The document provides specifications for replacing pressure reducing de-superheating (PRDS) and quench water valves. It specifies that the vendor must quote a complete PRDS valve system with pneumatic actuator and a complete quench water valve with pneumatic actuator. The distance between the control room and valves is approximately 650 meters. The plant environment is classified as hazardous and all equipment must be suitable for tropical conditions and resistant to chemicals present. Documentation of testing and certifications are required to be provided along with the valves.
The document provides specifications for replacing pressure reducing de-superheating (PRDS) and quench water valves. It specifies that the vendor must quote a complete PRDS valve system with pneumatic actuator and a complete quench water valve with pneumatic actuator. The distance between the control room and valves is approximately 650 meters. The plant environment is classified as hazardous and all equipment must be suitable for tropical conditions and resistant to chemicals present. Documentation of testing and certifications are required to be provided along with the valves.
The document provides specifications for replacing pressure reducing de-superheating (PRDS) and quench water valves. It specifies that the vendor must quote a complete PRDS valve system with pneumatic actuator and a complete quench water valve with pneumatic actuator. The distance between the control room and valves is approximately 650 meters. The plant environment is classified as hazardous and all equipment must be suitable for tropical conditions and resistant to chemicals present. Documentation of testing and certifications are required to be provided along with the valves.
The document provides specifications for replacing pressure reducing de-superheating (PRDS) and quench water valves. It specifies that the vendor must quote a complete PRDS valve system with pneumatic actuator and a complete quench water valve with pneumatic actuator. The distance between the control room and valves is approximately 650 meters. The plant environment is classified as hazardous and all equipment must be suitable for tropical conditions and resistant to chemicals present. Documentation of testing and certifications are required to be provided along with the valves.
Download as DOCX, PDF, TXT or read online from Scribd
Download as docx, pdf, or txt
You are on page 1of 6
GENERAL NOTES ON PRDS & QUENCH WATER VALVES
The Vendor shall quote complete Pressure reducing De- Superheating
valve (PRDS Valve) with piston type pneumatic actuator, complete quench water valve with pneumatic actuator & including all the accessories of both the valves to make the system complete as per the specification & service requirement. The vendor shall also quote for consumables, commissioning & two years operation spares. The distance between the Control room & the Valves (PRDS Valve & Quench Water valve) is 650 meter approx. In addition to the Specifications, given herewith the following shall also apply- The plant is classified as Hazardous area under Zone 2, Group IIC, T3 as per IEC 79 or equivalent. All field mounted instruments/equipment shall be suitable for mounting, function and storage in tropical climate as described below: .Climate Design Condition : Tropical with monsoon rain. Temp. range :-1.5 Deg C to 50 Deg C (85 deg C max surface In sun) Temperature range for actuator accessories: Suitable form service / surrounnding temperature. Party to specify, Relative Humidity :100% All the electric/Electronic equipment shall be tropicalized & immune to RF & EM Interferences. RFI & EMI tolerance limits must be indicated in the offer. Copper/Copper alloys are not to be used for tubing, valves, fittings etc. or on any part of an instrument exposed to the atmosphere or the medium as ammonia vapours will be present occasionally. Also valves accessories in contact with plant atmosphere shall be resistant to surrounding atmosphere containing Co2, Ammonia, Urea, Urea vapors. Fitting, tubing for pneumatic connections & bolts, fixing screws for actuators, SS304/316 shall be used. Field mounted instruments shall be installed intrinsically safe having ExibliCT3 Certificate & IP55 enclosures. Solenoids valves or servo valves shall be Ex-proof to meet Hazardous area classification as given above. Termination shall be arranged inside junction Box. Signal shall be segregated according to the voltage level. Air tubing shall be SS304/316. Pre dispatch inspection: Vendor shall inform readiness of material one week in advance for Inspection. However waiver of pre dispatch inspection by M/S N.F.L shall be intimated to Vendor. Party shall confirm the submission of following Test certificates in original duly stamped by Third Party inspection agency: The valve shall be in accordance with ANSI B 16.34 standard and indicated in the specification. Party shall furnish quality assurance plan along with their quotation. GENERAL NOTES ON PROS & QUENCH WATER VALVES
The Vendor shall quote complete Pressure reducing De- Superheating
valve (PRDS Valve) with piston type pneumatic actuator, complete quench water valve with pneumatic actuator & including all the accessories of both the valves to make the system complete as per the specification & service requirement. The vendor shall also quote for consumables, commissioning & two years operational Spares. The distance between the Control room & the Valves (PROS Valve & Quench water valve) is 650 meter approx. In addition to the Specifications, given herewith the following shall also apply. The plant is classified as Hazardous area under Zone 2, Group IC,T3 as per IEC 79 or equivalent. All field mounted instruments/equipment shall be suitable for mounting, functioning and storage in tropical climate as described below o Climate Design Condition : Tropical with monsoon rain. o Temp. range : +-1.5 Deg C to 50 Deg C (85 deg C max surface In sun) o Temperature range for actuator accessories: Suitable form service /surrounding temperature. Party to specify. o Relative Humidity :100% All the electric/Electronic equipment shall be tropicalized & immune to RF & EM Interferences. RFI & EMI tolerance limits must be indicated in the offer. Copper/Copper alloys are not to be used for tubing, valves, fittings etc or on any part of an instrument exposed to the atmosphere or the medium as ammonia vapours will be present occasionally. Also valves accessories in contact with plant atmosphere shall be resistant to surrounding atmosphere containing Co2, Ammonia, Urea, Urea vapors. Fitting, tubing for pneumatic connections & bolts, fixing screws for actuators, SS304/316 shall be used. Field mounted instruments shall be installed intrinsically safe having ExibliCT3 Certificate & IP55 enclosures. Solenoids valves or servo valves shall be Ex-proof to meet Hazardous area classification given above. Termination shall be arranged inside junction Box. Signal shall be segregated according to the voltage level. Air tubing shall be SS304/316. Pre dispatch inspection: Vendor shall inform readiness of material one week in advance for Inspection. However waiver of pre dispatch inspection by M/S N.FL shall be intimated to Vendor. Party shall confirm the submission of following Test certificates in original duly stamped by Third Party inspection agency: The valve shall be in accordance with ANSI 16.34 standard and with the pressure rating indicated in the specification. Party shall furnish quality assurance plan along with their quotation It is the responsibility of the Vendor to ensure that the valves are manufactured and tested in accordance with Indian Boiler regulation Act-1950 and this is certified by supplying the certificate form IIIC with each valve including all pressure bearing parts of instruments to be mounted on Boiler feed water & steam systems in complete accordance with above mentioned boiler regulations. Inspection as per requirement of technical scope of supply will be done by third party (Lloyds or Beuro or TUV), Inspection charges shall be included in quoted price. NFL representatives may also inspect the testing if required. Certificate of conformity. Material test certificate for body, Bonnet, trim. Yoke, actuator, studs & nuts, flanges, Branches and all internal indicating chemical composition, heat treatment, Mechanical properties etc. Ultrasonic examination as per ANSI B16:34 annex C for Body, Bonnet, Flanges and Branches etc. with acceptance as per ANSI B16:34 Annex-E Dye penetrate test as per ANSI B16:34 for Butt welded ends after Hydrostatic. WPS, WPQ, and PQR for all weld joints of valves. Magnetic particle examination of all welds joints as per ASME V Article 7 and acceptance as per ASME VIII Div. 1 Appendix 6. Radiographic examinations of all welds joints as per ASME V article 2 and acceptance as per ASME VIII Div.1 UW51 Ultrasonic examinations of all welds joints as per ASME V article 7 and acceptance as per ASME VIII Div. 1 Appendix 6. Post weld heat treatment record of all welds joints. Hydrostatic of valve body using water as per ANSI B16:34 Seat leakage of valves as per NIT requirement. The steam conversion valve 36-PV-01/3 shall be regarded as "Special class" valve, even if this may not be required according to the temperature pressure tables given in ANSI B16-1 Notes The offered PRDS valve with accessories should be compatible to direct replacement of existing PRDS valve and inlet, outlet, water inlet end connections should be suitable to retrofit with existing line with end connections. The details of end connections of exist in valve are given below: 1. Valve having Horizontal inlet connections, Horizontal water inlet end connections opposite to inlet end connection & bottom outlet end connection. 2. Distance from outlet end connection to center line of inlet end connection is 305 mm, Distance from outlet end connection to center line of water inlet end connection is 187 mm, Distance from inlet end connection to center line of outlet end connection is 305 mm, Distance from water inlet end connection to center line of outlet end connection is 406 mm, Distance form inlet end connection to water inlet end connection is 711 mm. The positive tolerances in End connections are acceptable. The offered quench valve with accessories should be compatible to direst replacement of existing quench valve and inlet & outlet end connections should be suitable to retrofit with existing line with end connections. The distance of inlet & outlet end connections of existing valve is 305 mm. The offer shall be complete with specific catalogue, GA Drawings, Schematic control functional drawings of actuator with accessories etc of offered valve indicating make & model no's as same is required for offer evaluation. All the deviation is to be clearly indicated. The supplier is to clarify in the offer that the following documents/Certificates shall be supplied along with the main supply- 1. Instruction, Operation & Maintenance manual for PRDS Valve, Quench valve & their accessories. 2. Documentations for checks performed during constructions, Hydrostatic body test and dye penetrate test etc. 3. Material & Workmanship guarantee / warranty certificates. 4. All the Bidders who are interested to submit the bid may visit the site to see the Actual valve installation conditions at site before submitting the quotations. The max. Pipe straight length available in upstream (inlet) of PROS valve is approx. 2.5 meters & max. Pipe straight length available in downstream (outlet) of PRDS valve is approx. 9.0 meters. This is for reference only. The max. Pipe straight length available in upstream (inlet) of Quench valve is approx. 1.0. meters & max. Pipe straight length available in downstream (outlet) of Quench valve is approx. 200 mm, This is for reference only.