Transmag (UK) Ltd manufactures single phase cast resin voltage transformers (VTs) for use in instrument control, metering, and protection applications in switchgear. The 420 series VTs have primary voltages up to 15.5kV and secondary voltages from 100√3 to 120√3V. They are designed to meet standards like BS EN 6044-2, ANSI-C57-13, and CAN3-C13. The VTs have a cast polyurethane or epoxy resin block construction and come with brass terminals and HV fuses. Various models and voltage ratios are available.

Uploaded by

Ari Mahita
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views3 pages

TMG420VT 2012

Transmag (UK) Ltd manufactures single phase cast resin voltage transformers (VTs) for use in instrument control, metering, and protection applications in switchgear. The 420 series VTs have primary voltages up to 15.5kV and secondary voltages from 100√3 to 120√3V. They are designed to meet standards like BS EN 6044-2, ANSI-C57-13, and CAN3-C13. The VTs have a cast polyurethane or epoxy resin block construction and come with brass terminals and HV fuses. Various models and voltage ratios are available.

Uploaded by

Ari Mahita
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Transmag (UK) Ltd

Cast Resin Voltage Transformers

420 Series TMG

Instrument Transformers Solu�on & Technology


Cast Resin Transformers

Introduc�on
Our 420 range of single phase voltage transformers with single or double fuse arrangements has been
designed for customers who prefer single phase configurations rather than our 3 phase monobloc cast-
ing. For switchgear applications in instrument control, metering and protection. Available with single
or double secondary windings for AC measurement of voltages between phase to ground or phase to
phase, with system voltages up to 15.5 KV.

Standards
Our units are designed to meet the requirements of BS EN 6044-2 BS7625, ANSI-C57-13, CAN3-C13
and AS 1675 standards and/or customers’ specific requirements.
All our units are ROHS compliant.

Construc�on
Cast polyurethane resin block complete with core and coils mounted onto a stainless steel base plate.
Comparative Tracking Index (CTI) of our polyurethane resin in volts >600 thus giving an assigned Per-
formance Level Category (PLC) of 0. Our units are also available cast in epoxy resin if required.
Cores are constructed from grain orientated silicon steel. Windings are in high grade copper double
coated with polyester. The units are fitted with brass M8 HV terminals and M6 brass LV terminals. HV
fuses are secured and mounted by 25mm spring clips. Dimensions are as per diagram.

Indoor voltage transformers with single or double secondary windings, system voltages up to 15.5KV.

Transmag (UK) Limited, Units 2 & 3, St Andrews, Bayly Works,


Great Barr Street, Birmingham, West Midlands, B9 4BB.
web: www.transmaguk.co.uk | email: [email protected] | tel: +44(0)121 753 4390 | fax: +44(0)121 773 9369
420 TMG Single Phase Cast Resin Voltage Transformers

Single phase, single pole V.T. with one H.V. protection fuse of 3.15A rating for measurement of voltages from phase to ground.

Technical Data

Connection: Line to Ground


Primary Voltage: 7.2 KV up to 15.5 KV
Secondary Voltage: 100 √3 to 120 √3 Volts
Frequency: 50/60 Hz
Rated Outputs: BSEN 30 VA, 100 VA, 200 VA, 300 VA, 200 VA, 200 VA
Accuracy Class: BSEN 0.2 0.5 1.0 3.0 3P 6P
Rated Outputs: ANSI W, X, M, Y, Z, ZZ
Accuracy Class: ANSI 0.3, 0.6, 1.2
Voltage Factor (RVF): 1.9 for 30 Secs
Insulation Level: 7.2/20/60 KV to 15.5/34/110 KV
Insulation Class: ‘E’
Ambient Temperature: -40 C to +70 C
Thermal Rating: 1500 VA @55 C Rise above 30 C ambient
Standards: BSEN 60044-2, ANSI C57-13 CAN3-C13 AS1675
Outline DRG: ID 1503 rev 4
Approx Weight: 38-48 Kgs

Other Voltages/Ratios are available upon request.

Selection Table

Model Number Drawing Number of Number of Connection RVF Standard


Number Secondaries Fuses
TMG-420S-7.2 FF1 ID. 1503 1 1 Line to Ground 1.9 for 30 Secs BSEN 60044-2
TMG-420S-7.2 FF2 ID. 1503 2 1 Line to Ground 1.9 for 30 Secs BSEN 60044-2
TMG-420S-10/12 FF1 ID. 1503 1 1 Line to Ground 1.9 for 30 Secs BSEN 60044-2
TMG-420S-10/12 FF2 ID. 1503 2 1 Line to Ground 1.9 for 30 Secs BSEN 60044-2
TMG-420S-13.8 FF1 ID. 1503 1 1 Line to Ground 1.9 for 30 Secs BSEN 60044-2
TMG-420S-13.8 FF2 ID. 1503 2 1 Line to Ground 1.9 for 30 Secs BSEN 60044-2
TMG-420S-14.4 FF1 ID. 1503 1 1 Line to Ground 1.9 for 30 Secs ANSI C57-13
TMG-420S-14.4 FF2 ID. 1503 2 1 Line to Ground 1.9 for 30 Secs ANSI C57-13
TMG-420S-15.5 FF1 ID. 1503 1 1 Line to Ground 1.9 for 30 Secs BSEN & ANSI
TMG-420S-15.5 FF2 ID. 1503 2 1 Line to Ground 1.9 for 30 Secs BSEN & ANSI

Transmag (UK) Limited, Units 2 & 3, St Andrews, Bayly Works,


Great Barr Street, Birmingham, West Midlands, B9 4BB.
web: www.transmaguk.co.uk | email: [email protected] | tel: +44(0)121 753 4390 | fax: +44(0)121 773 9369
420 TMG Single Phase Cast Resin Voltage Transformers

Transmag (UK) Limited, Units 2 & 3, St Andrews, Bayly Works,


Great Barr Street, Birmingham, West Midlands, B9 4BB.
web: www.transmaguk.co.uk | email: [email protected] | tel: +44(0)121 753 4390 | fax: +44(0)121 773 9369