Manual HPVFV Profibus
Manual HPVFV Profibus
Manual HPVFV Profibus
V3.0302
SOLCOM & HAPN (SHANGHAI) ELECTRIC CO., LTD
PROFILE
1. Communication activate
Parameter Menu Set Description
P27.0 PB_Connect [0]Disable
[1]Enable
2. Sub‐station define
Parameter Menu Set Description
P27.1 Station_No 0~127 ProfibusDP
sub‐station setting
Note: The products does not support broadcast commands.
The number of sub‐station does not define to 0.
B. Control words
1. Set CtrlWord1 as PB_DRIVE_IN1 to activate PB_DRIVE_IN1 to control drives.
Set P27.38=1 on menu and P3.0=3 (Fieldbus)
2. Set CtrlWord2 as PB_DRIVE_IN2 to activate PB_DRIVE_IN2 to control drives and PID
Set P27.39=2 on menu
3. Activate PB_DRIVE_IN3 to control output frequency. Know PB_DRIVE_IN3 concatenated coding
from link list as 44
Set P31.0=44 on menu and P3.1=3(Free_Func)
Note:
After program, have to shut down and re‐start the power to activate the new setting.
27
28
29
30
31
32 PID ctrl output 0‐8192(0x2000)‐>100%
33 Timer function output 0‐8192(0x2000)‐>100%
34 Analogue input 1 0‐8192(0x2000)‐>100%
35 Analogue input 2 0‐8192(0x2000)‐>100%
36 Analogue input 3 0‐8192(0x2000)‐>100%
37 Analogue input 4 0‐8192(0x2000)‐>100%
38 Analogue input 5 0‐8192(0x2000)‐>100%
39 Analogue reference 0‐8192(0x2000)‐>100%
SOLCOM & HAPN (SHANGHAI) ELECTRIC CO., LTD
Data connection
[70]Control word 3
Undefined, programmable
[71]Control word 4
byte name Description
0 Synchronous
control run
1 Synchronous
control fault reset
8 RS232C run
9 RS232C fault reset
10 RS232C directional
control
14 Overall work
15 Overall fault reset