PRESSURISATION
CONTROL SYSTEMS
FOR CAR PARKS, STAIRCASES, FIRE FIGHTING
LOBBIES AND ESCAPE ROUTES
EN-12101-3
Powered smoke and
heat exhaust ventilators
for use in Construction Works
SODECA has concentrated its activity on the production of
industrial fans, ventilation systems and extractors for the removal
Sodeca has begun a new Without a doubt, the most important factor for achieving our
objectives is the human factor, the great professionals who work
stage of study and design
at your service, offering not only ventilation equipment but also
of new trends in ventilation solutions to any ventilation need required by our customers.
which will help to preserve the
environment and to make the We offer you the possibility of visiting our facilities in Sant Quirze
energy saving which so much de Besora, with over 16,0002 square metres of built area, where
concerns today’s society. you will be able to see our fans being manufactured to the highest
standards of quality, complying with the ISO and AMCA standards.
EFFICIENT WORK
SODECA is pleased to
present its new efficient, high
performance “Efficient Work”
fans, equipped with high-tech
motors for greater energy
savings. These new products
exceed the requirements of
the Ecodesign ErP Directive
of 2009/125/CE and the (EU)
regulation 327/2011 governing
fans and adhere to the KYOTO
goals adopted by the EU
for cutting greenhouse gas
emissions.
Smoke Machine for performing real smoke tests THT/IMP installed in a car park
JET FAN VENTILATION ADVANTAGES OF THE SYSTEM
In recent years, horizontal ventilation systems, also known as The two most important advantages of the impulsion or induction
impulsion or induction ventilation systems, have been established as ventilation system are:
an alternative to the traditional ones which were based on networks • They keep contaminating gases at low concentration levels.
of ducts for extracting and supplying air. • They are better at controlling smoke during a fire and therefore
safer.
Long-range one-way or reversible 300 ºC/2h and 400 ºC/2h jet fans
with a circular (THT/IMP-C), octagonal (THT/IMP-L) or octagonal
painted (THT/IMP-O) design.
Fan:
• One-way or reversible fan unit including fan, silencers, deflectors
and support, approved for smoke extraction in accordance with
standard EN 12101-3, with certification no.: 0370-CPR-0394
• Adjustable rotors made of cast aluminium and designed to
produce great thrusts.
• Anti-contact protective grille pursuant to standard
THT/IMP-C
UNE‐EN ISO 12499.
• Deflector to increase the air range on the discharge side.
Reversible models are fitted with deflectors on both sides.
• High attenuation silencers with thermal and acoustic insulation.
• IAT series safety switch built into the fan (THT/IMP-L and
THT/ IMP-O) or on request (THT/IMP-C).
• Motor-rotor air direction or 100 % reversible.
• THT/IMP-C: Circular casing in painted sheet steel.
• THT/IMP-L: Galvanised sheet steel casing. Deflector for
• THT/IMP-O: Painted steel casing. increasing range
• THT/IMP-LS: Short length galvanised sheet steel casing.
THT/IMP-O
Motor: Finish:
• Class H motors, S1 continuous operation • Anticorrosive finish of polyester resin
and S2 emergency use, with ball bearings, polymerised at 190 ºC, previously
IP55 protection and 2 speeds. degreased with phosphate-free
• Three-phase 400V-50Hz. DHALANDER. nanotechnological treatment (THT/IMP-C,
• Maximum temperature of air to be carried: THT/IMP-O) or with a galvanised sheet
S1 continuous operation -20 ºC +40 ºC, steel anticorrosive finish (THT/IMP-L)
S2 operation 300 ºC/2h, 400 ºC/2h
On request:
THT/IMP-L
• Thrust features different from those
indicated.
CI
Long-range 300 ºC/2h and 400 ºC/2h centrifugal
induction jet fans for use in fire risk zones with
a low profile
0370-CPR-0715
Long-range 300 ºC/2h and 400 ºC/2h centrifugal induction jet fans for
use in fire risk zones with a low profile.
Fan:
• Sheet steel casing.
• Turbine with reaction blades in extremely robust sheet steel.
• IAT series safety switch built into the fan.
• Support feet included.
Motor: Finish:
• Class H motors, S1 continuous operation • Anti-corrosive finish of polyester
and S2 emergency use, with ball bearings, resin polymerised at 190 ºC, previously
IP55 protection and with 1 or 2 speeds, degreased with phosphate-free
depending on model. nanotechnological treatment.
• Three-phase 230/400V‐50Hz.
• Maximum temperature of air to be carried:
S1 continuous operation -20 ºC +40 ºC, S2
operation 300 ºC/2h, 400 ºC/2h.
THT 400 ºC/2h and 300 ºC/2h tubular axial extractor fans
with short housing
0370-CPR-0305
Tubular axial fans with short housing for working in fire risk zones.
Fan:
• Tubular sheet steel casing.
• Variable angle rotors made of cast aluminium.
• Approved in accordance with standard EN 12101-3. With certifications
no.: 0370-CPR-0305 (F400) and 0370-CPR-0973 (F300).
• Motor-rotor airflow direction.
Motor: Finish:
• Class H motors for S1 continuous operation • Anti-corrosive finish of polyester resin
and S2 emergency use. With ball bearings, polymerised at 190 ºC, previously degreased
IP55 protection and 1 or 2 speeds, depending with phosphate-free nanotechnological
on model. treatment.
• IE2 or IE3 efficiency motors depending on
model, except 2 speed and 8 poles. Available versions:
• Three-phase 230/400V‐50Hz (up to 3kW) and • THT/CL: tubular axial fans with long housing
400/690V‐50Hz (powers greater than 3kW). fitted with an inspection hatch.
• Maximum temperature of air to be carried:
S1 continuous operation -20 ºC +40 ºC, S2 On request:
operation 300 ºC/2h, 400 ºC/2h. • Motor-rotor airflow direction.
• Rotors 100 % reversible.
PRESSURISATION
CONTROL SYSTEMS
FOR STAIRCASES, FIRE-FIGHTING
LOBBIES AND ESCAPE ROUTES
KIT SOBREPRESIÓN
STAIRCASE OVERPRESSURE KIT STAIRCASE OVERPRESSURE KIT
For three-phase equipment
Staircase overpressure kit comprised of a control panel (BOXPRES KIT) and discharge units
(CJHCH or CJBD), for pressurising staircases and escape routes. Also available for NEOLINEO
and CJBC single-phase equipment.
The correct operation of the pressurisation systems depends not only on their sound design, but
on the correct regulation performed by the system. For this reason, it is extremely important to
have calibrated, high precision regulation elements that will permit both situations present in the
event of a fire to be maintained simultaneously, quickly and stably.
The BOXPRES control panel not only complies with the strictest requirements, it simplifies the work
STAIRCASE OVERPRESSURE KIT for the installer.
For three-phase equipment
It includes:
• A frequency changer programmed at 50 Pa.
• A differential pressure sensor.
• A magnetothermal switch.
• A line and failure led lamp.
• A check push button.
All the BOXPRES equipment interconnections have been made and tested. Ready to operate and
execute its function of controlling the installation pressure. Option of checking the installation to
prevent failures. Only the power supply line, discharge fan and fire signal need to be connected.
· Easy to install.
· A compact, autonomous solution.
· Preventive maintenance.
· Easy start-up.
· Safe, functional installation.
KIT BOXPDS Pressurisation equipment for staircases, escape
routes and firefighting lobbies, pursuant to
European standard EN 12101-6
KIT BOXPDS
• It is comprised of the BOXPDS control panel, a CJHCH ventilation unit
and a Damper Kit with a built-in optical smoke sensor.
BOXPDS
• Variable Frequency Drive. High precision differential pressure sensor.
Electric panel with magneto thermal protections and general power supply
failure indication.
• Electronic control for the management of alarms, maintenance, ModBUS
RTU port for BMS (Building management systems) connection and
DAMPER control.
• Certified power supply with batteries to ensure power supply to control
equipment in the event of a power failure.
Control panel:
• External control panel for real-time viewing of pressure, alarm pilot lamps
and manual system activation
· Easy to install.
· A compact, autonomous solution.
· Preventive maintenance.
· Easy start-up.
· Safe, functional installation.
+50 Pa +50 Pa
HATCH PDS
Pressurisation equipment for escape routes in the event of a fire, pursuant to the
requirements of European standard EN 12101-6. The HATCH PDS automatically regulates
the air flow and is able to maintain the 50 Pa overpressure, even in the present of
leakages in the installation. The system can maintain the overpressure (pressure criteria)
and a speed of 0.75 m/s in an open door situation (airflow criteria) almost immediately.
HATCH PDS
It is formed by a HATCH-S ventilation unit with a motorised hatch opening function
and a BOXPDS control panel.
• An extremely robust structure that is able to withstand severe weather changes.
• Equipment structure made of corrosive-proof galvanised sheet steel.
• Water-tight design to prevent the entry of water.
• Heat insulation to prevent hot air loss in the winter.
• Adaptable skirting for correct, easy installation on the roof.
Opening system:
• Motorised opening arms, with encapsulated IP-65 mechanism.
• Supply voltage 230V AC 50Hz or 24V DC.
• Reinforced, guaranteed system with more than 10,000 operations at maximum load.
• Maximum load 1000 Nw.
• Automatic opening via external control system signal (fire station, smoke detector,
manual switch...).
• Control systems not included in the supply.
• Manual opening for environmental ventilation via switch.
• Limit switch to signal the hatch position.
Fan:
• HCT series extractor fans.
• Tubular wrap in sheet steel with polyester resin anti-corrosive treatment.
• Cast aluminium rotors.
Motor:
• IE3 efficiency motors for powers equal to or greater than 0.75kW except single-phase,
2-speed and 8-pole.
• Class F motors with ball bearings and IP55 protection.
• Three-phase 230/400V-50Hz (up to 4kW) and 400/690V-50Hz (power higher than 4kW).
• Operating temperature: -25 ºC +50 ºC
Finish:
• Corrosion-proof galvanised sheet steel.
On request:
• Fitted with F-300 and F-400 rated fans.
• Reversible pressurisation equipment for smoke evacuation in case of need.
• Polyester resin anti-corrosive paint finish.
BOXPDS
• Variable Frequency Drive. • Certified power supply with batteries
• High precision differential pressure to ensure power supply to control
sensor. equipment in the event of a power failure.
• Electric panel with magneto thermal
protections and general power supply Control panel:
failure indication. • External control panel for real-time
• Electronic control for the management of viewing of pressure, alarm pilot lamps
alarms, maintenance, ModBUS RTU port and manual system activation.
for BMS (Building management systems)
connection and DAMPER control.
+50 Pa
PRESSKIT
The PRESSKIT equipment is comprised of one or more fans. In the case of fire
they are activated to exert an overpressure of 50Pa in safe zones and to prevent
the entry of smoke in escape routes for the evacuation of people.
Common characteristics:
• Self-regulation of pressure throughout the lobby.
• Brushless 24VDC E.C. fans with a maximum flow rate of 2,100m3/H.
• An overpressure of 50Pa is maintained in the lobby.
Equipment control:
• S models: Simplified regulation of the ventilation unit via a pressure
sensor with a built-in PID signal adjuster.
• P models: PLC control with multiple inputs, outputs, alarms and fan
regulation via PID signal.
• Delay in equipment connection depending on the fire door status.
• Power supply panel with autonomy of more than 2 hours through 18Ah
batteries.
• Ease in connecting equipment.
• Fast configuration and adjustment of all the parameters via LCD display
and keyboard.
• MANUAL system activation button.
• Viewing of pressure in safe zone and equipment status in real time.
PRESSURISATION FAN
• Brushless 24VDC fan, 0-10V analogue control input.
• Maximum flow rate 2,100m3/h.
• Mural fan for conduits with a diameter of 310mm.
• ROTOR-MOTOR air direction.
• Useful life in continuous operation of more than 20,000 hours.
• Rotor made of painted sheet steel.
• Protective anti-contact grille.
+50 Pa
CONTROL PANEL
• System control panel through small PLC that is easy to install. Control panel characteristics
Power supply 230VAC. Total voltage (V): 1x230 Max. current Output 2 (A): 7
• Digital input for detecting open door. Total current (A): 0.3 Protection (IP): 44
• Digital outputs indicating fire alarm activated, Output Voltage 1 (V): 19.7-28VDC Operating temperature (ºC): -25 to +60
through visual and acoustic indicator light that flashes with Output Voltage 2 (V): 19.7-28VDC Weight (Kg): 30.5
configurable times. Max. current Output 1 (A): 6
• Configurable connection delay times in the event of detecting
a fire alarm and fire doors open.
• Configuration of all the PID output parameters. PRESSURE SENSOR WITH DISPLAY
• Manual system activation button. (BUILT INTO CONTROL PANEL)
• Viewing of pressure in Pa in real time, indication of equipment • 0-100 Pa preconfigured differential pressure sensor.
status STANDBY/ PRESSURISING. • 0..10V analogue output.
• Possibility of controlling 2 fans with a single panel and power • LCD display.
source. (PRESSKIT TWIN). • Calibrated high precision analogue sensor.
• Regulation through a single control panel of 1 or 2 ventilation units.
• Key lock.
Certified: NR331151