Fusion Module 500

The document describes a smart mini data center solution that integrates UPS, power distribution, monitoring, and batteries in a prefabricated cabinet for fast deployment. The solution provides remote monitoring over a web interface and supports centralized management of multiple sites for efficient operation and maintenance.

Uploaded by

mika.adhi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
202 views20 pages

Fusion Module 500

The document describes a smart mini data center solution that integrates UPS, power distribution, monitoring, and batteries in a prefabricated cabinet for fast deployment. The solution provides remote monitoring over a web interface and supports centralized management of multiple sites for efficient operation and maintenance.

Uploaded by

mika.adhi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

FusionModule500

Smart Mini Data Center

HUAWEI TECHNOLOGIES CO., LTD.


01 FusionModule500
Smart Mini Data Center

Contents
02 Preface
03 Huawei Solution Overview
07 Customer Benefits
14 Key Components
15 System Parameters
17 Global Services and Applications
02
Preface

Does your equipment room look like this?

• Parts purchase, onsite installation, long delivery period, inconsistent appearance


• No remote monitoring function, no pre-warning for faults
• Low integration, large footprint
• No protection for batteries against overheat, frequent fire accidents in equipment rooms
• No auto-start function for civil air conditioners when power is restored, manual startup required

Do you want to deploy an


equipment room shown in
the figure?
03 FusionModule500
Smart Mini Data Center

Huawei Solution Overview

F usionModule500 smart mini data center solution integrates the UPS, power distribution,
monitoring, and batteries in a cabinet. All components are prefabricated, pre-installed, and
pre-commissioned before delivery, simplifying installation and enabling fast deployment. The
data center solution is equipped with a remote monitoring function over the web user interface
(WebUI), enabling remote O&M for a site. In addition, Huawei's NetEco can be deployed to
centrally monitor and manage multiple sites.

Integrated cabinet

Network cabinet+
Integrated cabinet

Network cabinet+
Integrated cabinet+
battery cabinet
04

01 Application Scenarios

• Network rooms, equipment rooms in branch offices, and equipment rooms to be modernized or
expanded
• Indoor data centers
• Tier I construction level

02 Applicable Industries

Finance (branches), government, education, medical, public security, transportation, energy, small- and
medium-sized enterprises, retail industry and carrier business halls, etc.
05 FusionModule500
Smart Mini Data Center

Huawei Solution Overview

03 System Architecture and Components

摄像头(可选)
Camera (optional)

Auto-start
民用空调来电 device
for a civil air conditioner
自启动器(可选)
when power is restored
(optional)

10-inch Pad (optional)


10寸PAD(可选)

04 Key Subsystems

UPS Power Distribution System Monitoring System


• Rack-mounted • UPS input • Monitoring • Temperature and humidity
module sensor, smoke detector
• 3 kVA • UPS output • 10-inch screen • Door status switch
• 6 kVA • Maintenance bypass • SMS alarm • Water sensor
• Camera • Intelligent battery
• 10 kVA • rPDU management
06

ECC800e monitoring
ECC800e监控模块
module

Power distribution
配电模块
module

UPS
UPS

电池包
Battery pack

Cabinet System Cabling System Surge Protection System


• 19-inch standard cabinet • Cable tray • Level C surge protective device (SPD)
• Perforated door • Cable manager for the entire system
• Network cabinet (600/800 mm wide) • Wire bushing • Level D SPD for the UPS
07 FusionModule500
Smart Mini Data Center

Customer Benefits Simple, Efficient, Reliable

01 Fast Delivery

Short installation labor hours and rapid service rollout

1-day delivery

• Different suppliers
• Components arrived in
different batches
• Onsite assembling

VS
2-hour delivery

• Unified brand
• Delivered as a whole
• Pre-installed and pre-
commissioned

Values
• Power distribution, UPS, monitoring modules, and sensors are pre-installed and pre-commissioned
• Cables are prefabricated
• It takes only 2 hours to install a single-cabinet solution, saving installation costs and enabling fast service rollout
08

02 Intelligent O&M

Remote monitoring over the WebUI, mobile O&M over the mobile phone app, local large-
screen display, and centralized management of multiple sites.

1 Remote Monitoring of a Smart Module

NetEco (optional)

Site

LAN switch (optional)


LAN switch LAN switch
(optional) (optional)
SMS alarm (optional)

Pad (optional)
ECC800e
●●●

VCN500 Camera
(optional) (optional)
FusionModule FusionModule
500 500
Site 1 Site n
Smoke UPS Cabinet Temperature Water PDN5000 Infrared Independent CIM
detector door status and humidity sensor remote deployment
sensor sensor control AI/DI unit
module (optional)
(optional) BIM (optional)

Values
• The ECC800e monitoring module monitors the UPS, ambient temperature and humidity sensor, water sensor, door
status sensor, and smoke detector in real time to ensure that IT equipment is operating in a reliable environment
• A 10-inch Pad can be used locally to communicate with the ECC800e monitoring module wirelessly and display
system running parameters in real time
• Alarm information is sent to O&M personnel by SMS immediately if an alarm is triggered
• Users can access the entire power and environment system of a module after logging in to the IP address of the
ECC800e monitoring module remotely over the WebUI. Then remote O&M can be performed
09 FusionModule500
Smart Mini Data Center

Customer Benefits Simple, Efficient, Reliable

2 Centralized monitoring and management of multiple modules


Centralized
network
management Mobile
Large-screen phone app
display

DC

DC DC
DC
DC

DC

Values
• For multiple sites, Huawei's NetEco can be used to centrally monitor and manage multiple modules
• The unique GIS map mode enables faulty sites to be displayed in highlighted icons. The site that triggers an alarm can
be quickly located using the GIS map
• The smart mini data center can be integrated by a third-party NMS (including but not limited to the eSight) and
managed by the same NMS as IT/IP equipment
• Remote and mobile O&M can be performed over the mobile phone app. The power and environment of an equipment
room can be monitored in real time anytime and anywhere so that the equipment room can be left unattended
• Equipment room view, alarm, rights and security, report, capacity, and asset management can be provided
10
Customer Benefits Simple, Efficient, Reliable

01 Small Footprint

Highly integrated, saving installation space

Monitoring module

24 U available
space

Power distribution
module

UPS module

Battery module

VS
Footprint: at least 10 m² Footprint: 5 m²
Traditional data center solution: 1 PDC + 1 battery cabinet + FusionModule500: 1 cabinet
1 tower-mounted UPS + 1 IT cabinet

Values
• The UPS, power distribution, monitoring, and battery pack are integrated in a cabinet. Compared with a traditional
mini data center, Huawei's smart mini data center saves at least 50% installation space
11 FusionModule500
Smart Mini Data Center

Customer Benefits Simple, Efficient, Reliable

01 Wireless Battery Monitoring

Battery SOC/SOH, intelligent shutdown in case of overheat

ECC800e monitoring module

Battery overheat
Battery overvoltage wifi
Internal resistance increase

iBAT iBOX

Values
Active O&M management, eliminating manual inspection
• The UPS monitors key parameters such as battery temperature in real time. If a battery overheats, the UPS
automatically shut down the battery string, preventing fire risks
• The battery voltage, temperature, current, and internal resistance are detected in real time. Key parameters are
monitored so that there is no need to periodically measure battery parameters. Battery performance is tested
automatically
• A unique algorithm is adopted to monitor battery SOC and SOH. Battery failure warnings can be generated

Wireless transmission and simple deployment


• Wireless transmission between iBat and iBox. Networking is flexible and complex cabling is not required, reducing
50% deployment time. The networking function is powerful.
• One iBox can connect to 300 iBat, reducing investment. The iBat and iBox can use battery power directly
12
Customer Benefits Simple, Efficient, Reliable

02 Auto-start Function of a Household Air Conditioner


When Power is Restored

Household air conditioner that can start automatically

Manual startup onsite


• The home air conditioner cannot
automatically start when power
is restored
• Requires manual startup onsite
• The equipment room is
overheating, causing equipment
breakdown risks

Automatic startup
VS
• The home air conditioner is Air conditioner
equipped with an auto-start automatically starts
device when power is restored
• The home air conditioner can
start automatically
• The temperature of the
equipment room is intelligently
controlled

Values
• Active O&M avoids equipment breakdown due to equipment room overheat
• Home air conditioners start automatically when power is restored and require no manual operations,
preventing equipment room overheating and equipment breakdown risks. The equipment room can be left
unattended
13 FusionModule500
Smart Mini Data Center

Key Components

1 Rack-mounted UPS Parameter


Type
Parameter Name 3kVA 6kVA 10kVA

Rated input voltage 220/230/240 V AC, 50/60 Hz, 1Ph+N+PE


Input
Input voltage range 80–280 V AC, 50/60 Hz, 1Ph+N+PE
parameters
Input frequency range 40–70 Hz
Rated voltage 220/230/240Vac,50Hz,1Ph+N+PE
Power factor 0.9
Output Maximum efficiency 94% 94.50%
parameters
105% ≤ load < 125%: transfer to bypass mode after 5 minutes
Overload capability 125% ≤ load < 150%: transfer to bypass mode after 1 minute
Load ≥ 150%: transfer to bypass mode after 0.1s
Installation mode Rack-mounted
Structural
parameters The AC input side meets level D surge protection requirements (5 kA
Surge protection
in differential mode and common mode, 8/20μs)
Dry contact, web, Modbus, and Simple Network Management
Port
Protocol (SNMP)
3 kVA, 6 kVA, 10 kVA
Operating temperature 0–40oC
Environment Relative humidity 0%–95% RH (non-condensing)
parameters
Altitude < 1000 m (derated when the altitude ranges from 1000 m to 4000 m)
Storage and
transportation –40oC to +70oC
temperature
Operating temperature 0–40oC
Height 2U
Noise <55dB
Certification CE, CB, RoHS, TLC, CQC, REACH, WEEE
Award Obtained Energy Star certification as the first batch in the industry, ECA

2 Integrated Power
Distribution Module
Item
Maximum input current
Specifications (3 kVA UPS)
32 A
Specifications (6 kVA/10 kVA UPS)
63 A

Number of phases Single-phase Single-phase

Input voltage 220 V/230 V/240 V 220 V/230 V/240 V

UPS input 32 A/1P 63 A/1P

UPS output 32 A/1P 63 A/1P

UPS maintenance bypass 32 A/2P 63 A/2P

Output branch 2x16 A/1P+3x10 A/1P 4x40 A/1P+1x16 A/1P

Dimensions W×D×H (mm) 430×450×130 430×450×130


14

3 ECC800e
Monitoring Collect FE port
Item Specifications
One WAN port and one LAN port

DO dry contact output One DO port

AI/DI port AI/DI_1–5/12V

RS485 port COM1, COM2–3/12V, one CAN port

USB port Supports USB2.0 and access of four USB devices

3G/4G antenna port Antenna access port for SMS alarm

Software Embedded software to implement monitoring over WebUI

4 (Optional) Infrared Remote Item Specifications


Control for Enabling Number of supported remote
4 (maximum)
the Auto-start Function of a control commands
Household Air Conditioner
Interworks with the monitoring system over Modbus-RTU to
When Power is Restored Communication
implement remote control

Baud rate 9600 bit/s

Infrared emission distance ≤ 10 m

Power supply 9–16 V DC

Current ≤ 350 mA

Indicator Communication indicator and Run indicator

Address setting Supports Modbus address setting

Supported household air


Gree, Media, Haier, Whirlpool, Samsung, Hitachi, and LG
conditioner brands

5 (Optional) Local Pad Item Specifications


Dimensions 10-inch (touchscreen)

Screen Capacitive touchscreen, supporting multi-point touch

Storage 16 GB

Memory 2 GB LPDDR3

Battery capacity 4800 mAh

Operating system Android 4.4 (KitKat) + EMUI 3.0

Communications mode WiFi


15 FusionModule500
Smart Mini Data Center

System Parameters
Item Description 42 U 24 U
Power system 220/230/240 V AC, 50/60 Hz, 1Ph+N+PE
Operating temperature 0-40oC
Equipment parameters
Humidity range 5–95%
Altitude 0–4000 m (derated when the altitude is above 1000 m)
Certification Certification CE, RoHS, REACH
Cabinet dimensions
600×2000×1100 600×1200×850
W x H x D (mm)
Cabinet system IT cabinet, IT cabinet + network cabinet, IT
Cabinet cabinet + battery cabinet, IT cabinet + network Single IT cabinet, IT cabinet + battery cabinet
cabinet + battery cabinet
36 U (without battery packs), 24 U (four battery 17 U (without battery packs), 11 U (two battery
ICT available space ICT space
packs) packs)
System input General input switch 32 A (3 kVA), 63 A (6 kVA, 10 kVA) 32 A (3 kVA), 63 A (6 kVA)
4×40 A/1P+1×16 A/1P (6 kVA/10 kVA) 4×40 A/1P+1×16 A/1P (6 kVA)
System output Output loop
2×16 A/1P+3×10 A/1P (3 kVA) 2×16 A/1P+3×10 A/1P (3 kVA)
Capacity 3 kVA, 6 kVA, 10 kVA 3 kVA, 6 kVA
Configuration Single UPS
UPS
Power factor 0.9
Power Efficiency 94% (3 kVA/6 kVA), 94.5% (10 kVA)
distribution Vertical installation (6 kVA/10 kVA UPS)
Installation mode Horizontal installation
system Horizontal installation (3 kVA UPS)
rPDU
Type IEC/GB
Configuration IEC: 20xC13+2xC19 IEC: 8xC13
Capacity 7 Ah/9 Ah
Battery pack
Quantity 0–4 0–2
Backup power Power backup mode Battery pack/rack/cabinet
Battery cabinet Battery cabinet 15 minutes to 4 hours
Monitoring collector ECC800e
Auto-start function of
an air conditioner when Optional
power is restored
SMS alarm Optional
Remote mobile APP Optional
Water sensor Standard configuration
Monitoring Temperature and
Standard configuration
system humidity sensor
Door status sensor Standard configuration
Smoke detector Standard configuration
10 inch display Optional
Intelligent battery
Optional (when batteries are used for backup power)
management
Web access Standard configuration
Video Optional
NMS NetEco6000 Optional, implement centralized monitoring and management of multiple sites
Heat
dissipation Heat dissipation Free cooling
system
Packing dimensions
734×2200×1268 734×1400×1068
W×H×D (mm)
Dimensions/
Integrated cabinet 144 kg (without
Weight 100 kg (without battery packs)
weight battery packs)
Battery pack weight 61 kg (7 Ah), 69 kg (9 Ah)
16
Global Services and Applications

01 Global Services

Huawei has full-time data center infrastructure service engineers in regions around the globe to provide
globalized professional services and fast response. Huawei offers customized services based on the demand of
the customer. Currently Huawei provides the following services:

• 140+ national delivery


management organizations
Proactive Customer
• 129+ national spare parts Commissioning
assurance support
service on the
centers service
NMS
Service
(inspection) Onsite support Hardware (warranty)
• 300+ regional warehousing 24x7 remote
support
support service
centers service (supervision) service
(installation)
• 22,000+ service personnel
• 24/7 service

02 Typical Application Customers

FusionModule500 has been deployed in 30+ countries,


Finance
500 modules deployed worldwide
• Shaanxi Rural Credit Cooperative 3000+
• People's Bank of China, Binzhou branch 10+
• China Everbright Bank
• Industrial and Commercial Bank of China 2000+
• China Construction Bank, Australia branch
Government
• Zhaoqing Local Taxation Bureau
• Jiuquan Municipal Bureau of Land and Resources
• Guazhou County Bureau of Land and Resources
• Aksay County Bureau of Land and Resources
Education
• Shanghai Pudong Education Bureau 200+
• Turkmenistan education 200+
• Aksu education 49
• Xinhe county education standardization 65+
Enterprise
• France SystemU supermarket 1500+
• Hunan Tobacco 10+
• Guangdong Medical Apparatus and Instruments
17 FusionModule500
Smart Mini Data Center

Global Services and Applications

03 Typical success story

ICBC National Reconstruction Project

Before the reform of Nantong Zhaohui branch data center

IT cabinet Home air Tower UPS PDU Battery box


conditioner
18

ICBC integrated cabinet standardization


construction background
In the era of large data, banks gradually transition from the
traditional management model to the cloud, As China's
largest commercial bank - ICBC, a total of more than
17,000 branches,How to integrate advanced information
technology into the vertical structure management of
financial, to use the bank's huge line of outlets to serve
After the reform customers in the competition to keep a leading position,
Become ICBC important issue what they are thinking about.
And how to build a modern intelligent DC room, ICBC is
exploring.

Three pain points of ICBC branchs


construction mode
1. The traditional branch DC room components from
different suppliers, on-site assembly, it is difficult to
realize large construction standardization
2. The traditional branch DC room components are
installed independently of each other, need special
room, covers large area, high rent cost
3. The traditional branch DC room without remote
monitoring, multi-network management isdifficulty,
operation and maintenance have high pressure

Transformation value
• Standardization construction: Uniform brand of parts,
factory pre-installed, pre-test, on-site installation, only
need to access the mains and the network that can
quickly achieve business on-line, realize the construction
of full standard coverage
• Saving area: UPS, power distribution, monitoring,
battery are integrated in a module, modular design,
saving room occupies at least 50%, reduce the room
rental
• Remote intelligent operation and maintenance: The
integrated cabinet provides unified northbound
interface, Can be local or remote to achieve intelligent
monitoring, Risk can be predicted in advance, Fault
can be quickly positioned. In addition, Can access the
headquarter management system to achieve centralized
and unified management
Copyright © Huawei Technologies Co., Ltd. 2017. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.

Trademark Notice

, HUAWEI, and are trademarks or registered trademarks of Huawei Technologies Co., Ltd.
Other trademarks, product, service and company names mentioned are the property of their respective owners.

General Disclaimer HUAWEI TECHNOLOGIES CO., LTD.

The information in this document may contain predictive statements including, Huawei Industrial Base
without limitation, statements regarding the future financial and operating results, Bantian Longgang
future product portfolio, new technology, etc. There are a number of factors Shenzhen 518129, P.R. China
that could cause actual results and developments to differ materially from those Tel: +86-755-28780808
expressed or implied in the predictive statements. Therefore, such information Version No.: M3-040174-20170508-E-2.0
is provided for reference purpose only and constitutes neither an offer nor an
acceptance. Huawei may change the information at any time without notice. www.huawei.com