General Notes and Specification: Computation of Loads

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

ISECO

OVERHEAD DISTRIBUTION
LEGEND / SYMBOL
COMPUTATION OF LOADS

PANELBOARD Total Load = 12160 VA


Assumed 1 x 25 kVA 1Ph
LIGHTING OUTLET LAYOUT INCANDESCENT BULB Service Entrance Conductors: Transformer
CONVENIENCE OUTLET 2.6% Impedance
IFL = [(12,160 VA x 125%) + (1,000 x 25%)] ÷ 230 Volts
AIRCONDITION UNIT OUTLET = 67.2 Amperes
9m 9m M KILOWATT-HOUR METER

CIRCUIT BREAKER USE : 2 - 14.0 mm THHN Cu WIRE IN 25mmØ CONDUIT


Sab

S S 1 GANG SWITCH 70A, 2P


S

S
S3W 3-WAY SWITCH Service Equipment (Main Breaker): 1 Set 2-22 mm2

S S
S
Sabc 3 GANG SWITCH LETTER SUBSCRIPT
IFL = [12160 - 1000 + (1,000 x 250%)] ÷ 230 Volts THW
Length 93 ft
INDICATES LIGHT CONTROLLED
= 59.39 Amperes Maximum

12m
S S Sab 2 GANG SWITCH LETTER SUBSCRIPT
12m

S3w
S3w
S INDICATES LIGHT CONTROLLED
Sab S
1 CIRCUIT HOMERUN,NUMBER INDICATES Use One - 60 AT ,2P,1Ø,60HZ, 230V
1 THE CIRCUIT NUMBER
2 LOADS SCHEDULE

Sab
S S S

GENERAL NOTES VOLTAGE DROP CALCULATION

Circuit 4: 2 - 3.5 mm2


RISER DIAGRAM

GROUND FLOOR SECOND FLOOR SINGLE LINE DIAGRAM AND SPECIFICATION THW copper
Wire length in ft: 30 ft max.
Load current: 52.87 Amperes
2 THHN copper
Wire length in ft: 75 ft max.
At point #1:
IF.L. = (kVAtransformer x 1000) ÷ 230 = (1 x 25 kVA x
Load current: 6.26 Amperes
Conductor resistance in Conductor resistance in Ohms/thousand feet: 1000) ÷ 230 = 108.7 Amperes
Ohms/thousand feet:0.321 2.05
VD = (2 x L x R x I) ÷ 1000 = (2 x 75 x 2.05 x
IS.C. = IF.L. ÷ Z = 108.7 ÷ 0.026 = 4,180 Amperes = 4
VD = (2 x L x R x I) ÷ 1000
= (2 x 30 x 0.321 x 52.87) ÷ 1000 6.26) ÷ 1000 = kAIC
= 1.02 volts 1.92volts At point #2:
%VD = (1.92 ÷ 230) x 100 = 0.83%
1. ALL ELECTRICAL WORKS AND INSTALLATIONS SHALL BE IN %VD = (1.02 ÷ 230) x 100 = 0.44% Voltage : 230 - 1.92 = 228.08 Volts Ffactor = (2 x L x I1-phase S.C.) ÷ (C x n x V)
Voltage at Service Drop to
230V,1Ø,60HZ ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION Panel Board: 230 - 1.02 = Conductor size = 2 - 22.0 mm2 THW
Circuit 5: 2 - 5.5 mm2
AC SOURCE M OF THE PHILIPPINE ELECTRICAL CODE (PART 1), ALL 228.98 volts 2 THHN copper
Wire length in ft: 20 ft max.
L(Length of conductor) = 93 ft
Circuit 1: 2 - 2.0 mm2
EXISTING CITY OR MUNICIPAL ORDINANCES, RULES AND THHN copper Load current: 8 Amperes
Conductor resistance in Ohms/thousand feet:
V (Voltage) = 230 Volts
REGULATIONS OF ISECO. Wire length in ft: 100ft max.
Load current: 3.91 Amperes
2.05 C ( Conductor factor) = 1,557
VD = (2 x L x R x I) ÷ 1000 = (2 x 20 x 2.05 x
Conductor resistance in 8) ÷ 1000 = n (Number of conductor pairs) = 1 set
2. ALL MATERIALS TO BE USED SHALL BE NEW AND INSTALLED Ohms/thousand feet: 3.26 0.65 volts Ffactor = (2 x 93 x 4,180) ÷(1,557 x 1 x 230) = 2.17
%VD = (0.65 ÷ 230) x 100 = 0.28%
IN APPLICATIONS FOR WHICH THEY ARE INTENDED VD = (2 x L x R x I) ÷ 1000 = (2 x 100
x 3.26 x 3.91) ÷ 1000 = Voltage : 230 - 0.65 = 353.84 Volts Mfactor = 1 ÷ (1 + Ffactor) =1 ÷ (1 + 2.17) = 0.315
3. ELECTRICAL INSTALLATIONS SHALL BE UNDER DIRECT 2.5 volts
%VD = (2.5÷ 230) x 100 = 1.09%
Circuit 6: 2 - 5.5 mm2 Current S.C.symmetrical rms = 4,180 Amperes x 0.315 =
2 THHN copper
1 2 SUPERVISION OF DULY LICENSED ELECTRICAL ENGINEER OR Voltage : 230 - 2.5 = 227.5Volts Wire length in ft: 35 ft max. 1316.7 Amperes Use: 1 kAIC
15A 15A Load current: 8 Amperes
At point #3:
REGISTERED MASTER ELECTRICIAN.
CONVENIENCE OUTLET LAYOUT 3 4
Circuit 2: 2 - 2.0 mm2 THHN copper
Wire length in ft: 130 ft max.
Conductor resistance in Ohms/thousand feet:
2.05 Ffactor = (2 x L x I1-phase S.C.) ÷(C x n x V)
20A 20A 4. MOUNTING HEIGHTS OF UTILITY BOX AND PANEL BOX FROM Load current: 5.22Amperes
VD = (2 x L x R x I) ÷ 1000 = (2 x 35 x 2.05 x
8) ÷ 1000 = Conductor size (submersible pump) = 2 - 3.5 mm2 THHN
5 6
FINISHED FLOOR LINE TO CENTER IS AS FOLLOWS, Conductor resistance in
Ohms/thousand feet: 3.26
1.15 volts
%VD = (1.15 ÷ 230) x 100 = 0.5% L(Length of conductor) = 33 ft (farthest Load)
30A 30A CONVENIENCE OUTLET - 30 cm (UTILITYBOX - HORIZONTAL) VD = (2 x L x R x I) ÷ 1000 = (2 x 130 Voltage : 230 - 1.15 = 228.9 Volts
V (Voltage) = 230 Volts
7 8 SWITCH - 135 cm (UTILITYBOX - VERTICAL) x 3.26 x 5.22) ÷ 1000 =
4.44volts Circuit 7: 2 - 3.5 mm2
9m 20A SPARE
PANELBOARD - 170 cm (PANEL BOX - VERTICAL) %VD = (4.44 ÷ 230) x 100 =1.93 % 2 THHN copper
Wire length in ft: 50 ft max.
C ( Conductor factor) = 617
9m 5. EXPOSED WIRE SHALL BE INSTALLED PARALLEL OR
Voltage : 230 - 4.44= 226Volts
Load current: 8 Amperes
Conductor resistance in Ohms/thousand feet:
n (Number of conductor pairs) = 1 set
Circuit 3: 2 - 3.5 mm2 Ffactor = (2 x 93 x 1316.7) ÷(617 x 1 x 230) = 1.73
PERPENDICULAR TO THE WALL. 2 THHN copper
2.05
VD = (2 x L x R x I) ÷ 1000 = (2 x 50 x 2.05 x 8) Mfactor = 1 ÷ (1 + Ffactor) = 1 ÷ (1 + 1.73) = 0.366
acu 6. THE SYSTEM VOLTAGE IS LINE TO GROUND, SINGLE PHASE, Wire length in ft: 68 ft max.
Load current: 5.48 Amperes
÷ 1000 =
Current S.C.symmetrical rms
5 230V. Conductor resistance in Ohms/thousand
1.64 volts
%VD = (1.64 ÷ 230) x 100 = 7.13% = 1316.7 Amperes x 0.366 = 481.91 Amperes
feet: 2.05
Voltage : 230 - 1.64 = 140.24Volts
3 6
2
8.0 mm THHN Cu WIRE 7. NO ALTERATION SHALL BE DONE IN THE PLAN UNLESS VD = (2 x L x R x I) ÷ 1000 = (2 x 68 x Use: 1 kAIC
2.05 x 5.48) ÷ 1000 =
acu
NOTED BY THE DESIGNER AND OWNER. 1.53volts
%VD = (1.53 ÷ 230) x 100 = 0.67%
Voltage : 230 - 1.53 = 228.5 Volts
12m

SCHEDULE OF LOADS
12m

VICINITY MAP
4
2
N
MAIN CONDUCTOR 14.0 mm MAIN BREAKER 60 AT
1 CONDUCTOR CONDUIT
CKT. DESCRIPTION OF LOAD VA
LOAD VOLTAGE CURRENT AT AF POLE
2
NO. NO. & SIZE TYPE DIAMETER TYPE
7 3
4
5
9 LIGHTING OUTLET 900
1200
230 3.91 15 50 2 2-2.0mm
2
2
THHN 20mm
20mm
PVC W E
12 LIGHTING OUTLET 230 5.22 15 50 2 2-2.0mm THHN PVC
6
7 7-CONVENIENCE OUTLET at 180VA 1260 230 5.48 20 50 2 2 2
2-3.5mm + 1-3.5mm (G) THHN 20mm PVC
8 8-CONVENIENCE OUTLET at 180VA 1440 230 6.26 20 50 2 2
2-3.5mm + 1-3.5mm 2 (G) THHN 20mm PVC
2

GROUND FLOOR SECOND FLOOR 1-1 HP AIRCONDITION UNIT


1-1 HP AIRCONDITION UNIT
1840
1840
230
230
8
8
30 50
30 50
2
2
2-5.5mm
2-5.5mm
2
THHN
THHN
15mm
15mm
PVC
PVC
THIS S
WATER PUMP 1840 230 8 20 50 2 2-3.5mm
2
THHN 15mm PVC SITE
SPARE 1840 230 8 THHN 15mm PVC
VA TOTAL: 12160
TOTAL: 52.87 Amperes CABUGAO MUNICIPAL
HALL
If = Itotal + 0.25HRM =52.87 + (0.25)(8)
USE : 2 - 14.0 mm2 THHN Cu WIRE IN 25mmØ CONDUIT
=54.87 Amperes ( Applying 80% Demand Factor) 60 AT ,2P ,230V MCB
If =43.90 Amperes

IN-CHARGE OF INSTALLATION PROJECT TITLE : OWNER : SHEET CONTENT : SHEET NO. :

PROFESSIONAL ELECTRICAL ENGINEER

PTR NO. : REG NO. : SINGLE FAMILY DWELLING FLOOR PLAN MS. LYCA F. NAVAL AS BUILT
ISS. ON: TIN NO. :

ISS. AT: LOCATION: BRGY. BACLIG CABUGAO, ILOCOS SUR