Directional Overcurrent Relay
Directional Overcurrent Relay
Applications
An overcurrent relay will operate for fault current flow in any direction, i.e., either in
forward or in the reverse direction. In order to achieve the operation of the relay in the
directional relay to the overcurrent relay, such a relay will respond to fault flow in a
particular direction.
relay. But in an overcurrent relay, the driving torque is developed due to the magnetic
fields produced by the operating current of the circuit given through a current
transformer.
While in the case of directional overcurrent relay the driving torque is developed due to
the magnetic fields produced by both the operating current and voltage of the circuit in
which it is connected for protection. The relay operates when the current exceeds a
The schematic diagram of the directional overcurrent relay is shown in the figure given
The directional unit mainly consists of an induction cup relay with two opposite poles
being fed by voltage and current. The potential coil on the upper electromagnet is
connected to the system voltage through a potential transformer. The coil on the lower
transformer.
Voltage is taken as the polarizing quantity which remains more or less fixed when the
other quantity i.e., the current undergoes wide changes in phase angle.
The two fluxes are produced by the two quantities for the production of torque. The
contacts of the directional unit are connected in series with another winding over the
The overcurrent unit may be of either a shaded pole type or wattmeter type. The coil
wound on the upper electromagnet of the overcurrent unit is tapped and connected to
The tapping’s are connected to a plug setting bridge to get the required current setting.
An aluminum disc is placed between the two magnets which consist of moving contact
that closes the fixed contact (trip circuit contacts) after the operations of the directional
relay unit.
During fault conditions, the fault current flows through the current coil of the relay
which produces a flux in the lower magnet of the directional unit while the current in
the voltage coil produces another flux in the upper magnet of the directional unit. The
two fluxes produce a positive torque that tends to close its contact and operate the
relay.
This in turn makes the relay current flow through the winding over the upper magnet of
the overcurrent unit and therefore produces a flux in this magnet. This flux induces all
the emf in the winding over the lower magnet of the overcurrent unit.
Since this winding is a closed path, the induced emf circulates a current which in turn
produces another flux. The two fluxes produce a torque that makes the overcurrent
It is clear that the operation of the overcurrent relay is controlled by a directional unit.
Therefore, the directional unit must operate first in order to operate the overcurrent
relay.
Parallel Feeder Protection - The below shows the protective scheme of the
parallel feeder.
(←). When there is a fault F on the feeder the current in the feeder reverses
and it makes directional relay A 2 operate and trips the feeder. Thus, the
faulty feeder is isolated from the system, and continuity of the supply
discrimination the relays on the source end buses are non-directional while
at the load end buses are given directional relays. As directional relays
should operate before non-directional ones, the relays are set for lower time
Ring Main System Protection - The protective scheme ring mains system is
shown in the below figure. The relays at source buses (A 1, B1 .. F1) are non-
directional because the relays may not operate for faults close to the source
the relays associated directly with the faulty section of the ring should
are used.
Directional Earth Fault Protection - In this type of relay, the voltage coil is
conditions, the residual current will be zero. When a fault occurs, the
residual current will have some value and if this current exceeds the
specified value, the relay operates. Relay senses the direction in which earth
In this system of earthing, the neutral point is earthed through the primary winding of a
single-phase voltage transformer as shown in the figure below. The secondary winding
of the voltage transformer is connected in series with a low resistor and a relay.
As the neutral of the system is connected through voltage transformer. A very high
reactance earthing is provided by the voltage transformer. The voltage transformer acts
as a fault indicator. If an earth fault occurs on any of the phases, it produces a voltage
across the relay connected across the secondary. The relay operates and trips the
protecting devices connected. The protecting device, thus isolates the circuit till the
fault is eliminated.
The voltage transformer earthed neutral acts as a reflection point for travelling waves
passing through the machine winding. These travelling waves cause high voltages in
the circuit and in order to prevent high voltage built up a surge diverter is connected
The neutral is earthed through a voltage transformer and thus its operational
For travelling waves, the earth neutral acts as a reflection point which may
Generally, at every voltage level, the neutral point is available from the generator or
transformer i.e., when the star connected. But when there is a delta connection or
when the neutral is desired on the busbars etc., then the neutral point will not be
available. In such cases, the most common method used for neutral grounding is
The earthing transformer, also known as the grounding transformer provides a neutral
point where it is not available. The earthing or grounding transformer provides a low
impedance path to the neutral and overvoltage’s due to arcing grounds, static induced
charges, and lightning surges are eliminated by discharging to earth. By using earthing
In a zig-zag transformer, there are three limbs and each limb is provided with two
identical windings. These windings are wound such that under normal conditions the
two fluxes on each limb oppose each other in such a manner that the net flux on each
limb is negligibly small. Hence, during normal conditions, the transformer draws very
During an earth fault on the circuit, the zero-sequence current will flow in the
transformer winding through the earthing. The earth fault current finds little
impedance. Earthing transformers are of short time rating (10 seconds to 1 minute)
which makes them small in size when compared to the power transformer of the same
rating.
with neutral connected to the ground. The terminals of the primary winding are
in delta connection and is not connected to any external circuit i.e., it operates
unloaded.
The operation of this transformer is similar to the zig-zag transformer, which offers high
impedance to the current under normal conditions, and on the occurrence of a ground
fault, a low impedance path is provided for the ground fault currents.
It should be ensured that not to operate more than one earthing transformer connected
to the same supply system at the same time and also short-circuit protection should be
resistance and reactance between them, then the grounding system is known as solid
Consider a 3-phase power system with neutral solidly grounded and an earth fault on
phase B as shown in the above figure. On the occurrence of earth fault over any phase,
the phase to earth voltage of the phase on which the earth fault occurs becomes zero
i.e., the potential of the neutral and phase B will be at earth potential. While the phase
It will be seen that the fault current I F will completely neutralize the capacitive current
ICF because IF is in phase opposition to ICF. In a solidly grounded system, the voltages of
healthy phases under earth fault conditions will not exceed 80% of the line to line
values. The capacitive currents flowing in the healthy phases are I CR and ICY will lead
their corresponding voltages by 90°. Earth fault current I F is a 90° lagging current (due
faulty phase. The total capacitive current ICF is a resultant of ICR and ICY.
We have seen that the phase-to-earth voltage of the phase with earth fault
becomes zero and it remains normal in the case of healthy phases. Hence,
current IF. These two currents will nullify each other completely. Hence in
cannot occur.
systems are less expensive for all operating voltages as the voltages of
healthy phases in case of line to a ground fault do not exceed 80% of the
line-to-line voltage, whereas in the case of other groundings the voltage of
gears due to the availability of a large fault current between the fault point
In solid grounding, there will be high fault currents which may cause the
currents.
The system in which the neutral point is grounded through a current limiting device
resistance grounding. This method is used when it becomes necessary to limit the earth
fault current.
The resistor used in this grounding may comprise either wire or water column
resistance and the value of resistance used is generally higher than the system
reactance so as to limit the power loss in the resistor due to earth fault.
The value of resistance required for grounding purposes increases with the increase in
operating voltage in order to limit the short circuit current during an earth fault. The
resistance grounded system with earth fault at point F in phase B is shown above and
Where,
IC = Capacitive current
IF = Fault current.
The current IF, IBR, and IBY will be flowing through fault point F in phase B. The phase
angle of the fault current will depend upon the impedance at the fault point. The
capacitive currents IBR and IBY will lag the voltages VBR and VBY respectively by 90°. The
fault current IF is resolved into two components one is the reactive component I X and
The resultant capacitive fault current will be in phase opposition with the reactive
component at fault point F. This resultant capacitive fault current can be neutralized by
used for low voltage short-length overhead lines, as the charging currents in these lines
are small.
If the earthing resistance is of low value (when I rea is equal to IC), the fault currents are
high and the system condition approaches the solid earthing. On the other hand, if the
earthing resistance is of higher value so that I rea is less than IC then the system
conditions approach that of the ungrounded neutral system with the risk of transient
overvoltages occurring.
The value of resistance is so chosen that at the time of an earth fault on any phase, a
current equal to the full load current of the largest alternator or transformer feeding the
system, flows in the earth connection. This will keep the overvoltages within limits
During an earth fault, the system neutral will almost be invariably displaced,
because of which there is a need for lightning arrestors, and also the
system.
The system in which the neutral point is grounded through impedance which is highly
reactance grounding.
...
If solid grounding is employed in the transmission lines whose operating voltage is 3.3
kV to 33 kV, then the fault currents will be high. In order to overcome this problem,
increasing the lagging current due to which the capacitive currents are neutralized.
reactance grounding, the value of reactance is selected such that it must keep currents
within the safe limit i.e., by reactance grounding the fault current is limited.
It also provides necessary phase opposition between capacitive ground current and the
fault current. Whereas in the case of resistance grounding only fault current is limited
Depending upon the ratio of zero sequence reactance X 0 to positive sequence reactance
X1 the system is said to be solidly grounded or reactance grounded. If the ratio (X 0/X1)
exceeds three, the system is said to be a reactance grounded system and if this ratio is
less than three, then the system is said to be a solidly grounded system. Even if the
neutral of the system is effectively grounded and the ratio exceeds three, then the
grounded system.
Reactance grounding is used for the lightly loaded transmission lines, underground
cables, synchronous condensers, and circuits that have high charging currents.
Reactance Grounding:
A 3-phase system provided with reactance grounding is shown in the below figure. In
Here the fault current is dependent upon the reactance. Thus, varying the reactance in
the neutral to earth line, the magnitude of the fault current can be varied.
system.
In reactance grounding under fault conditions, very high transient voltages
appear.
The resistance offered to the lightning current when the tower is directly exposed to
measured at 50 Hz. The performance of the line purely depends upon the value of
resistance during lightning. The resistance is the function of soil resistivity, critical
The voltage and the current transmitted into the tower will depend upon the surge
impedance of the tower and ground impedance (i.e., the tower-footing resistance) of
the tower. Taking all the factors into consideration such as wave shape, the magnitude
of lightning current striking the tower, surge impedance, potential wave at the top of
resistance is low, the chances of occurrence of flashover are eliminated and the
on the lines effectively with the help of ground wires. The tower-footing resistance lies
between 10-20Ω. For medium-voltage transmission lines, it is less than 10Ω. Thus, in
order to keep the tower-footing resistance low some special arrangements are made.
Reduction of Tower Footing Resistance:
The tower resistance is reduced by two methods, either by driving rods near the tower
and connecting them to the tower base or by burying counterpoise wires into the
The driven rods are made up of galvanized iron or copper weld. This method is best
suited in the locations where the soil is free from rocks i.e., it is best suited in sandy
soil. Sometimes driven galvanized iron pipes are also used. Below shows the driven rod
compared to driven rods due to its simple implementation. The wires are usually made
up of copper, aluminum, galvanized iron, or stranded cable and are arranged either
the line route and is connected to each tower base. This arrangement is more efficient
Current is drawn into the counterpoise from 1.5 to 2.5 km away from the point of the
stroke and fed into the stroke by means of the counterpoise wire and the overhead
ground wires.
The concentration of the current at any tower is thus reduced. The reduced current at
any tower causes a reduced voltage drop at the tower base, and thus the tower
potential is held to a value below the flashover voltage of the line insulators.
By the above methods, the lightning current is reduced, thereby reducing the voltage at
the base of the tower. Therefore, the potential value at the base of the tower is lower
than the flashover voltage and helps in neutralizing them to the ground. Hence, tower-