05 Setpoint Channel and Closed-Loop Control en
05 Setpoint Channel and Closed-Loop Control en
2
Setpoint channel .............................................................................................................................. 3
Setpoint source ................................................................................................................................ 4
Limitations ....................................................................................................................................... 9
Ramp-function generator .................................................................................................................. 10
Control modes ................................................................................................................................. 11
Open-loop control modes ................................................................................................................. 13
Speed control / Vector control .......................................................................................................... 15
Induction motor ................................................................................................................................ 17
Exercises ......................................................................................................................................... 23
Exercise 1: Setpoint source .............................................................................................................. 24
Exercise 2: Setpoint channel ............................................................................................................ 27
Macro P0015 Parameter P0015 serves to automate and thereby facilitate commissioning
through execution of a corresponding macro. When a selected macro is
executed, the programmed settings are applied and become effective.
The command sources, setpoint sources and outputs signals are pre-assigned
automatically. Different macros can be selected depending on the application
and requirements.
Note You can define the configuration of the command and setpoint sources either
manually or using parameter P0015. The I/O configuration is preassigned via
macros so that no further settings are necessary. A range of different settings
are possible depending on the Control Unit used. Detailed information is
provided in the Operating Instructions.
Scaling The scaling defines the percentage for the input signal, e.g. 0 to 10 V
corresponding to 0 to 100 %.
As a speed setpoint, the percentage refers to the reference speed (P2000) that
is defined automatically during commissioning as a function of the motor speed,
e.g. 4-pole motor => P2000 = 1500 rpm (synchronous speed)
Smoothing To smooth temporary variations in the measured value at the analog input, you
can specify a time constant. The larger the smoothing time constant, the slower
the response of the analog input to changes in the measured value.
Setpoint higher You can connect the source for increasing the setpoint of the motor
potentiometer here.
Setpoint lower You can connect the source for reducing the setpoint of the motor
potentiometer here.
Maximum value Enter the maximum value of the drive speed here. Changing the maximum
value affects the ramp-function generator, the limits and the programmable V/f
characteristic.
Parameters The fixed setpoints are defined by means of parameters P1001 to P1015 and
can be selected or combined by means of binector inputs P1020 to P1023.
Output value The effective fixed setpoint is available via the connector output r1024.
If this is to be used as the setpoint source, then macro parameter P0015 must
be changed, or the connector output r1024 must be connected to the main
setpoint P1070 or the additional setpoint P1075.
Scaling Defines the source from which the scaling of the main setpoint is read.
Scaling Defines the source from which the scaling of the additional setpoint is read.
Direction reversal Defines the source to initiate a direction reversal in the setpoint channel after
reaching the end point.
Block negative
direction of rotation Defines the source to block a negative direction of rotation.
Minimum limitation Here you can enter the permissible minimum speed. This speed is not
undershot during operation. The parameter value is valid for both motor
directions of rotation. In exceptional cases, the motor can operate below this
value (e.g. when reversing).
Maximum limitation This value serves as limit for the controller. This is the maximum speed value
the motor should achieve. A modification of this value affects the settings for the
controller and the ramp-function generator.
There are other limitation variants, i.e. an individual fixed limit can be specified
for the negative and the positive direction of rotation.
Typical times Depending on the moment of inertia of the driven mechanics, the ramp-up and
ramp-down times may vary significantly. For large fan drives, for example, times
between 30 and 120 seconds must be provided.
Resistance The motor primarily provides an inductive resistance. If the frequency of the
current is rising, the resistance increases too. A higher voltage is now called for,
even though the current flow is the same.
Ohmic resistance The ohmic resistance is also taken into account in the closed-loop control. It
only occurs distinctly at low output frequencies. This is reflected in the control,
by an increase in the V/f characteristic in the range from 0 to 5 Hz
approximately.
These open-loop and closed-loop control technologies differ from each other
both in their ability to control and regarding their technical complexity. Which
technology to use depends on the requirements relating to a specific
application.
Applications V/f control is generally used for simple applications (e.g. pumps and fans).
Vector control is preferred for demanding applications (e.g. winding machines)
where good control regarding speed and torque and good behavior in an
imperfect environment is required.
If these requirements also lie in the range from 0 Hz to around 1 Hz, then the
precision of the speed/torque is not sufficient without an encoder. In this case,
vector control with speed feedback must be used.
Freely programmable The relationship between speed and voltage is defined by the user.
Compensation The slip compensation can be used to compensate this behavior of the
induction motor. Here the load-related speed reduction is compensated by
increasing the inverter output frequency.
Sensorless Speed control is possible without directly measuring the motor speed and is
therefore also called sensorless vector control (SLVC).
Sequence The sequence in which this is carried out is also important as basic
commissioning delivers output data for the motor model and the motor
identification specifies these.
Stator The stator consists of punched sheet metal, layered to produce the round outer
shape of the motor. There are slots on the inside to accommodate the windings.
Rotor The rotor is also made of punched sheets. These sheets produce continuous,
rod-like hollow cavities when placed one on top of the other. These cavities are
cast in aluminum and then form the current-carrying rods.
For a short-circuit rotor, the short-circuit rings are also cast in aluminum at both
ends. Ultimately, current flows through the aluminum; the sheet serves to
conduct the magnetic field lines and for mechanical installation.
In the case of high-efficiency motors, the aluminum is partially or wholly
replaced by copper.
Benefit For control-related reasons, you are strongly advised to carry out motor data
identification because the equivalent circuit diagram data, motor cable
resistance, IGBT forward voltage and compensation for the IGBT lockout times
can only be estimated if the data on the type plate is used.
The stator resistance, for example is very important for the stability of vector
control and for the voltage boost in the V/f characteristic.
Motor data identification is essential if long supply cables or third-party motors
are used.
Note Basic commissioning must have been completed before the motor data
identification is selected.
Selecting measurements
yourself You should only select the measurement in the list manually if you are an
experienced user. This allows you to repeat a measurement, for example.
Task Test the diverse options for adjusting the analog input to the system!
1. The entire speed setting rate range should be controlled with setpoint of 2 to
5 V. For this, adjust the scaling of the analog input used
>> G120_ > Parameter > Input/outputs > Analog inputs
2. Test the behavior.
PPPPPPPPPPPPPPPPPPPPPPPPPPPPPP
PPPPPPPPPPPPPPPPPPPPPPPPPPPPPP
PPPPPPPPPPPPPPPPPPPPPPPPPPPPPP
PPPPPPPPPPPPPPPPPPPPPPPPPPPPPP
7. Now the drive should restart with the previous speed.
What setting is required?
PPPPPPPPPPPPPPPPPPPPPPPPPPPPPP
8. Test this saving of the motor potentiometer setpoint.
AI 0 = min:PPPPPPPPPPPPPPPPPrpm
AI 0 = max:PPPPPPPPPPPPPPPPPrpm
in this example (fmin=10 Hz, fSync=50 Hz, nSync=1500 rpm, since 4-pole):
Note: If the rated data of your training device are different to the above, please
calculate nmin accordingly.
Alternatively, fmin=10 Hz can be taken from the table below:
2-pole: nmin = 600 rpm
4-pole: nmin = 300 rpm
6-pole: nmin = 200 rpm
8-pole: nmin = 150 rpm
3. The analog input now has an invalid setting range. Change the scaling so
that the entire setting range is used:
>> G120_ > Inputs/outputs > Analog inputs
Here, please consider the parameterized minimum and maximum values in
relation to the reference speed (1500 rpm, p2000)
4. Test the new setting range.
PPPPPPPPPPPPPPPPPPPPPPPPPPPPPP
PPPPPPPPPPPPPPPPPPPPPPPPPPPPPP
PPPPPPPPPPPPPPPPPPPPPPPPPPPPPP