Name of work :- Supply, installation, testing commissioning of Air handling Unit of 8000 CFM x 2 Nos capacity at Lecture Hall (L-
5 & 6) with associated works.

Name of Agency
S.No. DISCRIPTION QTY. Unit RATE Rs. AMOUNT Rs.
EQUIPMENT & PIPING
DOUBLE SKIN AIR HANDLING UNITS
AIR HANDLERS UNITS
1 Supply, Installation, Testing and Commissioning of double skin sheet
metal construction horizontal floor mounted air handling units with
50 mm thick injected PUF of density not less than 40Kg/CuM.The
air handling units shall be complete with synthetic fibre filters (EU-
4) , coil section with multirows deep chilled water cooling
coil of copper tube and aluminium fins construction, fan
section complete with backward curved DIDW centrifugal fan ,
belt drive package, VFD compatible variable speed squirrel cage
induction motor (IE-3), stainless steel drain pan , manually
operated supply air damper (AL) and vibration isolation pads all
complete as per specifications.AHUs shall be selected for a maximum
face velocity of 500 FPM (2.5 MPS)and as per schedule of air handling
units under appendix VIII. Fan outlet velocity shall not exceed 1800
FPM (9.1 MPS).

a) 8000 CFM, 6Rows, static pressure 60 mmwg, 2.00 Nos. 0.00


2 Supply, Installation,Testing and Commissioning of variable frequency
drives for following Air Handling Units.Variable frequency drives
shall be provided with necessary temperature sensors and
transmitters complete with control wiring in all respect as required and
as per specs. The drives shall be suitable for the following
motor rating. VFDs shall be housed in the AHU electrical Panels.

a) 3.7- 4.0 KW (FC-102 Series) danfoss or equivalent. 2.00 Nos. 0.00


3 Supplying & laying , testing & commissioning mild steel ' C ' class pipe of
size as mentioned below on exposed surface / underground with
fabrication of bends, tees, reducers, ( brick masonry block & wooden
support for underground / MS angle- clamp & wooden support for
exposed surface ) alongwith priming coat of steel primer as per
standard specification

a) 100 mm 5.00 Mtr 0.00


b) 80 mm 5.00 Mtr 0.00
c) 65 mm 15.00 Mtr 0.00
d) 50 mm 10.00 Mtr 0.00
e) 32 mm 3.00 Mtr 0.00
f) 25 mm 5.00 Mtr 0.00
4 Supplying & fixing, insulation on existing pipe on exposed surface /
underground of following sizes with 50 mm thick thermocole
( polystrene) pipe section alongwith hessian cloth, wiremesh, bitumen,
& cement - sand plaster, painting two or more coat to give even shade
after applying one coat of ordinary paint etc complete as required.

a) 100 mm 5.00 Mtr 0.00


b) 80 mm 5.00 Mtr 0.00
c) 65 mm 15.00 Mtr 0.00
d) 50 mm 10.00 Mtr 0.00
e) 32 mm 3.00 Mtr 0.00
f) 25 mm 5.00 Mtr 0.00
5 Supplying, laying/ fixing, testing and commissioning of G.I 'B' class pipe
with 19 mm nitrile insulation of following sizes for drain water piping
on surface / underground (including fabrication of bends, tees,
reducers) with suppport and fittings as per standard specification
complete as required.

a) 50 mm 10.00 Mtr 0.00


b) 32 mm 10.00 Mtr 0.00
6 SITC of butterfly valves CI body with SS Disc Nitrile Rubber Seal & O-
Ring PN 16 pressure rating for chilled water with hand lever operated
including nut, bolt, flanges, gasket as kind of existing pipe, painting with
enamel etc. complete as reqd.

a) 65 mm 2.00 No. 0.00


b) 50 mm 2.00 No. 0.00
7 Y - STRAINER of Ductile CI Body flanged ends with stainless steel
strainer forchilled / hot water circulation as specified.

a) 65 mm 1.00 No. 0.00


b) 50 mm 1.00 No. 0.00
8 Supply and fixing of ss ball valve of following size with socket and nipple
of approved make or equivalent complete as required.
a) 25 mm 4.00 Nos. 0.00
9 Supply and fixing industrial type thermometer of proportioning length 4.00 Nos 0.00
with adjustable angle, direct reading including thermowell socket.
Thermometer shall be suitable to read water temperature of range 0°C
to 50°C completed as required.

10 Providing and fixing 0-150 PSIG industrial type pressure gauge in 4.00 Nos 0.00
position of 65/100 mm dia with petcock valves (gun metal / brass)
complete with pressure snobber, nipple etc complete as required.

11 Cutting, dismantling and removing old damaged/defective insulation of


thermocole insulation (i.e.- hessian cloth, wire mesh, send, cement,
plaster) from chilled water pipe line of following size, cleaning of pipe
and shifting the waste material up to desired location as reqd.

a) 20 mm to 100 mm dia 5.00 Mtr 0.00


12 Cutting and dismantling of damaged/defective MS pipe of following size
(on surface/recessed/underground ) i/c shifting to sectional store
complete as required.
a) 20 mm to 100 mm dia 5.00 Mtr 0.00
AIR DISTRUBUTION & INSULATION
13 Supplying, fabricating, installing and testing of GI sheet metal fabricated
ducts complete with supports Vanes, dampers. Links levers and
quadrants etc. as per specification and drawings. The flanges shall be of
hot dip galvanized. The rates shall include.

a) 22 gauge 40.00 sqm 0.00


b) 24 Gauge 100.00 sqm 0.00
14 Supplying and fixing of following thickness duly laminated aluminum foil
of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing
duct after applying suitable adhesive for Nitrile rubber. The joints shall
be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber
tape insulation complete as per specifications and as required.

a) 19 mm thick 150.00 SqM 0.00


15 Providing & fixing of accoustic insulation with open cell nitral rubber
supersilence (self adhesive) for AHU room of following thickness, on
existing surface with Adhesive/ dentrite etc. complete as required. (As
per specification)

a) 25 mm thick 40.00 SqM 0.00


b) 15 mm thick 40.00 SqM 0.00
16 Supply & Application of acoustic lining/ internal thermal insulation of
supply/return air ducting with fibre glass insulation as per the
specifications and drawings.

a) 25 mm thick 24.00 sqm 0.00


17 Supply, Installation , Testing and Commissioning of smoke cum fire
dampers of at least 90-120 minutes fire rating as per the approved
shop drawings and specifications. Interlocking of fire dampers using
copper control wiring shall be affected as required.

a) Bare fire dampers 1.20 SqM 0.00


18 Supply, Installation, Testing & Commissioning of smoke cum fire
dampers of at least 90 minutes fire rating as per the approved shop
drawings and specifications. Interlocking of fire dampers using copper
control wiring shall be affected as required.

a) Actuator with control panel, temperature sensor & spring return action 2.00 No. 0.00
and suitable for 10-12 NM Torque.
19 Supply, installation, testing and commissioning of powder coated 2.00 Sqm 0.00
Aluminium extruded liner multislot type HIT & MIS Diffusser with
damper as specification & the sizes will be as per schedules and
drawing.

20 Supply, fixing, testing & commissioning of supply air diffusers suitable 2.00 sqm 0.00
for fixing Grid/Gypsum ceiling of power coated aluminium with
aluminium control dampers with anti smudge ring & removable core.
21 Supplying, fixing, testing commissioning of return air diffusers of 2.00 sqm 0.00
powder coated aluminium without volume control dampers with anti
smudge ring & removable core…

22 Dismantling and removing of existing old ducts of any size i/c removing 40.00 SQM 0.00
of hangers, flanges, valve etc. as reqd.
23 Supply, installation, testing and commissioning of GI volume control 1.00 SqM 0.00
duct damper complete with neoprene rubber gaskets, nuts, bolts,
screws linkages, flanges etc., as per specifications.
24 Supply,Installation, Testing and Balancing of spigots factory fabricated
out of galvanised steel sheet of different sizes to facilitate flexible duct
connection.
a. 200mm dia 4.00 No. 0.00
25 Supply, Installation, Testing and Commissioning of pre-insulated factory
fabricated flexible ducts inner as well as outer skin constructed out of
reinforced aluminium foil as per the specifications. Ducts shall be of
following sizes :
a. 200mm dia 4.00 RM 0.00
26 Supply, installation, testing and commissioning of factory fabricated LP
Plenum for Multislot diffuser for supply air duly fitted on G.I Frame with
nut, bolt and washer between diffuser and flexible duct etc, complete
as required.
a) 800 X 250 X 250 mm 4.00 Nos. 0.00
POWER & CONTROL WIRING
27 S & Laying of one no. PVC insulated copper conductor un-armoured
control cable of 1.1 kV grade of following size and core.
a) 4 x 6 sqmm (on surface) 15.00 Mtr 0.00
28 Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level 15.00 Mtr 0.00
for conductor earth electrode, including connection/ termination with
GI thimble etc. as required.
29 Supply, installation, testing & commissoning of wall mounted cubicle
type electrical panels including system control wiring with incoming,
outgoing feeders as described below and as per specifications. AHU
panel casing shall be large enough to accommodate variable frequency
drives. VFDs have been accounted for seperately under equipment
portion schedule of quantities.

Panel-A (VFD PANEL)


Location : AHU Room
a 16 A TP MCB for 3.7-4.0 Kw motor -01 set.

Digital type voltmeter (0-500) V, digital type Ammeter, selector


b switches, RYB LED type indication lights --01 set.
Auto-manual type selector switch to facilitate auto start of AHU after
c toration of power.
Control wiring & safety circuit as required with start-stop PB's stayput 2.00 No. 0.00
or lockable type and tow sets of LED type ON OFF indication lights AHU
d panel as described above.

CIVIL ITEMS
30 Demolishing brick work manually/ by mechanical means including
stacking of serviceable material and disposal of unserviceable material
within 50 metres lead as per direction of Engineer-in-charge.

a) In cement mortar 4.00 Cum 0.00


31 Providing and fixing double scaffolding system (cup lock type) on the 200.00 SqM 0.00
exterior side, up to seven story height made with 40 mm dia M.S. tube
1.5 m centre to centre, horizontal & vertical tubes joining with cup &
lock system with M.S. tubes, M.S. tube challies, M.S. clamps and M.S.
staircase system in the scaffolding for working platform etc. and
maintaining it in a serviceable condition for the required duration as
approved and removing it there after .The scaffolding system shall be
stiffened with bracings, runners, connection with the building etc
wherever required for inspection of work at required locations with
essential safety features for the workmen etc. complete as per
directions and approval of Engineer-in-charge .The elevational area of
the scaffolding shall be measured for payment purpose .The payment
will be made once irrespective of duration of scaffolding. Note: - This
item to be used for maintenance work judicially, necessary deduction
for scaffolding in the existing item to be done.

Sub Total 0.00


32 Buy Back Cost of Old AHU including dismantling removing and taken 2.00 No. 0.00
away from side (except motor).3 phase Electric Motor will be shifted to
the sectional store by the contractor.

Total 0.00