cat. No. H185) for
*3. Set value: 4, Upper- and lower-limit range information on the operation of the standby sequence.
Case 1 Case 2 Case 3 (Always OFF)
*7. Refer to the E5@C-T Digital Temperature Controllers
H<0, L<0 Programmable Type User's Manual (Cat. No. H185) for
L H SP SP L H H SP L information on the loop burnout alarm (LBA).
H<0, L>0 H>0, L<0 H<0, L>0 *8. Refer to the E5@C-T Digital Temperature Controllers
|H| < |L| |H| > |L| H L SP |H| ≥ |L| Programmable Type User's Manual (Cat. No. H185) for
H>0, L<0 information on the PV change rate alarm.
SP H L |H| ≤ |L| *9. When heating/cooling control is performed, the MV absolute
upper limit alarm functions only for the heating operation and the
MV absolute lower limit alarm functions only for the cooling
operation.
74
E5CC-T
Characteristics
Thermocouple: (0.3% of indication value or 1°C, whichever is greater) 1 digit max. *1
Indication accuracy Platinum resistance thermometer: (0.2% of indication value or 0.8°C, whichever is greater) 1 digit max.
(at the ambient temperature of 23°C) Analog input: 0.2% FS 1 digit max.
CT input: 5% FS 1 digit max.
Transfer output accuracy 0.3% FS max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10°C, whichever is greater) 1 digit
max.
Influence of voltage *2 Other thermocouple input: (1% of indication value or 4°C, whichever is greater) 1 digit max. *3
Platinum resistance thermometer: (1% of indication value or 2°C, whichever is greater) 1 digit max.
Influence of EMS. Analog input: 1%FS 1 digit max.
(at EN 61326-1) CT input: 5% FS 1 digit max.
Input sampling period 50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1°C/ max. (100 max.)
Influence of signal source resistance
Platinum resistance thermometer: 0.1°C/ max. (10 max.)
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
Weight Controller: Approx. 120 g, Adapter: Approx. 10 g
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.61 or higher
E5CC-T top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port on
Setup Tool port
the computer. *5
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some
Approved standards
Standards models only.) *6
Conformed standards EN 61010-1 (IEC 61010-1)
EMI: EN 61326-1 *7
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326-1 *7
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1. The indication accuracy of K thermocouples in the 200 to 1300C range, T and N thermocouples at a temperature of 100C max., and U
and L thermocouples at any temperatures is 2C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800C is 3C max. The indication accuracy of the R
and S thermocouples at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W thermocouples is (0.3% of PV or
3C, whichever is greater) 1 digit max. The indication accuracy of PL II thermocouples is (0.3% of PV or 2C, whichever is greater) 1
digit max.
*2. Ambient temperature: 10°C to 23C to 55C, Voltage range: 15% to 10% of rated voltage
*3. K thermocouple at 100C max.: 10C max.
*4. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6. Refer to your OMRON website for the most recent information on applicable models.
*7. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
75
E5CC-T
Program Control
Number of programs (patterns) 8
Number of segments (steps) 32
Time setting (Segment set with set point and time.)
Segment setting method
Slope setting (Segment set with segment type, set point, slope, and time.)
0 h 0 min to 99 h 59 min
Segment times
0 min 0 s to 99 min 59 s
Alarm setting Set separately for each program.
Reset operation Select either stopping control or fixed SP operation.
Startup operation Select continuing, resetting, manual operation, or run mode.
Number of sets 8
PID sets
Setting method Set separately for each program (automatic PID group selection also supported).
Alarm SP function Select from ramp SP and target SP.
Segment operation Advance, segment jump, hold, and wait
Program status control
Program operation Program repetitions and program links
Wait method Waiting at segment ends
Wait operation
Wait width setting Same wait width setting for all programs
Number of outputs 2
Number of ON/OFF
Time signals 1 each per output
Operations
Setting method Set separately for each program.
Program status output Program end output (pulse width can be set), run output, stage output
PV start Select from segment 1 set point, slope-priority PV start
Program startup operation 0 h 0 min to 99 h 59 min
Standby
0 day 0 h to 99 day 23h
Operation end operation Select from resetting, continuing control at final set point, and fixed SP control.
Program SP shift Same program SP shift for all programs
76
E5CC-T
500
response wait time Default: 20 ms 300
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
100
Communications Functions 50
30
You can use the memory in the PLC to read and
write E5@C-T parameters, start and reset
operation, etc. The E5@C-T automatically
10
performs communications with PLCs. No
communications programming is required. 5
Number of connected Digital Temperature E5CC-T
Programless 3 250 VAC, 30 VDC
Controllers: 32 max.
communications * Applicable PLCs
(resistive load)
cosφ = 1
OMRON PLCs
1
CS Series, CJ Series, or 0 1 2 3 4 5 6
CP Series
Mitsubishi Electric PLCs Switching current (A)
MELSEC Q Series, L Series
77
E5CC-T
External Connections
E5CC-T
Control output 1
Relay output
250 VAC, 3 A E5CC T 3 5M
(1) (2) (3) (4) (5) (6)
(resistive load)
Voltage output Terminal type
(for driving SSR)
12 VDC, 21 mA Auxiliary outputs
Control output 2 The E5CC-T is set for a K-type thermocouple (input
Linear current output Relay output
0 to 20 mA DC Voltage output type = 5) by default. An input error (s.err) will occur
Models with 3 auxiliary outputs:
4 to 20 mA DC (for driving SSR) if the input type setting does not agree with the
250 VAC: 2 A
Load: 500 Ω max. 12 VDC, 21 mA (resistive load) temperature sensor. Check the input type.
(6) Options
001 003 004 005 006
Event inputs 1 and 2, Communications Communications (RS-485) Event inputs 1 to 4 Event inputs 1 and 2, and
and CT1 (RS-485), CT1, and CT2 and event inputs 3 and 4 transfer output
(−) B(+) B(+) (−)
13 13 13 (−) 13 13
RS-485 RS-485
14 14 14 14 14
EV1 A(−) A(−) EV1 EV1
EV2 15 15 15 EV2
15 EV2
15
16 16 (−)
16 (−) 16 16 +
CT1
17
CT1
COM 17 17 17 17 +V Transfer output
CT2 EV3 EV3 I
18 18 EV4 18 18 18 −
EV4
Relay output
Auxiliary outputs 1, 2, 3
: Reinforced insulation
: Functional isolation
78
E5CC-T
Nomenclature
E5CC-T Front panel
Temperature unit
Use the M Key to change to another parameter. Press U Key for at least 1 second
when Process value/Set point
Press M and D Keys simultaneously for at parameter are displayed in Program
least 1 second to switch between run and reset SP Mode to go to Display Segment
status. Selection parameter in Program
Setting Level.
Controllers
E5CC-T
Panel Cutout
Mounted Separately Group Mounted
(64) (48 × number of units - 2.5)+1.0
0
4 60
48 × 48 1 48 × 48
45+0.6
0
allow waterproofing.
45+0.6
0
79
E5CC-T
LED (RD)
USB connector
(type A plug)
LED (PWR) Serial connector
LED (SD)
10
Terminal Cover
(E53-COV23)
22 44.8
9.1
Waterproof Packing
Y92S-P8 (for DIN 48 48) The Waterproof Packing is provided with the Temperature Controller.
Order the Waterproof Packing separately if it becomes lost or damaged.
The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site.
Consider three years as a rough standard.)
80
E5CC-T
Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15 (Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 4002
25 3
Winding resistance: 182
10.5
100V
10 100Ω
E54-CT3
2.36 dia.
30 RL=10Ω
1
12 dia.
9
100μV
10
40 × 40 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
Frequency: 50 Hz
Armature Distortion
Approx. 3 dia. Plug ∞
10 factor
1kΩ
10%
Lead 500Ω 3%
1 1%
100mV
18
100Ω
50Ω
• Plug 10
RL=10Ω
1
Approx. 6 dia.
100μV
(22)
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
81
E5CC-T
Adapter
Y92F-45 Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@.
2. Only black is available.
3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial
Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel.
4. You cannot use this Adapter together with the Y92F-49 Adapter that is provided with the E5CC-T Temperature
Controller.
Fixture (Accessory)
4.7 76
69.6 to 77.6
72 × 72
67 × 67 87
48 × 48
2.2 4.7
62.8
To back of the E5CC-T
Mounted to E5CC-T
48
80.5
82
E5CC-T
87.7 69
79.2
12
67.6 28.9
83
Programmable Temperature Controller (Digital Controller)
Control Output 2
Event Inputs
• Voltage output (for driving SSR)
• None • Relay output
•2 • Linear current output
• PF (shift) Key
•4
• Setup Tool port on front panel
•6
• Temperature status display Auxiliary Outputs
• Operating and editting the program •4
Serial Communications • Independent heating and
• None cooling PID control
Transfer Output
• RS-485 • Parameter mask setting
• Display brightness setting • None
•1
84
E5EC-T/E5AC-T
Model Number Legend and Standard Models
Model Number Legend
Models with Screw Terminal
E5EC-T@@ 4 @ 5 M -@@@ (Example: E5EC-TRX4A5M-000)
A BC D E F
E5AC-T@@ 4 @ 5 M -@@@ (Example: E5AC-TRX4A5M-000)
A BC D E F
A B C D E F
Model No. of Power Meaning
Control outputs Terminal Input
auxiliary supply Options
1 and 2 type type
outputs voltage
E5EC-T 48 96 mm Programmable Type
E5AC-T 96 96 mm Programmable Type
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*2 CX Linear current output None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
QR Relay output
(for driving SSR)
RR Relay output Relay output
*2 CC Linear current output Linear current output
Voltage output
*2 CQ Linear current output
(for driving SSR)
Position-proportional relay Position-proportional
PR
output relay output
4 (auxiliary outputs 1 and 2 with same common and
4
auxiliary outputs 3 and 4 with same common)
A 100 to 240 VAC
D 24 VAC/DC
5 Screw terminal (with cover)
Control outputs 1 and 2 M Universal input
For RX,
QX, QQ, For CX or
For PR HB alarm and Event
QR, RR, or CC Communications Transfer output
HS alarm inputs
CQ
Selectable Selectable Selectable 000 --- --- --- ---
Option
selection Selectable Selectable 004 --- RS-485 2 ---
conditions Selectable 005 --- --- 4 ---
*1 Selectable 008 1 RS-485 2 ---
Selectable 010 1 --- 4 ---
Selectable 019 1 --- 6 Provided.
Selectable 021 --- --- 6 Provided.
Selectable Selectable 022 --- RS-485 4 Provided.
*1. The options that can be selected depend on the type of control output.
*2. The linear current output cannot be used as a transfer output.
85
E5EC-T/E5AC-T
Waterproof Packing
Applicable Controller Model
E5EC-T Y92S-P9
E5AC-T Y92S-P10
Note: This Waterproof Packing is provided with the Digital
Temperature Controller.
Waterproof Cover
Applicable Controller Model
E5EC-T Y92A-49N
E5AC-T Y92A-96N
Mounting Adapter
Model
Y92F-51 (2pcs)
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
86
E5EC-T/E5AC-T
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85 to 110% of rated supply voltage
E5EC-T 8.7 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC
Power consumption
E5AC-T 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 M min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method 2-PID control (with auto-tuning) or ON/OFF control
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,
Relay output
minimum applicable load: 5 V, 10 mA (reference value)
Control
Voltage output Output voltage: 12 VDC 20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
output
(for driving SSR) (The maximum load current is 21 mA for models with two control outputs.)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: approx. 10,000
Number of outputs 4
Auxiliary
output SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
Number of inputs 2, 4 or 6 (depends on model)
Contact input: ON: 1 k max., OFF: 100 k min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output Current output: 4 to 20 mA DC, Load: 500 max., Resolution: Approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 k min., Resolution: Approx. 10,000
Potentiometer input 100 to 10 k
Setting method Digital setting using front panel keys
11-segment digital display and individual indicators
Character height: E5EC-T: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm
E5AC-T: PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm
Indication method
Three displays. Contents: PV, SP, program No. and segment No., remaining segment time, or MV
(valve opening)
Numbers of digits: 4 digits
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout (HB)
alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust
Other functions
tuning, PV input shift, protection functions, extraction of square root, MV change rate limit, logic
operations, temperature status display, moving average of input value, and display brightness setting
10 to 55C (with no condensation or icing), For 3-year warranty: 10 to 50C with standard mounting
Ambient operating temperature
(with no condensation or icing)
Ambient operating humidity 25 to 85%
Storage temperature 25 to 65C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)
87
E5EC-T/E5AC-T
Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor 10 to 60 to 115 to 140 to
Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
specification
2300
2300
1800
1800
1700 1700
1700
1600
1500
1400
1300 1300 1300
Temperature range (°C)
1300
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.
Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29
88
E5EC-T/E5AC-T
Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP
X X
Absolute-value upper- ON ON The alarm will turn ON if the process value is larger than the
8 OFF PV OFF PV
limit 0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
Absolute-value upper- X X
ON ON A standby sequence is added to the absolute-value upper-
10 limit with standby OFF PV OFF PV
0 0 limit alarm (8). *6
sequence
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-
11 OFF PV OFF PV
with standby sequence 0 0 limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
14 OFF SP OFF SP
upper-limit alarm 0 0 is higher than the alarm value (X).
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
15 OFF SP OFF SP
lower-limit alarm 0 0 is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
89
E5EC-T/E5AC-T
*1. With set values 1, 4 and 5, the upper and lower limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence
be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above *2
“L” and “H.” • Case 1 and 2
*2. Set value: 1, Upper- and lower-limit alarm Always OFF when the upper-limit and lower-limit hysteresis overlaps.
Case 1 Case 2 Case 3 (Always ON)
H<0, L<0
• Case 3: Always OFF
L H SP SP L H H SP L *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 Always OFF when the upper-limit and lower-limit hysteresis
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| overlaps.
|H| < |L| |H| > |L|
H>0, L<0 *6. Refer to the E5@C-T Digital Temperature Controllers
SP H L |H| ≤ |L| Programmable Type User's Manual (Cat. No. H185) for
*3. Set value: 4, Upper- and lower-limit range information on the operation of the standby sequence.
Case 1 Case 2 Case 3 (Always OFF)
*7. Refer to the E5@C-T Digital Temperature Controllers
H<0, L<0 Programmable Type User's Manual (Cat. No. H185) for
L H SP SP L H H SP L information on the loop burnout alarm (LBA). This setting cannot
H<0, L>0 H>0, L<0 H<0, L>0 be used with a position-proportional model.
|H| < |L| |H| > |L| H L SP |H| ≥ |L| *8. Refer to the E5@C-T Digital Temperature Controllers
H>0, L<0 Programmable Type User's Manual (Cat. No. H185) for
SP H L |H| ≤ |L| information on the PV change rate alarm.
*9. When heating/cooling control is performed, the MV absolute
upper limit alarm functions only for the heating operation and the
MV absolute lower limit alarm functions only for the cooling
operation.
90
E5EC-T/E5AC-T
Characteristics
Thermocouple: (0.3% of indication value or 1°C, whichever is greater) 1 digit max. *1
Indication accuracy Platinum resistance thermometer: (0.2% of indication value or 0.8°C, whichever is greater) 1 digit max.
(at the ambient temperature of Analog input: 0.2% FS 1 digit max.
23°C) CT input: 5% FS 1 digit max.
Potentiometer input: 5% FS 1 digit max.
Transfer output accuracy 0.3% FS max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10°C, whichever is greater) 1 digit max.
Other thermocouple input: (1% of indication value or 4°C, whichever is greater) 1 digit max. *3
Influence of voltage *2 Platinum resistance thermometer: (1% of indication value or 2°C, whichever is greater) 1 digit max.
Analog input: 1%FS 1 digit max.
Influence of EMS. CT input: 5% FS 1 digit max.
(at EN 61326-1)
Input sampling period 50ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or°F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P)
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Standard, heating/cooling, or Position-proportional (Close): 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in
Integral time (I) units of 0.1 s)
Position-proportional (Floating): 1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)
Proportional band (P) for cooling
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Influence of signal source Thermocouple: 0.1°C/ max. (100 max.)
resistance Platinum resistance thermometer: 0.1°C/ max. (10 max.)
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
E5EC-T Controller: Approx. 210 g, Adapter: Approx. 4 g 2
Weight
E5AC-T Controller: Approx. 250 g, Adapter: Approx. 4 g 2
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.61 or higher
E5EC-T/E5AC-T top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB
port on the computer.*5
Setup Tool port
E5EC-T/E5AC-T front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion
Cable are used together to connect to a USB port on the computer.*5
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some
Approved standards
Standards models only.) *6
Conformed standards EN 61010-1 (IEC 61010-1)
EMI EN 61326-1 *7
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326-1 *7
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1. The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and
L thermocouples at any temperatures is 2°C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.
is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is 3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is 3°C 1 digit max. The indication accuracy of W thermocouples is (0.3% of PV or 3C, whichever
is greater) 1 digit max. The indication accuracy of PL II thermocouples is (0.3% of PV or 2°C, whichever is greater) 1 digit max.
*2. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3. K thermocouple at -100°C max.: 10°C max.
*4. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6. Refer to your OMRON website for the most recent information on applicable models.
*7. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
91
E5EC-T/E5AC-T
Program Control
Number of programs (patterns) 8
Number of segments (steps) 32
Time setting (Segment set with set point and time.)
Segment setting method
Slope setting (Segment set with segment type, set point, slope, and time.)
0 h 0 min to 99 h 59 min
Segment times
0 min 0 s to 99 min 59 s
Alarm setting Set separately for each program.
Reset operation Select either stopping control or fixed SP operation.
Startup operation Select continuing, resetting, manual operation, or run mode.
Number of sets 8
PID sets
Setting method Set separately for each program (automatic PID group selection also supported).
Alarm SP function Select from ramp SP and target SP.
Segment operation Advance, segment jump, hold, and wait
Program status control
Program operation Program repetitions and program links
Wait method Waiting at segment ends
Wait operation
Wait width setting Same wait width setting for all programs
Number of outputs 2
Number of ON/OFF
Time signals 1 each per output
Operations
Setting method Set separately for each program.
Program status output Program end output (pulse width can be set), run output, stage output
PV start Select from segment 1 set point, slope-priority PV start
Program startup operation 0 h 0 min to 99 h 59 min
Standby
0 day 0 h to 99 day 23h
Operation end operation Select from resetting, continuing control at final set point, and fixed SP control.
Program SP shift Same program SP shift for all programs
92
E5EC-T/E5AC-T
500
Communications 0 to 99 ms
300
response wait time Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can E5EC-T/E5AC-T
be individually set using the Communications Setting Level. 100 250 VAC, 30 VDC
(resistive load)
50 cosφ = 1
Communications Functions 30
You can use the memory in the PLC to read and
write E5@C-T parameters, start and reset
operation, etc. The E5@C-T automatically 10
performs communications with PLCs. No
communications programming is required. 5
Number of connected Digital Temperature
Programless 3
Controllers: 32 max.
communications * Applicable PLCs
OMRON PLCs 1
CS Series, CJ Series, or 0 1 2 3 4 5 6
CP Series Switching current (A)
Mitsubishi Electric PLCs
MELSEC Q Series, L Series
93
E5EC-T/E5AC-T
External Connections
E5EC-T/E5AC-T
E5EC T 4 5M E5AC T 4 5M
(1) (2) (3) (4) (5) (6) (1) (2) (3) (4) (5) (6)
Auxiliary outputs 1, 2
Auxiliary outputs 3, 4
: Reinforced insulation
: Functional isolation
94
E5EC-T/E5AC-T
Nomenclature
E5EC-T Front panel
PV or specified monitor/parameter
Operation indicators
No. 2 display
Top-panel
SP or specified monitor/parameter value Setup
Tool port
No. 3 display
Use S Key to change the Program No., segment No.,
digit (default setting). remaining segment time, or MV
(valve opening).
Use the U D Keys to set
Front-panel Setup Tool port the parameter.
E5AC-T
Front Panel
No. 2 display
SP or specified monitor/parameter value
95
E5EC-T/E5AC-T
Dimensions (Unit: mm)
Controllers
E5EC-T (64) • Setup Tool ports are provided as
4 60
48 1
standard feature. Use these ports to
44
connect a computer to the Digital
Temperature Controller. The E58-
CIFQ2 USB-Serial Conversion Cable
is required to connect to the port on
the top panel. The E58-CIFQ2 USB-
96 91 Serial Conversion Cable and E58-
110
CIFQ2-E Communications
Conversion Cable are required to
connect to the port on the front panel.
(You cannot leave either port
connected constantly during
operation.)
Waterproof
Packing (Accessory) Mounting Adapter
(Accessory)
60 min.
45-0.6
0
92+0.8
0
92-0.8
0
120 min.
96
E5EC-T/E5AC-T
E5AC-T (64)
60
96 x 96 4
1 91 x 91
110
Waterproof
Packing (Accessory) Mounting Adapter
(Accessory)
• Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the
Digital Temperature Controller. The E58-CIFQ2 USB-Serial Conversion Cable is required to
connect to the port on the top panel. The E58-CIFQ2 USB-Serial Conversion Cable and E58-
CIFQ2-E Communications Conversion Cable are required to connect to the port on the front panel.
(You cannot leave either port connected constantly during operation.)
92+0.8
0
97
E5EC-T/E5AC-T
LED (RD)
USB connector
(type A plug)
LED (PWR) Serial connector
LED (SD)
Conversion Cable
E58-CIFQ2-E
Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510) 250 263 1510
98
E5EC-T/E5AC-T
21.9 21.9
(2) (2)
131.7 131.7
Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15
(Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 4002
25 3
Winding resistance: 182
10.5 100V
40 10 ∞ Distortion
1kΩ factor
Two, 3.5 dia.
10%
1
10 3%
1%
100mV
30
10 100Ω
E54-CT3
2.36 dia. 1 RL=10Ω
30
12 dia.
9 100μV
10
1 10 100mA 1 10 100 1,000A
40 × 40
Thru-current (Io) A (r.m.s.)
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
Two, M3 (depth: 4) E54-CT3
Maximum continuous heater current: 120 A (50/60 Hz)
15
(Maximum continuous heater current for an OMRON Digital
Temperature Controller is 50 A.)
30
Number of windings: 4002
Winding resistance: 80.8
E54-CT3 Accessories 100V
Output voltage (Eo) V (r.m.s.)
Frequency: 50 Hz
• Armature Connection Example Distortion
∞
10 factor
Armature 1kΩ
10%
Approx. 3 dia. Plug 500Ω 3%
1 1%
Lead
100mV
100Ω
18 50Ω
10
RL=10Ω
• Plug
1
(22) 10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
99
E5@C/E5@C-T
Operation
Setting Levels Diagram
E5C
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.
Monitor/Setting
Press the O Key
Item Level
Press the O Key for Used to display
for at least 1 s. at least 3 s*2
specified monitor
and setting items.
Calibration Level
100
E5@C/E5@C-T
E5C-T
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Press O
Key for at
least 1 s. Press O Key
for less than 1 s.
Press O Key
PID Setting for less than 1 s. Adjustment Level
Level
Parameters for all PID Adjustment parameters
sets (e.g., PID (e.g., PID constants for
constants) current PID set)
Press S Key.*3
Calibration Level
101
E5@C/E5@C-T
Operation
Parameters
E5@C
The following pages describe the parameters set in each level. Pressing the M (Mode) Key at the last parameter in each level returns to the top
parameter in that level. Some parameters may not be displayed depending on the model and other settings.
Press the S Key*2
Power ON
Starting in Manual Mode.
Press the O Key for at least 3 s. Press the S Key*2
Starting in Other than the Auto/Manual Switch display
Manual Control Level Automatic
Press the O
Mode. Initial Setting Level
Press the S Key PID
for at least 1 s. C
25 Key or the S Press the Press the O Key for less than 1 s.
Control
0 only Key for at least O Key for
*1
PV/MV 1 s. *1 at least 1 s.
in-t Input Type
5
Adjustment Press the O Key less than 1 s.
M
Level Operation Level
in-h Scaling Upper Limit
Press the O Key less than 1 s. 100
Adjustment Level
Display M
Displayed only 25 Process Value/
al1h Alarm Value
in-l Scaling Lower Limit
l.adj once when
entering
0 Set Point 1 Upper Limit
0 1 0
adjustment level.
ins Process Value Input orl MV Change Rate
Limit M M
0.0 Shift 0.0 M
M M M 25 Process Value/
al1l Alarm Value
Lower Limit dp
Decimal Point
0 Set Point 2 0 1 0
at AT Execute/Cancel inrt Process Value Slope
db Position
off 1.000 Coefficient Proportional M M M
2.0
Dead Band Temperature Unit
M M a-m Auto/Manual Switch
al-2 Alarm d-u
M 0
Value 2 c
Communications
cmwt Writing rss Remote SP Input Shift
oc-h Open/Close Press the M M
off 0.0 Hysteresis
0.8 O Key M
M M for at m-sp Multi-SP
al2h Alarm Value sl-h SP Upper Limit
M least 3 s. 0 0 2
Upper Limit 1300
Remote SP Input
spmd SP Mode rsrt Extraction of
sqrp Square M M
lsp 1.000
Slope Coefficient Root
Low-cut Point
M
0.0
rsp Remote SP Monitor al2l Alarm Value sl-l SP Lower Limit
hb1
Heater Burnout i M
Detection 1 233 w1of Work Bit 1 M M
0.0 0 OFF Delay Heater Current 1 Value Alarm Value
s-hc Standard or
Heating/Cooling
M M ct1 Monitor al3h Upper Limit
stnd
M 0.0 0 3
ct2 Heater Current 2 d Derivative Time M
Value Monitor 40 w2on Work Bit 2 M M
0.0
0 ON Delay Heater Current 2 Value Alarm Value st ST (Self-tuning)
M ct2 Monitor al3l Lower Limit on
M M 0.0 0 3
Heater Burnout
c-p M
hb2 Detection 2
Proportional Band
w2of Work Bit 2 M M
0.0 8.0 (Cooling)
0 OFF Delay Leakage Current 1 Alarm
ptrn Program Pattern
M M lcr1 Monitor al-4 Value 4
off
M 0.0 0 M
lcr1 Leakage Current 1
c-i Integral Time
M M
0.0
Monitor
233 (Cooling) w3on Work Bit 3
ON Delay
cp Control Period (Heating)
0 Leakage Current 2 Alarm Value 20
M M lcr2 Monitor al4h Upper Limit
M 0.0 0 4 M
hs1 HS Alarm 1 c-d Derivative Time
M M c-cp Control Period (Cooling)
50.0 40 (Cooling) w3of Work Bit 3
OFF Delay 20
0 Alarm Value
M M prst Program Start al4l Lower Limit
M rset 0 4 M
Leakage Current 2
lcr2 Monitor c-db Dead Band M M orev Direct/Reverse Operation
0.0 0.0
w4on Work Bit 4
ON Delay Soak Time Remain or-r
0 sktr o MV Monitor
M M 0 0.0
(Heating) M
HS Alarm 2 M
hs2 of-r Manual Reset Value M M alt1 Alarm 1 Type
50.0 50.0 w4of Work Bit 4
RUN/STOP 2
0 OFF Delay r-s c-o MV Monitor
M M run 0.0
(Cooling) M
M alh1 Alarm 1
sp-0 SP 0
hys Hysteresis (Heating) M M
0 w5on Work Bit 5 0.2 Hysteresis
1.0
0 ON Delay al-1 Alarm
Value 1 v-m Valve Opening
Monitor M
M M 0 0.0
Hysteresis (Cooling) M alt2 Alarm 2 Type
sp-1 SP 1 chys M M 2
0 1.0 w5of Work Bit 5
OFF Delay
M
0 M
M Press the O and M Keys for Press the O and M Keys Press the O Key Alarm 2
M for at least 1 s. alh2
sp-2 SP 2
soak Soak Time at least 3 s. less than 1 s.
0.2 Hysteresis
0 1 w6on Work Bit 6
Communications
0 ON Delay
Protect Level M
M M Setting Level
Wait Band M The time taken to move to the protect level Displayed only for models with
sp-3 SP 3
wt-b can be adjusted by changing the "Move to communications. Changes are * Used with programless communications
0 off w6of Work Bit 6
OFF Delay
protect level time" setting. effective after cycling power or
0 after a software reset.
M pmov Move to Protect Level:
up 1 Upload
MV at Stop M 0
Displayed only when a Setting 1
sp-4 SP 4 mv-s password is set. Protocol Setting: Highest
1
0 0.0 w7on Work Bit 7 M psel Switches between maxu Communications
0
ON Delay cwf CompoWay/F and 0 M
Unit No.
M M Operation/Adjustment Protect Modbus.
up13 Upload
M oapt M M *3 Setting 13
sp-5 SP 5 mv-e MV at PV Error
Communications
0
0 0.0 w7of Work Bit 7
0
u-no Unit No. area Area
M
M 0 OFF Delay M 1 0
Download
M Initial Setting/Communications dn 1
SP Ramp Set Value M icpt Protect M M 31
Setting 1
sp-6 SP 6 sprt 1 Communications First Address
0 off w8on Work Bit 8 bps Baud Rate adrh M
0 ON Delay
M 9.6 0
Upper Word
Download
M M wtpt Setting Change Protect dn13
M M M 75
Setting 13
sp-7 SP 7 sprl SP Ramp Fall Value off
First Address
0 same w8of Work Bit 8 M len Communications
Data Length adrl Lower Word
M
OFF Delay 7 0 Copy
M M 0
pfpt PF Key Protect copy
M off
M M off *3
ol-h MV Upper Limit
Communications sbit Communications
rwat Receive Data
100.0 plcm Monitor
M 2
Stop Bits
1000
Wait Time
SP Slope
M
0
chgp Changed Parameters Only *3 sps *3
M off M M 1.000
ol-l MV Lower Limit
M prty Communications Communications
M
0.0 unit Node Number
even Parity 0 SP Offset
M pmsk Parameter Mask Enable spos *3
on M M 0.0
M sdwt
Send Data Wait M
prlp Password to Move to 20 Time
Protect Level *1. When the PF Setting parameter is set to A-M.
0
M *2. When the PF Setting parameter is set to PFDP.
M *3. Used with component communications.
102
E5@C/E5@C-T
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
M
Automatic Display RT SP Tracking
alh3 Alarm 3 init Parameter Initialization
ret rt sptr
off off Return Time off off
0.2 Hysteresis
M M M M M
alt4 Alarm 4 Type mspu Number of Multi-SP brgt Display Brightness hsu HS Alarm Use p-db PV Dead Band
off Points 3 on 0
2
M M M M M
Alarm 1 Latch Manual MV
Alarm 4 spru SP Ramp Time Unit a1lt hsl HS Alarm Latch manl Limit Enable
alh4 m off off off
0.2 Hysteresis
M M M M
M Direct Setting of
rest Standby Sequence a2lt Alarm 2 Latch
hsh HS Alarm Hysteresis pmvd Position Proportional
o1st Control Output 1 Signal Reset
a off 0.1 off MV
4-20
M M M M
M
PV Rate of Change
sb1n Auxiliary Output 1 a3lt Alarm 3 Latch lba LBA Detection Time pvrp
Calculation Period
o2st Control Output 2 Signal n-o Open in Alarm off 0 20
4-20
M M M M
M
sb2n Auxiliary Output 2 a4lt Alarm 4 Latch
lbal LBA Level hctm Heating/Cooling
trst Transfer Output Signal n-o Open in Alarm off 8.0 off Tuning Method
4-20
M M M M
M
Transfer Output Type
sb3n Auxiliary Output 3
prlt Move to Protect Level
Time lbab LBA Band ompw Minimum Output
tr-t Open in Alarm
n-o 3 3.0 1.0 ON/OFF Band
off
M M M M
M Auxiliary Output 4
Cold Junction Control Output 1 PF Setting
sb4n Open in Alarm cjc Compensation out1 pf
tr-h Transfer Output
Upper Limit n-o on Method o
Assignment
shft
100.0
M M M M
M
hbu HB ON/OFF a1on Alarm 1 ON Delay
out2 Control Output 2
Assignment pfd1 Monitor/Setting Item 1
tr-l Transfer Output
Lower Limit on 0 none 1
0.0
M M M M
M
Auxiliary Output 1
o1th Simple Transfer hbl Heater Burnout Latch a2on Alarm 2 ON Delay
sub1 Assignment pfd2 Monitor/Setting Item 2
Output 1 Upper Limit off 0 alm1 0
100.0
M M M M
M Auxiliary Output 2
hbh Heater Burnout a3on Alarm 3 ON Delay sub2 Assignment pfd3 Monitor/Setting Item 3
o1tl Simple Transfer
Ouptut 1 Lower Limit Hysteresis
0.1 0 alm2 0
0.0
M M M M
M
st-b ST Stable Range a4on Alarm 4 ON Delay
sub3 Auxiliary
Assignment
Output 3
pfd4 Monitor/Setting Item 4
ev-1 Event Input
Assignment 1 15.0
0 alm3 0
msp0
M M M M M
alfa α a1of Alarm 1 OFF Delay
sub4 Auxiliary Output 4
pfd5 Monitor/Setting Item 5
ev-2 Event Input
Assignment 2 0.65 0
Assignment
alm4 (E5EC/E5AC only) 0
stop
M M M M
M
ev-3 Event Input tidu Integral/Derivative a2of Alarm 2 OFF Delay alma Integrated Alarm spd1 PV/SP No. 1 Display
Selection
Assignment 3 1 Time Unit 0 49 Assignment 4
none
M M M M M
PV/SP No. 2 Display
Event Input at-g AT Calculated Gain a3of Alarm 3 OFF Delay
t-u Soak Time Unit spd2 Selection
ev-4 Assignment 4 0.8 0 m 0
none
M M M M
M Alarm 4 OFF Delay Alarm SP Selection MV Display Selection
ev-5 Event Input at-h AT Hysteresis a4of alsp odsl
0.8 0 sp-m o
Assignment 5
none
M M M M
M PV Decimal Point
Remote SP Input
ev-6
Event Input lcma Limit Cycle MV mvse MV at Stop and Error
Addition rs-t pvdp Display
Assignment 6 20.0 Amplitude off 4-20 on
none
M M M M
M PV Status Display
clfl Close/Floating inf Input Digital Filter amad Auto/Manual Select
Addition rspu Remote SP Enable pvst Function
flot 0.0 off off off
M M M M M
calb Motor Calibration mav Moving Average Count mant Manual Output Method rsph Remote SP
Upper Limit
svst SV Status Display
Function
off off hold 1300 off
M M M M M
MV Display Display Refresh
mot Travel Time o-dp mani Manual MV Initial Value rspl Remote SP
d.ref Period
30 M
off M0.0
Lower Limit
-200 0.25
M M M M M
sqr Extraction of Square lcmt LCT Cooling Output
Minimum ON Time
Root Enable 0.2
off
103
E5@C/E5@C-T
E5@C-T
Some parameters may not be displayed depending on the model and other settings.
* The monitor/setting items to display are set in the Monitor/Setting Item 1 to 5 parameters
25 PV/Manual MV (Advanced Function Setting Level).
50.0
Press S Key.*2 Press S Key.*2
Press O Key for Press O or S
at least 3 s while Key for at least
a-m is displayed. 1 s.*1
Press S
Key for at Program Setting Level
least 1 s.*1
U
Display Program
Selection
Operation Level 6 7
d.prg 45
23
01
Process Value/Set
D 25 Point 1 or Process
Value/Set Point 2 in
25 Process prgt Elapsed
Program Time
Press O M 0 Operation Level
Value/Set Point 1
0 0.00 Key for
M M
Monitor
less than
s-no Number of
Segments Used
Press the U Key
8 Display Segment Selection for at least 1 s in
Program Execution 1 s. Program SP Mode.
25 Process rptm Repetitions Monitor
M END or 0 to Number of segments used − 1
Value/Set Point 2
0 0
U
M M
ct1 67
a-m Auto/Manual Switch Heater Current 1 to
2 Value Monitor d.seg U
d.seg 3 45
0.0
end D 0 12 D
M M
pgsg Program No. Monitor/
Segment No. Monitor lcr1 Leakage Current 1
to 2 Value Monitor
For end M For 0 to 7 M
0.00 0.0 rpt Program
M
M
pid PID Set No.
0
Repetitions styp Segment n Format
1 M
ramp
prg Program Number
r-r Run/Reset M M
0 rst
(of the program)
link Program
M M al-1 Alarm Value
1 to 4 end
Link
Destination
sp Segment n SP
0 M 0
hold Hold
o MV Monitor M
(Heating) M
off 0.0 al1h Alarm
ts1s Time Signal 1 to 2
M M 0
Upper Limit
0
Set Segment pr Segment n Slope
1 to 4
0
seg Segment Number
c-o MV Monitor M M
M
0 0.0
(Cooling) al1l Alarm
Lower Limit
on1 Time Signal 1 to 2
ON Time
M 0 1 to 4 0.00 time Segment n Time
M
M 0.00
stbm Remaining
v-m Valve Opening M
0.00
Standby Time
Monitor of1 Time Signal 1 to 2
OFF Time
M
Monitor 0.0 0.00
M M
M
Press O Key for less than 1 s. Adjustment Level Press O Key for less than 1 s.
PID Setting Level
Adjustment Level
l.adj Display
d.pid U Display PID
1234 Displayed only once
p Proportional Band
1 2 Selection
M when entering lcr1 Leakage Current 1 to 2
3 4 Adjustment Level. 0.0 Value Monitor 8.0
5 6 Press O M M
7 8
D Key for less AT Execute/Cancel hs1
than 1 s.
at HS Alarm 1 to 2
i Integral Time
M off 50.0 233
1.p PID 1
Proportional 1.cdb PID 1 Dead M M M
8.0 Band
Band 0.0 cmwt Communications
Writing ins PV Input Shift d Derivative Time
M M off 0.0 40
1.i PID 1 Integral
Time 1.ofr PID 1 Manual M M M
233 Reset Value
s0.0 spmd SP Mode
inrt PV Input Slope c-p Proportional Band (Cooling)
M Coefficient
M psp 1.000 8.0
1.d PID 1
Derivative Time 1.olh PID 1 MV Upper M M M
40 Limit
100.0 fsp Fixed SP
wt-b Wait Band c-i Integral Time (Cooling)
M M 0 off 233
1.c-p PID 1
Proportional
1.oll PID 1 MV Lower M M M
Limit
8.0 0.0
Band (Cooling)
ct1 Heater Current 1 to 2 stb Standby Time c-d Derivative Time (Cooling)
M M Value Monitor
40
0.0 0.00
1.c-i PID 1 Integral 1.aut PID 1 Automatic M M M
Time (Cooling) Selection Range
233 1320 Upper Limit hb1 Heater Burnout
psps Program SP Shift Value c-db Dead Band
Detection 1 to 2
M M 0.0
0 0.0
1.c-d PID 1
Derivative Time
1.lba PID 1 LBA
Detection
M M M
40 (Cooling) 0 Time
M M
104
E5@C/E5@C-T
Press O Key
Protect Level for at least 1 s.
Press O + M Key
for at least 3 s. M Operation/Adjustment PF Key Protect
pmov oapt Protect pfpt
0 0 off
Move to Protect Level M M
Initial Setting/ Parameter Mask Enable
Press O + M Key for at least 3 s. (The key pressing icpt Communications Protect pmsk
time can be changed in the Move to Protect Level 1 on
Time parameter (Advanced Function Setting Level).) M M
Setting Change Protect Password to Move
wtpt prlp to Protect Level
Press O + M Key for at least 1 s. off 0
M M
Communications
psel Protocol Setting
sdwt Send Data
Wait Time
unit Node Number
cwf 20 0
M M M
of-r Manual Reset Value orl MV Change Rate
Limit u-no Communications
maxu
Highest
Communications up 1 Upload
Unit No.
50.0 0.0 1 0 Unit No. 0
Setting
1 to 23
M M M M M
hys Hysteresis (Heating)
db Position Proportional
bps Communications
area Area
1.0 2.0
Dead Band Baud Rate dn 1 Download
9.6 0 0 Setting
M M M M 1 to 43
M
chys Hysteresis (Cooling)
oc-h Open/Close
Hysteresis len Communications adrh
First Address
Upper Word Copy
1.0 0.8 7
Data Length
0 copy
M M off
M
M M
M
mv-r MV at Reset
sqrp Extraction of Square
Root Low-cut Point sbit Communications adrl
First Address
Lower Word
0.0 0.0 2
Stop Bits
0
M M M
M
mv-e MV at PV Error
w1on Work Bit 1 to 8 ON
prty Communications
rwat
Receive Data
Wait Time
0.0 Delay Parity
0 even 1000
M M M M
Work Bit 1 to 8 OFF
ol-h MV Upper Limit w1of Delay
100.0 0
Models with communications only: Changes to settings are applied
M
M when the power is cycled or a software reset is performed.
ol-l MV Lower Limit
105
E5@C/E5@C-T
rest Standby Sequence Reset hsu HS Alarm Use ompw Minimum Output ON/OFF
1.0 Band
a on
M M M
sb1n Auxiliary Output 1 to 4 hsl HS Alarm Latch lcmt LCT Cooling Output Min.
0.2 ON Time
n-o Open in Alarm off
M M M
on 0.1 shft
M M M
hbl Heater Burnout Latch lba LBA Detection Time pfd1 PF Monitor/Setting Item 1
off 0 1
M M M
at-h AT Hysteresis
sub1 Auxiliary Output 1 svst SV Status Display Function
0.8 alm1 Assignment
off
M M M
inf Input Digital Filter sub3 Auxiliary Output 3 burn Burnout Method
Assignment
0.0 alm3 up
M M M
Auxiliary Output 4
mav Moving Average Count sub4 Assignment pmst Parameter Mask Setting
off alm4 off
M M M
3 pv Selection Data
M
M
M
M
0 0
M
M
Manual MV Limit Enable
a1of Alarm 1 to 4 OFF Delay
manl
off
0
M
M
106
E5@C/E5@C-T
Error Displays (Troubleshooting)
When an error occurs, the No. 1 display or No. 2 display shows the error code.
Take necessary measure according to the error code, referring the following table.
Display Name Meaning Action Operation
The input value exceeded the control Check the wiring for input to be sure After the error occurs and it is
range.* it is wired correctly, not broken, and displayed, the alarm output will operate
The input type is not set correctly. not shorted. Also check the input as if the upper limit was exceeded.
The sensor is disconnected or short- type. It will also operate as if transfer
circuited. If there are no problems in the wiring output exceeded the upper limit.
The sensor is not wired correctly. or input type settings, cycle the If an input error is assigned to a
The sensor is not wired. power supply. control output or auxiliary output, the
If the display remains the same, output will turn ON when the input
* Control Range replace the Digital Temperature error occurs.
s.err Input error Temperature resistance Controller. The error message will appear in the
thermometer or thermocouple input: If the display is restored to normal, display for the PV.
SP Lower Limit - 20°C to SP Upper then the probable cause is external
Limit + 20°C noise affecting the control system. Note: 1. The heating and cooling
(SP Lower Limit - 40°F to SP Upper Check for external noise. control outputs will turn OFF.
Limit + 40°F) 2. When the manual MV, MV
ESIB input: Note: For a temperature resistance at stop, MV at reset, or MV
Same as specified input range. thermometer, the input is at error is set, the control
Analog input: considered disconnected if output is determined by the
Scaling range -5% to 105% the A, B, or B’ line is broken. set value.
This is not an error. It Control continues and operation is
is displayed when the normal.
[[[[ Below -1,999 control range is wider The value will appear in the display
than the display range for the PV.
Display and the PV exceeds Refer to the E5@C Digital Temperature
range the display range. - Controllers User’s Manual (Cat. No.
exceeded The PV is displayed H174) or the E5@C-T Digital
for the range that is Temperature Controllers
]]]] Above 9,999 given on the left (the Programmable Type User’s Manual
number without the (Cat. No. H185) for information on the
decimal point). controllable range.
After checking the input error, turn
the power OFF then back ON again.
The control outputs, auxiliary
If the display remains the same, the
A/D outputs, and transfer outputs turn
There is an error in the internal controller must be repaired.
e333 converter
circuits. If the display is restored to normal,
OFF. (A current output will be approx.
error 0 mA and a linear voltage output will
then a probable cause can be
be approx. 0V.)
external noise affecting the control
system. Check for external noise.
First, cycle the power supply.
If the display remains the same, the The control outputs, auxiliary
controller must be repaired. outputs, and transfer outputs turn
Memory There is an error in the internal
e111 error memory operation.
If the display is restored to normal, OFF. (A current output will be approx.
then a probable cause can be 0 mA and a linear voltage output will
external noise affecting the control be approx. 0V.)
system. Check for external noise.
Control continues and operation is
normal.
The error message will appear for the
This error is displayed when the peak following displays.
ffff Overcurrent
current exceeds 55.0 A.
-
Heater Current Value 1 Monitor
Heater Current Value 2 Monitor
Leakage Current Value 1 Monitor
Leakage Current Value 2 Monitor
The No. 1 display for the following
parameter flashes in Operation Level
or Adjustment Level.
ct1 If there is a HB or HS alarm, the No. Heater Current Value 1 Monitor
ct2 HB or HS
1 display will flash in the relevant - Heater Current Value 2 Monitor
lcr1 alarm
setting level. Leakage Current Value 1 Monitor
lcr2 Leakage Current Value 2 Monitor
However, control continues and
operation is normal.
"----" will be displayed for the Valve
Opening Monitor parameter if any of
the following error occurs.
Potentiometer • Motor calibration has not been Close control: The control output is
Input Error performed. OFF or the value that is set for the
---- (Position- • The wiring of the potentiometer is Check for the above errors. MV at PV Error parameter is output.
proportional incorrect or broken. Floating control: Operation will be
Models Only) • The potentiometer input value is normal.
incorrect (e.g., the input is out of
range or the potentiometer has
failed).
107
E5@C/E5@C-T
Safety Precautions
Be sure to read the precautions for all E5@C/E5@C-T models in the website at: http://www.ia.omron.com/.
Warning Indications
Minor electric shock or fire may occasionally occur.
Indicates a potentially hazardous Do not use any cables that are damaged.
situation which, if not avoided, may
CAUTION result in minor or moderate injury or in
property damage.
Never disassemble, modify, or repair the product or
Precautions for Supplementary comments on what to touch any of the internal parts. Minor electric shock,
do or avoid doing, to use the product
Safe Use fire, or malfunction may occasionally occur.
safely.
Supplementary comments on what to CAUTION - Risk of Fire and Electric Shock
Precautions for do or avoid doing, to prevent failure to 1. This product is UL listed *1 as Open Type Process
Correct Use operate, malfunction or undesirable Control Equipment. It must be mounted in an
effect on product performance. enclosure that does not allow fire to escape externally.
2. More than one disconnect switch may be required to
Meaning of Product Safety Symbols de-energize the equipment before servicing the product.
3. Signal inputs are SELV, limited energy. *2
Used to warn of the risk of electric shock under 4. Caution: To reduce the risk of fire or electric shock, do not
specific conditions. interconnect the outputs of different Class 2 circuits. *3
108
E5@C/E5@C-T
109
E5@C/E5@C-T
110
E5@C/E5@C-T
Others
1. Do not Connect or disconnect the Conversion Cable connector
repeatedly over a short period of time.
The computer may malfunction.
2. After connecting the Conversion Cable to the computer, check the
COM port number before starting communications. The computer
requires time to recognize the cable connection. This delay does
not indicate failure.
3. Do not connect the Conversion Cable through a USB hub. Doing
so may damage the Conversion Cable. 1. For waterproof mounting, waterproof packing must be installed on
4. Do not use an extension cable to extend the Conversion Cable the Digital Temperature Controller. Waterproofing is not possible
length when connecting to the computer. Doing so may damage when group mounting several Digital Temperature Controllers.
the Conversion Cable. The E5CC-U cannot be waterproofed even if the Waterproof
Packing is inserted.
2. Insert the E5CC/E5CC-B/E5CC-U/E5CC-T into the mounting hole
in the panel.
3. Push the adapter from the terminals up to the panel, and
temporarily fasten the E5CC/E5CC-B/E5CC-U/E5CC-T.
4. Tighten the two fastening screws on the adapter.
Alternately tighten the two screws little by little to maintain a
balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
111
E5@C/E5@C-T
Terminal Unit
(1)
112
E5@C/E5@C-T
2. Peel off the release paper from the double-sided tape on the End
Cover.
Vertical: OK Horizontal: NG
Adapter
Terminal Cover
(E53-COV17) Enlarged illustration of
(Sold separately) Terminal Section
E5EC/E5AC/E5EC-T/E5AC-T
Slightly bend the E53-COV24 Terminal Cover to attach it to the
terminal block as shown in the following diagram. The Terminal Cover
cannot be attached in the opposite direction.
113
E5@C/E5@C-T
Removing the Digital Temperature Controller from the case Removing the draw-out jig when only one hook is caught
E5GC in the draw-out jig insertion hole
You can use the Y92F-55 Draw-out Jig to remove the interior body of 1. Pull the Draw-out Jig slowly in the direction shown in the figure.
the Digital Temperature Controller from the case to perform (This step is the same even if the other hook is caught.)
maintenance without removing the terminal wiring. This is possible 2. Confirm that the Draw-out jig is free of the Draw-out jig insertion
only for the E5GC. Check the specifications of the case and Digital hole.
3. If the interior body separates from the rear case, slowly press the
Temperature Controller before removing the Digital Temperature
interior body into the rear case in a horizontal direction.
Controller from the case.
If you do not follow the procedures above, the Digital Controller
may be damaged.
1. Draw out the interior body from the rear case.
1. Slowly insert the Draw-out Jig into the Draw-out Jig insertion holes (2)
laterally until it clicks into place. (There is a hole at both the top and
(1)
bottom.) (If you attempt to draw out the interior body of the Digital
Controller when only one hook is engaged, the Digital Controller (3)
may be damaged.)
Rear case
Draw-out Jig insertion holes
Front panel
Draw-out Jig
Precautions when Wiring
• Separate input leads and power lines in order to prevent external
(1)
Hook noise.
• Use crimp terminals when wiring the screw terminal.
(2) (1) • Use the suitable wiring material and crimp tools for crimp terminals.
Draw-out Jig insertion holes • Tighten the terminal screws to a torque of 0.43 to 0.58 N·m.
2. Pull out the Draw-out Jig together with the front panel. Do not pull The specified torque is 0.5 N·m for the E5CC-U.
with excessive force. Slowly pull out the Digital Controller laterally.
(If you pull the interior body out at an angle, the Digital Controller E5CC/E5EC/E5AC/E5DC/E5@C-T/E5GC
may be damaged.)
3. After the interior body is free from the rear case, support the
(Controllers with Screw Terminal) and E5CC-U
interior body with one hand and draw it out slowly in a horizontal (Plug-in model)
direction. Wire Size
2. Insert the new interior body into the rear case. Use the wire sizes and stripping lengths given in the following table.
1. When inserting the interior body back into the rear case, make
sure the PCBs are parallel to each other, mount the sealing Model Wire Size Stripping length
rubber, and press the interior body toward the rear case and into E5CC/E5EC/E5AC/
position, making sure that the sealing rubber does not move. E5DC/E5GC 6 to 8 mm
AWG24 to AWG18
2. When you press the Digital Controller into position, press down on (Controllers with (without crimp
(0.21 to 0.82 mm2)
the rear case hooks so that the case hooks securely lock in place. Screw Terminal) / terminals)
E5@C-T
(There are rear case hooks at both the top and bottom of the rear
case.) If the Digital Controller is not correctly mounted into the rear 5 to 6 mm
AWG24 to AWG14
case, the rear case may not be waterproof. When inserting the E5CC-U (without crimp
(0.21 to 2.08 mm2)
terminals)
Digital Controller, do not allow the electronic components to touch
the rear case. • If you use crimp terminals, use the stripping length that is
recommended by the manufacturer of the crimp terminals.
Top View
Rear case hooks • To reduce the affects of noise, use shielded twisted-pair cable for
Sealing rubber position PCBs
the signal lines.
(1)
Crimp Terminal
For the E5CC/E5EC/E5AC/E5DC/E5GC (Controllers with Screw
Terminal) or E5@C-T, use the following types of crimp terminals for
M3 screws.
Case hooks
* Make sure that the top and bottom PCBs are parallel to each other and 5.8 mm max.
insert them into the rear case.
(2)
Rear case hooks 5.8 mm max.
For the E5CC-U, use the following types of crimp terminals for M3.5
screws.
(2)
7.2 mm max.
7.2 mm max.
114
E5@C/E5@C-T
• If you use crimp terminals for the E5DC, use crimp terminals with Checking Connections
insulation sleeves. If you use a bare crimp terminal with no • After insertion, pull gently on the wire to make sure that it will not
insulation, the terminal may short with the terminal above or below come out (i.e., to confirm that it is held by the terminal block).
it. If you use bare crimp terminals, cover the crimped sections with
insulating marking tubes. Secure the marking tubes so that they do
not move.
NA
OK
Although you can connect two crimp terminals with insulation
sleeves to one terminal, you cannot do so if the diameter of the
insulation sleeves is too large.
Recommended Crimp Terminals with Insulation Sleeves for the E5DC 2. Removal Method for Screwless Clamp Terminals
The same method is used to remove stranded wires, solid wires, and
Manufacturer Model number ferrules.
V1.25-B3A 1. Press the pusher with a flat-blade screwdriver.
J.S.T. Mfg. Co.
V0.5-3A 2. With the screwdriver still pressing the pusher, pull the wire out of
the terminal (Insertion) hole.
3. Remove the flat-blade screwdriver from the pusher.
E5GC (Controllers with Screwless Clamp
Terminal)
1. Connection Method for Screwless Clamp Terminals
The same method is used to connect stranded wires, solid wires, and
(2)
ferrules.
Pusher
0.8 to 1.4mm
(2)
8 to 12mm
(1)
Recommended ferrules
(3)
Manufacturer name Model number
Altech Corp. 2623.0
Daido Solderless Terminal Mfg. Co. AVA-0.5
J.S.T. Mfg. Co. TUB-0.5
TGNTC-1.25-9T
TGVTC-1.25-11T
TGNTC-1.25-11T
Single (1 wire) TC0.3-9.5
Nichifu Co., Ltd. TC1.25-11S-ST
TC1.25-11S
TC2-11S
TGWVTC-1.25-9T
Double (2 wires)
TGWVTC-1.25-11T
115
E5@C/E5@C-T
Checking Connections
• After the insertion, pull gently on the wire to make sure that it will
2.1 mm max.
not come off and the wire is securely fastened to the terminal block. 2.7 mm max.
• To prevent short circuits, insert stripped part of a stranded or solid
wire or the conductor part of a ferrule until it is hidden inside the
terminal insertion hole. (See the following diagram.)
116
E5@C/E5@C-T
Recommended Flat-blade Screwdriver Model Manufacturer
Use a flat-blade screwdriver to connect and remove wires.
XW4Z-00B Omron
Use the following flat-blade screwdriver.
The following table shows manufacturers and models as of 2015/Dec. ESD0.40✕2.5 Wera
SZF 0.4✕2.5 Phoenix Contact
Side Front
0.4✕2.5✕75 302 Wiha
2.5 mm dia. AEF.2.5✕75 Facom
210-719 Wago*
SDI 0.4✕2.5✕75 Weidmuller*
Three-year Guarantee
Period of Guarantee
The guarantee period of the Unit is three years starting from the date
the Unit is shipped from the factory.
Scope of Guarantee
The Unit is guaranteed under the following operating conditions.
1. Average Operating Temperature
(see note): 10C to 50C
2. Mounting Method: Standard mounting
(Mounted to panel or DIN Track.)
Top
Bottom
117
MEMO
118
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
OMRON ASIA PACIFIC PTE. LTD. OMRON (CHINA) CO., LTD. © OMRON Corporation 2011-2016 All Rights Reserved.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Room 2211, Bank of China Tower, In the interest of product improvement,
Alexandra Technopark, 200 Yin Cheng Zhong Road, specifications are subject to change without notice.
Singapore 119967 PuDong New Area, Shanghai, 200120, China
Tel: (65) 6835-3011/Fax: (65) 6835-2711 Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 Cat. No. H177-E2-09-X 0316 (1111)