FDM128

Download as pdf or txt
Download as pdf or txt
You are on page 1of 70

FDM128 Ethernet Display for Eight Devices

User Guide
DOCA0037EN-09
04/2021

www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Table of Contents
Safety Information ......................................................................................5
About the Book...........................................................................................7
Introduction ..............................................................................................10
Overview............................................................................................10
Architecture Examples ........................................................................12
Recommendations..............................................................................20
Certifications and Standards ................................................................22
General Specifications ........................................................................24
Functional Specifications ....................................................................26
Interface Specifications .......................................................................27
Presentation.............................................................................................28
Screen ...............................................................................................28
Menu Structure ...................................................................................30
Browsing ............................................................................................31
Configuration ...........................................................................................32
Prerequisites ......................................................................................32
Setting Wizard ....................................................................................34
Settings During Operation ...................................................................38
Operation.................................................................................................40
Logins and Access Codes ...................................................................40
General View......................................................................................43
Real-Time Alarms ...............................................................................46
Device View for Circuit Breakers and Switch-Disconnectors ...................48
Device View for Devices Connected to the Acti9 Smartlink .....................53
Update and Maintenance ..........................................................................57
Firmware Update ................................................................................57
Adding, Removing, and Replacing Devices...........................................59
Regular Cleaning ................................................................................60
Troubleshooting Checklists..................................................................61
Protecting the Environment..................................................................62
Appendices ................................................................................................63
FDM128 Icons..........................................................................................64
Icon List .............................................................................................64
Glossary of Acronyms ...............................................................................67
Acronym ............................................................................................67

DOCA0037EN-09 3
Safety Information

Safety Information
Important Information
Read these instructions carefully, and look at the equipment to become familiar
with the device before trying to install, operate, service, or maintain it. The
following special messages may appear throughout this documentation or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.

The addition of this symbol to a “Danger” or “Warning” safety label indicates that an
electrical hazard exists which will result in personal injury if the instructions are not
followed.

This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that follow this symbol to avoid possible injury or
death.

! DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
injury.

! WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or
serious injury.

! CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury.

NOTICE
NOTICE is used to address practices not related to physical injury.

Please Note
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction
and operation of electrical equipment and its installation, and has received safety
training to recognize and avoid the hazards involved.

FCC Notice
This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designated
to provide reasonable protection against harmful interference when the equipment
is operated in a commercial environment. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to
cause harmful interference in which case the user will be required to correct the
interference at this own expense.

DOCA0037EN-09 5
Safety Information

Cybersecurity Safety Notice

WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND
CONFIDENTIALITY
• Change default passwords at first use to help prevent unauthorized access
to device settings, controls, and information.
• Disable unused ports/services and default accounts to help minimize
pathways for malicious attackers.
• Place networked devices behind multiple layers of cyber defenses (such as
firewalls, network segmentation, and network intrusion detection and
protection).
• Use cybersecurity best practices (for example, least privilege, separation of
duties) to help prevent unauthorized exposure, loss, modification of data and
logs, or interruption of services.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

6 DOCA0037EN-09
About the Book

About the Book


Document Scope
This guide describes how to use the FDM128 Ethernet display for eight devices,
installed in an Ethernet network, to monitor and control the following devices:
• Circuit breakers equipped with communicating MicroLogic™ trip units, such
as:
◦ MasterPact™ MTZ circuit breakers
◦ MasterPact™ NT/NW circuit breakers
◦ ComPact™ NS circuit breakers
◦ ComPacT™ NSX circuit breakers
◦ PowerPact™ P- and R-frame circuit breakers
◦ PowerPacT™ H-, J-, and L-frame circuit breakers
NOTE: The information related to the new generation of ComPacT NSX
and PowerPacT H-, J-, and L-frame circuit breakers in this guide applies
to ComPact NSX and PowerPact H-, J-, and L-frame circuit breakers also.
The exceptions are mentioned wherever applicable.
The new ComPacT NSX and PowerPacT H-, J-, and L-frame ranges are
based on the same technical and dimensional architecture as that of
ComPact NSX and PowerPact H-, J-, and L-frame circuit breakers. The
electrical and mechanical performances of these two ranges are identical.
• Switch-disconnectors such as:
◦ MasterPact™ NT HA switch-disconnectors
◦ MasterPact™ NW NA/HA/HA10/HF switch-disconnectors
◦ ComPact™ NS NA switch-disconnectors
◦ PowerPact™ P- and R-frame switch-disconnectors
◦ ComPacT™ NSX NA switch-disconnectors
◦ PowerPacT™ H-, J-, and L-frame switch-disconnectors
• Smartlink™ devices, such as:
◦ Smartlink SI B gateway
◦ Smartlink Modbus gateway
• PowerTag™ devices such as:
◦ PowerTag Link gateway
◦ PowerTag Link B gateway
◦ PowerTag Link HD gateway
NOTE: The Smartlink product range is not available in the following countries:
United States, Canada, Mexico. Consult the catalog for the list of products
available in your country.

Validity Note
This guide is valid for FDM128 Ethernet display for eight devices.

Online Information
The technical characteristics of the devices described in this guide also appear
online. To access the information online, go to the Schneider Electric home page
at www.se.com.

DOCA0037EN-09 7
About the Book

The information contained in this guide is likely to be updated at any time.


Schneider Electric strongly recommends that you have the most recent and up-to-
date version available on www.se.com/ww/en/download.

Related Documents for IEC Devices


Title of Documentation Reference Number
Enerlin’X FDM128 - Ethernet Display for Eight Devices - Instruction Sheet HRB45777

Enerlin'X FDM128 - Ethernet Display for Eight Devices - Firmware Release Note DOCA0151EN

Enerlin’X IFM - Modbus-SL Interface for One Circuit Breaker - Instruction Sheet NVE85393
Enerlin’X IFE - Ethernet Interface for One Circuit Breaker - Instruction Sheet QGH13473

Enerlin’X IFE - Ethernet Interface for One Circuit Breaker - User Guide (IEC version) DOCA0142EN

Enerlin’X IFE - Ethernet Switchboard Server - User Guide (IEC version) DOCA0084EN

Enerlin’X EIFE - Embedded Ethernet Interface for One MasterPact MTZ Drawout Circuit Breaker - NVE23550
Instruction Sheet
Enerlin’X EIFE - Embedded Ethernet Interface for One MasterPact MTZ Drawout Circuit Breaker - DOCA0106EN
User Guide
Enerlin’X IO - Input/Output Application Module for One Circuit Breaker - Instruction Sheet HRB49217

Enerlin’X IO - Input/Output Application Module for One Circuit Breaker - User Guide (IEC version) DOCA0055EN

BCM ULP Circuit Breaker Communication Module - Installation Manual EAV3608000 (EN, ES, FR)

Acti9 Smartlink Modbus Communication System - User Manual DOCA0004EN

Acti9 Smartlink Ethernet Communication System - User Manual DOCA0073EN

Acti9 Smartlink SI B Communication System - User Manual DOCA0123EN

Acti9 Smartlink SI D Communication System - User Manual DOCA0115EN

EGX300 PowerLogic™ Ethernet Gateway - User Guide 63230-319-216 (EN, ES, FR)

MicroLogic 5/6/7 Trip Units for ComPacT NSX Circuit Breakers - User Guide DOCA0141EN

ComPact NSX Modbus Communication Guide DOCA0091EN


ComPacT NSX Modbus Communication Guide DOCA0213EN
MicroLogic A/E Trip Units for MasterPact NT/NW Circuit Breakers - User Guide 04443724AA (EN)

MicroLogic P Trip Units for MasterPact NT/NW Circuit Breakers - User Guide 04443726AA (EN)

MicroLogic H Trip Units for MasterPact NT/NW Circuit Breakers - User Guide 04443728AA (EN)

MasterPact NT/NW, ComPact NS Modbus Communication Guide DOCA0054EN

MasterPact MTZ1 Circuit Breakers and Switch-Disconnectors - User Guide DOCA0100EN


MasterPact MTZ2/MTZ3 Circuit Breakers and Switch-Disconnectors - User Guide DOCA0101EN
MicroLogic X Control Unit for MasterPact MTZ Circuit Breakers - User Guide DOCA0102EN

MasterPact MTZ Modbus Communication Guide DOCA0105EN


ULP System for ComPact and MasterPact Circuit Breakers - User Guide DOCA0093EN

TCSEGWB13FA0 - Portable Battery Powered Wi-Fi Access Point - Instruction Sheet NHA24030

You can download these technical publications and other technical information
from our website at https://www.se.com/en/download

8 DOCA0037EN-09
About the Book

Related Documents for UL/ANSI Devices


Title of Documentation Reference Number
Enerlin’X FDM128 - Ethernet Display for Eight Devices - Instruction Sheet HRB45777

Enerlin'X FDM128 - Ethernet Display for Eight Devices - Firmware Release Note DOCA0151EN

Enerlin’X IFM - Modbus-SL Interface for One Circuit Breaker - Instruction Sheet NVE85393
Enerlin’X IFE - Ethernet Interface for One Circuit Breaker - Instruction Sheet QGH13473

Enerlin’X IFE - Ethernet Interface for One Circuit Breaker - User Guide (UL version) 0602IB1801EN

Enerlin’X IFE - Ethernet Switchboard Server - User Guide (UL version) 1040IB1401 (EN)

Enerlin’X EIFE - Embedded Ethernet Interface for One MasterPact MTZ Drawout Circuit NVE23550
Breaker - Instruction Sheet
Enerlin’X EIFE - Embedded Ethernet Interface for One MasterPact MTZ Drawout Circuit DOCA0106EN
Breaker - User Guide
Enerlin’X IO - Input/Output Application Module for One Circuit Breaker - Instruction Sheet HRB49217

Enerlin’X IO - Input/Output Application Module for One Circuit Breaker - User Guide (UL 0613IB1317 (EN)
version)

BCM ULP Circuit Breaker Communication Module - Installation Manual EAV3608000 (EN, ES, FR)

EGX300 PowerLogic™ Ethernet Gateway - User Guide 63230-319-216 (EN, ES, FR)

MicroLogic 5 and 6 Trip Units for PowerPacT H-, J-, and L- Frame Circuit Breakers - User 48940-312 (EN, ES, FR)
Guide
PowerPact H-, J-, and L- Frame Circuit Breakers Modbus Communication Guide 0611IB1302 (EN)

MicroLogic 2.0A, 3.0A, 5.0A, and 6.0A Trip Units - Instruction Bulletin 48049-136 (EN, ES, FR)

MicroLogic 5.0P and 6.0P Trip Units - Instruction Bulletin 48049-137 (EN, ES, FR)

MicroLogic 5.0H and 6.0H Trip Units - Instruction Bulletin 48049-330 (EN, ES, FR)

MasterPact NT/NW, PowerPact P- and R-Frame Modbus Communication Guide 0613IB1313 (EN)

MicroLogic X Control Unit for MasterPact MTZ Circuit Breakers - User Guide DOCA0102EN

MasterPact MTZ Modbus Communication Guide DOCA0105EN


ULP System for PowerPact and MasterPact Circuit Breakers - User Guide 0602IB1503 (EN)

TCSEGWB13FA0 - Portable Battery Powered Wi-Fi Access Point - Instruction Sheet NHA24030

You can download these technical publications and other technical information
from our website at https://www.se.com/en/download

DOCA0037EN-09 9
Introduction

Introduction
Overview
Presentation
The FDM128 Ethernet display for eight devices is a 1-to-8 human machine
interface (HMI). The main component is a 5.7-inch touch screen.
An FDM128 display can be connected to devices via an Ethernet interface by
using:
• One or more Ethernet gateways (IFE server, Link150, PowerLogic EGX300
and EGX100 Ethernet, Acti9 Smartlink SI B, PowerTag Link B, Acti9
Smartlink SI D, or Acti9 Smartlink Ethernet gateways).
• One or more third-party Ethernet gateways that possess the appropriate
characteristics.
NOTE: FDM128 display does not support devices with local ID (Virtual ID)
from the Com'X or Link150 gateways.
Each type of connection is described further in this section.
The FDM128 display can monitor and control up to eight devices. The information
displayed includes measurements, alarms, and operating assistance data.
For ease of installation, a device discovery function is embedded in the FDM128
display.

Number and Nature of Connected Devices


Up to eight devices from the following list can be monitored simultaneously:
• MasterPact MTZ circuit breakers
• MasterPact NT/NW circuit breakers or switch-disconnectors
• ComPact NS 1600b-3200 circuit breakers or switch-disconnectors
• ComPact NS 630b-1600 circuit breakers or switch-disconnectors
• PowerPact P- and R-frame circuit breakers
• ComPacT NSX circuit breakers or switch-disconnectors
• PowerPacT™ H-, J-, and L-frame circuit breakers
• Acti9 Smartlink SI B
• Acti9 Smartlink SI D
• Acti9 Smartlink Modbus
• PowerTag Link
• PowerTag Link B
• PowerTag Link HD
NOTE: PowerTag Link B is equivalent to Acti9 Smartlink SI B.

10 DOCA0037EN-09
Introduction

Monitored Devices Through Acti9 Smartlink SI B


When an Acti9 Smartlink SI B is connected to the FDM128 display, the status of
the devices connected through the Acti9 Smartlink SI B can be viewed on the
FDM128 display.
The status of the following devices can be viewed on the FDM128 display:
• Acti9 iOF+SD24 and OF+SD24 indication auxiliaries
• Acti9 OF24 indication auxiliaries
• Acti9 SD24 indication auxiliaries
• Acti9 iACT24 and iATL24 auxiliaries for contactors and impulse relays in the
Acti9 range
• Acti9 RCA iC60 remote control module with Ti24 interface
• Acti9 Reflex iC60 integrated control circuit breaker with Ti24 interface
• Acti9 PowerTag energy sensors, which are directly mounted on a Acti9 circuit
breaker and communicate with the Acti9 Smartlink SI B through wireless
communication. Refer to the Component Part Numbers for the list of Acti9
PowerTag energy sensors , page 18.
• PowerTag NSX energy sensors, which are directly mounted on a ComPacT
NSX circuit breaker and communicate with the Acti9 Smartlink SI B through
wireless communication. Refer to the Component Part Numbers for the list of
PowerTag NSX energy sensors , page 18.
• iEM2000T, iEM3110, iEM3155, iEM3210, and iEM3255 energy meters
• ComPacT NSX OF+SD indication auxiliaries
NOTE: The Acti9 Smartlink product range is not available in the following
countries: United States, Canada, Mexico. Consult the catalog for the list of
products available in your country.

Monitored Devices Through Acti9 Smartlink SI D


When an Acti9 Smartlink SI D is connected to the FDM128 display, the status of
the devices connected through the Acti9 Smartlink SI D can be viewed on the
FDM128 display.
The status of the following devices can be viewed on the FDM128 display:
• Acti9 PowerTag energy sensors, which are directly mounted on a Acti9 circuit
breaker and communicate with the Acti9 Smartlink SI D through wireless
communication. Refer to the Component Part Numbers for the list of Acti9
PowerTag energy sensors , page 18.
• PowerTag NSX energy sensors, which are directly mounted on a ComPacT
NSX circuit breaker and communicate with the Acti9 Smartlink SI D through
wireless communication. Refer to the Component Part Numbers for the list of
PowerTag NSX energy sensors , page 18.
NOTE: The Acti9 Smartlink product range is not available in the following
countries: United States, Canada, Mexico. Consult the catalog for the list of
products available in your country.

DOCA0037EN-09 11
Introduction

Architecture Examples
FDM128 Display Connected to an IFE Server
The following diagram is an example of an IFE- based network architecture:

A FDM128 Ethernet display for eight H EIFE embedded Ethernet interface for one
devices MasterPact MTZ drawout circuit breaker
B IFE Ethernet switchboard server I ULP line termination
C IFM Modbus-SL interface for one J ULP cord
circuit breaker
D FDM121 ULP display for one circuit K NSX cord
breaker
E I/O input/output application module for L Acti9 Smartlink Modbus
one circuit breaker
F MasterPact MTZ drawout circuit Ethernet
breaker
G ComPacT NSX, PowerPacT H-, J-, or Modbus-SL
L-frame circuit breaker
24 Vdc

12 DOCA0037EN-09
Introduction

FDM128 Display Connected to an Acti9 Smartlink SI B Gateway


The following diagram is an example of an Acti9 Smartlink SI B network
architecture, in a floor switchboard application:

A FDM128 Ethernet display for eight devices

B ConneXium switch
C ComPacT NSX, PowerPacT H-, J-, or L-frame circuit breaker

D Acti9 Smartlink SI B
E Acti9 Smartlink Modbus
F Acti9 iEM energy meter

G Acti9 PowerTag energy sensor

Ethernet
Modbus-SL
24 Vdc
TI24 cord

DOCA0037EN-09 13
Introduction

FDM128 Display Connected to an Acti9 Smartlink SI D Gateway


The following diagram is an example of an Acti9 Smartlink SI D wireless network
architecture, in a floor switchboard application:

A FDM128 Ethernet display for eight devices

B ConneXium switch

C ComPacT NSX circuit breaker


D PowerTag NSX energy sensor

E Acti9 Smartlink SI D
F PowerTag energy sensor

Ethernet
24 Vdc

14 DOCA0037EN-09
Introduction

FDM128 Display Connected to a PowerLogic EGX300 or EGX100 Ethernet Gateway


The following diagram is an example of a network architecture with a PowerLogic
EGX300 Ethernet gateway:

A FDM128 Ethernet display for eight I ULP line termination


devices
B ConneXium switch J ULP cord

C EGX300 Ethernet gateway K BCM ULP

D IFM Modbus-SL interface for one L NSX cord


circuit breaker
E FDM121 ULP display for one circuit M Acti9 Smartlink Modbus
breaker
F CCM Modbus cradle communication Ethernet
module
G MasterPact NT/NW circuit breaker Modbus-SL
H ComPacT NSX, PowerPacT H-, J-, 24 Vdc
or L-frame circuit breaker

DOCA0037EN-09 15
Introduction

FDM128 Display Connected to Several IFE or Acti9 Smartlink SI B or


Acti9 Smartlink SI D
The following diagram is an example of an IFE- and Acti9 Smartlink SI B or Acti9
Smartlink SI D-based network architecture:

A FDM128 Ethernet display for eight I ULP line termination


devices
B ConneXium switch J NSX cord
C IFE Ethernet interface for one K PowerTag energy sensor
circuit breaker
D I/O input/output application module L Acti9 PowerTag energy sensor
for one circuit breaker
E MasterPact MTZ fixed circuit Ethernet
breaker
F ComPacT NSX, PowerPacT H-, J-, 24 Vdc
or L-frame circuit breaker
G Acti9 Smartlink SI B TI24 cord
H ULP cord 110/230 Vac

16 DOCA0037EN-09
Introduction

FDM128 Display Connected to Several Gateways


The following diagram is an example of architecture where the FDM128 display is
connected to several gateways:

A FDM128 Ethernet display for eight J Acti9 Smartlink Modbus


devices
B IFE Ethernet switchboard server K EIFE embedded Ethernet interface for one
MasterPact MTZ drawout circuit breaker
C IFM Modbus-SL interface for one L ULP cord
circuit breaker
D I/O input/output application module M NSX cord
for one circuit breaker
E MasterPact MTZ drawout circuit N Acti9 PowerTag energy sensor
breaker
F ComPacT NSX, PowerPacT H-, J-, Ethernet
or L-frame circuit breaker
G ConneXium switch Modbus-SL
H ULP line termination 24 Vdc
I Acti9 Smartlink SI B TI24 cord

DOCA0037EN-09 17
Introduction

Component Part Numbers


The following table lists the part numbers for the components in the architecture
diagrams:

Component Description Part Number

FDM128 Ethernet display for eight devices – LV434128

STU 5in7 front module spare part – HMIS85

IFE Ethernet interface for one circuit breaker – LV434001


IFE Ethernet switchboard server – LV434002
EIFE embedded Ethernet interface for one MasterPact EIFE embedded Ethernet interface LV851001
MTZ drawout circuit breaker
Spare part kit EIFE for one MasterPact LV851100SP
MTZ1 drawout circuit breaker
Spare part kit EIFE for one MasterPact LV851200SP
MTZ2/MTZ3 drawout circuit breaker
IFM Modbus-SL interface for one circuit breaker – LV434000
FDM121 ULP display for one circuit breaker – • TRV00121 (IEC)
• STRV00121 (UL)

I/O input/output application module for one circuit breaker – LV434063

ULP line termination 10 ULP line terminations TRV00880


ULP cord L = 0.3 m (0.98 ft) TRV00803

L = 0.6 m (1.97 ft) TRV00806

L = 1 m (3.28 ft) TRV00810

L = 2 m (6.56 ft) TRV00820

L = 3 m (9.84 ft) TRV00830

L = 5 m (16.40 ft) TRV00850

BCM ULP cord L = 0.35 m (1.15 ft) LV434195

L = 1.3 m (4.26 ft) LV434196

L = 3 m (9.84 ft) LV434197

TI24 cord - A9XCAS06


NSX cord L = 0.35 m (1.15 ft) LV434200

L = 1.3 m (4.27 ft) LV434201

L = 3 m (9.84 ft) LV434202

Acti9 Smartlink SI B – A9XMZA08


PowerTag Link B – A9XMZC20

Acti9 Smartlink Modbus – A9XMSB11


Acti9 Smartlink SI D – A9XMWA20
PowerLogic EGX300 Ethernet gateway – • EGX300 (Schneider
Electric)
• EGX300SD (Square D)

iEM2000T energy meter Single-phase energy meter without display A9MEM2000T

iEM3110 energy meter Three-phase energy meter with display A9MEM3110

iEM3155 energy meter Three-phase energy meter with display A9MEM3155

iEM3210 energy meter Three-phase energy meter with display A9MEM3210

iEM3255 energy meter Three-phase energy meter with display A9MEM3255

Acti9 PowerTag energy sensor One-phase wireless energy sensor A9MEM1520

One-phase and neutral wireless energy A9MEM1521


sensor

18 DOCA0037EN-09
Introduction

Component Description Part Number

One-phase and neutral wireless energy A9MEM1522


sensor
Three-phase wireless energy sensor A9MEM1540

Three-phase and neutral wireless energy A9MEM1541


sensor
Three-phase and neutral wireless energy A9MEM1542
sensor
One-phase and neutral wireless energy A9MEM1560
sensor
One-phase and neutral wireless energy A9MEM1561
sensor
One-phase and neutral wireless energy A9MEM1562
sensor
One-phase and neutral wireless energy A9MEM1563
sensor
Three-phase and neutral wireless energy A9MEM1570
sensor
Three-phase and neutral wireless energy A9MEM1571
sensor
Three-phase and neutral wireless energy A9MEM1572
sensor
Three-phase and neutral wireless energy A9MEM1580
sensor
Three-phase and neutral wireless energy A9MEM1590
sensor
Three-phase and neutral wireless energy A9MEM1591
sensor
Three-phase and neutral wireless energy A9MEM1592
sensor
Three-phase and neutral wireless energy A9MEM1593
sensor
PowerTag NSX Wireless Communication Energy Sensor Three-phase wireless communication LV434020
3P for ComPacT NSX100–250, ComPact INS250, energy sensor
ComPact INV100–250
PowerTag NSX Wireless Communication Energy Sensor Four-pole wireless communication energy LV434021
4P for ComPacT NSX100–250, ComPact INS250, sensor
ComPact INV100–250
PowerTag NSX Wireless Communication Energy Sensor Three-phase wireless communication LV434022
3P for ComPacT NSX400–630, ComPact INS320–630, energy sensor
ComPact INV320–630
PowerTag NSX Wireless Communication Energy Sensor Four-pole wireless communication energy LV434023
4P for ComPacT NSX400–630, ComPact INS320–630, sensor
ComPact INV320–630

NOTE: The Acti9 Smartlink product range is not available in the following
countries: United States, Canada, Mexico. Consult the catalog for the list of
products available in your country.

DOCA0037EN-09 19
Introduction

Recommendations
Critical Systems, Alarms, and Handling Requirements
Critical alarm indicators and system functions require independent and redundant
hardware protection and/or mechanical interlocks.
If the FDM128 Ethernet display for eight devices becomes inoperative due to
some reason (for example, due to an inoperative backlight), it may be difficult or
impossible to identify a function. Functions that may present a hazard if not
immediately executed, such as an emergency stop, must be provided
independently of the FDM128 display.
The design of the control system must take into account simultaneously:
• An inoperative FDM128 display.
• The operator inability to control the circuit breakers or to respond to detected
errors by using the FDM128 display.

Handling the LCD Panel


The following characteristics are specific to the LCD panel and are considered
normal behavior:
• LCD screen may show unevenness in the brightness of certain images.
These images may appear differently when seen from outside the specified
viewing angle. Extended shadows, or cross-talk, may also appear on the
sides of screen images.
• LCD screen pixels may contain black and white-colored spots and color
display may seem to have changed over time.
• When the same image is displayed for a long period, an after-image may
appear when the image changes. If this happens, turn off the FDM128
display, wait 10 seconds, and then restart it.
NOTE: Do not display the same image for a long time, change the screen
image periodically.

CAUTION
SERIOUS EYE AND SKIN INJURY
The liquid present in the LCD panel contains an irritant:
• Avoid direct skin contact with the liquid.
• Wear gloves when you handle a broken or leaking FDM128 display.
• Do not use sharp objects or tools in the vicinity of the LCD touch panel.
• Handle the LCD panel carefully to prevent puncture, bursting, or cracking of
the panel material.
If the panel is damaged and any liquid comes in contact with your skin,
immediately rinse the area with running water for at least 15 minutes.
If the liquid gets in your eyes, immediately rinse your eyes with running water for
at least 15 minutes and consult a doctor.
Failure to follow these instructions can result in injury or equipment
damage.

20 DOCA0037EN-09
Introduction

Using the Touch Panel Correctly

WARNING
UNINTENDED EQUIPMENT OPERATION
• Operate the touch panel with only one finger.
• Do not activate two or more points of the touch panel simultaneously.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

Use only one finger to select an object on the touch panel.


If the touch panel receives pressure at two or more points at the same time, an
unintended object could be selected.

DOCA0037EN-09 21
Introduction

Certifications and Standards


Introduction
Schneider Electric has submitted this product for independent testing and
qualification by third-party listing agencies. These agencies have certified this
product as meeting the following standards.
The FDM128 display is certified by the Underwriters Laboratories according to UL
508 for Industrial Control Equipment.
The FDM128 display is designed to comply with merchant navy bridge and deck
requirements (refer to the Schneider Electric website for installation guidelines).
For detailed information, contact your local distributor or see the catalog and
marking on the product.

Compliance with Standards


The FDM128 display complies with the following standards:
• IEC 60947-1 general rules
• UL 508, Industrial Control Equipment
• CSA C22.2 No. 14-05 Industrial Control Equipment
• IACS E10

Hazardous Substances
The FDM128 display is designed for compliance with the following directives and
standards:
• WEEE, Directive 2002/96/EC
• RoHS, Directive 2002/95/EC
• RoHS China, Standard SJ/T 11363-2006

UL Conditions of Acceptability for the FDM128 Display


The FDM128 display is suitable for use in hazardous locations in accordance with
Class 1, Division 2 standards. All relevant local, state, and regional codes must be
followed.

22 DOCA0037EN-09
Introduction

CE Markings

This product conforms to the requirements for applying the label.

WARNING
RISK OF EXPLOSION IN HAZARDOUS LOCATIONS
• Verify that the power, input, and output (I/O) wiring are in accordance with
Class I, Division 2 wiring methods.
• Do not substitute components that could impair compliance to Class I,
Division 2.
• Do not connect or disconnect equipment unless power has been switched off
or the area is known to be non-hazardous.
• Securely lock externally connected units and each interface before turning
on the power supply.
• Do not disconnect while the circuit is live.
• Front panel is a potential electrostatic charging hazard. Wipe the front panel
of the terminal with a damp cloth before turning on.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

DOCA0037EN-09 23
Introduction

General Specifications
Electrical Characteristics
Characteristic Value
Rated input voltage 24 Vdc

Input voltage limits 20.4–28.8 Vdc

Acceptable voltage drop ≤ 7 ms

Power consumption ≤ 6.8 W

In-rush current ≤ 30 A
Voltage endurance between power terminal and functional 1,000 Vac 20 mA for 1 minute
ground (FG)

Insulation resistance between power terminal and functional 10 MΩ or higher at 500 Vdc
ground (FG)

Physical Characteristics

Characteristic Value
Ambient operating temperature (cabinet interior and panel face) –10 °C to +55 °C (14–131 °F)

Storage temperature –40 °C to +85 °C (–40 °F to +185 °F)

Relative humidity 95 % without condensation (non-condensing, wet bulb temperature 55


°C (131 °F) or less)

Air purity (dust) ≤ 0.1 mg/m3 (≤ 10-7 oz/ft3) (non-conductive levels)

Corrosive gases Free of corrosive gases

Atmospheric pressure 800–1,114 hPa (2000 m (6,500 ft) or lower)

Mechanical Characteristics
Characteristic Value
Vibration immunity (operating) IEC 60068-2-6

1 gn (1 g) 5–150 Hz (maximum 3.5 mm (0.13 in.))

Protection (front panel) IP65 (IEC 60529)

Protection structure Type 4X indoor, installed on a panel

Protection (rear panel) IP20 (IEC 60529)

Shock immunity (operating) IK05 (IEC 60068-2-75)

15 gn (1 g) 11 ms

Cooling method Natural air circulation

Weight 0.25 kg (0.55 lb.)

Color Front bezel: dark gray

Material PC/PBT and PAA

24 DOCA0037EN-09
Introduction

Electrical Environment Specifications

Characteristic Value
Noise immunity Noise voltage: 1,000 Vp-p

Pulse width: 1 µs

Rising time: 1 ns

High energy surges 2 kV CM, 0.5 kV DM on DC power supply

2 kV CM on shielded cables
Electrical fast transient burst 2 kV CM, 2 kV DM on DC power supply

1 kV on shielded cables
Radiated radio frequency electromagnetic field 10 V/m / 80 MHz to 2 GHz

Sinus amplitude modulated 80 %

1 kHz + internal clock frequency

Electrostatic discharge immunity 8.8 kV direct contact

12 kV air contact
Power frequency magnetic field 100 A/m continuous

Grounding D-type grounding (SG-FG connected)

CM: Common Mode

DM: Differential Mode

DOCA0037EN-09 25
Introduction

Functional Specifications
Display Characteristics

Characteristic Description

Type Color TFT LCD

Resolution (pixels) 320 x 240 (QVGA)

Active display area (W x H) 115.2 x 86.4 mm (4.53 x 3.40 in.)

Display colors 65,536 colors

Backlight LED backlight

Lifetime: 50,000 hours before dimmed to 50 % brightness

Ambient temperature: 25 °C (77 °F)

Non-exchangeable

Brightness adjustment 16 levels of adjustment available via touch panel in the General settings menu.

Brightness on LCD surface White LED: 350 cd/m2 (33 cd/ft2) maximum

View angle • 80 degrees: left, right


• 70 degrees: up
• 70 degrees: down
(Test condition: contrast ratio > 2)

Clock
Variations in operating conditions can cause a clock shift from -380 seconds to
+90 seconds per month.

Touch Panel
Characteristic Description

Type Analog resistance film type (metal tab, golden plated)

Lifetime 1 million touches or more

26 DOCA0037EN-09
Introduction

Interface Specifications
USB1 Interface (USB Peripherals)

HOST Interface Characteristic Value


Transmission speed High speed 480 Mbps

Full speed 12 Mbps

Low speed 1.5 Mbps

Maximum current supplied 250 mA

Maximum transmission distance 5 m (16.40 ft) at 12 Mbps

Connector USB Type-A V2.0

Ethernet Interface
LED Description

Green 1 Link state


Green 2 Activity

DOCA0037EN-09 27
Presentation

Presentation
Screen
Overview
The following figure describes the display area:

A Header
B Title bar
C Headpiece

D Right area

E Left area
F Footer

Header
The header (A) is composed of the following elements:
• Product name (FDM128) and access profile
• Direct-access icons to the main functions

Icon Description

Go to General view menu , page 43.

Refresh the display of the names of connected devices.

Locate the device (or intelligent modular unit) , page 44.

Go to Login/Access Code settings menu , page 40.

Go to Editing devices menu , page 38.

28 DOCA0037EN-09
Presentation

Icon Description

Go to Communication settings menu , page 35.

Go to General settings menu , page 34.

Title Bar
The title bar (B) contains the title of the screen or name of the selected device.

Main Area
The main area includes the headpiece (C), the right area (D), and the left area (E).
The following table describes the parts of the main display area:

Position Description Use

Headpiece (C) Right area title Navigate through the submenus items.

Right area (D) Information Displays information of the selected submenu or submenu item.

Information screens depend on the device.

Left area (E) Submenus, if applicable Navigate through the submenus.

Various contents depending on the device.

Footer
The footer (F) contains some navigation icons depending on the selected screen.
The icons are listed in the appendix , page 64.
If there is more than one page in the selected submenu, the screen number is
displayed. The screen number format is X/Y, where X is the current screen
number and Y is the total number of screens.

DOCA0037EN-09 29
Presentation

Menu Structure
Menu Types
FDM128 menus are divided into two types:
• Settings menus: blue title bar background
• Operation menus: green title bar background

Settings Menus
Settings menus are composed of two sequences:
• General settings sequence
• Settings sequence for devices: communication settings, device discovery,
and editing devices
The setting wizard, page 34 of the FDM128 display guides you through these
sequences.

General View
The General view menu is used to monitor up to eight devices at the same time.
For further information, refer to the general view topic, page 43.

Device View
Device view menus are only accessible from the General view menu.
The Device view for circuit breakers menu is composed of the following
submenus:
• Quick view , page 49
• Measures , page 49
• Alarm history , page 50
• Control , page 50
• Maintenance , page 51
• I/O1 and I/O2 , page 52
The Device view for Acti9 Smartlink SI B menu is composed of the following
submenus:
• Status
• Counters (energy, water, gas...)
• Control , page 54
• PowerTag , page 54
The Device view for Acti9 Smartlink SI D menu is composed of PowerTag
submenu , page 54.

30 DOCA0037EN-09
Presentation

Browsing
Navigate Through the Screens
In a menu or a submenu, you can navigate through the screens by using the
footer icons.
The browsing actions are executable by pressing the icons. Refer to the icon list,
page 64 to get the meaning of each of them.
The icons are available depending on the network configuration, the selected
menu, and the possible actions.
NOTE: A gray icon means that the option or action is not available in the
actual context.

Data Entry
When an action requires an alphanumeric entry (for example, typing a
designation), the following touch keyboard is displayed:

When an action requires a numeric entry (for example, typing an IP address), the
numeric keyboard is displayed.
NOTE: You can also display the numeric keyboard by pressing the 123 key on
the alphanumeric keyboard.

DOCA0037EN-09 31
Configuration

Configuration
Prerequisites
Ethernet Network
The Ethernet connections of the IP devices in the Ethernet network must be
correctly installed and configured.
NOTE: To connect to an Ethernet device outside the subnetwork a popup
message requests your confirmation to connect to another subnetwork.
The Ethernet network may include the following IP devices:
• EGX300 or EGX100 gateways
• Link150 gateways
• IFE or EIFE interfaces
• IFE server
• Acti9 Smartlink Ethernet devices
• Acti9 Smartlink SI B
• Acti9 Smartlink SI D
• PowerTag Link
• PowerTag Link B
• PowerTag Link HD
• Third-party gateways
NOTE: FDM128 display does not support devices with local ID (Virtual ID)
from the Com'X or Link150 gateways.
For further information, refer to the corresponding user guides , page 8.
NOTE: PowerTag Link B is equivalent to Acti9 Smartlink SI B.

Modbus Serial Line Network


The devices in the Modbus serial line network must be correctly installed and
configured with the following Modbus parameters:

Parameter Value
Modbus address (slaves only) The Modbus address of each monitored device must be unique. The range of Modbus
addresses is [1-247].

Physical interface RS-485 2-wire

Transmission mode RTU (Automatic)

Communication speed The communication speed must be the same for all devices.

Parity The parity must be the same for all devices.

Response time-out 1 second

To check the Modbus parameters of each monitored device, refer to , page 8:


• The BCM ULP Circuit Breaker Communication Module Installation Manual
• The IFM Modbus-SL Interface for One Breaker - Instruction Sheet
• The Acti9 Smartlink Modbus Communication System User Manual

32 DOCA0037EN-09
Configuration

Architecture Network Limitation


The limitations of the architecture network are as follows:
• Modbus serial line time out in the IFE device should be 1 s
• To avoid communication error or not to overload the network, a maximum of
two FDM128 displays must be connected to the same IFE device. The
FDM128 displays can scan data of the same circuit breaker.

DOCA0037EN-09 33
Configuration

Setting Wizard
Wizard Presentation
A setting wizard is automatically launched at first power-on to help you set up the
FDM128 display.
The setting wizard guides you through three main configuration parts:
1. FDM128 display general settings
2. Communication settings depending on the network architecture
3. Editing device function
Each configuration part is described further in this section.
It is recommended that you update the communication settings each time you
modify the communication network.

General Settings
The following table describes the sequence of steps presented by the setting
wizard to configure the FDM128 general settings:

Step Screen Action

1 Welcome Touch the screen to start the wizard.


2 Language Select a language.

In the footer, press to access the next step.

3 Refresh Rate Press one of the two possible ways to set manually the real-time sample rate in the
General View:
• Fast (default setting): refresh every 3 s for circuit breakers and 5 s for Acti9
Smartlink.
• Slow: refresh every 10 s for all devices.
Example:
• 8 MasterPact MTZ circuit breakers connected in Fast refresh mode has a
maximum duration equal to (8x3) = 24 seconds.
• 8 MasterPact MTZ circuit breakers connected in Slow refresh mode has a
maximum duration equal to (8x10) = 80 seconds.

In the footer, press to access the next step.

4 Phase labels Press one of the two possible ways to represent the phases 1,2,3,N (default setting), or
A,B,C,N.

In the footer, press to access the next step.

5 Units of measurement I/O Select the units of measurement for the analog input of the I/O modules:
• The unit of temperature (°C (default setting) or °F)
• The unit of volume (m3 (default setting) or gallon US or gallon UK)

In the footer, press to access the next step.

6 Brightness Press the -/+ icons to adjust the brightness level of the display.

In the footer, press Finish.

The setting wizard displays the Selection of the communication architecture screen
to allow you to set up the FDM128 communication. Follow the communication settings
procedure that corresponds to your network architecture.

34 DOCA0037EN-09
Configuration

Communication Settings for a Single Gateway-Based Architecture


This procedure is applicable when:
• The FDM128 display is connected to an IFE interface, page 16 or an EIFE
interface , page 12
• The FDM128 display is connected to an Acti9 Smartlink SI B or Acti9
Smartlink SI D gateway , page 13
• The FDM128 display is connected to an EGX gateway
The FDM128 setting wizard guides you through the following steps:

Step Action

1 Configure the FDM128 display within the network.

Set the following parameters:


• The FDM128 IP address
• The subnet mask
• The default gateway IP address

2 Press YES to indicate that the FDM128 display is connected to a gateway.

3 Set the IP address of the gateway.

4 Enter Modbus range between 1–247.

5 Press Start to launch the device discovery sequence , page 36.

Up to 16 devices are displayed.

6 Select up to eight devices among the devices displayed.

7 If you select less than eight devices among the devices displayed, you are prompted for an additional gateway. Press NO.

8 If needed, you can configure manually extra IFE, EIFE, Acti9 Smartlink SI B, or Acti9 Smartlink SI D devices.

9 Press Finish.

The FDM128 display can now monitor the list of selected devices.

The setting wizard displays the Editing devices screen to allow you to edit the label and name of the devices.

Communication Settings for Several Gateway-Based Architectures


This procedure is applicable when the FDM128 display is connected to several
gateways, page 17.
The FDM128 setting wizard guides you through the following steps:

Step Action

1 Configure the FDM128 display within the network.

Set the following parameters:


• The FDM128 IP address
• The subnet mask
• The default gateway IP address

2 Press YES to indicate that the FDM128 display is connected to a gateway.

3 Set the IP address of the gateway.

4 Enter Modbus range between 1–247.

5 Press Start to launch the device discovery sequence , page 36.

Up to 16 devices are displayed.

6 Select up to eight devices among the devices displayed.

7 If you select less than eight devices among the devices displayed, you are prompted for an additional gateway.

If you have another gateway to configure, press YES and go back to step 3.

DOCA0037EN-09 35
Configuration

Step Action

8 When you have configured all gateways, press NO. You can now manually configure extra IFE, EIFE, Acti9 Smartlink SI B,
or Acti9 Smartlink SI D devices.
9 Press Finish.

The FDM128 display can now monitor the list of selected devices.

The setting wizard displays the Editing devices screen to allow you to edit the label and name of the devices.

NOTE: Before launching the auto discovery, make sure that the Modbus serial
line time out is 1 s.

Communication Settings for Several IFE, EIFE, Acti9 Smartlink SI B, or Acti9 Smartlink
SI D Architecture
The procedure is applicable when the FDM128 display is connected to several
IFE, EIFE , Acti9 Smartlink SI B, or Acti9 Smartlink SI D, page 16 devices.
The FDM128 setting wizard guides you through the following steps:

Step Action

1 Configure the FDM128 display within the network.

Set the following parameters:


• The FDM128 IP address
• The subnet mask
• The default gateway IP address

2 Press NO to indicate that there is no gateway.

3 Configure manually up to eight IFE, EIFE, Acti9 Smartlink SI B, or Acti9 Smartlink SI D devices.

4 Press Finish.

The FDM128 display can now monitor the list of selected devices.

The setting wizard displays the Editing devices screen to allow you to edit the label and name of the devices.

Device Discovery
The device discovery feature enables detection of devices in a given Modbus
range (1–247).
NOTE: The default Modbus range is 1–10.
The device discovery sequence detects up to 16 devices on the network as per
the given Modbus range. These devices are displayed sorted in ascending order
of Modbus address, with the Modbus address indicated in the first column.
The device discovery sequence time varies depending on the Modbus range
selected.
NOTE: The 16 detected devices are those with the 16 first Modbus addresses.
Among the detected devices, you can select a maximum of eight devices.
The FDM128 display guides you through the following device discovery
procedure:

36 DOCA0037EN-09
Configuration

Step Action

1 The device discovery sequence is started during the communication settings procedure.

A progress bar is displayed during the device discovery sequence.


NOTE: During the device discovery, if you want to stop the discovery sequence, press Cancel. It will take you back to
the Device Discovery page.

2 In the list of the discovered devices, select the check box for each device you want to include.

Devices previously selected in a device discovery loop are displayed in gray.

3 Press Finish.

The Editing devices screen appears.

Manual Configuration of IFE, EIFE, Acti9 Smartlink SI B, and Acti9 Smartlink SI D


You configure devices manually either after a device discovery sequence, or if you
do not have a IFE, EIFE, Acti9 Smartlink SI B, or Acti9 Smartlink SI D gateway.
To configure devices manually during the device settings sequence, proceed as
follows:

Step Action

1
On the configuration screen, tick the check boxes of the number of IFE, EIFE, Acti9 Smartlink SI B, or Acti9 Smartlink SI D
devices to configure.

2 For each selected device, set its IP address.

3 Press OK to launch the device discovery sequence.Device Discovery page is displayed with the list of available gateways.
NOTE: A maximum of 8 devices can be discovered.
4 Select up to eight devices among the devices displayed.

5 If you select less than eight devices among the devices displayed, you are prompted for an additional gateway. Press NO.

6 If needed, you can configure manually extra IFE, EIFE, Acti9 Smartlink SI B, or Acti9 Smartlink SI D devices.

7 Press Finish.

The FDM128 display can now monitor the list of selected devices.

The setting wizard displays the Editing devices screen to allow you to edit the label and name of the devices.

Power Loss
In case of power loss, the FDM128 display retains the settings.

DOCA0037EN-09 37
Configuration

Settings During Operation


General Settings
Setting functions that can be used during operation, without restarting the setting
wizard, are:
• Modifying the general settings
• Editing devices
• Adding single IP devices manually

During operation, you can access the General settings menu by pressing .

Editing Devices
Limitations
When the following devices are used together, you cannot write or edit the device
name:
• MasterPact with BCM module, firmware version lower than 3.2.5.
• ComPact NS with BCM module, firmware version lower than 3.2.5.
• PowerPact P- and R-frame with BCM module, firmware version lower than
3.2.5.
An example network architecture is provided in this guide, page 15.
Prerequisites
Before editing devices, you must verify that the following prerequisites are met:
• Circuit breaker must be in the remote control mode.
• Device logging in the IFE or EIFE webpage must be disabled.
• Only the following characters are allowed:
◦ Upper case letters from A to Z
◦ Lower case letters from a to z
◦ Digits from 0 to 9
◦ Hyphen -
• Before editing the name and label of the circuit breaker:
◦ The EIFE intrusive command mode must be unlocked
◦ The locking pad of the IFE, or IFM interface must point to the open
padlock, as shown in the following graphic

When the communication network is configured, access the Editing devices

menu by pressing .
Use the Editing devices menu to:
• Provide a label for each device:
The label is defined in the ID field and is only displayed in the FDM128
display. The ID field contains up to 4 characters.
• Rename a device:
The name is defined in Name field and is the actual name of the device. You
may need to use the device password to rename the device. The Name field
contains up to 12 characters.
NOTE: Press OK to validate the settings and go back to the operation mode.

38 DOCA0037EN-09
Configuration

Communications Settings
During operation, you can access the Communication settings menu by

pressing .

Use this menu to:


• View the present communication settings configuration.
• Restart the setting wizard, page 34, beginning at the point following the
general settings, where you can modify the FDM128 display settings.
• If the number of devices is less than eight, manually add an IFE interface, an
EIFE interface, an Acti9 Smartlink SI B, or an Acti9 Smartlink SI D.

Access Code Settings


During operation, you can access the Access Code settings menu by pressing

. Use this menu to view and edit user login and access code settings, page
40.

DOCA0037EN-09 39
Operation

Operation
Logins and Access Codes
Levels of Access
The FDM128 display requires login and access code combinations to access the
following functions:
• Monitoring functions:
By default, you do not need to log in to access monitoring functions (viewer or
guest) access).
• Operation functions:
Log in as an operator to access operation functions (operator access).
• Administration, communication, and other advanced functions:
Log in as administrator to access advanced functions (administrator access).
The various functions that available at different access levels are listed in the
table.

Function Type Guest Operator Administrator

IO output control Control No Yes Yes

Light and load control Control No Yes Yes

Breaker control Control No No Yes


Acti9 device control Control No Yes Yes
Reset measurement (min max, energy) Configuration No Yes Yes

Edit breaker device names Configuration No No Yes

Discovery of devices Configuration No No Yes

General settings (language, date, brightness) Configuration No Yes Yes

Configuration of login and access code Configuration No No Yes

Monitoring Monitor Yes Yes Yes

NOTE: Menus and functions that are not available at an access level are
grayed out.

Login Procedure
To log in to the FDM128 display, follow these steps:

Step Action

1
Press .

The Operator/Administrator access screen opens.

2 Enter your login and access code.

3 Press OK.

In the screen header, you can now access the direct function icons for your level.

40 DOCA0037EN-09
Operation

Logout Procedure
To log out of the FDM128 display, follow these steps:

Step Action

1
When you are logged in to the FDM128 display, press .

The Login/Access code management screen opens.

2 Press Logout.

3 When prompted to confirm logout, press YES.

In the screen header, you can now access only the Login/Access code function icon.

NOTE: If you do not touch any button or function on the FDM128 display for
25 minutes, you are automatically logged out.

Configuring Logins and Access Codes


The predefined default user login/access code combinations are:
• For the administrator: admin/admin
• For the operator: oper/oper
If you need to change a login name or access code, follow these steps:

Step Action

1 Log in as administrator.

In the General view screen, in the screen header, you can now access all the direct function icons.

2
Press .

The Login/Access code management screen opens.

3 Press Configuration.

The Operator : login configuration screen opens.

4 Type the new login for an operator.

The login:
• Is case-sensitive.
• Can contain from 1 to 16 characters.
• Can contain alphanumeric characters and symbols, excluding the space character.

After editing the operator login value, press to go to the next screen.

The Operator : access code configuration screen opens.

5 Type the new access code for an operator.

The access code:


• Is case-sensitive.
• Can contain from 1 to 16 characters.
• Can contain alphanumeric characters and symbols, excluding the space character.

After editing the operator access code value, press to go to the next screen.

The Administrator : login configuration screen opens.

6 Type the new login for an administrator.

The login:
• Is case-sensitive.
• Can contain from 1 to 16 characters.
• Can contain alphanumeric characters and symbols, excluding the space character.

DOCA0037EN-09 41
Operation

Step Action

After editing the administrator login value, press to go to the next screen.

The Administrator : access code configuration screen opens.

7 Type the new access code for an administrator.

The login:
• Is case-sensitive.
• Can contain from 1 to 16 characters.
• Can contain alphanumeric characters and symbols, excluding the space character.
After editing the administrator access code value, do one of the following:

• Press one or more times to go back to previous login and access code configuration screens.
• Press OK.
8 When prompted to confirm changes to the logins and access codes, press YES.

Login/Access code Reset

You can restore the default login and access code settings by pressing and
holding it down for 10 seconds.

42 DOCA0037EN-09
Operation

General View
Overview
The General view menu allows you to monitor up to eight selected devices
through summarized information.
There are two display modes:
• Icon
• List
Switch between display modes by pressing the corresponding icon in the lower
right corner of the screen.
From this menu, you can reach the Device view screens of the monitored
devices:
• Device view for ComPact, PowerPact, MasterPact circuit breakers, page 48.
• Device view for Acti9 Smartlink devices, page 53.

Icon Mode

In the icon mode, the eight devices are displayed on one screen, each one by an
icon.
To reach a Device view, press the corresponding icon.
NOTE: If only one device is discovered, the display, skips the General view
and displays the Device view of the discovered device.

List Mode

In the list mode, four devices are displayed per screen, one per line.

To reach Device view, press on the corresponding line.

DOCA0037EN-09 43
Operation

Locating Intelligent Modular Units


The FDM128 display enables you to identify a circuit breaker that is part of a
monitored intelligent modular unit (IMU), by making its MicroLogic trip unit or
FDM121 display blink.
NOTE: A modular unit is a mechanical and electrical assembly containing one
or more products that perform a function in a switchboard (incoming
protection, motor command, and control). An IMU is a circuit breaker in which
internal communicating components and external ULP modules are
connected to one IFM, IFE, or EIFE interface. An example of internal
communicating component is the MicroLogic trip unit. Examples of external
ULP modules are the FDM121 display or the I/O module.
To locate an IMU:

Step Action

1
From the General view, in list mode, press .

The list of locatable IMU displays.


NOTE: If you do not perform any action on this screen for more than 25 minutes, you are redirected back to the General
view screen.
2
From the General settings screen, press the corresponding to the device to locate.

The backlighting of the MicroLogic trip unit, or FDM121 display, or both if present, start blinking for around 15 seconds.

During this time, also blinks on the FDM128 display.

Viewing Devices Updated Remotely


The FDM128 display can display the names of the circuit breakers and the name
of the Acti9 Smartlink SI B, Acti9 Smartlink SI D, and Acti9 Smartlink Modbus that
they are connected to. The names can be remotely updated using EcoStruxure
Power Commission software. In this case, you have to refresh the displayed
names to see the new names.

To refresh the display of names, press . A progress bar is displayed while the
screen is refreshed.
In networks where names can be updated at anytime, it is recommended to
refresh the FDM128 display periodically.

44 DOCA0037EN-09
Operation

ERMS Status for MasterPact MTZ Circuit Breaker


The ERMS status is displayed in the General view for a MasterPact MTZ circuit
breaker.
Icon Mode

In the icon mode, the device with its ERMS mode engaged displays a blue ERMS
message below the device icon.
To reach a Device view, press the corresponding icon.
List Mode

In the list mode, the device with its ERMS mode engaged displays the Ir settings
in blue.

To reach Device view, press on the corresponding line.


Device View

In the Device view, the device with its ERMS mode engaged displays an ERMS
message in the title bar.

DOCA0037EN-09 45
Operation

Real-Time Alarms
Overview
Alarms are displayed differently according to their priority level.
NOTE: The alarms must be acknowledged on the circuit breakers. There is no
acknowledgment from the FDM128 display.

Alarms for Circuit Breakers


The circuit breaker predefined alarms are displayed on the FDM128 display as
follows:

Alarm Priority Description

Trip When a trip occurs, the FDM128 screen shows a pop-up window. The following window represents an example of a
trip on circuit breaker CB01.

You must close this window before returning to the General view.

This alarm also appears as a red icon on the General view screen and on the title bar of the Device view screen.

High The device icon turns red to indicate a high-priority alarm , page 43.

This alarm also appears as a red icon on the title bar of the Device view screen.

Medium When a medium-priority alarm occurs, an orange icon appears on the General view screens and on the title bar of
the Device view screens.
Low Low-priority alarms are only registered in the alarm history and viewable in the Alarm history submenu.

NOTE: The circuit breaker alarms configured using EcoStruxure Power


Commission software are only registered in the alarm history and viewable in
the Alarm history submenu. For information about configuring alarms using
EcoStruxure Power Commission software, refer to the circuit breaker
documentation.

Alarms for Circuit Breakers Connected to Acti9 Smartlink SI B Device


Alarms are raised depending on the type of circuit breaker:
• Acti9 circuit breakers: when an alarm occurs, the FDM128 screen shows a
pop-up window. You must close this window before returning to the General
view. This alarm also appears as a red icon on the General view screen and
in the corresponding Acti9 Smartlink SI B and Acti9 Smartlink Modbus Device
view (Status).
• Other circuit breakers: an alarm appears as a red icon on the General view
screen and in the corresponding Device view (Status).
An example of this type of circuit breaker is item C in the architecture diagram
showing the FDM128 display connected to an Acti9 Smartlink SI B, page 13.

46 DOCA0037EN-09
Operation

General View Grid Screen Icons


Icon Color Description

Red There is an active alarm with a high severity or


the circuit breaker has tripped.

Partial orange (current value and ID are A medium severity alarm is active.
displayed)

Full orange (only ID is displayed) FDM128 display has lost the communication
with the circuit breaker. Check the cable
connection or check if the Modbus serial line
time out is set to 1 s.
Full orange (ID and disconnected symbols are The circuit breaker is in disconnected position.
displayed)

To check the details on the current Active alarm, refer to the Alarm history
submenu.

DOCA0037EN-09 47
Operation

Device View for Circuit Breakers and Switch-Disconnectors


Overview
For each submenu selected in the left tab of the main area, a headpiece allows
you to navigate through the tabs. Press the corresponding tab title to display it.
Data displayed in the Device view screen depends on the type of device. For
circuit breakers, it depends also on the type of MicroLogic trip unit installed. Refer
to the relevant MicroLogic user guides , page 8.
The table lists the features available per device type:

Features MasterPact MTZ MasterPact NT/NW, ComPacT NSX and MasterPact NT/NW,
circuit breakers ComPact NS, and PowerPacT H-, J-, or ComPact, and
PowerPact P- and R- L-frame circuit PowerPact switch-
Frame circuit breakers disconnectors
breakers
Quick Views ✓ ✓ ✓ ✓

Measures/I ✓ ✓ ✓ –

Measures/V ✓ ✓ ✓ –

Measures/PQS ✓ ✓ ✓ –

Measures/E ✓ ✓ ✓ –

Measures/F-PF-Cosphi ✓ ✓ ✓ –

Measures/THD ✓ ✓ ✓ –

Alarm History/Trip ✓ ✓ ✓ –

Alarm History/Alarm ✓ – ✓ –

Alarm History/Active ✓ – – –

Alarm History/Maintenance – – ✓ –

Alarm History/BSCM – – ✓ –

Control ✓ ✓ ✓ ✓

Maintenance/Information ✓ ✓ ✓ ✓

Maintenance/Product ID ✓ ✓ ✓ ✓

IO/Status ✓ ✓ ✓ ✓

IO/Counters ✓ ✓ ✓ ✓

IO/Control ✓ ✓ ✓ ✓

48 DOCA0037EN-09
Operation

Measurement Display Modes


Measurements can be displayed in the following modes:
• Numeric
• Bargraph
• Dial
To switch between modes, press the icon at the bottom-right of the screen.

Numeric Mode Bargraph Mode Dial Mode

To read the voltage bar graph correctly, you must set up the primary nominal
voltage of the circuit breaker.

Quick View
The Quick view submenu displays the status and main measurements, and
protection settings (long time, short time, instantaneous, ground fault, or earth
leakage) from a single circuit breaker.
There is no tab in this submenu.

Measures
The Measures submenu displays measurements from a single circuit breaker.
The tabs are the following:
• I
• V
• PQS
• E
• F-PF-Cosϕ
• THD
In tabs where the maximum measurement can be reset, you can reset the
measurements when the remote control is enabled (IFM or IFE locking pad points
to the open padlock, or the EIFE intrusive commands mode is unlocked). In these
conditions, press the Reset button to access the RESET screen, where:

• Pressing resets the measurements on the previous screen.

• Pressing resets the maximum values, minimum values, and


energy counters of the circuit breaker.
NOTE: The data for Minimum/Maximum CosØ per phase and Minimum/
Maximum THD are not available in FDM128 display when connected to
MasterPact MTZ circuit breaker. Use EcoStruxure Power Commission to
check the values.

DOCA0037EN-09 49
Operation

Alarm History
The Alarm history submenu gives access to the various histories of the circuit
breaker.
The table presents the description and number of records of each history
according to the circuit breaker.

Tab Description Number of records: Number of records: Number of records:


ComPacT NSX and MasterPact NT/NW, MasterPact MTZ circuit
Active List of active alarm PowerPacT H-, J-, or L- ComPact NS, and breakers
frame circuit breakers: PowerPact P- and R-
Frame circuit breakers
Trip Trip history 17 10 10

Alarm Alarm history 10 – 10

Active Active alarms – – 40


Mainten. Operation history 10 – –

BSCM BSCM event history 10 – –

Each record is summarized by three elements:


• Date and time of event occurrence and completion
• Designation
• Code
NOTE:
• The active alarm events for MasterPact MTZ circuit breaker are not
displayed from most recent to the oldest. The order is shown randomly.
• To refresh the Alarm history submenu, you need to exit and return to the
Alarm history submenu.

Control

DANGER
HAZARD OF ELECTRIC SHOCK
• Check that the downstream electrical equipment is safe.
• Check that you control the appropriate circuit breaker.
Failure to follow these instructions will result in death or serious injury.

WARNING
HAZARD OF CLOSING ON ELECTRICAL FAULT
Do not close the circuit breaker again without first inspecting and, if necessary,
repairing the downstream electrical equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

Before controlling a circuit breaker, you have to:


• Verify that you are logged as an administrator. The control functions can be
accessed only when you are logged in as an administrator.
• Verify that MasterPact MTZ circuit breakers are equipped with MX and XF
communicating voltage releases.
• Verify that MasterPact NT/NW, ComPact NS, or PowerPact P-frame circuit
breakers are equipped with a BCM ULP, MX, and XF communicating voltage
releases or a communicating motor mechanism.

50 DOCA0037EN-09
Operation

• Verify that ComPacT NSX or PowerPacT H-, J-, or L-frame circuit breakers
are equipped with a BSCM and a communicating motor mechanism in
automatic mode.
• Verify that the circuit breaker is in remote control mode.
• Verify that you know the circuit breaker password. The password of the circuit
breaker is set using the EcoStruxure Power Commission software.
• Verify that the IFE or IFM locking pad points to the unlocked position, when
the circuit breaker is connected to an IFE or IFM interface.
• Verify that the intrusive command mode is unlocked, when the circuit breaker
is connected to an EIFE interface.
The Control submenu allows you to check the status and to execute actions
remotely to operate the circuit breaker.
The table presents the possible actions depending on the circuit breaker:

Action Circuit breaker

Open All circuit breakers

Close All circuit breakers


Reset ComPacT NSX and PowerPacT H-, J-, or L-frame circuit breakers only

The FDM128 display takes you through the following sequence:

Step Action

1 In the submenu Control, press the action for the target circuit breaker.

A breaker opening confirmation popup is displayed.

2 Click OK to continue.

A password popup is displayed.

3 Enter the circuit breaker password.

4 Press Enter.

A popup message confirms that the command is successfully sent.


NOTE: The popup message only confirms that the command is successfully sent. It does not confirm weather the
complete operation is successful.

5 Press OK to close the result popup.

Maintenance
The table presents the functions of each tab of the Maintenance submenu:

Tab Function
Information Maintenance information available for MasterPact MTZ circuit breakers:
• remaining service life rate
• contact wear rate
• load profile
• circuit breaker operation counter values
• cradle counter values
Maintenance information available for MasterPact NT/NW, ComPact NS, ComPacT NSX and
PowerPact circuit breakers:
• contact wear rate
• load profile
• circuit breaker operation counter values
• cradle counter values
NOTE: The value displayed for operation counter corresponds to the resettable counter.

Product ID Displays the identification data of all ULP modules of the intelligent modular unit.

DOCA0037EN-09 51
Operation

I/O1 and I/O2


For each connected I/O module, the I/O1 and I/O2 submenus allow you to:
• Check the status of its inputs
• Control its outputs
• Read its pulse counters
Before controlling an I/O module output, you have to:
• Verify that the output of the I/O module is assigned using EcoStruxure Power
Commission software.
• Verify that you know the I/O module password. The password of the I/O
module is set using EcoStruxure Power Commission software.
• Verify that the I/O module locking pad points to the unlocked position.
• Verify that the IFE or IFM locking pad points to the unlocked position when the
I/O module is connected to an IFE or IFM interface.
• Verify that the intrusive command mode is unlocked when the I/O module is
connected to an EIFE interface.
The Control submenu allows you to check the status and to execute actions
remotely to actuate the I/O module output.
The possible actions are to open or close the output.
The FDM128 display takes you through the following sequence:

Step Action

1 In the submenu Control, press the action for the target output.

A password popup is displayed.

2 Enter the I/O module password.

A confirmation popup is displayed.

3 Press YES.

The following operations occur:


1. The command is sent to the output.
2. The output executes the command.
3. When the execution of the command is finished, a result popup is displayed with a failure or success message.

4 Press OK to close the result popup.

52 DOCA0037EN-09
Operation

Device View for Devices Connected to the Acti9 Smartlink


Overview
For each submenu selected in the left tab of the main area, a headpiece allows
you to navigate through the tabs. Press the corresponding tab title to display it.
Data displayed in the Device view screen depends on the device connected to
the Acti9 Smartlink. Refer to the relevant user guides , page 8.
Each Acti9 Smartlink device concentrates data from connected devices on its
channels.
NOTE: The Acti9 Smartlink product range is not available in the following
countries: United States, Canada, Mexico. Consult the catalog for the list of
products available in your country.
The table lists the features available per device type:

Features Acti9 Smartlink SI B Acti9 Smartlink SI D Acti9 Smartlink Modbus

PowerTag Link

PowerTag Link HD

Control ✓ – ✓

Status ✓ ✓ ✓

Counters ✓ ✓ ✓

Monitoring Information
Depending on the type of the connected device, the Device view displays:
• The status of the connected device (only for Acti9 Smartlink SI B and Acti9
Smartlink Modbus)
• The counters measured by the connected device (only for Acti9 Smartlink SI
B and Acti9 Smartlink Modbus)
• Buttons to control other devices connected to the Acti9 Smartlink (only for
Acti9 Smartlink SI B and Acti9 Smartlink Modbus)
• Metering data provided by PowerTag energy sensors (only for Acti9 Smartlink
SI B and Acti9 Smartlink SI D)
For example, the layout of the Device view for a device connected to an Acti9
Smartlink SI B is as follows:

NOTE: When browsing an Acti9 Smartlink device view for the first time or after
a configuration update, it may take up to 20 seconds for the displayed data to
refresh.

DOCA0037EN-09 53
Operation

Control

DANGER
HAZARD OF ELECTRIC SHOCK
• Check that the downstream electrical equipment is safe.
• Check that you control the appropriate circuit breaker.
Failure to follow these instructions will result in death or serious injury.

WARNING
HAZARD OF CLOSING ON ELECTRICAL FAULT
Do not close the circuit breaker again without first inspecting and, if necessary,
repairing the downstream electrical equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

The procedure to control an Acti9 Smartlink device is as follows:

Step Action

1 In the submenu Control, press the action (Open or Close) for the target device.

2 Press YES.

The following operations occur:


1. The command is sent to the device.
2. The device executes the command.
3. When the execution of the command is finished, a result popup is displayed with a detected failure or success
message.

3 Press OK to close the result popup.

PowerTag for Acti9 Circuit Breakers


The FDM128 display can show data from up to 20 PowerTag energy sensors per
Acti9 Smartlink SI B, Acti9 Smartlink SI D, PowerTag Link, or PowerTag Link HD.
PowerTag Link HD stores configuration details of 100 PowerTags in a block of 500
registers (5 registers for each PowerTag). The FDM128 display scans only the first
300 registers from the block and displays the first 40 PowerTag energy sensors
discovered.
The data from each energy sensor is displayed on a dedicated page.
The below figure shows the PowerTag screen of Acti9 Smartlink SI B.

54 DOCA0037EN-09
Operation

The below figure shows the PowerTag screen of Acti9 Smartlink SI D.

Depending on whether the PowerTag energy sensor is single- or three-phase, the


following information is displayed in the submenu.
For single-phase PowerTag energy sensors:
• Label
• Asset name
• Current (I)
• Total active energy (Resettable)
• Voltage status
• Voltage (phase-to-neutral voltage)
For three-phase PowerTag energy sensors:
• Label
• Asset name
• Current (I) among the phases Ia, Ib, and Ic
• Total active energy (Resettable)
• Voltage status
• Average voltage (phase-to-phase voltage)
For three-phase and neutral PowerTag energy sensors:
• Label
• Asset name
• Current (I) among the phases Ia, Ib, and Ic
• Total active energy (Resettable)
• Voltage status
• Average voltage (phase-to-neutral voltage)

DOCA0037EN-09 55
Operation

PowerTag for ComPacT NSX Circuit Breakers


The FDM128 display can show data from up to 20 PowerTag NSX energy sensors
per Acti9 Smartlink SI B or Acti9 Smartlink SI D. The data from each energy
sensor is displayed on a dedicated page.
The below figure shows the PowerTag screen of Acti9 Smartlink SI B.

The below figure shows the PowerTag screen of Acti9 Smartlink SI D.

The following information is displayed in the submenu of PowerTag NSX energy


sensors:
• Label
• Asset name
• Current (I)
• Total active energy (Resettable)
• Power Factor
• Average voltage
• Voltage status

56 DOCA0037EN-09
Update and Maintenance

Update and Maintenance


Firmware Update
Firmware Update Policy
The primary reason for updating the firmware of a FDM128 display is to obtain the
latest FDM128 features. If the latest FDM128 features are not required, it is not
mandatory to update the firmware of FDM128 display.
If you notice a bug on the FDM128 display, refer to FDM128 firmware release note
to check if the bug is corrected in a later version of the firmware. Update the
firmware of the FDM128 display to benefit from the correction. If there is no bug fix
available, call the Customer Care Centre.

Prerequisites
To update the FDM128 firmware, use a USB memory key.
This USB memory key must be:
• Formatted in FAT32 system format
• Empty

DANGER
HAZARD OF ELECTRICAL SHOCK
• Ensure that the zone is safe before connecting or disconnecting the USB
key.
• Use the USB connector for a temporary connection during maintenance and
configuration of equipment.
Failure to follow these instructions will result in death or serious injury.

Downloading the Latest Firmware Version

Step Action

1 Go to the Schneider Electric home page www.se.com.

2 In the Search box, type the reference of the FDM128 display (LV434128) or the name of the product offer (FDM128).
• Do not include leading or trailing blank spaces in the search string.
• To get information on similar modules, use asterisks (*).

3 If you entered the reference, go to the Product datasheets search results.

If you entered the name of the product offer, go to the Product Offer search results.

Click the link of the FDM128 display product.

4 Click Documents and Downloads, then go to Firmware - Updates section.

The list of available firmware for the FDM128 display is displayed.

5 Click the link Firmware update for Enerlin’X FDM128 (zip) of the FDM128 firmware version you want to download.

Save the .zip file on your computer.

DOCA0037EN-09 57
Update and Maintenance

Updating the Firmware

WARNING
LOSS OF DATA
Note down the old configuration settings to re-configure them after firmware
update.
REQUIRES CLEANUP
The configuration settings of the FDM128 display (such as IP configuration and
slave device configuration) may be lost when the FDM128 firmware is updated.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

After downloading the firmware, update the FDM128 display as follows:

Step Action

1 Extract files from the .zip file.

2 Load the extracted files onto the USB memory key.

3 Ensure that the FDM128 display is powered ON.

4 Plug the USB memory key into the USB1 port on the FDM128 display.

5 Follow the instructions on the FDM128 screen.

58 DOCA0037EN-09
Update and Maintenance

Adding, Removing, and Replacing Devices


Adding New Devices

Step Action

1 Ensure that settings of the new devices are compliant with the prerequisites, page 32.

2
Press the icon to update the FDM128 communication settings.

3 For devices connected through a gateway:


1. Press Redo all the settings.
2. Set the communication settings according to your gateway-based architecture, page 35.
For devices connected directly:
1. Press Add manually single IP devices.
2. Manually configure their IP addresses, page 37.

Removing Selected Devices

Step Action

1 Disconnect the devices from the network.


2
Press the icon to update the FDM128 communication settings.

3 For devices connected through a gateway:


1. Press Redo all the settings.
2. Set the communication settings according to your gateway-based architecture, page 35.

Replacing MicroLogic

Step Action

1 Replace the MicroLogic trip unit.

2
Press the icon to update the FDM128 communication settings, page 36.

3 For devices connected through a gateway:


1. Press Redo all the settings.
2. Set the communication settings according to your gateway-based architecture, page 35.

DOCA0037EN-09 59
Update and Maintenance

Regular Cleaning
Cleaning the Display

NOTICE
EQUIPMENT DAMAGE
• Power off the FDM128 display before cleaning it.
• Do not use hard or sharp objects to operate the touch panel since it can
damage the panel surface.
• Do not use paint thinner, organic solvents, or a strong acid compound to
clean the FDM128 display.
Failure to follow these instructions can result in equipment damage.

When the surface or the frame of the display gets dirty, soak a soft cloth in water
with a neutral detergent, wring the cloth tightly, and wipe the display.

60 DOCA0037EN-09
Update and Maintenance

Troubleshooting Checklists
Introduction

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel.
• Before working on the equipment, ensure that you are working in a safe area
Failure to follow these instructions will result in death or serious injury.

When a problem is detected, go through the checklist and follow the instructions
given.
Possible problems that could occur when using an FDM128 display are:
• Panel display is blank.
• Connected equipment cannot be used.
• Panel does not respond or responds slowly.
• Panel beeps when powered on.
NOTE: Contact your local Schneider Electric vendor or your local distributor.

Panel Display Is Blank


If the display is blank, perform the following check steps:

Step Check/Operation Solution

1 Is the FDM128 display using the correct rated voltage? Verify the power supply connections and levels.

2 Is the power supply off or disconnected? Follow the instructions in the Instruction Sheet to reconnect
the power supply.

3 Is the backlight lit? Potential detected problem with the FDM128 display.
Contact your local Schneider Electric distributor.

4 Is the problem resolved? If none of the previous steps resolve the detected problem,
verify the hardware.

Display Replacement
The following replacements are available:
• Front part only: reference HMIS85
• Whole device, including the front part: reference LV434128
For information about how to reinstall the product, see the Instruction Sheet.

Connected Equipment Cannot Be Used


If the FDM128 display does not communicate with connected equipment, perform
the following check steps:

Step Check/Operation Solution

1 Is the power supply off or disconnected? Verify the power supply connections and levels.

2 Is the communication cable connected correctly? For more information about cable diagrams, refer to FDM128
Ethernet Display for Eight Devices Instruction Sheet.

3 Is the problem resolved? If none of the previous steps resolve the communication
problem, then check the hardware.

DOCA0037EN-09 61
Update and Maintenance

Protecting the Environment


Recycling Packaging
The packaging materials from this equipment can be recycled. Please help protect
the environment by recycling them in appropriate containers.
Thank you for playing your part in protecting the environment.

End-of-Life Recycling
At end of life, the FDM128 display has been optimized to decrease the amount of
waste and valorize the components and materials of the product in the usual end
of life treatment process.
The design has been achieved so components are able to enter the usual end-of-
life treatment processes as appropriate: depollution if recommended, reuse and/or
dismantling if recommended to increase the recycling performances, and
shredding for separating the rest of materials.

62 DOCA0037EN-09
Appendices
What’s in This Part
FDM128 Icons ...............................................................................................64
Glossary of Acronyms.....................................................................................67

DOCA0037EN-09 63
FDM128 Icons

FDM128 Icons
What’s in This Chapter
Icon List........................................................................................................64

Icon List
Header Icons
Icon Description

Go to General view menu

Refresh the display of the names of connected devices

Locate the device

Go to Login/Access Code settings menu

Go to Editing devices menu

Go to Communication settings menu

Go to General settings menu

Footer Icons
Icon Description

Go to next screen

Go to previous screen

Switch to bargraph mode

Switch to numeric mode

Switch to dial mode

Switch to icon mode

Switch to list mode

Locate a circuit breaker

64 DOCA0037EN-09
FDM128 Icons

Action Icons
Icon Description

Reset measurements displayed in the previous screen

Reset all measurements and counters of the circuit breaker

Reset circuit breaker

Locate a circuit breaker

Decrease level

Increase level

Display next tabs

Display previous tabs

Alarm Status Icons


Icon Description

Circuit breaker status is OK

Circuit breaker is offline

Medium priority alarm is occurring

High priority alarm is occurring

Circuit Breakers Status Icons


Icon Description

Circuit breaker is charged

Circuit breaker is discharged

Circuit breaker is closed

Circuit breaker is open

Withdrawable circuit breaker is connected

Withdrawable circuit breaker is disconnected

Capacitive load

Inductive load

Cradle position: Test active

DOCA0037EN-09 65
FDM128 Icons

Icon Description

Cradle position: Test disabled

Global health status (For MasterPact MTZ only)

66 DOCA0037EN-09
Glossary of Acronyms

Glossary of Acronyms
What’s in This Chapter
Acronym .......................................................................................................67

Acronym
Acronyms and Definitions
The following table lists the acronyms used in various screens and their respective
definition:

Acronym Definition

EpIn Energy active delivered count positively

EpOut Energy active received count negatively

EqIn Energy reactive delivered count positively

EqOut Energy reactive received count negatively

NA Not applicable (means either the data is not available from the circuit
breaker or communication error)

DOCA0037EN-09 67
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.se.com

As standards, specifications, and design change from time to time,


please ask for confirmation of the information given in this publication.

© 2021 – Schneider Electric. All rights reserved.


DOCA0037EN-09

You might also like