MAINTAINED/NON MAINTAINED ILLUMINATION SIGNS WITH GREEN LEDs

TECHNICAL CHARACTERISTICS (for LED MODULE Specs. see page 4)


MLD-28S/g MLD-34S/g MLD-44S/g
Mains voltage 220-240V AC/50-60Hz
Maximum power consumption 3W / 7.5VA 3W / 8VA
Battery (Ni-Cd) 3.6V/1Ah
Battery protection Overcharging and deep discharging protection
Recharging time 24h
Minimum emergency duration 3h
Light source intensity (Mains / Emerg) 18lm / 18lm 22lm / 18lm
Degrees of cover protection IP 40
Class of cover protection class II
Produced in accordance with EN 60598-1, EN 60598-2-1, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Operation temperature range 5 to 40 ο C
Relative humidity Up to 95%
External panel's dimensions 280x100mm 340x170mm 440x220mm
External dimensions (LxWxH) 305x25x155mm 350x25x205mm 465x25x275mm
Construction materials ABS/PC,Plexiglass,PVC
Typical weight 500gr. 800gr. 1160gr.
Guarantee 3 years (1 year for the battery)

Thank you for your trust in our product


Olympia Electronics - European manufacturer
GENERAL depending on the requirements of the installation.
These new sign illumination luminaires, use a new The package includes all the required materials for
technology, friendly to the environment , with high mounting on the wall or on the ceiling. The pages
illuminated L.E.D.s. L.E.D. technology has very low 2,3 and 4 show us the mounting methods.
power consumption. The edge illumination sign is used
as a maintained backup lighting with indications WARNING !!
symbols. Each package contains arrows stickers which 1. Read carefully this instruction manual.
are used to quickly design the required sign which is 2. Before service interrupt the mains power supply.
suitable for each occasion. 3. The device must be connected to the mains
Just place the sign on the figure which is designed on power supply through a fuse dependent by the total
the packages and stick the arrow. amount of the line’s power load.
Each model combines modern, aesthetics, together 4. It is suggested to check every month the
with functionality. The exit illumination signs are used in indication LED for battery charging, and by pushing
every public area where clear direction and good briefly the TEST button to check the emergency
appearance are important. circuit. The sign should light for a few seconds
powered by the battery and then, will turn to normal
NON MAINTAINED OPERATION operation. In the opposite condition contact the
By default the illumination sign operates as maintained. installer.
The device has a possibility to operate as non 5. Every six months, a full duration check should be
maintained. To change the maintained to non carried out by disconnecting the mains power
maintained operation follow the relative instructions on supply . Count the autonomous duration of the
page 6. All models must be permanently connected to luminaire and in case of no correspondence to
the mains power supply as shown on page 2. The stated emergency duration replace the battery. The
legend is screened on to a clear acrylic sheet which replacement of the battery must be done using parts
has the marking on the marking panel with the light that of the same type, by the manufacturer or by a
comes from the top of the luminaire and diffracts, giving competent person.
light to the marking panel. The luminaire has an 6. In case of inactive use for a period greater than 2
indication (CHARGE) for the charging of the battery months, disconnect the battery by pulling out the
and a (TEST) button to TEST the emergency circuit battery’s connector.
and the LEDs for good operation only when the 7. Replaced batteries must not be thrown into
luminaire is powered by the mains power supply. The trash bins. They must be returned to
unit must be mounted in a clearly visible area and can special battery disposal points. Do not
either be hung on a ceiling or mounted on a wall incinerate.

Page 1 from 6 922504400_09_028


MOUNTING METHODS

Preparation procedure Connection of the included terminal block


for ceiling mounting L
L
BROWN 230V AC
N BLUE N
Attention!!! Interrupt the mains power supply.

Hanging installation on
suspended ceilings using the
special mounting brackets 1. Open the pre-etched knock out and pass
contained in the package. the cable through.
2. Place the plastic part for mounting the sign.
3. Place the cable holding accessory and mount it by
tightening the screw with the included grommet.
4. Connect the wires to the included terminal block and place it
in the plastic mounting part.
5. Follow the procedure bellow (figure 1).

Ceiling Mounting
2

S1 3
MLD-28 S: 29,5cm
MLD-34 S: 35,7cm
MLD-44 S: 45,7cm 4

Hanging installation on
suspended ceilings using the Figure 1
special mounting brackets

1. Attention!!! Choose the installation area to insure that the mounting surface is appropriate for the
installation of the illumination sign.
2. Measure the space S according to the illumination sign’s type and drill the appropriate holes in the
ceiling for the installation of the included mounting plugs Nr 6.
3. Place the mounting plugs Nr 6 and mount the sign by tightening the included mounting screws.
4. Refit the plastic cover on each side.
5. Power the illumination sign and check the illumination sign’s operation.
Suspended ceiling mounting bases

A-1018/PL

A-1020/PL
Recessed mounted installation
on suspended ceilings using
440
the base type Α-1018/PL,
Α-1020/PL, Α-1021. 75 A-1021
Ø6

Page 2 from 6 922504400_09_028


Ceiling Mounting

MLD-28 S: 22cm
S2
MLD-34 S: 28cm
MLD-44 S: 37,5cm
5. Place the mounting accessories in the
wall and tighten the mounting screw.
1. Place the plastic mounting part

2. Tighten the screw.


3. Pass the cable in the canal.
4. Connect the wires to the included terminal block and place it
in the plastic mounting part.
6. Place the plastic cover.

OPTIONAL !!
When a triple core cable must be used, then follow the figures 2,3 bellow.

Figure 2 Electrical box


(Not included)
ELECTRICAL BOX INSTALLATION
1. Attention!!! Interrupt the mains power supply.
2. Perform the preparation procedure for ceiling mounting on
page 2 and exclude step 4.
3. Perform the procedure for ceiling mounting figure 1.
4. For the installation of the electrical box you may need to
open holes in the ceiling and at it’s cable entrances, for the
entrance of the power and illumination sign’s cables. Install the electrical box next to the sign so as to
cover the cable (figure 2).
5. After mounted the electrical box open the cover and perform the electrical connection according to
Figure 3. After the connection close the cover of the box.
6. Power the illumination sign and check the illumination sign’s operation.

Electrical
220-240V AC/50-60Hz

box
Use a certified electrical box 250V AC (IP40) to L
perform the electrical connection, with minimum GND
internal space 35x35x25mm to install the 3 pole
terminal block. In this box install a certified 3 pole N
BROWN
terminal block 250V AC/16A 2,5mm² providing
terminals to connect the live wire L, the neutral N
and the ground GND. To this terminal block is BLUE
connected the power cable with a cross section of Figure 3
1,5mm². Install the electrical box in an appropriate
area in the ceiling. Install securely the 3 pole
terminal block and perform the connection according to figure 3.

The electrical box and the 3 pole terminal block not included. Installation may require
advice from a qualified person.

Page 3 from 6 922504400_09_028


Wall Mounting
6 5. Place the mounting accessories in the wall
and screw the mounting screws

Flag mounted installation on


a wall using the special
mounting bracket contained 1. Open the pre-etched knock out and pass the cable
in the package. through.
2. Place the single mounting plastic part
3. Tighten the mounting screw.
4. Connect the wires to the included terminal block and
place it in the plastic mounting part.
6. After finishing the installation, secure the cable with a
suitable cable detention bracket (not included) to ensure
immobilization of the cable at a distance of no more than
5cm from the luminaire’s cable entry.

Wall in bottom view

Wall mounted installation 1. Open the pre-etched knock out and pass the
using the special mounting cable through.
brackets contained in the 2. Place the plastic part
package. 3. Place the cable holding accessory and mount it by
tightening the screw with the included grommet.
4. Connect the wires to the included terminal block and
place it in the plastic mounting part.
5. Place the mounting accessories in the wall
and tighten the mounting screw figure 1 step 3.
6. Place the plastic cover.

Electric connection and Eco Light dimensions in mm Packagecontents


Package contents
a
220-240V AC/50-60Hz

The package contains:


1. The illumination sign
60mm 2. The instructions manual
3. Plastic bag with supporting
MLD-28 : 305(a) x 95(b) materials.
b MLD-34 : 365(a) x 165(b)

L N MLD-44 : 465(a) x 215(b)

LED MODULE CHARACTERISTICS


MLD-28S/g MLD-34S/g MLD-44S/g
Manufacturer Olympia Electronics S.A.
Model Number 1702161 1802161 1902161
Voltage Range 12-14V DC
Nominal Power 980mW 975mW
Connections Fixed connection between main pcb and led module
Temperature (tc) 40 °C max. across the board

Page 4 from 6 922504400_09_028


BATTERY REPLACEMENT PROCESS
4 5 6

7 8 9

10 11 12

Before service interrupt the mains power supply.


1 Remove the plastic cover from each side. (figure 1, step 4).
2 Unfasten the mounting screws to unmount the illumination sign (figure 1, step 2).
3 You have to disconnect the power supply wires of the sign from the terminal block.
4 Unfasten the mounting screw of the bracket and remove it.
5 Unfasten the mounting screw (with the cable holding accessory) of the bracket and remove the
bracket.
6 Unfasten the screws without moving the marking panel.
7 Unfasten the screw and remove the marking panel.
8 Slide out the led strip with a flat blade screwdriver.
9 Pull carefully the led strip by holding it from the two sides as shown on the picture.
10 Remove the used battery and place a new one with the same type Α-939/ΗΤ with same cables
and connector.
11 Push carefully the led strip by holding it from the two sides as shown on the picture.
12 Push the led strip to face the edge of the plastic cover.
ATTENTION !!! Don’t apply force to the test button.
13 Refit the removed parts in steps 7,6,5 and 4.
WARNING!! Use a maximum torque of 0,25Νm to tighten the screws (step 6 & 7) and a maximum
torque of 0,6Νm to tighten the screws (step 4,5).
14 Mount the illumination sign with the mounting screws (figure 1, step 4).
15 Connect the power supply wires of the sign to the terminal block (step 3). Refit the plastic
cover (figure 1, step 5) and power the illumination sign.

NOTE!! After finishing the installation you must power the luminaire at least for 24 hours for
battery charging to perform the nominal autonomy.

Page 5 from 6 922504400_09_028


MAINTAINED TO NON MAINTAINED SELECTION CAPABILITY
Power on the device and press continuously the TEST button for 5 seconds, until the led strip
turns off. Release the button and after a short emergency test, the device operates as
non-maintained. If you want to restore the previous condition (maintained operation), press
continuously the TEST button for 10 seconds, until the led strip lights. Release the button and
after a short emergency test, the device operates as maintained illumination sign.

Troubleshooting
Trouble Solution
The battery has lost it’s energy
Wait at least for 1 hour for the battery to be charged.
The battery is not connected
1. The illumination sign does not light when the TEST
Attach the battery’s connector to the appropriate
button is pressed.
connector on the P.C.B.
The battery is inappropriate
Τhe battery must be replaced.
The battery has lost it’s energy
2. During the 6month autonomous check, the Wait at least for 24 hours for the battery to be fully
illumination sign does not light or has less autonomy charged.
than the nominal. The battery is inappropriate
Τhe battery must be replaced.
The illumination sign is adjusted to operate as
non-maintained
3. The illumination sign does not light in normal
Choose (if you must) to turn the operation to
operation.
maintained, according to relative paragraph in
page 6.
The battery has lost it’s energy
Wait at least for 24 hours for the battery to be fully
charged.
4. The illumination sign does not light during a mains The battery is not connected
failure. Attach the battery’s connector to the appropriate
connector on the P.C.B.
The battery is inappropriate
Τhe battery must be replaced.

The light source contained in this luminaire shall only be replaced by the manufacturer, or his
agent, or a similar qualified person.

NOTE! The light source is non-user replaceable.


ATTENTION!! If the external flexible cable or cord of this luminaire is damaged, it shall be exclusively
replaced by the manufacturer or his service agent or a similar qualified person in order to avoid a hazard.

WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty
is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which
accompanies each product. This warranty ceases to exist if the buyer does not follow the technical
instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods
provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully
agreed to them in writing. Products that have been damaged can be returned to the premises of our
company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
buyer the transportation cost.
HEAD OFFICE
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
[email protected]

Page 6 from 6 922504400_09_028