Csi 23-0510 - Square Meter Construction LLC Plot No-9132693

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

M/S.

SQUARE METER CONSTRUCTION LLC


Dubai, United Arab Emirates

Our Ref : CSI-23-510


Date : 07-12-2023
Attention : Project Engineer
Subject : Residential Villa G+2 Floor for Ms. Zubaida Humood M. Alattar Plot No. 9132693, Umm
Nahad Third, DUBAI - UAE.
Soil Bearing Capacity (SBC) & Level Confirmation for Shallow & Raft Foundation at Pump
Room
Dear Sir,
Further to your instructions regarding site inspection for the subject project please note the following.
• The site had been excavated up to -2.45m Below Existing Ground Level and compacted in
preparation for the construction of Shallow & Raft foundations.
• Total of Two (02) nos. of in-situ density tests and One (01) no. of Proctor tests were carried out by us
(Al Mawazeen Lab). Test results are presented in our lab reports (Attached).
• Degrees of compaction obtained from the tests was 96% of Maximum Dry Density (MDD) for road
base material.
• The recommendations are given in Soil Report done by M/s. Trans Fast Engineering Laboratory, Soil
Report ref No. TFL/G-1264/22, dated 26th April 2022 & DM Approved Drawing Ref No. 380830-6-1,
dated 30th November 2023.
• Examination of the formation level and sidewalls indicated that subsurface conditions are consistent
with those explained in the above-mentioned report.
• No additional comment is required here as the Soil Report & DM Approved Drawing Ref No. 380830-
6-1 is being followed.

Conclusion:
Based on the above results and careful observation of Soil Report & DM Approved Drawing Ref No. 380830-6-1
table 01 can be used safely for Shallow & Raft foundations to be set at foundation level of -2.45m for Pump
Room Below Existing Ground Level.
Table 1: Assessment of bearing pressure for Shallow & Raft Foundations at Pump Room
Foundation Depth (m), Modulus of Sub-
Type of Foundation Width Allowable Bearing
Below Existing Ground Grade Reaction
foundation (m) Pressure (KN/m2)
Level (kN/m3)
Conventional Pad Up to 3.0 160 19200
-2.45m / Isolated Footing 3.1 to 5.0 150 18000
Raft - 180 10800
We hope that the above information will satisfy your requirements, however if you require further
information, please do not hesitate to contact us.
Thanking You,
For Al Mawazeen Soil Testing Lab

____________________________
Engr. Muhammad Afrasiyab
Geotechnical Engineer