Differential Air Pressure Switch
Technical Data
Medium Air and neutral gases
Pressure Range 0.2 … 50 mbar
Tolerable overload on one side 75 mbar at –30 … 75 °C
50 mbar at –30 … 85 °C
Repeatability 0.2 … 3 mbar ±0.025 mbar
0.5 … 5 mbar ±0.05 mbar
1 … 10 mbar ±0.05 mbar
5 … 20 mbar ±0.05 mbar
10 … 50 mbar ±0.15 mbar
Switching Load Resistive Load 5 A at 250 Vac
4 A at 30 Vdc
Inductive 0.8 A at 250 Vac
0.7 A at 30 Vdc
Materials in contact with the medium Case: PC 10% GF
Cover: PC
Diaphragm: Silicone LSR
tempered 200 °C, free of gas emissions
Temperature Medium and ambiance –30 … +85 °C
Storage –40 … +85 °C
Service life Mechanical > 106 switching cycles
Electrical connection Screw terminals or AMP connectors 6.3 mm or 4.8 mm accord-
ing to DIN 46244
Cable gland PG11 with cable strain relief
Protection standard Without Cover IP 00
With Cover IP 54
Pressure connections Pipe ø 6.2 mm
Adapter inside thread G1/8
2
Field Devices Europe SPD910
Ordering Information
TAC Item Number Item Reference Description Replaces
004701090 SPD910-2000Pa Switch Pres Air SPD910-2000Pa –
004701080 SPD910-1000Pa Switch Pres Air SPD910-1000Pa –
004701070 SPD910-500Pa Switch Pres Air SPD910-500Pa SPD900-600Pa
004701060 SPD910-300Pa Switch Pres Air SPD910-300Pa SPD900-200Pa
Dimensions
Fig. 1
Flow area
1)
Fig. 2
Flow area
Function
The pressure switch has two separate pressure
chambers, each with its own connection. The switch
operates when the setpoint is either exceeded or not
reached.
Vacuum Monitoring
Connect the pressure switch via P2. Do not connect
P1. Leave P1 open. Pake sure that dirt can not get
into P1.
into P2.
Filter Monitoring
Connect P1 before the filter and P2 after it.
Fan Monitoring
Connect P1 after the fan (in blowing direction) and
P2 before the fan.