Tech Note 368 - Network Setup For AppEngine Redundancy
Tech Note 368 - Network Setup For AppEngine Redundancy
All Tech Notes and KBCD documents and software are provided "as is" without warranty of any kind. See the Terms of
Use for more information.
Topic#: 002024
Created: October 2004
Introduction
This Tech Note explains the necessary network settings for the Redundancy Message
Channel (RMC) for a redundant AppEngine configuration.
The first card is for the supervisory network and the second one is for the RMC network
(Redundancy Message Channel).
The RMC network is dedicated for redundancy monitoring and data synchronization between
redundant AppEngine pairs.
It is setup with an Ethernet crossover cable between two computers (Figure 1 below).
Detailed Setup
The following steps explain the network configuration setup for a PC hosting redundancy
enabled AppEngine.
These steps are recorded using Windows 2003 Server Operating System and apply to other
operating systems as well.
https://wdnresource.wonderware.com/support/kbcd/html/1/t002024.htm 7/6/2011
Network Setup for AppEngine Redundancy Page 2 of 11
The Command Prompt returns the IP settings for both Ethernet connections (Figure 2
below):
3. Document the Local Area Connection numbers along with IP Addresses to identify the
Primary and RMC networks.
6. Right-click and rename each Local Area Connection Number to Primary- and RMC
Networks as appropriate (Figure 3 below):
https://wdnresource.wonderware.com/support/kbcd/html/1/t002024.htm 7/6/2011
Network Setup for AppEngine Redundancy Page 3 of 11
8. Set the binding order to ensure Primary Network is the first to be accessed by network
services (Figure 4 below):
https://wdnresource.wonderware.com/support/kbcd/html/1/t002024.htm 7/6/2011
Network Setup for AppEngine Redundancy Page 4 of 11
11. Select Internet Protocol (TCP/IP) and click the Properties button.
The Primary network may be configured to obtain dynamic or Static IP Addresses (Figure
6 below):
https://wdnresource.wonderware.com/support/kbcd/html/1/t002024.htm 7/6/2011
Network Setup for AppEngine Redundancy Page 5 of 11
https://wdnresource.wonderware.com/support/kbcd/html/1/t002024.htm 7/6/2011
Network Setup for AppEngine Redundancy Page 6 of 11
14. Verify that the Register this connection’s addresses in DNS option is selected and
that the other settings are consistent (Figure 8 below):
https://wdnresource.wonderware.com/support/kbcd/html/1/t002024.htm 7/6/2011
Network Setup for AppEngine Redundancy Page 7 of 11
15. Click OK to save the settings and exit the dialog box.
https://wdnresource.wonderware.com/support/kbcd/html/1/t002024.htm 7/6/2011
Network Setup for AppEngine Redundancy Page 8 of 11
The RMC Network must be configured for static IP Address (Figure 10 below).
Note: Consult your Network Administrator for IP Address and Subnet Mask values.
https://wdnresource.wonderware.com/support/kbcd/html/1/t002024.htm 7/6/2011
Network Setup for AppEngine Redundancy Page 9 of 11
https://wdnresource.wonderware.com/support/kbcd/html/1/t002024.htm 7/6/2011
Network Setup for AppEngine Redundancy Page 10 of 11
21. Verify that the Register this connection’s Addresses in DNS checkbox option is NOT
selected for RMC Network (Figure 12 below):
https://wdnresource.wonderware.com/support/kbcd/html/1/t002024.htm 7/6/2011
Network Setup for AppEngine Redundancy Page 11 of 11
S. Mariyala
Tech Notes are published occasionally by Wonderware Technical Support. Publisher: Invensys Systems, Inc., 26561
Rancho Parkway South, Lake Forest, CA 92630. There is also technical information on our software products at
Wonderware Technical Support
back to top
©2011 Invensys Systems, Inc. All rights reserved. No part of the material protected by this copyright may be
reproduced or utilized in any form or by any means, electronic or mechanical, including photocopying, recording,
broadcasting, or by anyinformation storage and retrieval system, without permission in writing from Invensys Systems,
Inc. Terms of Use.
https://wdnresource.wonderware.com/support/kbcd/html/1/t002024.htm 7/6/2011