TwoandThreeWindingTransformersandCirculatingCurrents Presentation HRS2019
TwoandThreeWindingTransformersandCirculatingCurrents Presentation HRS2019
PSE.com // GeneralPAC.com 1
Purpose at the 2019 HRS
• Intention is to share our knowledge and passion for Power
Systems Engineering & Protection
PSE.com // GeneralPAC.com
Assumed Knowledge
• Basic understanding of symmetrical components - Phase &
Ground faults
PSE.com // GeneralPAC.com
Outcomes & Takeaways
• Better understanding of transformers under faulted conditions
PSE.com // GeneralPAC.com
Outcomes & Takeaways
• Sit back… Relax… and Enjoy the show.
PSE.com // GeneralPAC.com
Video Tutorial available on Youtube
• Search for “General PAC” or visit generalpac.com
• Topic “Fault Analysis in Power System”
PSE.com // GeneralPAC.com
2 Winding Transformer
DABY-G
115 kV 30 MVA 13.8 kV
MVASC =
600 MVA
Example
AB Y
Line A Line a
Line B Line b
Line C Line c
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
6 Step Process to calculate fault current
Step 1: Convert the system quantities into per-unit
quantities
Step 2: Identify the type of fault
Step 3: Draw the unfaulted sequence networks
Step 4: Interconnect the faulted sequence networks
Step 5: Hand Calculate Sequence Currents & Voltages
Step 6: Convert to Phase currents & voltages
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
`
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
Sequence Components
Source
Generator Transformer System
115kV 13.8kV
ZG(1) ZT(1) ZG(1) ZT(1)
j0.05 j0.10 j0.05 j0.10
Positive
Sequence
1pu + = 1pu
115kV 13.8kV
ZG(2) ZT(2) ZG(2) ZT(2)
Zero
=
j0.05 j0.10 j0.05 j0.10
Sequence +
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
3PH Fault 1LG Fault
115kV 13.8kV
ZG(1) ZT(1)
115kV 13.8kV
ZG(1) ZT(1) 1 PU
1 pu 115kV 13.8kV
ZG(2) ZT(2)
Open
(0) 115kV 13.8kV
ZG ZT(0)
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
3 Phase Fault Big Picture 1 of 5
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
3 Phase Fault Big Picture Comparison
1004|-60 8367|-90
1004|180 8367|150
1004| 60 8367| 30
PSE.com // GeneralPAC.com
1LG Fault Big Picture
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
Step #4
PSE.com // GeneralPAC.com
Step #5
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
1LG Fault Big Picture Comparison
PSE.com // GeneralPAC.com
LL Fault Big Picture 1 of 1
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
2LG Fault Big Picture 1 of 1
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
PSE.com // GeneralPAC.com
3 Winding Transformer Example
Y-D-YG
115 kV 30 MVA 13.8 kV
MVASC =
600 MVA
PSE.com // GeneralPAC.com
Sequence Components
Transformer System
Generator
115kV 13.8kV
ZH(1) ZM(1) ZG(1)) ZH(1) ZM(1)
ZG(1)
Sequence
1pu + = 1pu
T T
Negative ZL(2)
Sequence + =
ZL(2)
T
T
115kV Open
13.8kV (0) 13.8kV
Open ZG(0) ZT(0) ZM
ZH(0) ZM(0)
ZG(0)
Sequence + T
T
PSE.com // GeneralPAC.com
3 Phase Fault Big Picture 1 of 1
PSE.com // GeneralPAC.com
1LG Fault Big Picture 1 of 1
PSE.com // GeneralPAC.com
LL Fault Big Picture 1 of 1
PSE.com // GeneralPAC.com
Questions?