INSTR Panel Guard 701 770 140425
INSTR Panel Guard 701 770 140425
INSTR Panel Guard 701 770 140425
701-15H, 770-15H
701-35H, 770-35H
701S-48
701S-48
208GK-15H
208GK-35H
OPERATION & SAFETY
MAXIMUM AIRFLOW (SLPM) THROUGH PIPE AT 0.3 BAR PRESSURE DROP (6.9 BAR AND 21OC)
Pipe Length Pipe Size (Nominal) - Schedule 40
(Meters) 1/4 3/8 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2
3 821 1840 3396 7188 13584 27677 42117 81023 128369
6 594 1302 2406 5094 9622 19584 29687 57279 90786 I M P O R TA N T
9 481 1047 1981 4160 7839 15990 24225 46780 74188
12 425 906 1698 3594 6792 13839 20999 40497 64184 Please read all instructions BEFORE
15 368 821 1528 3226 6085 12367 18763 36224 57421 attempting to use this product
18 340 736 1387 2943 5547 11292 17150 33083 52412
21 311 708 1302 2717 5122 10471 15877 30621 48535
24 283 651 1217 2547 4811 9792 14829 28640 45393
27 269 623 1132 2406 4528 9226 13980 26998 42790
31 255 594 1075 2264 4302 8745 13273 25612 40611 10125 Carver Road, Cincinnati, OH 45242
Rubber hose maximum airflow rating: 1/2” I.D. rubber hose = 3/8” pipe; 3/4” I.D. rubber hose = 1/2” pipe
Phone: 513-891-7474 • Fax: 513-891-4092
Toll Free: 800-441-7475
www.vortec.com • [email protected]
LIT0152
(27o to 32oC). The Panel Guard will not work properly
GENERAL SAFETY CONSIDERATIONS PANEL GUARD ASSEMBLY at pressures below 70 psig (4.8 bar).
(Drawing shown below is not to scale)
WARNING: COMPRESSED AIR COULD CAUSE
DEATH, BLINDNESS OR INJURY
Models 770, 770BSP, 770-15H, 770-15HBSP, 770-35H, 770-35HBSP
MAINTENANCE
1. Do not operate at compressed air pressures above Panel Guards have no moving parts and can be
150 psig (10.3 bar). disassembled for cleaning. Do not remove or adjust the
2. Do not operate at supply line temperatures above brass thermostat.
110oF (43oC). Unscrew the cold cap and remove the generator for
3. Avoid direct contact with compressed air. cleaning.
4. Do not direct compressed air at any person. Temperature ranges are calibrated at the factory and are
5. When using compressed air, wear safety glasses with non-adjustable.
Vent
side shields.
TROUBLESHOOTING
INTRODUCTION Insufficient airflow may be caused by the following:
A Panel Guard is designed to use filtered compressed 1. Undersized compressed air line size.
air to cool industrial control cabinets without the use 2. Compressed air pressure too low.
of any refrigerants. Hot air in the cabinet is vented to
3. Partial or complete blockage of internal compressed
the surroundings through a built in relief valve in the
air path, due to dirt.
Panel Guard. The Panel Guard uses a fixed mechanical
thermostat (non-adjustable) to maintain cabinet Insufficient cold air temperature may be caused by:
temperature within the desired range. 1. Compressed air line temperature too high.
2. Water vapor in the compressed air supply.
COMPRESSED AIR SUPPLY 3. Loose cold cap. This may occur if not tightened
The compressed air supply must be filtered to remove properly after disassembled for cleaning.
Installation procedures:
water and dirt using a 5 micron or smaller filter. Failure If trouble persists, please contact Vortec at 1-800-441-
to use a filter may cause clogging (and freezing) of the 1. Cut a 1-15/16” (1-1/2” knockout size) hole in the
enclosure. 7475.
compressed air paths inside the Vortec product. Filter
recommendations are given in Table 1. 2. Insert Panel Guard into cut-out.
3. Tightly thread locknut onto the Panel Guard.
LIMITED WARRANTY
Filter elements must be changed on a regular basis.
Frequency of change is determined by the condition of 4. Perforate the ducting kit with several 1/8” holes and Vortec compressed air products manufactured by ITW
the compressed air supply. Filters should be installed in secure to interior of enclosure. Air Management will be replaced or repaired if found
the compressed air supply line as close as possible to to be defective due to manufacture defect within ten
5. Attach the ducting kit to cold outlet of Panel Guard.
the Vortec product. years from the date of invoice. Refer to our website
6. Connect compressed air filter to Panel Guard. Install www.vortec.com for full warranty details and limitations.
The appropriate size of compressed air supply line the compressed air filter as close as possible to the ITW Air Management makes no specific warranty
should be selected to ensure optimal performance of the Panel Guard, in a location where the temperature merchantability or warrant of fitness to a particular
Vortec product. Please refer to Table 2 to determine what does not exceed 125oF (52oC). purpose.
supply line size is recommended for your application. 7. Connect compressed air supply to filter.
Contact Vortec at 1-800-441-7475 for further assistance.
8. Operate the Panel Guard at 90 to 100 psig (6.2 to
6.9 bar) compressed air pressure. Do not operate at
INSTALLATION AND OPERATION pressures above 150 psig (10.3 bar). Operation at
To maintain the Type 4 rating, the Panel Guard must pressures less than 90 psig (6.2 bar) and above 100
be installed in a vertical orientation on a flat horizontal psig (6.9 bar) can affect the “on” and “off” temperatures
surface of a Type 4 rated enclosure (see the figure at which the unit cycles. The Panel Guard will cycle on
below). and off to maintain temperatures between 80o to 90oF