DC12 100
DC12 100
Dimensions
Unit: mm Dimension: 328(L) ×172(W) ×222(H) Terminal F12
5
2
37
Terminal F5
F.V/Time 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
9.60V 320.7 226.9 181.4 112.7 65.00 38.89 26.88 22.03 18.03 12.42 10.50 5.78
10.0V 311.4 215.8 177.7 110.8 64.70 38.60 26.78 21.93 17.93 12.32 10.40 5.67
10.2V 302.2 208.2 174.9 109.8 64.10 38.31 26.57 21.83 17.82 12.22 10.30 5.57
10.5V 271.3 192.1 166.5 107.1 63.50 38.02 26.47 21.62 17.61 12.12 10.20 5.46
10.8V 244.9 175.2 153.5 102.4 62.00 37.33 25.75 21.11 17.29 11.92 10.10 5.36
11.1V 209.1 156.6 137.7 95.91 58.90 35.68 24.62 20.09 16.55 11.41 9.80 5.04
o
Constant Power Discharge Characteristics: W (25 C)
F.V/Time 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
9.60V 3317 2416 1996 1284 751.1 458.4 319.9 262.6 215.1 148.3 125.5 69.26
10.0V 3251 2342 1964 1269 749.3 456.0 320.0 262.3 214.6 147.6 124.7 68.06
10.2V 3214 2280 1941 1260 743.5 453.3 318.6 261.7 213.9 146.6 123.6 66.80
10.5V 2926 2123 1852 1230 736.8 450.0 317.4 259.3 211.3 145.4 122.4 65.54
10.8V 2665 1957 1712 1179 723.2 444.2 308.7 253.4 207.5 143.0 121.2 64.28
11.1V 2341 1770 1541 1108 692.3 427.7 295.4 241.1 198.6 136.9 117.6 60.50
100
120 Supplementary charge required
0℃ (Carry out supplementary charge
before use if 100% capacity is
100 80 requires)
Capacity (%)
10℃
Supplementary charge required
80 60
Capacity(%)
before use.
This supplementary charge will help
to recover the capacity and should
60 20℃ be made as early as possible.
100% 80% 50% 30% 15% 40 40℃ 30℃
D.O.D D.O.D D.O.D D.O.D D.O.D Supplementary charge may often
40 fail to recover the capacity.
The battery should never be left
20 standing till this state is reached
20
0
Supplementary charge and storage
2 4 6 8 10 12 14 16 18 20 22 24 guidelines
0 300 600 900 1200 1500 1800
Number of Cycle(Times) Storage Time (months)
15 120 0.24
13
Charge Volume
14 100 0.20
Charge Voltage Terminal Voltage (V)
12
Charge Voltage(V)
13 80 0.16
① Discharge
100%(0.05CA×20h) 11
0.05C
12 50%(0.05CA×10h) 60 0.12 0.16C 0.093C
② Charge 0.35C
Charge Voltage2.275V/C
Charge Current0.1CA 10
40 0.08 0.62C
11 ③ Temperature 25 ℃
3C 1C
10 20 0.04 9
Charge Current
0.6 1.2 3 6 12 30 1 2 5 10 20 24
9 0 0
0 2 4 6 8 10 12 14 16 18 20 24 28 min Hr
Charge Time (h) Discharge Time
Constant Voltage -0.2Cx2h+14.4-14.7Vx24h,Max. Current 0.3C ※ Effect of temperature on cycle charge voltage: -4mV/℃/Cell.
Constant Current -0.2Cx2h+0.1Cx7h+0.05Cx4h
※ There are a number of factors that will affect the length of cyclic service.
Fast -0.2Cx2h+0.3Cx3h