FDM128
FDM128
FDM128
User Guide
DOCA0037EN-09
04/2021
www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Table of Contents
Safety Information ......................................................................................5
About the Book...........................................................................................7
Introduction ..............................................................................................10
Overview............................................................................................10
Architecture Examples ........................................................................12
Recommendations..............................................................................20
Certifications and Standards ................................................................22
General Specifications ........................................................................24
Functional Specifications ....................................................................26
Interface Specifications .......................................................................27
Presentation.............................................................................................28
Screen ...............................................................................................28
Menu Structure ...................................................................................30
Browsing ............................................................................................31
Configuration ...........................................................................................32
Prerequisites ......................................................................................32
Setting Wizard ....................................................................................34
Settings During Operation ...................................................................38
Operation.................................................................................................40
Logins and Access Codes ...................................................................40
General View......................................................................................43
Real-Time Alarms ...............................................................................46
Device View for Circuit Breakers and Switch-Disconnectors ...................48
Device View for Devices Connected to the Acti9 Smartlink .....................53
Update and Maintenance ..........................................................................57
Firmware Update ................................................................................57
Adding, Removing, and Replacing Devices...........................................59
Regular Cleaning ................................................................................60
Troubleshooting Checklists..................................................................61
Protecting the Environment..................................................................62
Appendices ................................................................................................63
FDM128 Icons..........................................................................................64
Icon List .............................................................................................64
Glossary of Acronyms ...............................................................................67
Acronym ............................................................................................67
DOCA0037EN-09 3
Safety Information
Safety Information
Important Information
Read these instructions carefully, and look at the equipment to become familiar
with the device before trying to install, operate, service, or maintain it. The
following special messages may appear throughout this documentation or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
The addition of this symbol to a “Danger” or “Warning” safety label indicates that an
electrical hazard exists which will result in personal injury if the instructions are not
followed.
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that follow this symbol to avoid possible injury or
death.
! DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
! WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or
serious injury.
! CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction
and operation of electrical equipment and its installation, and has received safety
training to recognize and avoid the hazards involved.
FCC Notice
This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designated
to provide reasonable protection against harmful interference when the equipment
is operated in a commercial environment. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to
cause harmful interference in which case the user will be required to correct the
interference at this own expense.
DOCA0037EN-09 5
Safety Information
WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND
CONFIDENTIALITY
• Change default passwords at first use to help prevent unauthorized access
to device settings, controls, and information.
• Disable unused ports/services and default accounts to help minimize
pathways for malicious attackers.
• Place networked devices behind multiple layers of cyber defenses (such as
firewalls, network segmentation, and network intrusion detection and
protection).
• Use cybersecurity best practices (for example, least privilege, separation of
duties) to help prevent unauthorized exposure, loss, modification of data and
logs, or interruption of services.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
6 DOCA0037EN-09
About the Book
Validity Note
This guide is valid for FDM128 Ethernet display for eight devices.
Online Information
The technical characteristics of the devices described in this guide also appear
online. To access the information online, go to the Schneider Electric home page
at www.se.com.
DOCA0037EN-09 7
About the Book
Enerlin'X FDM128 - Ethernet Display for Eight Devices - Firmware Release Note DOCA0151EN
Enerlin’X IFM - Modbus-SL Interface for One Circuit Breaker - Instruction Sheet NVE85393
Enerlin’X IFE - Ethernet Interface for One Circuit Breaker - Instruction Sheet QGH13473
Enerlin’X IFE - Ethernet Interface for One Circuit Breaker - User Guide (IEC version) DOCA0142EN
Enerlin’X IFE - Ethernet Switchboard Server - User Guide (IEC version) DOCA0084EN
Enerlin’X EIFE - Embedded Ethernet Interface for One MasterPact MTZ Drawout Circuit Breaker - NVE23550
Instruction Sheet
Enerlin’X EIFE - Embedded Ethernet Interface for One MasterPact MTZ Drawout Circuit Breaker - DOCA0106EN
User Guide
Enerlin’X IO - Input/Output Application Module for One Circuit Breaker - Instruction Sheet HRB49217
Enerlin’X IO - Input/Output Application Module for One Circuit Breaker - User Guide (IEC version) DOCA0055EN
BCM ULP Circuit Breaker Communication Module - Installation Manual EAV3608000 (EN, ES, FR)
EGX300 PowerLogic™ Ethernet Gateway - User Guide 63230-319-216 (EN, ES, FR)
MicroLogic 5/6/7 Trip Units for ComPacT NSX Circuit Breakers - User Guide DOCA0141EN
MicroLogic P Trip Units for MasterPact NT/NW Circuit Breakers - User Guide 04443726AA (EN)
MicroLogic H Trip Units for MasterPact NT/NW Circuit Breakers - User Guide 04443728AA (EN)
TCSEGWB13FA0 - Portable Battery Powered Wi-Fi Access Point - Instruction Sheet NHA24030
You can download these technical publications and other technical information
from our website at https://www.se.com/en/download
8 DOCA0037EN-09
About the Book
Enerlin'X FDM128 - Ethernet Display for Eight Devices - Firmware Release Note DOCA0151EN
Enerlin’X IFM - Modbus-SL Interface for One Circuit Breaker - Instruction Sheet NVE85393
Enerlin’X IFE - Ethernet Interface for One Circuit Breaker - Instruction Sheet QGH13473
Enerlin’X IFE - Ethernet Interface for One Circuit Breaker - User Guide (UL version) 0602IB1801EN
Enerlin’X IFE - Ethernet Switchboard Server - User Guide (UL version) 1040IB1401 (EN)
Enerlin’X EIFE - Embedded Ethernet Interface for One MasterPact MTZ Drawout Circuit NVE23550
Breaker - Instruction Sheet
Enerlin’X EIFE - Embedded Ethernet Interface for One MasterPact MTZ Drawout Circuit DOCA0106EN
Breaker - User Guide
Enerlin’X IO - Input/Output Application Module for One Circuit Breaker - Instruction Sheet HRB49217
Enerlin’X IO - Input/Output Application Module for One Circuit Breaker - User Guide (UL 0613IB1317 (EN)
version)
BCM ULP Circuit Breaker Communication Module - Installation Manual EAV3608000 (EN, ES, FR)
EGX300 PowerLogic™ Ethernet Gateway - User Guide 63230-319-216 (EN, ES, FR)
MicroLogic 5 and 6 Trip Units for PowerPacT H-, J-, and L- Frame Circuit Breakers - User 48940-312 (EN, ES, FR)
Guide
PowerPact H-, J-, and L- Frame Circuit Breakers Modbus Communication Guide 0611IB1302 (EN)
MicroLogic 2.0A, 3.0A, 5.0A, and 6.0A Trip Units - Instruction Bulletin 48049-136 (EN, ES, FR)
MicroLogic 5.0P and 6.0P Trip Units - Instruction Bulletin 48049-137 (EN, ES, FR)
MicroLogic 5.0H and 6.0H Trip Units - Instruction Bulletin 48049-330 (EN, ES, FR)
MasterPact NT/NW, PowerPact P- and R-Frame Modbus Communication Guide 0613IB1313 (EN)
MicroLogic X Control Unit for MasterPact MTZ Circuit Breakers - User Guide DOCA0102EN
TCSEGWB13FA0 - Portable Battery Powered Wi-Fi Access Point - Instruction Sheet NHA24030
You can download these technical publications and other technical information
from our website at https://www.se.com/en/download
DOCA0037EN-09 9
Introduction
Introduction
Overview
Presentation
The FDM128 Ethernet display for eight devices is a 1-to-8 human machine
interface (HMI). The main component is a 5.7-inch touch screen.
An FDM128 display can be connected to devices via an Ethernet interface by
using:
• One or more Ethernet gateways (IFE server, Link150, PowerLogic EGX300
and EGX100 Ethernet, Acti9 Smartlink SI B, PowerTag Link B, Acti9
Smartlink SI D, or Acti9 Smartlink Ethernet gateways).
• One or more third-party Ethernet gateways that possess the appropriate
characteristics.
NOTE: FDM128 display does not support devices with local ID (Virtual ID)
from the Com'X or Link150 gateways.
Each type of connection is described further in this section.
The FDM128 display can monitor and control up to eight devices. The information
displayed includes measurements, alarms, and operating assistance data.
For ease of installation, a device discovery function is embedded in the FDM128
display.
10 DOCA0037EN-09
Introduction
DOCA0037EN-09 11
Introduction
Architecture Examples
FDM128 Display Connected to an IFE Server
The following diagram is an example of an IFE- based network architecture:
A FDM128 Ethernet display for eight H EIFE embedded Ethernet interface for one
devices MasterPact MTZ drawout circuit breaker
B IFE Ethernet switchboard server I ULP line termination
C IFM Modbus-SL interface for one J ULP cord
circuit breaker
D FDM121 ULP display for one circuit K NSX cord
breaker
E I/O input/output application module for L Acti9 Smartlink Modbus
one circuit breaker
F MasterPact MTZ drawout circuit Ethernet
breaker
G ComPacT NSX, PowerPacT H-, J-, or Modbus-SL
L-frame circuit breaker
24 Vdc
12 DOCA0037EN-09
Introduction
B ConneXium switch
C ComPacT NSX, PowerPacT H-, J-, or L-frame circuit breaker
D Acti9 Smartlink SI B
E Acti9 Smartlink Modbus
F Acti9 iEM energy meter
Ethernet
Modbus-SL
24 Vdc
TI24 cord
DOCA0037EN-09 13
Introduction
B ConneXium switch
E Acti9 Smartlink SI D
F PowerTag energy sensor
Ethernet
24 Vdc
14 DOCA0037EN-09
Introduction
DOCA0037EN-09 15
Introduction
16 DOCA0037EN-09
Introduction
DOCA0037EN-09 17
Introduction
18 DOCA0037EN-09
Introduction
NOTE: The Acti9 Smartlink product range is not available in the following
countries: United States, Canada, Mexico. Consult the catalog for the list of
products available in your country.
DOCA0037EN-09 19
Introduction
Recommendations
Critical Systems, Alarms, and Handling Requirements
Critical alarm indicators and system functions require independent and redundant
hardware protection and/or mechanical interlocks.
If the FDM128 Ethernet display for eight devices becomes inoperative due to
some reason (for example, due to an inoperative backlight), it may be difficult or
impossible to identify a function. Functions that may present a hazard if not
immediately executed, such as an emergency stop, must be provided
independently of the FDM128 display.
The design of the control system must take into account simultaneously:
• An inoperative FDM128 display.
• The operator inability to control the circuit breakers or to respond to detected
errors by using the FDM128 display.
CAUTION
SERIOUS EYE AND SKIN INJURY
The liquid present in the LCD panel contains an irritant:
• Avoid direct skin contact with the liquid.
• Wear gloves when you handle a broken or leaking FDM128 display.
• Do not use sharp objects or tools in the vicinity of the LCD touch panel.
• Handle the LCD panel carefully to prevent puncture, bursting, or cracking of
the panel material.
If the panel is damaged and any liquid comes in contact with your skin,
immediately rinse the area with running water for at least 15 minutes.
If the liquid gets in your eyes, immediately rinse your eyes with running water for
at least 15 minutes and consult a doctor.
Failure to follow these instructions can result in injury or equipment
damage.
20 DOCA0037EN-09
Introduction
WARNING
UNINTENDED EQUIPMENT OPERATION
• Operate the touch panel with only one finger.
• Do not activate two or more points of the touch panel simultaneously.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
DOCA0037EN-09 21
Introduction
Hazardous Substances
The FDM128 display is designed for compliance with the following directives and
standards:
• WEEE, Directive 2002/96/EC
• RoHS, Directive 2002/95/EC
• RoHS China, Standard SJ/T 11363-2006
22 DOCA0037EN-09
Introduction
CE Markings
WARNING
RISK OF EXPLOSION IN HAZARDOUS LOCATIONS
• Verify that the power, input, and output (I/O) wiring are in accordance with
Class I, Division 2 wiring methods.
• Do not substitute components that could impair compliance to Class I,
Division 2.
• Do not connect or disconnect equipment unless power has been switched off
or the area is known to be non-hazardous.
• Securely lock externally connected units and each interface before turning
on the power supply.
• Do not disconnect while the circuit is live.
• Front panel is a potential electrostatic charging hazard. Wipe the front panel
of the terminal with a damp cloth before turning on.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
DOCA0037EN-09 23
Introduction
General Specifications
Electrical Characteristics
Characteristic Value
Rated input voltage 24 Vdc
In-rush current ≤ 30 A
Voltage endurance between power terminal and functional 1,000 Vac 20 mA for 1 minute
ground (FG)
Insulation resistance between power terminal and functional 10 MΩ or higher at 500 Vdc
ground (FG)
Physical Characteristics
Characteristic Value
Ambient operating temperature (cabinet interior and panel face) –10 °C to +55 °C (14–131 °F)
Mechanical Characteristics
Characteristic Value
Vibration immunity (operating) IEC 60068-2-6
15 gn (1 g) 11 ms
24 DOCA0037EN-09
Introduction
Characteristic Value
Noise immunity Noise voltage: 1,000 Vp-p
Pulse width: 1 µs
Rising time: 1 ns
2 kV CM on shielded cables
Electrical fast transient burst 2 kV CM, 2 kV DM on DC power supply
1 kV on shielded cables
Radiated radio frequency electromagnetic field 10 V/m / 80 MHz to 2 GHz
12 kV air contact
Power frequency magnetic field 100 A/m continuous
DOCA0037EN-09 25
Introduction
Functional Specifications
Display Characteristics
Characteristic Description
Non-exchangeable
Brightness adjustment 16 levels of adjustment available via touch panel in the General settings menu.
Brightness on LCD surface White LED: 350 cd/m2 (33 cd/ft2) maximum
Clock
Variations in operating conditions can cause a clock shift from -380 seconds to
+90 seconds per month.
Touch Panel
Characteristic Description
26 DOCA0037EN-09
Introduction
Interface Specifications
USB1 Interface (USB Peripherals)
Ethernet Interface
LED Description
DOCA0037EN-09 27
Presentation
Presentation
Screen
Overview
The following figure describes the display area:
A Header
B Title bar
C Headpiece
D Right area
E Left area
F Footer
Header
The header (A) is composed of the following elements:
• Product name (FDM128) and access profile
• Direct-access icons to the main functions
Icon Description
28 DOCA0037EN-09
Presentation
Icon Description
Title Bar
The title bar (B) contains the title of the screen or name of the selected device.
Main Area
The main area includes the headpiece (C), the right area (D), and the left area (E).
The following table describes the parts of the main display area:
Headpiece (C) Right area title Navigate through the submenus items.
Right area (D) Information Displays information of the selected submenu or submenu item.
Footer
The footer (F) contains some navigation icons depending on the selected screen.
The icons are listed in the appendix , page 64.
If there is more than one page in the selected submenu, the screen number is
displayed. The screen number format is X/Y, where X is the current screen
number and Y is the total number of screens.
DOCA0037EN-09 29
Presentation
Menu Structure
Menu Types
FDM128 menus are divided into two types:
• Settings menus: blue title bar background
• Operation menus: green title bar background
Settings Menus
Settings menus are composed of two sequences:
• General settings sequence
• Settings sequence for devices: communication settings, device discovery,
and editing devices
The setting wizard, page 34 of the FDM128 display guides you through these
sequences.
General View
The General view menu is used to monitor up to eight devices at the same time.
For further information, refer to the general view topic, page 43.
Device View
Device view menus are only accessible from the General view menu.
The Device view for circuit breakers menu is composed of the following
submenus:
• Quick view , page 49
• Measures , page 49
• Alarm history , page 50
• Control , page 50
• Maintenance , page 51
• I/O1 and I/O2 , page 52
The Device view for Acti9 Smartlink SI B menu is composed of the following
submenus:
• Status
• Counters (energy, water, gas...)
• Control , page 54
• PowerTag , page 54
The Device view for Acti9 Smartlink SI D menu is composed of PowerTag
submenu , page 54.
30 DOCA0037EN-09
Presentation
Browsing
Navigate Through the Screens
In a menu or a submenu, you can navigate through the screens by using the
footer icons.
The browsing actions are executable by pressing the icons. Refer to the icon list,
page 64 to get the meaning of each of them.
The icons are available depending on the network configuration, the selected
menu, and the possible actions.
NOTE: A gray icon means that the option or action is not available in the
actual context.
Data Entry
When an action requires an alphanumeric entry (for example, typing a
designation), the following touch keyboard is displayed:
When an action requires a numeric entry (for example, typing an IP address), the
numeric keyboard is displayed.
NOTE: You can also display the numeric keyboard by pressing the 123 key on
the alphanumeric keyboard.
DOCA0037EN-09 31
Configuration
Configuration
Prerequisites
Ethernet Network
The Ethernet connections of the IP devices in the Ethernet network must be
correctly installed and configured.
NOTE: To connect to an Ethernet device outside the subnetwork a popup
message requests your confirmation to connect to another subnetwork.
The Ethernet network may include the following IP devices:
• EGX300 or EGX100 gateways
• Link150 gateways
• IFE or EIFE interfaces
• IFE server
• Acti9 Smartlink Ethernet devices
• Acti9 Smartlink SI B
• Acti9 Smartlink SI D
• PowerTag Link
• PowerTag Link B
• PowerTag Link HD
• Third-party gateways
NOTE: FDM128 display does not support devices with local ID (Virtual ID)
from the Com'X or Link150 gateways.
For further information, refer to the corresponding user guides , page 8.
NOTE: PowerTag Link B is equivalent to Acti9 Smartlink SI B.
Parameter Value
Modbus address (slaves only) The Modbus address of each monitored device must be unique. The range of Modbus
addresses is [1-247].
Communication speed The communication speed must be the same for all devices.
32 DOCA0037EN-09
Configuration
DOCA0037EN-09 33
Configuration
Setting Wizard
Wizard Presentation
A setting wizard is automatically launched at first power-on to help you set up the
FDM128 display.
The setting wizard guides you through three main configuration parts:
1. FDM128 display general settings
2. Communication settings depending on the network architecture
3. Editing device function
Each configuration part is described further in this section.
It is recommended that you update the communication settings each time you
modify the communication network.
General Settings
The following table describes the sequence of steps presented by the setting
wizard to configure the FDM128 general settings:
3 Refresh Rate Press one of the two possible ways to set manually the real-time sample rate in the
General View:
• Fast (default setting): refresh every 3 s for circuit breakers and 5 s for Acti9
Smartlink.
• Slow: refresh every 10 s for all devices.
Example:
• 8 MasterPact MTZ circuit breakers connected in Fast refresh mode has a
maximum duration equal to (8x3) = 24 seconds.
• 8 MasterPact MTZ circuit breakers connected in Slow refresh mode has a
maximum duration equal to (8x10) = 80 seconds.
4 Phase labels Press one of the two possible ways to represent the phases 1,2,3,N (default setting), or
A,B,C,N.
5 Units of measurement I/O Select the units of measurement for the analog input of the I/O modules:
• The unit of temperature (°C (default setting) or °F)
• The unit of volume (m3 (default setting) or gallon US or gallon UK)
6 Brightness Press the -/+ icons to adjust the brightness level of the display.
The setting wizard displays the Selection of the communication architecture screen
to allow you to set up the FDM128 communication. Follow the communication settings
procedure that corresponds to your network architecture.
34 DOCA0037EN-09
Configuration
Step Action
7 If you select less than eight devices among the devices displayed, you are prompted for an additional gateway. Press NO.
8 If needed, you can configure manually extra IFE, EIFE, Acti9 Smartlink SI B, or Acti9 Smartlink SI D devices.
9 Press Finish.
The FDM128 display can now monitor the list of selected devices.
The setting wizard displays the Editing devices screen to allow you to edit the label and name of the devices.
Step Action
7 If you select less than eight devices among the devices displayed, you are prompted for an additional gateway.
If you have another gateway to configure, press YES and go back to step 3.
DOCA0037EN-09 35
Configuration
Step Action
8 When you have configured all gateways, press NO. You can now manually configure extra IFE, EIFE, Acti9 Smartlink SI B,
or Acti9 Smartlink SI D devices.
9 Press Finish.
The FDM128 display can now monitor the list of selected devices.
The setting wizard displays the Editing devices screen to allow you to edit the label and name of the devices.
NOTE: Before launching the auto discovery, make sure that the Modbus serial
line time out is 1 s.
Communication Settings for Several IFE, EIFE, Acti9 Smartlink SI B, or Acti9 Smartlink
SI D Architecture
The procedure is applicable when the FDM128 display is connected to several
IFE, EIFE , Acti9 Smartlink SI B, or Acti9 Smartlink SI D, page 16 devices.
The FDM128 setting wizard guides you through the following steps:
Step Action
3 Configure manually up to eight IFE, EIFE, Acti9 Smartlink SI B, or Acti9 Smartlink SI D devices.
4 Press Finish.
The FDM128 display can now monitor the list of selected devices.
The setting wizard displays the Editing devices screen to allow you to edit the label and name of the devices.
Device Discovery
The device discovery feature enables detection of devices in a given Modbus
range (1–247).
NOTE: The default Modbus range is 1–10.
The device discovery sequence detects up to 16 devices on the network as per
the given Modbus range. These devices are displayed sorted in ascending order
of Modbus address, with the Modbus address indicated in the first column.
The device discovery sequence time varies depending on the Modbus range
selected.
NOTE: The 16 detected devices are those with the 16 first Modbus addresses.
Among the detected devices, you can select a maximum of eight devices.
The FDM128 display guides you through the following device discovery
procedure:
36 DOCA0037EN-09
Configuration
Step Action
1 The device discovery sequence is started during the communication settings procedure.
2 In the list of the discovered devices, select the check box for each device you want to include.
3 Press Finish.
Step Action
1
On the configuration screen, tick the check boxes of the number of IFE, EIFE, Acti9 Smartlink SI B, or Acti9 Smartlink SI D
devices to configure.
3 Press OK to launch the device discovery sequence.Device Discovery page is displayed with the list of available gateways.
NOTE: A maximum of 8 devices can be discovered.
4 Select up to eight devices among the devices displayed.
5 If you select less than eight devices among the devices displayed, you are prompted for an additional gateway. Press NO.
6 If needed, you can configure manually extra IFE, EIFE, Acti9 Smartlink SI B, or Acti9 Smartlink SI D devices.
7 Press Finish.
The FDM128 display can now monitor the list of selected devices.
The setting wizard displays the Editing devices screen to allow you to edit the label and name of the devices.
Power Loss
In case of power loss, the FDM128 display retains the settings.
DOCA0037EN-09 37
Configuration
During operation, you can access the General settings menu by pressing .
Editing Devices
Limitations
When the following devices are used together, you cannot write or edit the device
name:
• MasterPact with BCM module, firmware version lower than 3.2.5.
• ComPact NS with BCM module, firmware version lower than 3.2.5.
• PowerPact P- and R-frame with BCM module, firmware version lower than
3.2.5.
An example network architecture is provided in this guide, page 15.
Prerequisites
Before editing devices, you must verify that the following prerequisites are met:
• Circuit breaker must be in the remote control mode.
• Device logging in the IFE or EIFE webpage must be disabled.
• Only the following characters are allowed:
◦ Upper case letters from A to Z
◦ Lower case letters from a to z
◦ Digits from 0 to 9
◦ Hyphen -
• Before editing the name and label of the circuit breaker:
◦ The EIFE intrusive command mode must be unlocked
◦ The locking pad of the IFE, or IFM interface must point to the open
padlock, as shown in the following graphic
menu by pressing .
Use the Editing devices menu to:
• Provide a label for each device:
The label is defined in the ID field and is only displayed in the FDM128
display. The ID field contains up to 4 characters.
• Rename a device:
The name is defined in Name field and is the actual name of the device. You
may need to use the device password to rename the device. The Name field
contains up to 12 characters.
NOTE: Press OK to validate the settings and go back to the operation mode.
38 DOCA0037EN-09
Configuration
Communications Settings
During operation, you can access the Communication settings menu by
pressing .
. Use this menu to view and edit user login and access code settings, page
40.
DOCA0037EN-09 39
Operation
Operation
Logins and Access Codes
Levels of Access
The FDM128 display requires login and access code combinations to access the
following functions:
• Monitoring functions:
By default, you do not need to log in to access monitoring functions (viewer or
guest) access).
• Operation functions:
Log in as an operator to access operation functions (operator access).
• Administration, communication, and other advanced functions:
Log in as administrator to access advanced functions (administrator access).
The various functions that available at different access levels are listed in the
table.
NOTE: Menus and functions that are not available at an access level are
grayed out.
Login Procedure
To log in to the FDM128 display, follow these steps:
Step Action
1
Press .
3 Press OK.
In the screen header, you can now access the direct function icons for your level.
40 DOCA0037EN-09
Operation
Logout Procedure
To log out of the FDM128 display, follow these steps:
Step Action
1
When you are logged in to the FDM128 display, press .
2 Press Logout.
In the screen header, you can now access only the Login/Access code function icon.
NOTE: If you do not touch any button or function on the FDM128 display for
25 minutes, you are automatically logged out.
Step Action
1 Log in as administrator.
In the General view screen, in the screen header, you can now access all the direct function icons.
2
Press .
3 Press Configuration.
The login:
• Is case-sensitive.
• Can contain from 1 to 16 characters.
• Can contain alphanumeric characters and symbols, excluding the space character.
After editing the operator login value, press to go to the next screen.
After editing the operator access code value, press to go to the next screen.
The login:
• Is case-sensitive.
• Can contain from 1 to 16 characters.
• Can contain alphanumeric characters and symbols, excluding the space character.
DOCA0037EN-09 41
Operation
Step Action
After editing the administrator login value, press to go to the next screen.
The login:
• Is case-sensitive.
• Can contain from 1 to 16 characters.
• Can contain alphanumeric characters and symbols, excluding the space character.
After editing the administrator access code value, do one of the following:
• Press one or more times to go back to previous login and access code configuration screens.
• Press OK.
8 When prompted to confirm changes to the logins and access codes, press YES.
You can restore the default login and access code settings by pressing and
holding it down for 10 seconds.
42 DOCA0037EN-09
Operation
General View
Overview
The General view menu allows you to monitor up to eight selected devices
through summarized information.
There are two display modes:
• Icon
• List
Switch between display modes by pressing the corresponding icon in the lower
right corner of the screen.
From this menu, you can reach the Device view screens of the monitored
devices:
• Device view for ComPact, PowerPact, MasterPact circuit breakers, page 48.
• Device view for Acti9 Smartlink devices, page 53.
Icon Mode
In the icon mode, the eight devices are displayed on one screen, each one by an
icon.
To reach a Device view, press the corresponding icon.
NOTE: If only one device is discovered, the display, skips the General view
and displays the Device view of the discovered device.
List Mode
In the list mode, four devices are displayed per screen, one per line.
DOCA0037EN-09 43
Operation
Step Action
1
From the General view, in list mode, press .
The backlighting of the MicroLogic trip unit, or FDM121 display, or both if present, start blinking for around 15 seconds.
To refresh the display of names, press . A progress bar is displayed while the
screen is refreshed.
In networks where names can be updated at anytime, it is recommended to
refresh the FDM128 display periodically.
44 DOCA0037EN-09
Operation
In the icon mode, the device with its ERMS mode engaged displays a blue ERMS
message below the device icon.
To reach a Device view, press the corresponding icon.
List Mode
In the list mode, the device with its ERMS mode engaged displays the Ir settings
in blue.
In the Device view, the device with its ERMS mode engaged displays an ERMS
message in the title bar.
DOCA0037EN-09 45
Operation
Real-Time Alarms
Overview
Alarms are displayed differently according to their priority level.
NOTE: The alarms must be acknowledged on the circuit breakers. There is no
acknowledgment from the FDM128 display.
Trip When a trip occurs, the FDM128 screen shows a pop-up window. The following window represents an example of a
trip on circuit breaker CB01.
You must close this window before returning to the General view.
This alarm also appears as a red icon on the General view screen and on the title bar of the Device view screen.
High The device icon turns red to indicate a high-priority alarm , page 43.
This alarm also appears as a red icon on the title bar of the Device view screen.
Medium When a medium-priority alarm occurs, an orange icon appears on the General view screens and on the title bar of
the Device view screens.
Low Low-priority alarms are only registered in the alarm history and viewable in the Alarm history submenu.
46 DOCA0037EN-09
Operation
Partial orange (current value and ID are A medium severity alarm is active.
displayed)
Full orange (only ID is displayed) FDM128 display has lost the communication
with the circuit breaker. Check the cable
connection or check if the Modbus serial line
time out is set to 1 s.
Full orange (ID and disconnected symbols are The circuit breaker is in disconnected position.
displayed)
To check the details on the current Active alarm, refer to the Alarm history
submenu.
DOCA0037EN-09 47
Operation
Features MasterPact MTZ MasterPact NT/NW, ComPacT NSX and MasterPact NT/NW,
circuit breakers ComPact NS, and PowerPacT H-, J-, or ComPact, and
PowerPact P- and R- L-frame circuit PowerPact switch-
Frame circuit breakers disconnectors
breakers
Quick Views ✓ ✓ ✓ ✓
Measures/I ✓ ✓ ✓ –
Measures/V ✓ ✓ ✓ –
Measures/PQS ✓ ✓ ✓ –
Measures/E ✓ ✓ ✓ –
Measures/F-PF-Cosphi ✓ ✓ ✓ –
Measures/THD ✓ ✓ ✓ –
Alarm History/Trip ✓ ✓ ✓ –
Alarm History/Alarm ✓ – ✓ –
Alarm History/Active ✓ – – –
Alarm History/Maintenance – – ✓ –
Alarm History/BSCM – – ✓ –
Control ✓ ✓ ✓ ✓
Maintenance/Information ✓ ✓ ✓ ✓
Maintenance/Product ID ✓ ✓ ✓ ✓
IO/Status ✓ ✓ ✓ ✓
IO/Counters ✓ ✓ ✓ ✓
IO/Control ✓ ✓ ✓ ✓
48 DOCA0037EN-09
Operation
To read the voltage bar graph correctly, you must set up the primary nominal
voltage of the circuit breaker.
Quick View
The Quick view submenu displays the status and main measurements, and
protection settings (long time, short time, instantaneous, ground fault, or earth
leakage) from a single circuit breaker.
There is no tab in this submenu.
Measures
The Measures submenu displays measurements from a single circuit breaker.
The tabs are the following:
• I
• V
• PQS
• E
• F-PF-Cosϕ
• THD
In tabs where the maximum measurement can be reset, you can reset the
measurements when the remote control is enabled (IFM or IFE locking pad points
to the open padlock, or the EIFE intrusive commands mode is unlocked). In these
conditions, press the Reset button to access the RESET screen, where:
DOCA0037EN-09 49
Operation
Alarm History
The Alarm history submenu gives access to the various histories of the circuit
breaker.
The table presents the description and number of records of each history
according to the circuit breaker.
Control
DANGER
HAZARD OF ELECTRIC SHOCK
• Check that the downstream electrical equipment is safe.
• Check that you control the appropriate circuit breaker.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF CLOSING ON ELECTRICAL FAULT
Do not close the circuit breaker again without first inspecting and, if necessary,
repairing the downstream electrical equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
50 DOCA0037EN-09
Operation
• Verify that ComPacT NSX or PowerPacT H-, J-, or L-frame circuit breakers
are equipped with a BSCM and a communicating motor mechanism in
automatic mode.
• Verify that the circuit breaker is in remote control mode.
• Verify that you know the circuit breaker password. The password of the circuit
breaker is set using the EcoStruxure Power Commission software.
• Verify that the IFE or IFM locking pad points to the unlocked position, when
the circuit breaker is connected to an IFE or IFM interface.
• Verify that the intrusive command mode is unlocked, when the circuit breaker
is connected to an EIFE interface.
The Control submenu allows you to check the status and to execute actions
remotely to operate the circuit breaker.
The table presents the possible actions depending on the circuit breaker:
Step Action
1 In the submenu Control, press the action for the target circuit breaker.
2 Click OK to continue.
4 Press Enter.
Maintenance
The table presents the functions of each tab of the Maintenance submenu:
Tab Function
Information Maintenance information available for MasterPact MTZ circuit breakers:
• remaining service life rate
• contact wear rate
• load profile
• circuit breaker operation counter values
• cradle counter values
Maintenance information available for MasterPact NT/NW, ComPact NS, ComPacT NSX and
PowerPact circuit breakers:
• contact wear rate
• load profile
• circuit breaker operation counter values
• cradle counter values
NOTE: The value displayed for operation counter corresponds to the resettable counter.
Product ID Displays the identification data of all ULP modules of the intelligent modular unit.
DOCA0037EN-09 51
Operation
Step Action
1 In the submenu Control, press the action for the target output.
3 Press YES.
52 DOCA0037EN-09
Operation
PowerTag Link
PowerTag Link HD
Control ✓ – ✓
Status ✓ ✓ ✓
Counters ✓ ✓ ✓
Monitoring Information
Depending on the type of the connected device, the Device view displays:
• The status of the connected device (only for Acti9 Smartlink SI B and Acti9
Smartlink Modbus)
• The counters measured by the connected device (only for Acti9 Smartlink SI
B and Acti9 Smartlink Modbus)
• Buttons to control other devices connected to the Acti9 Smartlink (only for
Acti9 Smartlink SI B and Acti9 Smartlink Modbus)
• Metering data provided by PowerTag energy sensors (only for Acti9 Smartlink
SI B and Acti9 Smartlink SI D)
For example, the layout of the Device view for a device connected to an Acti9
Smartlink SI B is as follows:
NOTE: When browsing an Acti9 Smartlink device view for the first time or after
a configuration update, it may take up to 20 seconds for the displayed data to
refresh.
DOCA0037EN-09 53
Operation
Control
DANGER
HAZARD OF ELECTRIC SHOCK
• Check that the downstream electrical equipment is safe.
• Check that you control the appropriate circuit breaker.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF CLOSING ON ELECTRICAL FAULT
Do not close the circuit breaker again without first inspecting and, if necessary,
repairing the downstream electrical equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Step Action
1 In the submenu Control, press the action (Open or Close) for the target device.
2 Press YES.
54 DOCA0037EN-09
Operation
DOCA0037EN-09 55
Operation
56 DOCA0037EN-09
Update and Maintenance
Prerequisites
To update the FDM128 firmware, use a USB memory key.
This USB memory key must be:
• Formatted in FAT32 system format
• Empty
DANGER
HAZARD OF ELECTRICAL SHOCK
• Ensure that the zone is safe before connecting or disconnecting the USB
key.
• Use the USB connector for a temporary connection during maintenance and
configuration of equipment.
Failure to follow these instructions will result in death or serious injury.
Step Action
2 In the Search box, type the reference of the FDM128 display (LV434128) or the name of the product offer (FDM128).
• Do not include leading or trailing blank spaces in the search string.
• To get information on similar modules, use asterisks (*).
If you entered the name of the product offer, go to the Product Offer search results.
5 Click the link Firmware update for Enerlin’X FDM128 (zip) of the FDM128 firmware version you want to download.
DOCA0037EN-09 57
Update and Maintenance
WARNING
LOSS OF DATA
Note down the old configuration settings to re-configure them after firmware
update.
REQUIRES CLEANUP
The configuration settings of the FDM128 display (such as IP configuration and
slave device configuration) may be lost when the FDM128 firmware is updated.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Step Action
4 Plug the USB memory key into the USB1 port on the FDM128 display.
58 DOCA0037EN-09
Update and Maintenance
Step Action
1 Ensure that settings of the new devices are compliant with the prerequisites, page 32.
2
Press the icon to update the FDM128 communication settings.
Step Action
Replacing MicroLogic
Step Action
2
Press the icon to update the FDM128 communication settings, page 36.
DOCA0037EN-09 59
Update and Maintenance
Regular Cleaning
Cleaning the Display
NOTICE
EQUIPMENT DAMAGE
• Power off the FDM128 display before cleaning it.
• Do not use hard or sharp objects to operate the touch panel since it can
damage the panel surface.
• Do not use paint thinner, organic solvents, or a strong acid compound to
clean the FDM128 display.
Failure to follow these instructions can result in equipment damage.
When the surface or the frame of the display gets dirty, soak a soft cloth in water
with a neutral detergent, wring the cloth tightly, and wipe the display.
60 DOCA0037EN-09
Update and Maintenance
Troubleshooting Checklists
Introduction
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel.
• Before working on the equipment, ensure that you are working in a safe area
Failure to follow these instructions will result in death or serious injury.
When a problem is detected, go through the checklist and follow the instructions
given.
Possible problems that could occur when using an FDM128 display are:
• Panel display is blank.
• Connected equipment cannot be used.
• Panel does not respond or responds slowly.
• Panel beeps when powered on.
NOTE: Contact your local Schneider Electric vendor or your local distributor.
1 Is the FDM128 display using the correct rated voltage? Verify the power supply connections and levels.
2 Is the power supply off or disconnected? Follow the instructions in the Instruction Sheet to reconnect
the power supply.
3 Is the backlight lit? Potential detected problem with the FDM128 display.
Contact your local Schneider Electric distributor.
4 Is the problem resolved? If none of the previous steps resolve the detected problem,
verify the hardware.
Display Replacement
The following replacements are available:
• Front part only: reference HMIS85
• Whole device, including the front part: reference LV434128
For information about how to reinstall the product, see the Instruction Sheet.
1 Is the power supply off or disconnected? Verify the power supply connections and levels.
2 Is the communication cable connected correctly? For more information about cable diagrams, refer to FDM128
Ethernet Display for Eight Devices Instruction Sheet.
3 Is the problem resolved? If none of the previous steps resolve the communication
problem, then check the hardware.
DOCA0037EN-09 61
Update and Maintenance
End-of-Life Recycling
At end of life, the FDM128 display has been optimized to decrease the amount of
waste and valorize the components and materials of the product in the usual end
of life treatment process.
The design has been achieved so components are able to enter the usual end-of-
life treatment processes as appropriate: depollution if recommended, reuse and/or
dismantling if recommended to increase the recycling performances, and
shredding for separating the rest of materials.
62 DOCA0037EN-09
Appendices
What’s in This Part
FDM128 Icons ...............................................................................................64
Glossary of Acronyms.....................................................................................67
DOCA0037EN-09 63
FDM128 Icons
FDM128 Icons
What’s in This Chapter
Icon List........................................................................................................64
Icon List
Header Icons
Icon Description
Footer Icons
Icon Description
Go to next screen
Go to previous screen
64 DOCA0037EN-09
FDM128 Icons
Action Icons
Icon Description
Decrease level
Increase level
Capacitive load
Inductive load
DOCA0037EN-09 65
FDM128 Icons
Icon Description
66 DOCA0037EN-09
Glossary of Acronyms
Glossary of Acronyms
What’s in This Chapter
Acronym .......................................................................................................67
Acronym
Acronyms and Definitions
The following table lists the acronyms used in various screens and their respective
definition:
Acronym Definition
NA Not applicable (means either the data is not available from the circuit
breaker or communication error)
DOCA0037EN-09 67
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.se.com