Conclusion:
Based on the above results and careful observation of Soil Report & DM Approved Drawing Ref No. 380830-6-1
table 01 can be used safely for Shallow & Raft foundations to be set at foundation level of -2.45m for Pump
Room Below Existing Ground Level.
Table 1: Assessment of bearing pressure for Shallow & Raft Foundations at Pump Room
Foundation Depth (m), Modulus of Sub-
Type of Foundation Width Allowable Bearing
Below Existing Ground Grade Reaction
foundation (m) Pressure (KN/m2)
Level (kN/m3)
Conventional Pad Up to 3.0 160 19200
-2.45m / Isolated Footing 3.1 to 5.0 150 18000
Raft - 180 10800
We hope that the above information will satisfy your requirements, however if you require further
information, please do not hesitate to contact us.
Thanking You,
For Al Mawazeen Soil Testing Lab
____________________________
Engr. Muhammad Afrasiyab
Geotechnical Engineer