Name of work :- Supply, installation, testing commissioning of Air handling Unit of 8000 CFM x 2 Nos capacity at Lecture Hall (L-
5 & 6) with associated works.
Name of Agency
S.No. DISCRIPTION QTY. Unit RATE Rs. AMOUNT Rs.
EQUIPMENT & PIPING
DOUBLE SKIN AIR HANDLING UNITS
AIR HANDLERS UNITS
1 Supply, Installation, Testing and Commissioning of double skin sheet
metal construction horizontal floor mounted air handling units with
50 mm thick injected PUF of density not less than 40Kg/CuM.The
air handling units shall be complete with synthetic fibre filters (EU-
4) , coil section with multirows deep chilled water cooling
coil of copper tube and aluminium fins construction, fan
section complete with backward curved DIDW centrifugal fan ,
belt drive package, VFD compatible variable speed squirrel cage
induction motor (IE-3), stainless steel drain pan , manually
operated supply air damper (AL) and vibration isolation pads all
complete as per specifications.AHUs shall be selected for a maximum
face velocity of 500 FPM (2.5 MPS)and as per schedule of air handling
units under appendix VIII. Fan outlet velocity shall not exceed 1800
FPM (9.1 MPS).
10 Providing and fixing 0-150 PSIG industrial type pressure gauge in 4.00 Nos 0.00
position of 65/100 mm dia with petcock valves (gun metal / brass)
complete with pressure snobber, nipple etc complete as required.
a) Actuator with control panel, temperature sensor & spring return action 2.00 No. 0.00
and suitable for 10-12 NM Torque.
19 Supply, installation, testing and commissioning of powder coated 2.00 Sqm 0.00
Aluminium extruded liner multislot type HIT & MIS Diffusser with
damper as specification & the sizes will be as per schedules and
drawing.
20 Supply, fixing, testing & commissioning of supply air diffusers suitable 2.00 sqm 0.00
for fixing Grid/Gypsum ceiling of power coated aluminium with
aluminium control dampers with anti smudge ring & removable core.
21 Supplying, fixing, testing commissioning of return air diffusers of 2.00 sqm 0.00
powder coated aluminium without volume control dampers with anti
smudge ring & removable core…
22 Dismantling and removing of existing old ducts of any size i/c removing 40.00 SQM 0.00
of hangers, flanges, valve etc. as reqd.
23 Supply, installation, testing and commissioning of GI volume control 1.00 SqM 0.00
duct damper complete with neoprene rubber gaskets, nuts, bolts,
screws linkages, flanges etc., as per specifications.
24 Supply,Installation, Testing and Balancing of spigots factory fabricated
out of galvanised steel sheet of different sizes to facilitate flexible duct
connection.
a. 200mm dia 4.00 No. 0.00
25 Supply, Installation, Testing and Commissioning of pre-insulated factory
fabricated flexible ducts inner as well as outer skin constructed out of
reinforced aluminium foil as per the specifications. Ducts shall be of
following sizes :
a. 200mm dia 4.00 RM 0.00
26 Supply, installation, testing and commissioning of factory fabricated LP
Plenum for Multislot diffuser for supply air duly fitted on G.I Frame with
nut, bolt and washer between diffuser and flexible duct etc, complete
as required.
a) 800 X 250 X 250 mm 4.00 Nos. 0.00
POWER & CONTROL WIRING
27 S & Laying of one no. PVC insulated copper conductor un-armoured
control cable of 1.1 kV grade of following size and core.
a) 4 x 6 sqmm (on surface) 15.00 Mtr 0.00
28 Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level 15.00 Mtr 0.00
for conductor earth electrode, including connection/ termination with
GI thimble etc. as required.
29 Supply, installation, testing & commissoning of wall mounted cubicle
type electrical panels including system control wiring with incoming,
outgoing feeders as described below and as per specifications. AHU
panel casing shall be large enough to accommodate variable frequency
drives. VFDs have been accounted for seperately under equipment
portion schedule of quantities.
CIVIL ITEMS
30 Demolishing brick work manually/ by mechanical means including
stacking of serviceable material and disposal of unserviceable material
within 50 metres lead as per direction of Engineer-in-charge.
Total 0.00
Notes:- The above work may also have to be executed during night shift from 6:00 PM to 6:00 AM in addition to normal working hours in
case of requirement during running of classes (if required).