0% found this document useful (0 votes)
45 views

Assignment 03

This document contains 6 questions regarding refrigeration systems for an HVAC assignment. It includes diagrams of refrigeration cycles with single-stage and two-stage compression, with and without intercooling and flash gas removal. Students are asked to calculate parameters like compressor power requirements, refrigerating capacities, coefficient of performance, and rate of refrigerant compressed based on data provided for each system.

Uploaded by

MHK Zark
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views

Assignment 03

This document contains 6 questions regarding refrigeration systems for an HVAC assignment. It includes diagrams of refrigeration cycles with single-stage and two-stage compression, with and without intercooling and flash gas removal. Students are asked to calculate parameters like compressor power requirements, refrigerating capacities, coefficient of performance, and rate of refrigerant compressed based on data provided for each system.

Uploaded by

MHK Zark
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Department of Mechanical Engineering

National University of Technology


ME 4109 –Heating, Ventilation and Air Conditioning
Assignment 03
Submission Deadline: 18-12-2023 Total Marks: 60
[CLO-2, C-3, PLO-2]
Q.1. In a refrigerant 12 refrigeration system the capacity is 180 kW at a temperature of -30°C. The vapor from
the evaporator is pumped by one compressor to the condensing pressure of 1500 kPa. Later the system is
revised to a two-stage compression operating on the cycle shown in Figure 1 with intercooling but no removal
of flash gas at 600 kPa.

a) Calculate the power required by the single compressor in the original system.
b) Calculate the total power required by the two compressors in the revised system.

Figure 1 Intercooling system in Q.1.

Q.2. A refrigerant 12 system has a capacity of 180 kW at an evaporating temperature of -30°C when the
condensing pressure is 1500 kPa.

a) Compute the power requirement for a system with a single compressor.


b) Compute the total power required by the two compressors in the system shown in Figure 2 where there
is no intercooling but there is flash-gas removal at 600 kPa.

Page 1 of 5
Figure 2 Flash Gas Removal System in Q.2.

Q.3. A two-stage ammonia system using flash-gas removal and intercooling operates on the cycle shown in
Figure 3. The condensing temperature is 35°C. The saturation temperature of the intermediate-temperature
evaporator is 0° C, and its capacity is 150 kW. The satm.1tion temperature of the low-temperature evaporator
is -40° C, and its capacity is 250 kW. What is the rate of refrigerant compressed by the high-stage compressor?

Figure 3 Diagram for Q.3.


Page 2 of 5
Q.4. A two-stage refrigerant 22 system that uses flash-gas removal and intercooling serves a single low-
temperature evaporator, as in Figure 4. The evaporating temperature is -40 oC, and the condensing temperature
is 30 oC. The pumping capacities of the high- and low-stage compressors are shown in Fig. 5. What is

a) the refrigerating capacity of the system


b) the intermediate pressure

Figure 4 Diagram for Q.4.

Figure 5 Pumping capacity of low and high compressors of system in Q.4.

Q.5. In an NH3 refrigeration system installed in a cold store as shown in Figure 6, the evaporator provides 300
kW of refrigeration at -30°C. The system uses two-stage compression as shown in the figure, with intercooling
Page 3 of 5
and removal of flash gas. The condensing temperature is 35°C. Draw the cycle on a p-h diagram and calculate
the following:

a) The power required by the compressor.


b) The coefficient of performance.

Figure 6 Diagram for Q.5.

Q.6. A two-stage ammonia system designed for a fish freezing plant, uses flash gas removal and intercooling
operation (Figure 7). The condensing temperature is 35°C. The saturation temperature of the high-temperature
evaporator is 0°C and its capacity is 90 kW. The saturation temperature of the low-temperature evaporator is
-40°C and its capacity is 170 kW of refrigeration. Draw the cycle on a p-h diagram. Determine the following:

a) The rate of refrigerant compressed by the high-stage compressor


b) The power required by the compressors
c) The coefficient of performance.

Page 4 of 5
Figure 7 Diagram for Q.6.

Page 5 of 5

You might also like