0% found this document useful (0 votes)
202 views11 pages

Event

This document contains log entries from a network management card monitoring a Smart-UPS SRT 5000 UPS over time. It logs user logins and logouts to the interface, UPS events like bypass mode or low battery notifications, and battery replacement recommendations. The UPS is configured with switched outlet groups and has experienced issues with its internal battery pack not being installed properly.

Uploaded by

panjiibrahim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
202 views11 pages

Event

This document contains log entries from a network management card monitoring a Smart-UPS SRT 5000 UPS over time. It logs user logins and logouts to the interface, UPS events like bypass mode or low battery notifications, and battery replacement recommendations. The UPS is configured with switched outlet groups and has experienced issues with its internal battery pack not being installed properly.

Uploaded by

panjiibrahim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
You are on page 1/ 11

Network Management Card AOS v6.5.

0
Smart-UPS & Matrix-UPS APP v6.5.0
NMC Serial Number: 5A1808T33121

Model: Smart-UPS SRT 5000


UPS Serial Number: AS1808171254
Firmware Revision: UPS 04.7 (ID1013)

Date Time Name Contact Location System IP


09/06/2023 08:44:50 AFC-SSM-PGUPS-01 Unknown AFC-SSM-PGUPS-01
10.60.7.144

Date Time User Event Code


09/06/2023 08:43:26 apc Web user 'apc' logged in from 10.60.250.137. 0x0015
09/06/2023 06:57:21 System Web user 'apc' logged out from 10.60.7.21.
0x001F
09/06/2023 06:54:14 apc Web user 'apc' logged in from 10.60.7.21. 0x0015
09/06/2023 05:35:40 System Web user 'apc' logged out from 10.60.250.137.
0x001F
09/06/2023 05:32:40 apc Web user 'apc' logged in from 10.60.250.137. 0x0015
09/06/2023 05:31:56 System Web user 'apc' logged out from 10.60.250.137.
0x001F
09/06/2023 05:30:05 Device UPS: In bypass in response to the UPS front-
panel or a user-initiated software command, typically for maintenance. 0x011C
09/06/2023 05:28:07 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
09/06/2023 05:27:33 Device UPS: The battery power is too low to support
the load; if power fails, the UPS will be shut down immediately. 0x0107
09/06/2023 05:27:33 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/06/2023 05:27:33 Device UPS: Restored the local network management
interface-to-UPS communication. 0x0101
09/06/2023 05:27:25 apc Web user 'apc' logged in from 10.60.250.137. 0x0015
09/06/2023 05:27:09 System Network service started. IPv6 address
FE80::2A29:86FF:FE04:AC8B assigned by link-local autoconfiguration. 0x0007
09/06/2023 05:27:07 System Network service started. System IP is
10.60.7.144 from manually configured settings. 0x0007
09/06/2023 05:27:03 System Network Interface coldstarted. 0x0001
09/06/2023 05:26:30 Device UPS: A battery charger fault exists. 0x012A
09/06/2023 05:26:24 Device UPS: A battery charger fault no longer exists.
0x012B
09/06/2023 05:25:47 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
09/06/2023 05:25:13 Device UPS: The output power is turned off. 0x0114
09/06/2023 05:25:13 Device UPS: The graceful shutdown period has ended.
0x014F
09/06/2023 05:25:13 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is off. 0x0186
09/06/2023 05:25:13 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is off. 0x0186
09/06/2023 05:25:13 Device UPS: The battery power is too low to support
the load; if power fails, the UPS will be shut down immediately. 0x0107
09/06/2023 05:25:13 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/06/2023 05:25:13 Device UPS: A battery charger fault exists. 0x012A
09/06/2023 05:25:13 Device UPS: Restored the local network management
interface-to-UPS communication. 0x0101
09/06/2023 05:24:49 System Network service started. IPv6 address
FE80::2A29:86FF:FE04:AC8B assigned by link-local autoconfiguration. 0x0007
09/06/2023 05:24:48 System Network service started. System IP is
10.60.7.144 from manually configured settings. 0x0007
09/06/2023 05:24:43 System Network Interface coldstarted. 0x0001
09/06/2023 05:18:34 apc Web user 'apc' logged in from 10.60.250.137. 0x0015
09/06/2023 05:18:27 Device UPS: The output power is turned off. 0x0114
09/06/2023 05:18:27 Device UPS: The graceful shutdown period has ended.
0x014F
09/06/2023 05:18:27 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is off. 0x0186
09/06/2023 05:18:27 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is off. 0x0186
09/06/2023 05:18:27 Device UPS: The battery power is too low to support
the load; if power fails, the UPS will be shut down immediately. 0x0107
09/06/2023 05:18:27 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/06/2023 05:18:27 Device UPS: A battery charger fault exists. 0x012A
09/06/2023 05:18:26 Device UPS: Restored the local network management
interface-to-UPS communication. 0x0101
09/06/2023 05:18:03 System Network service started. IPv6 address
FE80::2A29:86FF:FE04:AC8B assigned by link-local autoconfiguration. 0x0007
09/06/2023 05:18:01 System Network service started. System IP is
10.60.7.144 from manually configured settings. 0x0007
09/06/2023 05:17:57 System Network Interface coldstarted. 0x0001
09/06/2023 05:16:42 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
09/06/2023 05:16:10 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/06/2023 05:16:10 Device UPS: Battery life exceeded cleared. 0x018D
09/06/2023 05:15:51 Device UPS: A battery charger fault exists. 0x012A
09/06/2023 05:15:48 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
09/06/2023 05:15:45 Device UPS: A battery charger fault no longer exists.
0x012B
09/06/2023 04:57:12 apc Web user 'apc' logged in from 10.60.250.137. 0x0015
09/06/2023 04:21:42 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
09/06/2023 04:21:37 Device UPS: Internal pack disconnected cleared. 0x01A1
09/06/2023 04:21:09 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/06/2023 04:21:08 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned off. 0x0135
09/06/2023 04:21:08 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned off. 0x0135
09/06/2023 04:21:08 Device UPS: A battery charger fault exists. 0x012A
09/06/2023 04:21:07 Device UPS: The output power is turned off. 0x0114
09/06/2023 04:21:07 Device UPS: The graceful shutdown period has ended.
0x014F
09/06/2023 04:20:53 Device UPS: Internal pack disconnected. 0x01A0
09/05/2023 21:06:43 System NTP update successful. 0x004A
09/04/2023 23:17:11 Device UPS: Self-Test passed. 0x01D2
09/04/2023 23:16:50 Device UPS: Self-Test started by automatic timer.
0x0137
09/01/2023 23:10:20 Device UPS: Battery life exceeded cleared. 0x018D
09/01/2023 01:06:26 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
09/01/2023 01:05:48 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
09/01/2023 01:05:42 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
09/01/2023 01:05:42 Device UPS: Battery life exceeded cleared. 0x018D
08/31/2023 22:49:59 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/31/2023 21:11:48 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/31/2023 21:10:56 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/31/2023 21:10:56 Device UPS: Battery life exceeded cleared. 0x018D
08/31/2023 21:09:00 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/31/2023 20:51:49 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/31/2023 20:51:14 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/31/2023 20:51:14 Device UPS: Battery life exceeded cleared. 0x018D
08/31/2023 20:42:13 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/31/2023 20:38:49 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/31/2023 20:37:55 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/31/2023 20:37:55 Device UPS: Battery life exceeded cleared. 0x018D
08/31/2023 18:11:55 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/31/2023 18:11:49 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/31/2023 18:11:11 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/31/2023 18:11:11 Device UPS: Battery life exceeded cleared. 0x018D
08/31/2023 17:57:49 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/31/2023 17:57:49 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/31/2023 17:57:30 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/31/2023 17:57:30 Device UPS: Battery life exceeded cleared. 0x018D
08/30/2023 04:03:07 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/30/2023 04:02:50 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/30/2023 04:02:29 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/30/2023 04:02:29 Device UPS: Battery life exceeded cleared. 0x018D
08/30/2023 03:59:33 Device UPS: Internal pack, cartridge 1 is installed.
0x0130
08/30/2023 03:58:50 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/30/2023 03:58:49 Device UPS: Internal pack, cartridge 1 is not
installed. 0x012F
08/28/2023 01:11:04 Device UPS: No longer on battery power. 0x010A
08/28/2023 01:11:04 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
08/28/2023 00:52:56 Device UPS: Bypass not in range ; distorted waveform.
0x020F
08/28/2023 00:52:55 Device UPS: On battery power in response to low input
voltage. 0x0109
08/27/2023 02:34:15 Device UPS: No longer on battery power. 0x010A
08/27/2023 02:34:14 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
08/27/2023 02:32:46 Device UPS: Bypass not in range ; distorted waveform.
0x020F
08/27/2023 02:32:46 Device UPS: On battery power in response to distorted
input. 0x0109
08/27/2023 02:19:38 Device UPS: No longer on battery power. 0x010A
08/27/2023 02:19:37 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
08/27/2023 02:18:48 Device UPS: Bypass not in range ; distorted waveform.
0x020F
08/27/2023 02:18:48 Device UPS: On battery power in response to rapid
change of input. 0x0109
08/22/2023 21:06:33 System NTP update successful. 0x004A
08/21/2023 23:17:36 Device UPS: Self-Test passed. 0x01D2
08/21/2023 23:17:15 Device UPS: Self-Test started by automatic timer.
0x0137
08/20/2023 22:45:04 Device UPS: Battery life exceeded cleared. 0x018D
08/08/2023 21:06:36 System NTP update successful. 0x004A
08/07/2023 23:18:14 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
08/07/2023 23:18:01 Device UPS: Self-Test passed. 0x01D2
08/07/2023 23:17:40 Device UPS: Self-Test started by automatic timer.
0x0137
07/25/2023 21:06:27 System NTP update successful. 0x004A
07/24/2023 23:19:02 Device UPS: Self-Test passed. 0x01D2
07/24/2023 23:18:41 Device UPS: Self-Test started by front panel. 0x0137
07/24/2023 23:18:40 Device UPS: Battery life exceeded cleared. 0x018D
07/20/2023 02:16:34 Device UPS: No longer on battery power. 0x010A
07/20/2023 02:16:33 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
07/20/2023 00:46:11 Device UPS: On battery power in response to distorted
input. 0x0109
07/20/2023 00:46:11 Device UPS: Bypass not in range ; distorted waveform.
0x020F
07/15/2023 07:37:03 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
07/11/2023 23:24:40 Device UPS: Self-Test passed. 0x01D2
07/11/2023 23:24:19 Device UPS: Self-Test started by front panel. 0x0137
07/11/2023 21:06:00 System NTP update successful. 0x004A
07/01/2023 07:37:28 Device UPS: Battery life exceeded cleared. 0x018D
07/01/2023 03:35:20 Device UPS: No longer on battery power. 0x010A
07/01/2023 03:35:19 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
07/01/2023 03:32:04 Device UPS: On battery power in response to distorted
input. 0x0109
07/01/2023 03:32:04 Device UPS: Bypass not in range ; distorted waveform.
0x020F
07/01/2023 00:56:52 Device UPS: No longer on battery power. 0x010A
07/01/2023 00:56:52 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
07/01/2023 00:54:20 Device UPS: On battery power in response to distorted
input. 0x0109
07/01/2023 00:54:20 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/29/2023 23:56:03 Device UPS: Self-Test passed. 0x01D2
06/29/2023 23:55:43 Device UPS: Self-Test started by automatic timer.
0x0137
06/29/2023 23:54:54 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
06/27/2023 21:05:55 System NTP update successful. 0x004A
06/15/2023 23:56:25 Device UPS: Self-Test passed. 0x01D2
06/15/2023 23:56:04 Device UPS: Self-Test started by front panel. 0x0137
06/15/2023 23:55:40 Device UPS: Self-Test passed. 0x01D2
06/15/2023 23:55:19 Device UPS: Self-Test started by front panel. 0x0137
06/15/2023 23:55:15 Device UPS: Battery life exceeded cleared. 0x018D
06/14/2023 03:37:04 Device UPS: No longer on battery power. 0x010A
06/14/2023 03:37:04 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
06/14/2023 03:35:01 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/14/2023 03:35:01 Device UPS: On battery power in response to distorted
input. 0x0109
06/14/2023 01:11:18 Device UPS: No longer on battery power. 0x010A
06/14/2023 01:11:18 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
06/14/2023 01:09:08 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/14/2023 01:09:08 Device UPS: On battery power in response to distorted
input. 0x0109
06/13/2023 21:05:56 System NTP update successful. 0x004A
06/06/2023 22:38:49 Device UPS: Self-Test passed. 0x01D2
06/06/2023 22:38:28 Device UPS: Self-Test started by automatic timer.
0x0137
05/30/2023 21:05:27 System NTP update successful. 0x004A
05/25/2023 03:25:52 Device UPS: No longer on battery power. 0x010A
05/25/2023 03:25:51 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/25/2023 03:25:00 Device UPS: On battery power in response to distorted
input. 0x0109
05/25/2023 03:25:00 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/25/2023 02:17:45 Device UPS: No longer on battery power. 0x010A
05/25/2023 02:17:43 Device UPS: On battery power in response to distorted
input. 0x0109
05/25/2023 01:29:53 Device UPS: No longer on battery power. 0x010A
05/25/2023 01:29:52 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/25/2023 01:29:13 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/25/2023 01:29:12 Device UPS: On battery power in response to low input
voltage. 0x0109
05/23/2023 22:39:14 Device UPS: Self-Test passed. 0x01D2
05/23/2023 22:38:54 Device UPS: Self-Test started by automatic timer.
0x0137
05/21/2023 21:44:42 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
05/16/2023 21:05:18 System NTP update successful. 0x004A
05/09/2023 22:39:39 Device UPS: Self-Test passed. 0x01D2
05/09/2023 22:39:18 Device UPS: Self-Test started by automatic timer.
0x0137
05/07/2023 21:45:05 Device UPS: Battery life exceeded cleared. 0x018D
05/02/2023 21:05:20 System NTP update successful. 0x004A
04/25/2023 22:40:03 Device UPS: Self-Test passed. 0x01D2
04/25/2023 22:39:42 Device UPS: Self-Test started by automatic timer.
0x0137
04/23/2023 07:19:08 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
04/18/2023 21:04:31 System NTP update successful. 0x004A
04/11/2023 22:40:26 Device UPS: Self-Test passed. 0x01D2
04/11/2023 22:40:05 Device UPS: Self-Test started by front panel. 0x0137
04/09/2023 07:20:29 Device UPS: Self-Test passed. 0x01D2
04/09/2023 07:20:08 Device UPS: Self-Test started by front panel. 0x0137
04/09/2023 07:19:57 Device UPS: Self-Test passed. 0x01D2
04/09/2023 07:19:37 Device UPS: Self-Test started by front panel. 0x0137
04/09/2023 07:19:33 Device UPS: Battery life exceeded cleared. 0x018D
04/04/2023 21:03:51 System NTP update successful. 0x004A
04/02/2023 18:05:49 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
03/29/2023 22:38:14 Device UPS: Self-Test passed. 0x01D2
03/29/2023 22:37:53 Device UPS: Self-Test started by front panel. 0x0137
03/29/2023 22:37:20 Device UPS: Self-Test passed. 0x01D2
03/29/2023 22:36:59 Device UPS: Self-Test started by front panel. 0x0137
03/21/2023 21:03:57 System NTP update successful. 0x004A
03/20/2023 21:22:12 Device UPS: Self-Test passed. 0x01D2
03/20/2023 21:21:52 Device UPS: Self-Test started by automatic timer.
0x0137
03/19/2023 18:06:13 Device UPS: Battery life exceeded cleared. 0x018D
03/18/2023 02:16:28 Device UPS: No longer on battery power. 0x010A
03/18/2023 02:16:27 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
03/18/2023 02:10:18 Device UPS: Bypass not in range ; distorted waveform.
0x020F
03/18/2023 02:10:18 Device UPS: On battery power in response to distorted
input. 0x0109
03/18/2023 01:23:15 Device UPS: No longer on battery power. 0x010A
03/18/2023 01:23:14 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
03/18/2023 01:00:17 Device UPS: Bypass not in range ; distorted waveform.
0x020F
03/18/2023 01:00:16 Device UPS: On battery power in response to distorted
input. 0x0109
03/17/2023 22:59:47 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
03/07/2023 21:03:50 System NTP update successful. 0x004A
03/06/2023 21:22:38 Device UPS: Self-Test passed. 0x01D2
03/06/2023 21:22:17 Device UPS: Self-Test started by automatic timer.
0x0137
03/03/2023 23:00:11 Device UPS: Battery life exceeded cleared. 0x018D
02/21/2023 21:03:51 System NTP update successful. 0x004A
02/20/2023 21:23:02 Device UPS: Self-Test passed. 0x01D2
02/20/2023 21:22:42 Device UPS: Self-Test started by automatic timer.
0x0137
02/10/2023 15:57:48 Device UPS: Battery life exceeded. Order replacement
battery, APCRBC140, for the internal pack, cartridge 1. 0x018C
02/07/2023 21:03:57 System NTP update successful. 0x004A
02/06/2023 21:23:28 Device UPS: Self-Test passed. 0x01D2
02/06/2023 21:23:07 Device UPS: Self-Test started by automatic timer.
0x0137
02/05/2023 22:16:22 Device UPS: Battery near end of life cleared. 0x018B
01/25/2023 16:37:33 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
01/24/2023 21:03:45 System NTP update successful. 0x004A
01/23/2023 21:24:24 Device UPS: Self-Test passed. 0x01D2
01/23/2023 21:24:02 Device UPS: Self-Test started by front panel. 0x0137
01/15/2023 14:19:14 System Web user 'apc' logged out from 10.60.250.21.
0x001F
01/15/2023 14:16:14 apc Web user 'apc' logged in from 10.60.250.21. 0x0015
01/11/2023 21:22:05 Device UPS: Self-Test passed. 0x01D2
01/11/2023 21:21:44 Device UPS: Self-Test started by automatic timer.
0x0137
01/11/2023 16:37:54 Device UPS: Battery near end of life cleared. 0x018B
01/10/2023 21:03:31 System NTP update successful. 0x004A
12/28/2022 21:22:30 Device UPS: Self-Test passed. 0x01D2
12/28/2022 21:22:09 Device UPS: Self-Test started by automatic timer.
0x0137
12/27/2022 21:03:22 System NTP update successful. 0x004A
12/14/2022 21:22:55 Device UPS: Self-Test passed. 0x01D2
12/14/2022 21:22:34 Device UPS: Self-Test started by front panel. 0x0137
12/13/2022 21:03:10 System NTP update successful. 0x004A
12/08/2022 16:55:55 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
12/05/2022 01:36:17 Device UPS: No longer on battery power. 0x010A
12/05/2022 01:36:16 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
12/05/2022 01:36:02 Device UPS: Bypass not in range ; distorted waveform.
0x020F
12/05/2022 01:36:01 Device UPS: On battery power in response to rapid
change of input. 0x0109
12/05/2022 01:15:41 Device UPS: No longer on battery power. 0x010A
12/05/2022 01:15:41 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
12/05/2022 01:15:29 Device UPS: Bypass not in range ; distorted waveform.
0x020F
12/05/2022 01:15:29 Device UPS: On battery power in response to rapid
change of input. 0x0109
12/03/2022 21:45:17 Device UPS: Self-Test passed. 0x01D2
12/03/2022 21:44:56 Device UPS: Self-Test started by automatic timer.
0x0137
11/29/2022 21:02:21 System NTP update successful. 0x004A
11/24/2022 16:56:19 Device UPS: Battery near end of life cleared. 0x018B
11/19/2022 21:45:42 Device UPS: Self-Test passed. 0x01D2
11/19/2022 21:45:21 Device UPS: Self-Test started by automatic timer.
0x0137
11/19/2022 21:13:40 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
11/15/2022 21:01:49 System NTP update successful. 0x004A
11/05/2022 21:46:23 Device UPS: Self-Test passed. 0x01D2
11/05/2022 21:46:02 Device UPS: Self-Test started by front panel. 0x0137
11/05/2022 21:14:26 Device UPS: Self-Test passed. 0x01D2
11/05/2022 21:14:05 Device UPS: Self-Test started by front panel. 0x0137
11/05/2022 21:14:03 Device UPS: Battery near end of life cleared. 0x018B
11/01/2022 21:01:56 System NTP update successful. 0x004A
10/27/2022 20:16:26 Device UPS: Self-Test passed. 0x01D2
10/27/2022 20:16:05 Device UPS: Self-Test started by automatic timer.
0x0137
10/18/2022 21:02:00 System NTP update successful. 0x004A
10/13/2022 20:16:51 Device UPS: Self-Test passed. 0x01D2
10/13/2022 20:16:30 Device UPS: Self-Test started by automatic timer.
0x0137
10/11/2022 20:09:35 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
10/04/2022 21:02:02 System NTP update successful. 0x004A
09/29/2022 20:17:15 Device UPS: Self-Test passed. 0x01D2
09/29/2022 20:16:55 Device UPS: Self-Test started by automatic timer.
0x0137
09/27/2022 20:10:00 Device UPS: Battery near end of life cleared. 0x018B
09/20/2022 21:01:31 System NTP update successful. 0x004A
09/15/2022 20:17:41 Device UPS: Self-Test passed. 0x01D2
09/15/2022 20:17:20 Device UPS: Self-Test started by automatic timer.
0x0137
09/15/2022 20:17:20 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
09/06/2022 21:01:02 System NTP update successful. 0x004A
09/01/2022 20:18:09 Device UPS: Self-Test passed. 0x01D2
09/01/2022 20:17:48 Device UPS: Self-Test started by front panel. 0x0137
09/01/2022 20:17:46 Device UPS: Battery near end of life cleared. 0x018B
08/25/2022 14:41:18 apc Web user 'apc' logged out from 10.60.250.147. 0x001F
08/25/2022 14:40:47 apc Web user 'apc' logged in from 10.60.250.147. 0x0015
08/25/2022 14:40:40 apc Web user 'apc' logged out from 10.60.250.147. 0x001F
08/25/2022 14:40:16 apc Web user 'apc' logged in from 10.60.250.147. 0x0015
08/23/2022 21:00:33 System NTP update successful. 0x004A
08/21/2022 21:30:30 Device UPS: Self-Test passed. 0x01D2
08/21/2022 21:30:09 Device UPS: Self-Test started by automatic timer.
0x0137
08/21/2022 18:00:20 Device UPS: Battery near end of life. Order
replacement battery, APCRBC140, for the internal pack, cartridge 1. 0x018A
08/09/2022 20:59:46 System NTP update successful. 0x004A
08/07/2022 21:30:54 Device UPS: Self-Test passed. 0x01D2
08/07/2022 21:30:33 Device UPS: Self-Test started by automatic timer.
0x0137
07/26/2022 20:58:56 System NTP update successful. 0x004A
07/24/2022 21:31:47 Device UPS: Self-Test passed. 0x01D2
07/24/2022 21:31:26 Device UPS: Self-Test started by front panel. 0x0137
07/13/2022 03:42:32 Device UPS: Self-Test passed. 0x01D2
07/13/2022 03:42:11 Device UPS: Self-Test started by automatic timer.
0x0137
07/12/2022 20:59:02 System NTP update successful. 0x004A
07/09/2022 00:29:02 Device UPS: No longer on battery power. 0x010A
07/09/2022 00:29:02 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
07/08/2022 23:23:20 Device UPS: On battery power in response to low input
voltage. 0x0109
07/08/2022 23:23:20 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/29/2022 03:42:56 Device UPS: Self-Test passed. 0x01D2
06/29/2022 03:42:35 Device UPS: Self-Test started by automatic timer.
0x0137
06/28/2022 20:59:08 System NTP update successful. 0x004A
06/15/2022 03:43:21 Device UPS: Self-Test passed. 0x01D2
06/15/2022 03:43:01 Device UPS: Self-Test started by automatic timer.
0x0137
06/14/2022 20:59:18 System NTP update successful. 0x004A
06/10/2022 00:50:42 Device UPS: No longer on battery power. 0x010A
06/10/2022 00:50:42 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
06/10/2022 00:50:22 Device UPS: On battery power in response to distorted
input. 0x0109
06/10/2022 00:50:22 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/09/2022 23:49:40 Device UPS: No longer on battery power. 0x010A
06/09/2022 23:49:39 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
06/09/2022 23:49:17 Device UPS: Bypass not in range ; distorted waveform.
0x020F
06/09/2022 23:49:16 Device UPS: On battery power in response to low input
voltage. 0x0109
06/01/2022 03:44:08 Device UPS: Self-Test passed. 0x01D2
06/01/2022 03:43:48 Device UPS: Self-Test started by automatic timer.
0x0137
06/01/2022 03:43:46 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned on. 0x0134
06/01/2022 03:43:46 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned on. 0x0134
06/01/2022 03:43:46 Device UPS: The output power is now turned on. 0x0113
06/01/2022 03:43:46 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn on, sequenced. 0x0174
06/01/2022 03:43:46 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn on, sequenced. 0x0174
05/31/2022 23:10:57 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned off. 0x0135
05/31/2022 23:10:57 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned off. 0x0135
05/31/2022 23:10:57 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn off, sequenced. 0x0174
05/31/2022 23:10:57 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn off, sequenced. 0x0174
05/31/2022 23:10:57 Device UPS: The output power is turned off. 0x0114
05/31/2022 23:10:57 Device UPS: The graceful shutdown period has ended.
0x014F
05/31/2022 20:59:26 System NTP update successful. 0x004A
05/23/2022 00:02:32 Device UPS: No longer on battery power. 0x010A
05/23/2022 00:02:31 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/23/2022 00:02:13 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/23/2022 00:02:13 Device UPS: On battery power in response to distorted
input. 0x0109
05/22/2022 23:38:38 Device UPS: No longer on battery power. 0x010A
05/22/2022 23:38:38 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/22/2022 23:38:21 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/22/2022 23:38:21 Device UPS: On battery power in response to distorted
input. 0x0109
05/22/2022 07:32:56 Device UPS: Self-Test passed. 0x01D2
05/22/2022 07:32:35 Device UPS: Self-Test started by front panel. 0x0137
05/22/2022 05:03:04 Device UPS: No longer on battery power. 0x010A
05/22/2022 05:03:03 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/22/2022 05:02:59 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/22/2022 05:02:59 Device UPS: On battery power in response to rapid
change of input. 0x0109
05/21/2022 23:29:02 Device UPS: No longer on battery power. 0x010A
05/21/2022 23:29:02 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/21/2022 23:28:56 Device UPS: On battery power in response to distorted
input. 0x0109
05/21/2022 23:28:56 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/20/2022 20:39:08 Device UPS: Self-Test passed. 0x01D2
05/20/2022 20:38:47 Device UPS: Self-Test started by front panel. 0x0137
05/17/2022 20:59:34 System NTP update successful. 0x004A
05/15/2022 03:13:15 Device UPS: No longer on battery power. 0x010A
05/15/2022 03:13:15 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/15/2022 03:13:09 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/15/2022 03:13:09 Device UPS: On battery power in response to distorted
input. 0x0109
05/15/2022 01:08:10 Device UPS: No longer on battery power. 0x010A
05/15/2022 01:08:09 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
05/15/2022 01:08:02 Device UPS: Bypass not in range ; distorted waveform.
0x020F
05/15/2022 01:08:02 Device UPS: On battery power in response to distorted
input. 0x0109
05/08/2022 21:32:31 Device UPS: Self-Test passed. 0x01D2
05/08/2022 21:32:10 Device UPS: Self-Test started by automatic timer.
0x0137
05/03/2022 20:59:42 System NTP update successful. 0x004A
04/24/2022 21:32:51 Device UPS: Self-Test passed. 0x01D2
04/24/2022 21:32:30 Device UPS: Self-Test started by front panel. 0x0137
04/22/2022 02:13:11 Device UPS: No longer on battery power. 0x010A
04/22/2022 02:13:10 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
04/22/2022 02:12:34 Device UPS: Bypass not in range ; distorted waveform.
0x020F
04/22/2022 02:12:34 Device UPS: On battery power in response to distorted
input. 0x0109
04/21/2022 23:09:42 Device UPS: No longer on battery power. 0x010A
04/21/2022 23:09:41 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
04/21/2022 23:09:29 Device UPS: Bypass not in range ; distorted waveform.
0x020F
04/21/2022 23:09:29 Device UPS: On battery power in response to distorted
input. 0x0109
04/21/2022 04:13:25 Device UPS: No longer on battery power. 0x010A
04/21/2022 04:13:25 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
04/21/2022 04:13:11 Device UPS: On battery power in response to distorted
input. 0x0109
04/21/2022 04:13:11 Device UPS: Bypass not in range ; distorted waveform.
0x020F
04/20/2022 23:16:33 Device UPS: No longer on battery power. 0x010A
04/20/2022 23:16:33 Device UPS: An input voltage or frequency problem no
longer prevents switching to bypass mode. 0x0210
04/20/2022 23:16:22 Device UPS: Bypass not in range ; distorted waveform.
0x020F
04/20/2022 23:16:22 Device UPS: On battery power in response to distorted
input. 0x0109
04/19/2022 20:59:51 System NTP update successful. 0x004A
04/15/2022 00:50:59 Device UPS: Self-Test passed. 0x01D2
04/15/2022 00:50:38 Device UPS: Self-Test started by automatic timer.
0x0137
04/15/2022 00:50:37 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned on. 0x0134
04/15/2022 00:50:37 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned on. 0x0134
04/15/2022 00:50:37 Device UPS: The output power is now turned on. 0x0113
04/15/2022 00:50:36 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn on, sequenced. 0x0174
04/15/2022 00:50:36 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn on, sequenced. 0x0174
04/14/2022 23:01:28 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned off. 0x0135
04/14/2022 23:01:28 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned off. 0x0135
04/14/2022 23:01:28 Device UPS: The output power is turned off. 0x0114
04/14/2022 23:01:28 Device UPS: The graceful shutdown period has ended.
0x014F
04/14/2022 23:01:27 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn off, sequenced. 0x0174
04/14/2022 23:01:27 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn off, sequenced. 0x0174
04/14/2022 04:01:18 Device UPS: Self-Test passed. 0x01D2
04/14/2022 04:00:58 Device UPS: Self-Test started by automatic timer.
0x0137
04/14/2022 04:00:57 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned on. 0x0134
04/14/2022 04:00:57 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned on. 0x0134
04/14/2022 04:00:56 Device UPS: The output power is now turned on. 0x0113
04/14/2022 04:00:56 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn on, sequenced. 0x0174
04/14/2022 04:00:56 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn on, sequenced. 0x0174
04/14/2022 01:46:00 Device UPS: The power for switched outlet group 2,
Outlet Group 2, is now turned off. 0x0135
04/14/2022 01:46:00 Device UPS: The power for switched outlet group 1,
Outlet Group 1, is now turned off. 0x0135
04/14/2022 01:46:00 Device UPS: Switched outlet group 2, Outlet Group 2,
has been commanded to turn off, sequenced. 0x0174
04/14/2022 01:46:00 Device UPS: Switched outlet group 1, Outlet Group 1,
has been commanded to turn off, sequenced. 0x0174
04/14/2022 01:46:00 Device UPS: The output power is turned off. 0x0114
04/14/2022 01:46:00 Device UPS: The graceful shutdown period has ended.
0x014F
04/11/2022 20:15:41 Device UPS: Self-Test passed. 0x01D2
04/11/2022 20:15:20 Device UPS: Self-Test started by front panel. 0x0137
04/07/2022 00:06:21 Device UPS: Self-Test passed. 0x01D2

You might also like