K - 220kV Line-3Bus-HADALA 220VDC - RZ - 20032015

Download as pdf or txt
Download as pdf or txt
You are on page 1of 129

ABCD

CUSTOMER:GUJARAT ENERGY TRANS. CORP.LTD


PROJECT : SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S
DRAWING : 220KV LINE (3-BUS) CONTROL & PROTN
P.O NO : CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 Dt.08.10.2014
CONTROL VOLTAGE-220V DC; QTY-12 NOS

SALES ORDER NO.: - 3269034460


ENGG. REF. NO.: KW85
LIST OF DOCUMENTS SUBMITTED

S.NO. DESCRIPTION DRAWING NO. ISSUE

1 Board Formation Drawing CPG KW85 BF7 Z-19.03.2015


2 Board Formation Drawing CPG KW85 BF8 Z-19.03.2015
3 Panel Construction Drawing CPG KW85 PC1 Z-19.03.2015
4 Panel Construction Drawing CPG KW85 PC2 Z-19.03.2015
5 GA - Drawing Panel Type 2C1 CPG KW85 2C1(F) Z-19.03.2015
6 Internal GA - Drawing Panel Type 2C1 CPG KW85 2C1(R) Z-19.03.2015
7 Legend-Panel Type 2C1 CPG KW85 2C1 (L) Z-19.03.2015
8 GA - Drawing Panel Type 2R1 CPG KW85 2R1(F) Z-19.03.2015
9 Internal GA - Drawing Panel Type 2R1 CPG KW85 2R1(R) Z-19.03.2015
10 Legend-Panel Type 2R1 CPG KW85 2R1 (L) Z-19.03.2015
11 Schematic Drawing CPD KW85 SC21 Z-19.03.2015
12 Equipment wise schedule EW852C1 Z-19.03.2015
13 Wire wise schedule WW852C1 Z-19.03.2015
14 Equipment wise schedule EW852R1 Z-19.03.2015
15 Wire wise schedule WW852R1 Z-19.03.2015
DEV REF. MATERIAL NAME MAKE DESCRIPTION

52X1 VAJC11ZF1004ABA ALSTOM CONTACT MULTIPLICATION RELAY -BREAKER 2-52


4M 4B : FLAG-YES : 220V-250V DC : ELECTRICAL RESET;1/2 N VERTICAL WD:01VAJC11ZF001
52X2 VAJC11ZF1004ABA ALSTOM CONTACT MULTIPLICATION RELAY -BREAKER 2-52
4M 4B : FLAG-YES : 220V-250V DC : ELECTRICAL RESET; 1/2 N VERTICAL WD:01VAJC11ZF001
80A VAA11YF8752CA ALSTOM DC SUPPLY SUPERVISION RELAY - SOURCE 1
2M 2C/O SR: FLAG-RE: AUX VOLTAGE1:110-125V DC;AUX VOLTAGE2:220-250V DC;100 +-20 MSECS TDDO
WD: 01 VAA11YF 002
80B VAA11YF8752CA ALSTOM DC SUPPLY SUPERVISION RELAY - SOURCE 2
2M 2C/O SR: FLAG-RE: AUX VOLTAGE1:110-125V DC;AUX VOLTAGE2:220-250V DC;100 +-20 MSECS TDDO
WD: 01 VAA11YF 002
80C GBVAA11YF5752AA ALSTOM AUXILIARY RELAY - DC FAIL ACCEPT
2M 2C/O SR: FLAG-NO:110-125/220-250V AC WD:01VAA11YF002
89AX1 VAJC11ZF1004ABA ALSTOM AUX RELAY -ISOLATOR 89A
4M 4B : FLAG-YES : 220V-250V DC : ELECTRICAL RESET;1/2 N VERTICAL WD:01VAJC11ZF001
89BX1 VAJC11ZF1004ABA ALSTOM AUX RELAY -ISOLATOR 89B
4M 4B : FLAG-YES : 220V-250V DC : ELECTRICAL RESET;1/2 N VERTICAL WD:01VAJC11ZF001
89CX1 VAJC11ZF1004ABA ALSTOM 'AUX RELAY -ISOLATOR 89C
4M 4B : FLAG-YES : 220V-250V DC : ELECTRICAL RESET;1/2 N VERTICAL WD:01VAJC11ZF001
89LEX VAJC11ZF1004ABA ALSTOM AUX RELAY -ISOLATOR 89 E/S
4M 4B : FLAG-YES : 220V-250V DC : ELECTRICAL RESET; 1/2 N VERTICAL WD:01VAJC11ZF001
89LX VAJC11ZF1004ABA ALSTOM AUX RELAY -ISOLATOR 89L
4M 4B : FLAG-YES : 220V-250V DC : ELECTRICAL RESET;1/2 N VERTICAL WD:01VAJC11ZF001
A1 GBCAA2L1MMMM00610 RISHAB AMMETER MILLIAMMETER;96 Sq mm 240 DEG END ZERO INPUT CURRENT 4-20 mA;ACCURACY: 1.0
SCALE:0-300-600-1200 A. 100% SCALE;ADDITIONAL SCALE FOR 3rd RATIO:0-1200 A; AMMETER
A2 GBCAA2L1MMMM00610 RISHAB AMMETER MILLIAMMETER;96 Sq mm 240 DEG END ZERO INPUT CURRENT 4-20 mA;ACCURACY: 1.0
SCALE:0-300-600-1200 A. 100% SCALE;ADDITIONAL SCALE FOR 3rd RATIO:0-1200 A; AMMETER
A3 GBCAA2L1MMMM00610 RISHAB AMMETER MILLIAMMETER;96 Sq mm 240 DEG END ZERO INPUT CURRENT 4-20 mA;ACCURACY: 1.0
SCALE:0-300-600-1200 A. 100% SCALE;ADDITIONAL SCALE FOR 3rd RATIO:0-1200 A; AMMETER
CS1 S22N120SRL2PM108 ALSTOM CB CONTROL SWITCH CIRCUIT BREAKER - 52 OPEN -NEUTRAL -CLOSE
CONTROL SWITCH 22 WAY NON-LOCK SPRING RETURN WITH LOST MOTION DEVICE;20A RATING
CS2 S04N120SRPM101 ALSTOM CONTROL SWITCH ISOLATOR - 9A OPEN - NEUTRAL - CLOSE
CONTROL SWITCH 4 WAY NON-LOCK SPRING RETURN;20A RATING
CS3 S04N120SRPM101 ALSTOM CONTROL SWITCH ISOLATOR -2- 389B OPEN- NEUTRAL - CLOSE
CONTROL SWITCH 4 WAY NON-LOCK SPRING RETURN;20A RATING

SCHEME REF: ENGG.REF.NO: KW85 CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD LEGEND TO GA DRAWING PREPARED BY: GKA REVISION: Z

NETWORK NO.: . PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S PANEL TYPE: 2C1 FILE: KW852C1 CHECKED BY: JKK DATE: 19.03.2015

FINISHED GOOD: . P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India Limited - AUTOMATION SAS TITLE: 220kV LINE CONTROL PANEL APPROVED BY: JKK SCALE: NIL
Dated 08.10.14
SALES ORDER-ITEM: - PALLAVARAM CHENNAI 600043 DRG. NO.: CPG KW85 2C1 (L) SHT 1 OF 4
DEV REF. MATERIAL NAME MAKE DESCRIPTION

CS4 S04N120SRPM101 ALSTOM CONTROL SWITCH ISOLATOR - 9L OPEN - NEUTRAL - CLOSE


CONTROL SWITCH 4 WAY NON-LOCK SPRING RETURN;20A RATING
CS5 S04N120SRPM101 ALSTOM CONTROL SWITCH ISOLATOR - 9C OPEN - NEUTRAL - CLOSE
CONTROL SWITCH 4 WAY NON-LOCK SPRING RETURN;20A RATING
DCSS S10N90SPPM103 ALSTOM SELECTOR SWITCH DC SUPPLY " SOURCE 1 - INDEPENDENT - SOURCE 2"
SELECTOR SWITCH 10 WAY NON-LOCK STAYPUT;20A RATING
FC GBCAA0181M11M ALAN MICROPROCESSOR BASED FACIA ANNUNCIATOR SIZE:72*34; 6C*6R AUX SUP: 88-285V AC/DC: INBUILT AC/DC FAIL WITH
RS485 W/O BUILT IN PUSH BUTTON
PB01 CPB1111000 TEKNIC PUSH BUTTON - RED - 1NO+1NC - ANNUN ACCEPT
PB02 CPB1211000 TEKNIC PUSH BUTTON - YELLOW 1 NO + 1 NC - ANNUN RESET
PB03 CPB1511000 TEKNIC PUSH BUTTON - GREEN - 1 NO + 1 NC - ANNUN TEST
PB04 GBCPF0501104 TEKNIC PUSH BUTTON BLACK 2NO+2NC - DC FAIL TEST
PB05 GBCPF0501104 TEKNIC PUSH BUTTON BLACK 2NO+2NC - DC FAIL ACCEPT
S1 CES0000012 DAV SEMAPHORE INDICATOR - 48DIA BEZEL 220V DC CIRCUIT BREAKER - 52
S2 GBCES0000014 DAV SEMAPHORE INDICATOR - 36DIA BEZEL; 220V DC ISOLATOR - 89A
S3 GBCES0000014 DAV SEMAPHORE INDICATOR - 36DIA BEZEL; 220V DC ISOLATOR - 89B
S4 GBCES0000014 DAV SEMAPHORE INDICATOR - 36DIA BEZEL; 220V DC ISOLATOR - 89L
S5 GBCES0000014 DAV SEMAPHORE INDICATOR - 36DIA BEZEL; 220V DC ISOLATOR - 89C
S6 GBCES0000014 DAV SEMAPHORE INDICATOR - 36DIA BEZEL; 220V DC -LINE E/S
SL01 GBCIL3144100 TEKNIC LED GREEN 220V DC 22.5MMCB OPEN
SL02 GBCIL3114100 TEKNIC LED RED 220V DC 22.5 MM CB CLOSED
SL03 GBCIL3124100 TEKNIC LED AMBER 220V DC 22.5 MM-CB-AUTO TRIP
SL04 GBCIL3154100 TEKNIC LED MILKY WHITE 220V DC 22.5MM - SF6 GAS PRESSURE NORMAL
SL05 GBCIL3134100 TEKNIC LED BLUE 220V DC 22.5 MM -CB SPRING CHARGED
SL06 GBCIL3144100 TEKNIC LED GREEN 220V DC 22.5MM 89A ISOL OPEN
SL07 GBCIL3114100 TEKNIC LED RED 220V DC 22.5 MM 89A ISOL CLOSED
SL08 GBCIL3144100 TEKNIC LED GREEN 220V DC 22.5MM 89B ISOL OPEN
SL09 GBCIL3114100 TEKNIC LED RED 220V DC 22.5 MM 89B ISOL CLOSED
SL10 GBCIL3144100 TEKNIC LED GREEN 220V DC 22.5MM 89L ISOL OPEN
SL11 GBCIL3114100 TEKNIC LED RED 220V DC 22.5 MM 89L ISOL CLOSED
SL12 GBCIL3144100 TEKNIC LED GREEN 220V DC 22.5MM 89C ISOL OPEN

SCHEME REF: ENGG.REF.NO: KW85 CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD LEGEND TO GA DRAWING PREPARED BY: GKA REVISION: Z

NETWORK NO.: . PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S PANEL TYPE: 2C1 FILE: KW852C1 CHECKED BY: JKK DATE: 19.03.2015

FINISHED GOOD: . P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India Limited - AUTOMATION SAS TITLE: 220kV LINE CONTROL PANEL APPROVED BY: JKK SCALE: NIL
Dated 08.10.14
SALES ORDER-ITEM: - PALLAVARAM CHENNAI 600043 DRG. NO.: CPG KW85 2C1 (L) SHT 2 OF 4
DEV REF. MATERIAL NAME MAKE DESCRIPTION

SL13 GBCIL3114100 TEKNIC LED RED 220V DC 22.5 MM 89C ISOL CLOSED
SL14 GBCIL3144100 TEKNIC LED GREEN 220V DC 22.5MM LINE E/S OPEN
SL15 GBCIL3114100 TEKNIC LED RED 220V DC 22.5 MM LINE E/S CLOSED
SL51 GBCIL3157100 TEKNIC LED MILKY WHITE 240V AC 22.5MM - DC FAIL
SS CSS1000001 BCH 12 PIN SYNCHRONISING SOCKET
SSS S12LT180SPPM101 ALSTOM SELECTOR SWITCH - " CHK. SYN. - OFF - BYPASS"
SELECTOR SWITCH 12 WAY LOCKABLE STAYPUT;20A RATING
TTB CTB4000002 DAV DAV MAKE TEST TERMINAL BLOCK 3PH 4 WIRE - FDR#5
TTS S30LT90SPPM126 ALSTOM SELECTOR SWITCH - TRIP TRANSFER - "NORMAL - INTER-TRANSFER"
SELECTOR SWITCH 30 WAY LOCKABLE STAYPUT;20A RATING
TVM GBEB4B18100511181F L&T STATIC ENERGY METER (ER300P) 3PART CL:-0.5S 3PH 4WIRE 3ELE 300-600-1200/1A-220KV/110V; MDI
30MIN; RS485; SPECIAL: SUITABLE FOR GETCO DAS CONECTIVITY
VAR GBCQA2Q1MMMM01700 RISHAB DC MILLI AMMETER 96 MM SQ 240 DEG SCALE 4-20mA CENTRE ZERO 125/250MVAR , CL: 1.0

VB GBCVA2L1MMMM00200 RISHAB ANALOG VOLTMETER MILLIAMMETER, 96 Sq mm 240 DEG EZ I/P 4-20 mA;ACCURACY CL:1.0;SCALE:0-250 kV.
- BUS VOLTAGE
VL GBCVA2L1MMMM00200 RISHAB ANALOG VOLTMETER MILLIAMMETER, 96 Sq mm 240 DEG EZ I/P 4-20 mA;ACCURACY CL:1.0;SCALE:0-250 kV.
- LINE VOLTAGE
VS GBBEW5131800 SWITRON 8 POSITION V/SEL.SWITCH - FOR BUS VOLTAGE;10A RATING
W GBCPA2Q1MMMM01A00 RISHAB DC MILLI AMMETER 96 MM SQ 240 DEG SCALE 4-20mA CENTRE ZERO 125/250MW , CL: 1.0

INTERNALLY MOUNTED EQUIPMENTS

AT1 GBCTA22500031XXX2D RISHABH CURRENT TRANSDUCER O/P:4-20mA (DUAL) EZ,CL:0.5 AUX SUP:220V DC 300-600-1200/1A; LR: 750ohms
AT2 GBCTA22500031XXX2D RISHABH CURRENT TRANSDUCER O/P:4-20mA (DUAL) EZ,CL:0.5 AUX SUP:220V DC 300-600-1200/1A; LR: 750ohms
AT3 GBCTA22500031XXX2D RISHABH CURRENT TRANSDUCER O/P:4-20mA (DUAL) EZ,CL:0.5 AUX SUP:220V DC 300-600-1200/1A; LR: 750ohms
CIL GBCPE0000600 COMPAC COMPACT FLOURESCENT LAMP WITH FIXTURE- 11W 230V AC
EBZ1 CBH1000000 BHARANI FOUR TONE BUZZER 40-300V DC/230VAC TRIP, NON-TRIP, AC / DC FAIL
EBZ2 CBH1000000 BHARANI FOUR TONE BUZZER 40-300V DC/230VAC TRIP, NON-TRIP, AC / DC FAIL
EBZ3 CBH1000000 BHARANI FOUR TONE BUZZER 40-300V DC/230VAC TRIP, NON-TRIP, AC / DC FAIL
HS GBCPF0500901 SWITRON HEATER SWITCH
HT GBCPA0178101 SOFIA/SPM HEATER 230V AC 50HZ, 60W
PS GBCPE0000344 ANCHOR/OSWAL POWER SOCKET 5/15A WITH SWITCH + PLUG 3PIN 230V AC 3 PIN 230V AC
TH GBCPE0000612 MAVIS / APT CTRLS THERMOSTAT 230V AC, 30 - 80 DEG C 230V, 85 DEG C
52X3 VAJC11ZF1004ABA ALSTOM AUX RELAY -BREAKER 52
4M 4B : FLAG-YES : 220V-230V DC : 1/2 N VERTICAL WD:01VAJC11ZF 001

SCHEME REF: ENGG.REF.NO: KW85 CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD LEGEND TO GA DRAWING PREPARED BY: GKA REVISION: Z

NETWORK NO.: . PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S PANEL TYPE: 2C1 FILE: KW852C1 CHECKED BY: JKK DATE: 19.03.2015

FINISHED GOOD: . P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India Limited - AUTOMATION SAS TITLE: 220kV LINE CONTROL PANEL APPROVED BY: JKK SCALE: NIL
Dated 08.10.14
SALES ORDER-ITEM: - PALLAVARAM CHENNAI 600043 DRG. NO.: CPG KW85 2C1 (L) SHT 3 OF 4
DEV REF. MATERIAL NAME MAKE DESCRIPTION

89CX2 VAJC11ZF1004ABA ALSTOM AUX RELAY -ISOLATOR 89C


4M 4B : FLAG-YES : 220V-230V DC : 1/2 N VERTICAL WD:01VAJC11ZF001
VART GBCTQ2M5400310170D RISHABH VAR TRANSDUCER 3PH 4W 3ELE O/P:4-20mA (DUAL) CENTRE ZERO AUX:220V DC 300-600-1200/1A-220KV/110V
SCALE:250-125-0-125-250MVAR: LR: 750ohms
VBT GBCTV225400000020D RISHABH VOLTAGE TRANSDUCER O/P:4-20mA (DUAL) EZ,CL:0.5 AUX SUP:220VDC 220KV/110V 0-250KV;LR: 750ohms
VLT GBCTV225G00000020D RISHABH VOLTAGE TRANSDUCER O/P:4-20mA (DUAL) EZ,CL:0.5 AUX SUP:220VDC 220KV/63.5V 0-250KV; LR: 750ohms
WT GBCTP2M54003101A0D RISHABH WATT TRANSDUCER 3PH 4W 3ELE O/P:4-20mA (DUAL) CENTRE ZERO AUX:220VDC 220KV/110V-300-600-1200/1A-SCALE
:250-125-0-125-250MW: LR: 750ohms

SCHEME REF: ENGG.REF.NO: KW85 CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD LEGEND TO GA DRAWING PREPARED BY: GKA REVISION: Z

NETWORK NO.: . PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S PANEL TYPE: 2C1 FILE: KW852C1 CHECKED BY: JKK DATE: 19.03.2015

FINISHED GOOD: . P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India Limited - AUTOMATION SAS TITLE: 220kV LINE CONTROL PANEL APPROVED BY: JKK SCALE: NIL
Dated 08.10.14
SALES ORDER-ITEM: - PALLAVARAM CHENNAI 600043 DRG. NO.: CPG KW85 2C1 (L) SHT 4 OF 4
DEV REF. MATERIAL NAME MAKE DESCRIPTION

195B MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY - TC-1 B PHASE


1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
195R MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY -TC-1 R PHASE
1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
195Y MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY -TC-1 Y PHASE
1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
21M1 P44491AJ6M0550K ALSTOM NUMERICAL DIST PROTN RELAY TYPE MICOM P444,110-250V DC/100-240V AC,CT-1&5A;24I/P;46O/P;CHK
SYNC;IEC61850 WITH IRIG-B,100MBPS
21M2 GBD6024I34OIBFO GE DISTANCE PROTN RELAY, AUX:125/250 V AC/DC, CT/VT: STANDARD 4VT/4CT, DIGITAL I/O: 24 DIGITAL INPUTS
34 OUTPUTS- MAIN-2 ( CORTEC CODE - D60-J03-HKH-F8L-H6D-M6T-P67-U67-W4L ) FO PORT WITH IRIG-B
295B MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY - TC-2 B PHASE
1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
295R MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY -TC-2 R PHASE
1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
295Y MVAXM31D1CE3005A ALSTOM TRIP COIL SUPERVISION RELAY -TC-2 Y PHASE
1M 2B SR : FLAG-REV : 220-250V DC WD:Z1MVAXM31001SHT1
75A MVAJM14JB1002A1 ALSTOM VOLTAGE SELECTION RELAY
8M 2B ER : FLAG-YES : 220-250V DC SIZE-2
75B MVAJM14JB1002A1 ALSTOM VOLTAGE SELECTION RELAY
8M 2B ER : FLAG-YES : 220-250V DC SIZE-2
75C MVAJM14JB1002A1 ALSTOM VOLTAGE SELECTION RELAY
8M 2B ER : FLAG-YES : 220-250V DC SIZE-2
75D MVAJM14JB1002A1 ALSTOM VOLTAGE SELECTION RELAY
8M 2B ER : FLAG-YES : 220-250V DC SIZE-2
86A MVAJ205LA1004A ALSTOM HIGH SPEED TRIPPING RELAY GROUP A
HI/LO BURDEN : FLAG-YES : 220-250V DC : 16M 4B ELEC. RESET WITH HAND RESET FLAG WD:01 MVAJ 205 01
86AX MVAAM11B1BA8000A ALSTOM AUXILLARY RELAY GROUP-A CONTACT MULTLIPLICATION RELAY
8M S/R FLAG- YES 110-125VDC 220-250V DC RWD 01 MVAAM11 027
86B MVAJ205LA1004A ALSTOM HIGH SPEED TRIPPING RELAY GROUP B
HI/LO BURDEN : FLAG-YES : 220-250V DC : 16M 4B ELEC. RESET WITH HAND RESET FLAG WD:01 MVAJ 205 01
27RN MVAGM11B1APC1251A ALSTOM NO VOLT RELAY - FOR EARTH SWITCH INTERLOCK
1M 1B SR : FLAG-REV : 63.5V AC : 50HZ :DO : 16 / 38 VAC WD:01MVAGM11006

SCHEME REF: ENGG.REF.NO: KW85 CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD LEGEND TO GA DRAWING PREPARED BY: GKA REVISION: Z

NETWORK NO.: . PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S PANEL TYPE: 2R1 FILE: KW852R1 CHECKED BY: JKK DATE: 19.03.2015

FINISHED GOOD: . P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India Limited - AUTOMATION SAS TITLE: 220kV LINE PROTECTION PANEL APPROVED BY: JKK SCALE: NIL
Dated 08.10.14
SALES ORDER-ITEM: - PALLAVARAM CHENNAI 600043 DRG. NO.: CPG KW85 2R1 (L) SHT 1 OF 3
DEV REF. MATERIAL NAME MAKE DESCRIPTION

86B2 MVAJM11JA1000A ALSTOM HIGH SPEED TRIPPING RELAY -B-PHASE


LO BURDEN : FLAG-YES : 220-250V DC : 10M SR WD:01MVAJM11011
86BX MVAAM11B1BA8000A ALSTOM AUXILLARY RELAY GROUP-B CONTACT MULTLIPLICATION RELAY
8M S/R FLAG- YES 110-125VDC 220-250V DC RWD 01 MVAAM11 027
86R2 MVAJM11JA1000A ALSTOM HIGH SPEED TRIPPING RELAY -R-PHASE
LO BURDEN : FLAG-YES : 220-250V DC : 10M SR WD:01MVAJM11011
86Y2 MVAJM11JA1000A ALSTOM HIGH SPEED TRIPPING RELAY -Y-PHASE
LO BURDEN : FLAG-YES : 220-250V DC : 10M SR WD:01MVAJM11011
95/86A MVAXM21C1CE3005A ALSTOM HIGH SPEED TRIPPING RELAY SUPERVISION RELAY - GROUP A TRIP RELAY
1M 2B SR : 220-250V DC : FLAG-REV. WD:F1MVAXM21001
95/86B MVAXM21C1CE3005A ALSTOM HIGH SPEED TRIPPING RELAY SUPERVISION RELAY - GROUP B TRIP RELAY
1M 2B SR : 220-250V DC : FLAG-REV. WD:F1MVAXM21001
96 MVAJ205LA1004A ALSTOM HIGH SPEED TRIPPING RELAY LBB TRIP
HI/LO BURDEN : FLAG-YES : 220-250V DC : 16M 4B ELEC. RESET WITH HAND RESET FLAG WD:01 MVAJ 205 01
ARS S08N90SPPM102 ALSTOM SELECTOR SWITCH - AUTO RECLOSE IN-OUT
SELECTOR SWITCH 8 WAY NON-LOCK STAYPUT;20A RATING
BLKA MPGTESTBLOCK ALSTOM TEST BLOCK - DISTANCE PROTECTION -21M1
STANDARD TEST BLOCK
BLKB MPGTESTBLOCK ALSTOM TEST BLOCK - DISTANCE PROTECTION -21M1
STANDARD TEST BLOCK
BLKC MPGTESTBLOCK ALSTOM TEST BLOCK - DISTANCE PROTECTION-21M2
STANDARD TEST BLOCK
BLKD MPGTESTBLOCK ALSTOM TEST BLOCK - DISTANCE PROTECTION -21M2
STANDARD TEST BLOCK
CSS1 S08N90SPPM102 ALSTOM SELECTOR SWITCH - "CARRIER" CHANNEL "IN-OUT"
SELECTOR SWITCH 8 WAY NON-LOCK STAYPUT;20A RATING
CSS2 S08N90SPPM102 ALSTOM SELECTOR SWITCH - "CARRIER-2" CHANNEL "IN-OUT"
SELECTOR SWITCH 8 WAY NON-LOCK STAYPUT;20A RATING
ITX1 MVAJM14JB1000A1 ALSTOM CONTROL RELAY-IT MODE CONTACT MULTIPLICATION
10M E/R : FLAG-YES: 220-250V DC: WD: 01 MVAJM14 011
ITX2 MVAJM14JB1000A1 ALSTOM CONTROL RELAY-IT MODE CONTACT MULTIPLICATION
10M E/R : FLAG-YES: 220-250V DC: WD: 01 MVAJM14 011

SCHEME REF: ENGG.REF.NO: KW85 CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD LEGEND TO GA DRAWING PREPARED BY: GKA REVISION: Z

NETWORK NO.: . PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S PANEL TYPE: 2R1 FILE: KW852R1 CHECKED BY: JKK DATE: 19.03.2015

FINISHED GOOD: . P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India Limited - AUTOMATION SAS TITLE: 220kV LINE PROTECTION PANEL APPROVED BY: JKK SCALE: NIL
Dated 08.10.14
SALES ORDER-ITEM: - PALLAVARAM CHENNAI 600043 DRG. NO.: CPG KW85 2R1 (L) SHT 2 OF 3
DEV REF. MATERIAL NAME MAKE DESCRIPTION

ITX3 MVAJM14JB1000A1 ALSTOM CONTROL RELAY-IT MODE CONTACT MULTIPLICATION


10M E/R : FLAG-YES: 220-250V DC: WD: 01 MVAJM14 011
ITX4 MVAJM14JB1000A1 ALSTOM CONTROL RELAY-IT MODE CONTACT MULTIPLICATION
10M E/R : FLAG-YES: 220-250V DC: WD: 01 MVAJM14 011
IX1 MVAJM14JB1002A1 ALSTOM AUXILIARY RELAY
8M 2B ER : FLAG-YES : 220-250V DC SIZE-2
NIX1 MVAJM14JB1002A1 ALSTOM AUXILIARY RELAY
8M 2B ER : FLAG-YES : 220-250V DC SIZE-2
NIX2 MVAJM14JB1004A1 ALSTOM AUXILIARY RELAY
6NO, 4NC ER; FOLLOW ON FLAG 220 TO 250 V DC WITHOUT CT SHORT WD:01 MVAJM14 011
PB01 CPF0501104 TEKNIC PUSH BUTTON - BLACK - 3NO+3NC - 86A/86B/96 TRIP RELAY RESET
RX1 MVAAM11B1BA2530A ALSTOM AUXILIARY RELAY - DIRECT TRIP RECEIVED CH-1
2M 2C FLAG YES 110-125/220-250V DC WD:Z1MVAAM11001
RX2 MVAAM11B1BA2530A ALSTOM AUXILIARY RELAY - DIRECT TRIP RECEIVED CH-2
2M 2C FLAG YES 110-125/220-250V DC WD:Z1MVAAM11001
SL16 CIL3114100 TEKNIC LED INDICATING LAMP RED 220V DC 22.5MM - BUS-1 VT SELECTED
SL17 CIL3114100 TEKNIC LED INDICATING LAMP RED 220V DC 22.5MM - BUS-2 VT SELECTED
SX1 MVAAM11B1AA9531A ALSTOM AUXILLARY RELAY - DIRECT TRIP SEND CH-1
6M S/R NO FLAG 220V DC RWD 01 MVAAM11 020
SX2 MVAAM11B1AA9531A ALSTOM AUXILLARY RELAY - DIRECT TRIP SEND CH-2
6M S/R NO FLAG 220V DC RWD 01 MVAAM11 020
89AX2 MVAJM14JB1004A1 ALSTOM CONTROL RELAY - CMR ISOLATOR 89A
6NO 4NC ER; 220 TO 250 V DC WD:01 MVAJM14 011

INTERNALLY MOUNTED EQUIPMENTS


CIL CPE0000600 COMPAC COMPACT FLOURESCENT LAMP WITH FIXTURE- 11W 230V AC
HS CPF0500901 SWITRON HEATER SWITCH
HT CPA0178101 SOFIA/SPM HEATER 230V AC 50HZ, 60W
PS CPE0000345 ANCHOR/OSWAL POWER SOCKET 5/15A WITH SWITCH + PLUG 3PIN 230V AC
TH CPE0000612 MAVIS / APT CTRLS THERMOSTAT 240V AC, 30 - 90 DEG C
89BX2 MVAJM14JB1004A1 ALSTOM CONTROL RELAY - CMR ISOLATOR 89B
6NO 4NC ER; 220 TO 250 V DC WD:01 MVAJM14 011

SCHEME REF: ENGG.REF.NO: KW85 CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD LEGEND TO GA DRAWING PREPARED BY: GKA REVISION: Z

NETWORK NO.: . PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S PANEL TYPE: 2R1 FILE: KW852R1 CHECKED BY: JKK DATE: 19.03.2015

FINISHED GOOD: . P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India Limited - AUTOMATION SAS TITLE: 220kV LINE PROTECTION PANEL APPROVED BY: JKK SCALE: NIL
Dated 08.10.14
SALES ORDER-ITEM: - PALLAVARAM CHENNAI 600043 DRG. NO.: CPG KW85 2R1 (L) SHT 3 OF 3
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION FERRULE NUMBERING STANDARDS
RELAY COIL - DS
CUB.ILLUMN.LAMP WITH D/S FERRULE - "A" : CT CIRCUIT - MAIN PROTECTION
MAKE CONTACT GENERAL SYMBOL

MAKE CONTACT - FERRULE - "B" : CT CIRCUIT - BUSBAR PROTECTION


DELAYED PICKUP RELAY COIL - HEATER
MAKE CONTACT - SLOW RELEASING FERRULE - "C" : CT CIRCUIT - BACKUP PROTECTION
DELAYED DROP OFF

MAKE CONTACT WITH RELAY COIL - HEATER SWITCH FERRULE - "D" : CT CIRCUIT - METERING
BLOWOUT MAGNET
SLOW OPERATING
MAKE CONTACT - POWER SOCKET FERRULE - "E" : VT CIRCUIT - PROTECTION/METERING
HAND RESET
FERRULE - "G" : VT CIRCUIT - SYNCHRONISING
MAKE CONTACT - THERMOSTAT
THYRISTOR FLASHER RELAY
FUSE FERRULE - "H" : AUXILIARY AC CIRCUIT

BREAK CONTACT FERRULE - "J" : AUXILIARY DC CIRCUIT


RELAY COIL - LINK

HAND RESET TEST BLOCK - MPG FERRULE - "K" : CONTROL CIRCUITS


BREAK CONTACT -
DELAYED PICKUP RESISTOR FERRULE - "L" : INDICATION & ALARM CIRCUITS
BREAK CONTACT - FLAG INDICATOR STABILISING RESISTOR FERRULE - "P" : DC CIRCUIT - BUSBAR PROTECTION CIRCUITS
DELAYED DROP OFF

BREAK CONTACT WITH DISCONNECTING FERRULE - "S" : EVENT LOGGER/DAS/SCADA CIRCUITS


METROSIL SURGE DIVERTOR
BLOWOUT MAGNET TB AT C&R PANLES
BREAK CONTACT - TERMINAL BOARD FERRULE - "U" : SPARE CONTACTS
HAND RESET
CONTROL/SEL SW.-TYPE ODS
AT C&R PANLES
TERMINAL BOARD TB No CIRCUIT
AT CT/VT KIOSK /PLCC PANEL INDICATING LAMP

TERMINAL BOARD TB1 CT CIRCUITS


CHANGE OVER CONTACT SEMAPHORE INDICATOR
AT CIRCUIT BREAKER
TB2 VT CIRCUITS
CHANGE OVER CONTACT - TERMINAL BOARD ELECTRIC BELL
HAND RESET FOR BCU I/P & O/P CKTS TB3 AC/DC CIRCUITS I/C
TB4 BUS COUPLER CONTROL CIRCUITS
CHANGE OVER CONTACT - TERMINAL BOARD
ELECTRIC HOOTER
DELAYED PICKUP AT ISOLATOR TB4A TBC CONTROL CIRCUITS
TB5 ANNUNCIATION
CHANGE OVER CONTACT -
BUSWIRE
DELAYED DROP OFF TB7 SPARE CONTACTS

TB8 INTERPANEL WIRING CKTS

TERMINAL BLOCK NO
WIRE CROSS REFERENCE STANDARDS TBRTU RTU CONTACTS
TB1 CCC
WIRE NO
L101 FERRULE NO TYPE 1 WAY NO
20 SHEET NO PANEL TYPE

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852101
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 LIST OF STANDARD SCHEMATIC SYMBOLS DRG. NO.: CPD KW85 SC21 SHT 01 OF 67
BLANK SHEET

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852102
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 BLANK SHEET DRG. NO.: CPD KW85 SC21 SHT 02 OF 67
BLANK SHEET

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852103
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 BLANK SHEET DRG. NO.: CPD KW85 SC21 SHT 03 OF 67
BASE FILE:
MAIN BUS-1 220KV, 3200A, 40KA, 3 sec

FOR ALSTOM REF:

SALES ORDER: -
MAIN BUS-2 220KV, 3200A, 40KA, 3 sec

SCHEME TYPE: FEEDER


TRANSFER BUS 220KV, 3200A, 40KA, 3 sec

2-989A 2-989B 2-989C

ENGG.REF.NO.: KW85
2-952

2-989L

Dated 08.10.2014
2-989LE

P1

P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779
2-9CT
CORE-1

CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD


PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S
RATIO : 1200-600-300/1A 11
METERING
CLASS : 0.5
BURDEN: 15VA
ISF<5

CORE-2

ALSTOM T&D India


RATIO :1200-600-300/1A
CLASS : PS DISTANCE PROTECTION 15
VK >=350/700/1400 MAIN-1
Imag <= 100/50/25mA @ VK
Rct <= 3/6/12 Ohms

ABCD
PALLAVARAM CHENNAI 600043
CORE-3

- Limited - AUTOMATION SAS


RATIO :1200-600-300/1A
CLASS : PS DISTANCE PROTECTION 23
VK >=350/700/1400 MAIN-2
Imag <= 100/50/25mA @ VK
Rct <= 3/6/12 Ohms

CORE-4
PANEL TYPES: 2C1 2R1

RATIO :1200-600-300/1A
SCHEMATIC DRAWING

CLASS : PS
BUSBAR PROTECTION
VK >=350/700/1400
SINGLE LINE DIAGRAM

Imag <= 100/50/25mA @ VK


Rct <= 3/6/12 Ohms
P2
TITLE: 220KV LINE CONTROL & PROTECTION

2-9WT

2-9CVT
FILE: DW852104

220KV LINE CVT.

WDG-1
METERING CKT.& SYNC CKT 11
14
PREPARED BY:

220KV LINE CAPACITOR VT WDG-2


1Ø CVT DISTANCE PROTN MAIN-1
CHECKED BY: JKK

15
APPROVED BY: JKK
GKA

RATIO : 220KV /110V /110V/110V MAIN-2


23
3 3 3 3
WDG-3
BURDEN : 50VA DISTANCE PROTN MAIN-1
CLASS : 0.2/3P/3P 15
MAIN-2
23
2-9LA
SCALE:
REVISION:

--
Z
DATE: 19.03.2015

LINE BAY
DRG. NO.: CPD KW85 SC21 SHT 04 OF 67
2C1

BB2 TB3
TB3A

ACDB/ADJ. PANEL
AC SUPPLY FROM
1H1 1H1 H1 PH

240V. 50HZ.
1 1 1

TB3
TB3A 1H2 1H2 H2 N
2 2
2

1
2 16A 1

LK91
FS91

1
16A 1

1
CIL
H4

FS92

FS93
LK92

LK93
DS

4A
1 2

H3

2
2

2
HS TH HT

H11
H5 H7

H21

H22
H12
1 2 1 2 1 2

PS TO DC FAIL
SW

1 2
06

TO ANNUN
60

2R1
AC SUPPLY FROM
240V. 50HZ.

BB2 TB3
TB3A 1H1 H1
ACDB PANEL

1 1
1H1 1
TB3
TB3A 1H2 H2
2 2 2
1H2

1
2 16A 1

LK94
FS94

1
1
CIL
H14

FS95

LK95
16A
DS

1 2
H13

2
HS TH HT
H15 H17

H19

H18
1 2 1 2 1 2

PS
SW H18
1 2

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852105
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 AC SUPPLY DISTRIBUTION DRG. NO.: CPD KW85 SC21 SHT 05 OF 67
EQPT DCSS EQPT 80A/B/C
TYPE ODS TYPE VAA11
LOC 2C1 LOC 2C1
2C1

INDEPENDENT
SOURCE-2
SOURCE-1
BOARD-1 220V CONTROL
ODS/10/N/90/SP/PM/103
DC SUPPLY-1
+ -
FS TB3 FS101 J25
+VE J11 J13
4 1 2
16A 1P1 1P2
. .

1P3 1P4
FS FS102 J26
-VE J12 J14
5 1 2
16A 2P1 2P2
J15

2P3 2P4
. .

TO DC DISTRIBUTION
BOARD-2 220V CONTROL 3P1 3P2
DC SUPPLY-2 J16
07
+ - 3P3 3P4
FS TB3 FS103
+VE J21 J23
6 1 2
16A 4P1 4P2
FS FS104
-VE J22 J24
7 1 2
16A 4P3 4P4
DC-1 FAIL TEST DC-2 FAIL TEST J15
80A 80B
PB04 PB04 5P1 5P2
J17 J27
1P1 1P2 8 2P1 2P2 8 J16
J14 J24
10 10 5P4
9 9
5P3

DCSS
L255 TO ANNUN
59 L255
5 59 TO ANNUN
5
.
59 .
1 2 59
1 2
H21 DC FAIL LAMP H22
K201 K297A TO MAIN-2 DR
28 28 05 SL51 05
6 7 K201 K297B H22
28 28 TO 80B H23
6 7
MAIN-2 DR 11 1 2
TB7
U2
TB7 EBZ2
U1 SPARE TB7 TB7 H21
1 15 2 U3 U4
14 SPARE 3 4
3 14 15 4 80A 80C H25 __ __ H22
11 5 1 2
. BUZZER FOR
3 4 1 2 DC FAIL AL.

80C
H27
80C
6 7 8 H22
10
DC FAIL ACCEPT .
PB05
H27
1P3 1P4

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852106
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DC DISTRIBUTION & SUPERVISION DRG. NO.: CPD KW85 SC21 SHT 06 OF 67
2C1 2R1

+VE J15 TB8 TB8 J15


1 1
06
-VE J16 J16
2 2

1
1

FS17

FS18
6A

FS19

FS20
6A
FS11

FS15

FS16

6A
FS10

FS12

6A
2 10A

2 10A
FS1

FS5

FS9
FS6
FS2

4A

4A

6A

6A
4A

4A

6A

6A

2
2

K101

K102

K171

K172
K501

K502

K601

K602

K901

K902
L101

L102
K1

K2

TO SYN CKT TO ISOL. TO TRANSDUCER TO DIST. PROTN D/T CH-1


TO CB CLSG& TO ANNUN MAIN-1
TC-1 CKT CKT CONTROL CKT 31
17
38 60 14 49 11 GROUP-A TRIP
34
VOLTAGE SELN CKT
09

+VE J25 TB8 TB8


J25
3 3
06 -VE J26 J26
4 4

1
FS21

FS22
6A

FS23

FS24
6A

6A

6A
1

2
FS13

2
FS14
2 10A

2 10A
FS3

FS7

FS8
FS4

4A

6A
4A

6A

K201

K202

K701

K702
2

2
K802
K801
K52
K51

L2
L1

TO DIST. PROTN 31
TO CB TC-2 TO INDICATION TO AUX.RELAY MAIN-2 D/T CH-2
CKT CONTROL CKT CON.MUL.CKT 27
GROUP-B TRIP
40 54 44
35

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852107
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DC DISTRIBUTION DRG. NO.: CPD KW85 SC21 SHT 07 OF 67
R Y B

2- 9WT

RATIO: 220KV 110V 110V 110V


3 3 3 3
CONNECTION:
Ua

WDG: 1 WDG: 2 WDG: 3


N
BURDEN: 50VA BURDEN: 50VA BURDEN: 50VA
CLASS:0.2 CLASS:3P CLASS:3P

220KV LINE

HRC
FUSE

BMK

2C1 2R1
TB2

TB2

TB2
29

30

33

34
2
1

E181L
E121L
E171L
E111L

.
.
R N R N R N

TO SYNCH. SCHEME 14
TO IND VOLTMETER 13 TO DISTANCE PROTN. 15
MAIN-1 & MAIN-2

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852108
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 220KV LINE VT CIRCUIT DRG. NO.: CPD KW85 SC21 SHT 08 OF 67
EQPT 75A,B,C,D
TYPE MVAJM14
LOC 2R1
2R1

07

+VE

NIX1 89AX2
75B
K101 K101B K275 K288A K102
O O 28
66 45 10 27
75A

89AX2
K276 K102
R 26
45 25

2RP3 75A
ITX1 ITX2
TB4A 89AX TB4A
K101 X4-A X4-A
K286C K275A 75D
67 5 6 67 K286A K102
1 2 89AX2 O O 28
ITX2 10 27
X4-A 89AX X4-A TB4A
K276B 75C
7 8 67 45
3
ITX2
TB4A X4-A 89BX X4-A TB4A ITX2
K101 K102
K286E K285 R
9 10 25 26
67 67
52 4 89BX2
X4-A 89BX X4-A ITX2 75C
TB4A
K286B
11 12 67 46
5
REF. DWG. G719EA-
YC9029-WC203-B SHT. 23,24

NIX1 89BX2 75B


75A
K101 K101C K286 K288B K102
O O 28
66 46 10 27

89BX2
K285A
R 26
46 25
75B

75C
K286D K102
27
O O 28
10
75D

K102
R 26
25
75D

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852109
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 VOLTAGE SELECTION CKT DRG. NO.: CPD KW85 SC21 SHT 09 OF 67
2R1
TB2 75A 75B TB2

VT SUPPLY (METERING CORE)

VT SUPPLY (METERING CORE)


BB1 BB1
1E111 R 1E111 E111 E11 E11 E211 R 1E211 1E211

FROM EXISTING PANEL


FROM EXISTING PANEL
220KV BUS-1 CORE-1
9 11 9 11

220KV BUS-2 CORE-1


1 13
TB2 1 75A 75B TB2 13
1E131 Y 1E131 E131 E31 E31 E231 Y 1E231 1E231
2 13 15 13 15 14
TB2 2 75A 75B TB2 14
1E151 B 1E151 E151 E51 E51 E251 B 1E251 1E251
3 17 19 17 19 15
TB2 3 75A 75B TB2 15
1E171 N 1E171 E171 E71 E71 E271 N 1E271 1E271
4 1075A 12 10 12 16
4 75B 16
.

TB2
. . .

25

26

27

28
18 75A20 18 20
TO ADJ. PANEL

TO ADJ. PANEL
L1 L61
75B
L1 L63
55 14 75A 16 55 TO IND. CKT 55 14 75B 16 55 TO IND. CKT

6 8
75A TO METERING CIRCUIT
& SYN .SCHEME
6 75B 8
5 7 11 5 75B 7
75A
K286 K288B K275 K288A
09 1 3 09 TO VOLTAGE SEL. 09 1 3 09 TO VOLTAGE SEL.

TO ADJ. PANEL
TO ADJ. PANEL

75A 75B
TB7 U9 TB7 TB7 U11 TB7
U10 U12 SPARE
SPARE TO DIST PROTN MAIN-1
12 4 2 32 4 4
14 15
BB1 TB2 75C 75D TB2 BB1
1E121 R 1E121 E121 E21 E21 E221 R 1E221 1E221
5 7 5 7
VT SUPPLY (PROTN CORE)

5 17
TB2 5 75C 75D TB2 17
FROM EXISTING PANEL
220KV BUS-1 CORE-2

VT SUPPLY (PROTN CORE)


Y

FROM EXISTING PANEL


1E141 1E141 E141 E41 E41 E241 Y 1E241 1E241

220KV BUS-2 CORE-2


6 6 8 6 8 18
TB2 6 TB2 18
75C 75D
1E161 B 1E161 E161 E61 E61 E261 B 1E261 1E261
7 TB2 9 75C 11 9 75D 11 TB2 19
N 7 19
1E181 1E181 E181 E81 E81 E281 N 1E281 1E281
8 10 12 10 12 20
TB2 8 TB2 20
BB1 75C 75D BB1
1E116 R 1E116 E116 E16 E16 E216 R 1E216 1E216
9 13 15 13 15 21
9 21

TB2

VT SUPPLY (PROTN CORE)


75C 75D TB2

FROM EXISTING PANEL


220KV BUS-2 CORE-3
1E136 Y 1E136 E136 E36 E36 E236 Y 1E236 1E236
10 14 16 14 16 22
10 22
VT SUPPLY (PROTN CORE)
FROM EXISTING PANEL
220KV BUS-1 CORE-3

TB2 75C 75D TB2


1E156 B 1E156 E156 E56 E56 E256 B 1E256 1E256
11 17 19 17 19 23
11 23

TB2 75C 75D TB2


1E176 N 1E176 E176 E76 E76 E276 N 1E276 1E276
12 18 20 18 20 24
12 24
75C 75D
TO DIST PROTN MAIN-2 23
K286 K286D K275 K286A
09 1 75C 3 09
TO VOLTAGE SEL. 09 1 TO VOLTAGE SEL.
75D 3 09

TO ADJ. PANEL
2 4 2 4
TO ADJ. PANEL

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852110
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 VOLTAGE SELECTION CKT DRG. NO.: CPD KW85 SC21 SHT 10 OF 67
EQPT W/VAR EQPT WT/VART
TYPE METER TYPE TRANSDUCER
LOC 2C1 LOC 2C1
BUS SIDE
2C1
BMK
P1
TB1 D13
D11
1
12

2 D33
D31 12
3

4 D53
D51 12
5

6 D71
D71
12
7
D71S
8

P2

LINE SIDE

K901

K902

K901

K902
D11

D12

D31

D32

D51

D52

D12

D13

D32

D33

D52

D53
1 2 3 4 5 6 16 15 1 2 3 4 5 6 16 15
CORE-1
RATIO : 1200-600-300/1A WT VART
CLASS : 0.5
BURDEN: 15VA OUTPUT-1 OUTPUT-2 OUTPUT-1 OUTPUT-2
ISF<5 9 10 11 12 14 13 8 7 9 10 11 12 14 13 8 7
E113

E133

E153

E173

E113

E133

E153

E173
S3

S7
S4

S8
S1

S5
S2

S6
(125/250-0-125/250MVAR)
(125/250-0-125/250MW)

TBRTU

TBRTU
11

13
12

14
1

1
VAR
W
TO RTU/SCADA TO RTU/SCADA
2

2
S2

S6
K901 K901
+VE
07 12
K902 K902
-VE
07 12
TB2
E11 FS113 E113
E113
R 13
1 2
4 2A
FROM 220KV SELECTED

TB2 FS133 E133


BUSVT SUPPLY

Y E31 E133
13
1 2
5 2A
B TB2
E51
FS153 E153
E153
10 1 2 13
6 2A
TB2 LK173 E173
N E71 E173 13
1 2
7

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852111
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 METERING CKT DRG. NO.: CPD KW85 SC21 SHT 11 OF 67
EQPT AT-1,2,3
TYPE TRANSDUCER
LOC 2C1
EQPT A1,A2,A3
2C1
TYPE METER
LOC 2C1

K901 K901
11 +VE 13
220V DC K902
K902 -VE
11 13

D13 D15
11 13

D33 D35
11 13

CT SUPPLY D55
D53
11 13

D71 D71
11 13
K901

K902

K901

K902

K901

K902
D13

D15

D33

D35

D53

D55
1 2 16 15 1 2 16 15 1 2 16 15

AT1 AT2 AT3


OUTPUT-1 OUTPUT-2 OUTPUT-1 OUTPUT-2 OUTPUT-1 OUTPUT-2
10 9 14 13 10 9 14 13 10 9 14 13
S16

S20

S24
S15

S19

S23
S14

S18

S22
S13

S17

S21
TBRTU

TBRTU

TBRTU
15

17

19
16

18

20
TO RTU/SCADA TO RTU/SCADA TO RTU/SCADA
1 1 1

A1 A2 A3
S14

S18

S22
2 2 2

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852112
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 METERING CKT DRG. NO.: CPD KW85 SC21 SHT 12 OF 67
2C1

K901
220V DC
12 K902

TTB
D16
D15 1
2 D71
3
D36 08
CT SUPPLY 4
D35
12 5 D71
6
D56
D55 7
8 D71
9

1
D71

1
FS25

LK25
2A
D71
D71

D56
D36
D71
D16

2
TBRTU

K901

K902
K902 S28

OUTPUT-2

E12

E72
15

13

TO RTU
1S 1L 2S 2L 3S 3L
21

K901 S27 TVM 7 8 16 15

16

14
V2
B
22

E377 S26 VLT

OUTPUT-1
8

9
VBT
N
VS

R Y B
Y

OUTPUT-1 OUTPUT-2
E378 S25 1 2

10
VB 10 9 14 13

S38
S37
S36
R

(0-250KV)

S35
V1
N

TBRTU

23

24
E378

E114

E134

E154

E174

(0-250KV)

1
E113 A2 A1

VL
TO RTU/SCADA

2
SELECTED BUS E133 B2 B1
VT SUPPLY
11 TTB
E153 C2 C1

E173 N2 N1

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852113
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 METERING CKT DRG. NO.: CPD KW85 SC21 SHT 13 OF 67
2C1

CHK SYN

BYPASS
OFF
E11 FS74 G21 G22 RUNNING BUS
R
220KV SELECTED 1
2A
2
BUSVT SUPPLY
E71 LK74 G81 G72
COMMON NEUTRAL
10 N 1 2

E111L FS75 G11 INCOMING BUS


R G12
220KV LINE 1 2
2A
VT SUPPLY
E171L LK75 G71 CLOSING I/L
08 N 1 2

K10 K12
CB CLOSING K11 G12
I/L CKT
. 12
38 11 1 G72

10 2
K501 K503 G22
SYNCH 7 SS 3
DC SUPPLY
K502 K504 8 4
07
T NC 9 5
K507 K505 6
CS1 63
SSS
63

N I T 2CP3
BB2
E111T E111T TB2 X12

65 65 5 9
5
TO TBC
BB2 SYNC. SCHEME
E171T E171T TB2

65 65 6 10
6

TTS REF. DWG. (4) - G719EA-


YC9029-WC203-B SHT. 10

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852114
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 SYNCHRONISING CKT DRG. NO.: CPD KW85 SC21 SHT 14 OF 67
2R1 EQPT 21M1
TYPE MICOMP444
BUS SIDE
LOC 2R1
P1
BMK MiCOM P444
TB1 A11 BLKA 21M1
R A12 C3
A72
C2
1 S3 R3

2 BLKA
Y A31 A32
C6 C5
3 S4 R4

4 BLKA A52
B A51
R5 C9 C8
5 S5

6 A71 BLKA A72


N
7 S6 R6 NOTE: NEUTRAL DR CURRENT
8
CAN
. BE DERIVED INTERNALLY

TB1
C11 A75
9

C12 A74
10

P2

LINE SIDE TB1


A73
CORE-2 11
RATIO :1200-600-300/1A A71
CLASS : PS 12
VK >=350/700/1400
Imag <= 100/50/25mA @ VK
Rct <= 3/6/12 Ohms

FS211 21M1
R E21 E123 BLKA E124 C19
1 2 S7 R7
2A
FOR MUTUAL
220KV SELECTED Y FS411 E143 BLKA E144
E41 C20 COMPENSATION
BUSVT SUPPLY 1 S8 R8
2A 2 FROM PARALLEL LINE
FS611 E163 BLKA E164 (IF APPLICABLE)
10 B E61 C21
1 2 S9 R9
2A

N E81 LK811 E183 BLKA E184


C22
1 2 S10 R10

FS121 E22 BLKB E23


E121L C23
220KV LINE 1 2 S7 R7
2A
VT SUPPLY
E181L
LK181 E82 BLKB E83 C24
08 1 2 S8 R8

TO MAIN-2
23 PROTECTION

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852115
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DISTANCE PROTECTION (MAIN-1) - AC CIRCUIT DRG. NO.: CPD KW85 SC21 SHT 15 OF 67
OUTPUT CONFIGURATION OUTPUT CONFIGURATION INPUT CONFIGURATION

OUTPUT No. ASSIGNMENT OUTPUT No. ASSIGNMENT INTPUT No. ASSIGNMENT

OUTPUT - RL1 A/R LOCKOUT - TO ANNUN OUTPUT - RL36 LBB INI TO TBC BUSBAR - R PH INPUT - 1 MAIN / TBC CB 'R' PHASE OPEN
OUTPUT - RL2 DIST PROT OPTD - TO ANNUN OUTPUT - RL37 LBB INI TO TBC BUSBAR - Y PH INPUT - 2 MAIN / TBC CB 'Y' PHASE OPEN
OUTPUT - RL3 POWER SWING BLOCK ALARM - TO ANNUN OUTPUT - RL38 LBB INI TO TBC BUSBAR - B PH INPUT - 3 MAIN / TBC CB 'B' PHASE OPEN
OUTPUT - RL4 SOTF OPERATED - TO ANNUN OUTPUT - RL39 SPARE INPUT - 4 HMI BLOCK
OUTPUT - RL5 OVER VOLTAGE OPTD - TO ANNUN OUTPUT - RL40 SPARE INPUT - 5 BUSBAR PROTN OPTD
OUTPUT - RL6 VT FUSE FAIL - TO ANNUN OUTPUT - RL41 SPARE INPUT - 6 BAY IN INTER MODE
OUTPUT - RL7 BROKEN CONDUCTOR ALARM - TO ANNUN OUTPUT - RL42 TO TBC LBB TRIP INPUT - 7 BAY IN TRANSFER MODE
OUTPUT - RL8 A/R OPERATED - TO ANNUN OUTPUT - RL43 TC-2 R PH TRIP - TBC CB INPUT - 8 TC-1 FAULTY
OUTPUT - RL9 POWER SWING TRIP - TO ANNUN OUTPUT - RL44 TC-2 Y PH TRIP - TBC CB INPUT - 9 LBB START
OUTPUT - RL10 CARRIER FAIL CH-1 - TO ANNUN OUTPUT - RL45 TC-2 B PH TRIP - TBC CB INPUT - 10 DIRECT TRIP SEND CH-1
OUTPUT - RL11 CARRIER SEND CH-1 TO ANNUN OUTPUT - RL46 TO RELAY TEST KIT INPUT - 11 AUTO RECLOSE IN
OUTPUT - RL12 CARRIER RECEIVE CH-1- TO ANNUN. INPUT - 12 MAIN-2 OPTD
OUTPUT - RL13 LBB PROTN OPTD - TO ANNUN INPUT - 13 CARRIER HEALTHY CH- 1
OUTPUT - RL14 CARRIER SEND (CHANNEL-1) INPUT - 14 CARRIER RECEIVED CH -1
OUTPUT - RL15 TC-1 R PH TRIP - MAIN CB INPUT - 15 CARRIER HEALTHY CH- 2
OUTPUT - RL16 TC-1 Y PH TRIP - MAIN CB INPUT - 16 D/T RECEIVED CH -1
OUTPUT - RL17 TC-1 B PH TRIP - MAIN CB INPUT - 17 MAIN CB READY FOR CLOSE
OUTPUT - RL18 TC-1 R PH TRIP - TBC CB INPUT - 18 MAIN CB LOCK OUT
OUTPUT - RL19 TC-1 Y PH TRIP - TBC CB INPUT - 19 LBB INITIATION 'R' PHASE-FROM MAIN-2
LED CONFIGURATION
OUTPUT - RL20 TC-1 B PH TRIP - TBC CB INPUT - 20 LBB INITIATION 'Y' PHASE-FROM MAIN-2
(USER PROGRAMMABLE LED's)
OUTPUT - RL21 DIRECT TRIP SEND CH-1 INPUT - 21 LBB INITIATION 'B' PHASE-FROM MAIN-2
OUTPUT - RL22 LBB INI. TO MAIN CB BUSBAR R-PH LED REF FUNCTION INPUT - 22 MAIN / TBC SOTF INI
OUTPUT - RL23 LBB INI. TO MAIN CB BUSBAR Y-PH INPUT - 23 MAIN / TBC LBB TRIP OPTD
R-PH FAULT
OUTPUT - RL24 LBB INI. TO MAIN CB BUSBAR B-PH INPUT - 24 3-PH TRIP RELAY OPTD
OUTPUT - RL25 DT SEND CH-2 Y-PH FAULT
OUTPUT - RL26 AUTO RECLOSE-TO TBC CB LED CONFIGURATION
(A/R L/O, POWER SWING,
B-PH FAULT (DEDICATED LED's)
OUTPUT - RL27 TO GRP-A TRIP RELAY MU.PH/Z2,Z3, O/V FAULTS)
OUTPUT - RL28 CB CLOSING CKT - AUTO RECLOSE LED REF FUNCTION
Z1 OPTD.
OUTPUT - RL29 MAIN-1 OPTD TO MAIN-2
OUTPUT - RL30 LBB TRIP RELAY Z2 OPTD. TRIP

OUTPUT - RL31 TO TBC BUSBAR LBB START


Z3 OPTD. ALARM
OUTPUT - RL32 TO BB PU LBB START
OUTPUT - RL33 TC-2 R PH TRIP - MAIN CB SOTF OPTD. OUT OF SERVICE
OUTPUT - RL34 TC-2 Y PH TRIP - MAIN CB
CARRIER AIDED TRIP RELAY HEALTHY
OUTPUT - RL35 TC-2 B PH TRIP - MAIN CB

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852116
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DISTANCE RELAY LED CONFIGURATION (MAIN-1) DRG. NO.: CPD KW85 SC21 SHT 16 OF 67
2R1

07 21M1 07

BASE FILE:
+VE -VE
K101 - K102

FOR ALSTOM REF:


+N2 -N1

SALES ORDER: -
-

SCHEME TYPE: FEEDER


AUX.VOLTAGE

K109 K102
D2 D1

ENGG.REF.NO.: KW85
20 MAIN /TBC CB R PHASE
L1 OPEN

K111
20 D4 D3
MAIN /TBC CB Y PHASE
L2 OPEN

K113
20 D6 D5 MAIN /TBC CB B PHASE

Dated 08.10.2014
L3 OPEN

FS33 K115
2 D8 D7 HMI BLOCK
1 4A
L4

K117 BUSBAR PROTN OPTD

P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779
19 D10 D9

L5

CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD


PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S
IX1
K119
D12 D11 BAY IN INTER MODE
47
L6
2C1
TB8 TB8 TB8 TB8 K121 BAY IN TRANSFER MODE
K121 D14 D13

ALSTOM T&D India


65
5 5 6 6 L7
TTS

195R/Y/B K123
D16 D15 TC-1 FAULTY
39

ABCD
L8

PALLAVARAM CHENNAI 600043


- Limited - AUTOMATION SAS
86BX
21M1
35
21M2 K102
K125 E2 E1 LBB START
29
86AX
L9
34
SX1
K127 DIRECT TRIP SEND CH-1
E4 E3
32
PANEL TYPES: 2C1 2R1

L10
SCHEMATIC DRAWING

IN OUT
K129 E6 E5 AUTO RECLOSE IN
64
ARS L11

21M2
K131
TITLE: 220KV LINE CONTROL & PROTECTION

E8 E7 MAIN-2 OPTD
29
L12
PLCC PANEL- CARRIER CH-1
TB4 CARRIER HEALTHY TB4 FS28
FILE: DW852117

K133
FS27 E10 E9 2 CARRIER HEALTHY CH- 1
1 4A
1 2 1 2
4A L13

IN OUT CARR.RECEIVE
K145A TB4 TB4
K135
PREPARED BY:

E12 E11 CARRIER RECEIVED CH -1


3 (CODE-1) 4
CSS1 L14
CHECKED BY: JKK
APPROVED BY: JKK
GKA

64 PLCC PANEL- CARRIER CH-2


IN OUT
TB4 CARRIER HEALTHY TB4
K145B K137 CARRIER HEALTHY CH- 2
E14 E13
5
6
CSS2 L15
64
21 RX1
REVISION:

SCALE: --
DISTANCE PROTECTION (MAIN-1) - DC OPTO I/P CKT DRG. NO.: CPD KW85 SC21 SHT 17

K139
E16 E15 D/T RECEIVED CH -1
Z

31
L16 18
DATE: 19.03.2015

18
OF 67
LBB INITATION 'Y' FROM MAIN-2

LBB INITATION 'B' FROM MAIN-2


LBB INITATION 'R' FROM MAIN-2

MAIN / TBC LBB TRIP OPTD

3-PH TRIP RELAY OPTD


MAIN / TBC SOTF INI
READY FOR CLOSE
MAIN CB/TBC CB

MAIN CB / TBC CB
SF6 LOCK OUT
K102
17

47
K102

K102

K102

K102

K102

K102

K102
F11

F13

F15
F1

F3

F5

F7

F9
21M1

L17

L18

L19

L20

L21

L22

L23

L24
F10

F12

F14

F16
F2

F4

F6

F8
K143

K147

K153

K155
K145

K149
K141

K151
19

20
19

19
19
30
30
30

86Y2
86R2

86B2

19 47
K101
2R1

17

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852118
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DISTANCE PROTECTION (MAIN-1) - DC OPTO I/P CKTDRG. NO.: CPD KW85 SC21 SHT 18 OF 67
2R1

18
86AX
K101 K155 3PH TRIP RELAY OPTD
34 18

86BX

35
FROM TBC PANEL

ITX1 86 TBC ITX1


K159 TB4A X4A X4A
TB4A
K113A
11 12
67 FROM B/B PANEL(BB1) 67
6 7
24PU
TB4 TB4
FROM B/B PANEL(BB1) REF CPD KW85 SCXX SHT 25
7 8
20
3PU ITX1
TB4A K105H K117
BUSBAR PROTN OPTD
67 17
REF CPD KW85 SCXX SHTXX 8

96A ITX1
X4A X4A TB4A K105J
29 30
REF. DWG. (4) - G719EA- 67
9
YC9029-WR203-B SHT. 14, 15 96
K101 K153
MAIN CB/ TBC LBB OPTD
37 18
2- 52
NIX1 TB4 X1-64 X1-63 TB4
K199A K141 CB READY FOR A/R
10 CB READY
66 44 43 18
2-52 TBC CB 11

ITX1
TB4A K105G
20
CB READY 11 67

ITX1
K199C TB4A X1-110 X1-109 TB4
K143
10
MAIN CB/TBC SF6 LOCK OUT
67 18
44 43 12

REF. DWG. (4) - G71AHS


DA403 W455-A- SHT. 03

ITX1
TB4A K105N
12 67

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1
CHECKED BY: JKK
FILE: DW852119
DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DISTANCE PROTECTION (MAIN-1) - DC OPTO I/P CKTDRG. NO.: CPD KW85 SC21 SHT 19 OF 67
2R1

19
FROM TBC PANEL 2C1
220KV TBC CB
TB4A TB4A N I T TB8 TB8
K159 K141T
13 1 54 54

TB4A K143T TB8 TB8


2 55 55

TB4A K147T TB8 TB8


3 56 56

65

X4A T N C X4A TB4A ITX1


K105M
21 22 14
19 REF. DWG. (4) - G719EA- 67
YC9029-WC203-B SHT. 26

2C1
T N C
K199A TB8 TB8 TB8 TB8 K151
7 7 8 8
18 MAIN / TBC CB SOTF INI
CS1 63

2-52
220KV MAIN CB
S1LA-9 S1LA-10 TB4 NIX1
K141A K109
17 MAIN / TBC CB R-PH OPEN
13
122 121

S1LB-9 S1LB-10 TB4 K143A K111


17 MAIN / TBC CB Y-PH OPEN
14
122 121

S1LC-9 S1LC-10 TB4


K113
K147A
17 MAIN / TBC CB B-PH OPEN
15
122 121
66

REF. DWG. (4) - G71AHS


DA403 W455-A- SHT. 04

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1
CHECKED BY: JKK
FILE: DW852120
DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DISTANCE PROTECTION (MAIN-1) - DC OPTO I/P CKTDRG. NO.: CPD KW85 SC21 SHT 20 OF 67
2R1

BASE FILE:
21M1

FOR ALSTOM REF:

SALES ORDER: -
58 L201 N11 L243 58
N12 TO ANNUNCIATION

SCHEME TYPE: FEEDER


WD1
(RELAY INOPERATIVE)

N13 N14
WD2

TO ANNUN.
L201 M1 L215 57
57 RL1 M2 A/R LOCKOUT

ENGG.REF.NO.: KW85
TO ANNUN.
L203 57
M3 M4 DIST PROTN OPTD
RL2
TO ANNUN.
M5 L225 57
RL3 M6 POWER SWING BLOCK

RL4 TO ANNUN.
M7 M8 L227
58 58 SOTF OPTD

Dated 08.10.2014
L201 RL5 TO ANNUN.
M9 M10 L229
58
O/V OPTD

RL6 L233 TO ANNUN.


M11 M12
58
VT FUSE FAIL
M14 L253 TO ANNUN.

P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779
59
RL7 BROKEN CONDUCTOR ALARM
M15 M13

CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD


PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S
M17 L251 TO ANNUN.
59 AUTO RECLOSE
M18 RL8 M16

L211 TO ANNUN.
L1 L2

ALSTOM T&D India


RL9 57 POWER SWING TRIP OPTD.

59 L201 L3 L263 TO ANNUN.


L4 59
RL10 CARRIER FAIL CH-1

ABCD
RL11 TO ANNUN.
L5 L259

PALLAVARAM CHENNAI 600043


L6 59 CARRIER SEND CH-1

RL12

- Limited - AUTOMATION SAS


L261 TO ANNUN.
L7 L8 59 CARRIER RECEIVED CH-1

RL13 TO ANNUN.
L9 L213
L10 57 LBB PROTN OPTD

K101D IN OUT RL14


K111B K320
TB4 CARRIER SEND (CHANNEL-1)
17 L11 L12
PANEL TYPES: 2C1 2R1

PLCC PANEL
16
SCHEMATIC DRAWING

CSS1
L14 K3A
64
RL15
K1A BLKA L13
K13 L15
39
S1 R1
K3B
NOTE: "RL14" SHOULD OPERATE IN 'I-T' POSITION OF TTS SWITCH WHICH IS GIVEN TO THE OPTO OF MAIN-1

L17 TO TC-1 TRIP


RL16 (MAIN CB)
L18 L16
TITLE: 220KV LINE CONTROL & PROTECTION

39

K1 K3C
K2
RL17
FILE: DW852121

K1T RL18
BLKB K403A
41 K407 K3
S5 R5 K4
DISTANCE PROTECTION (MAIN-1) - OUTPUT CONTACTS

TO TC-1 TRIP
RL19
(TBC CB)
K403B
PREPARED BY:

K5 K6 41
CHECKED BY: JKK
APPROVED BY: JKK
GKA

RL20
K7 K403C
K8

RL21
K171 K187
K9 K10 32
32 DIRECT TRIP SEND CH-1
REVISION:

SCALE: --

DRG. NO.: CPD KW85 SC21 SHT 21


Z
DATE: 19.03.2015

OF 67
21M1 2R1
RL22

BASE FILE:
P141A K12 P111A
42 K11

FOR ALSTOM REF:


K14 P113A LBB INITIATION

SALES ORDER: -
SCHEME TYPE: FEEDER
RL23 TO MAIN CB BUSBAR
K15 K13
42
P115A
K17

K18 RL24
K16

RL25
K701 J1
K787
33 J2 33 DT SEND CH-2
RL26
1K15 1K17A TO TBC CB
43 J3 J4 43 AUTO RECLOSE LOCKOUT

ENGG.REF.NO.: KW85
K101 RL27
BLKA
34 K101A J5 K103 34 TO GRP-A TRIP RELAY
S2 R2 J6
(A/R L/O, POWER SWING,
RL28 MU.PH/Z2,Z3, O/V FAULTS)
K7
J7 K14 TO CB CLOSING CKT
38 J8 38
(AUTO RECLOSE )
RL29
K201 K229 TO MAIN-2
27 J9 J10 27 (MAIN-1 OPTD)
P1 RL30

Dated 08.10.2014
BLKB P15C P153
37 J11 J12 37 TO LBB TRIP RELAY
S2 R2

RL31 TO TBC CB BUSBAR PU


J14 P123C
42 LBB START
P143C J15 J13
42

J17 P121A TO MAIN CB BUSBAR PU

P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779
42 LBB START
P143A J18 RL32 J16
42

CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD


PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S
RL33
K51A BLKB K55 H1
K53A
40 H2
S6 R6

RL34
TO TC-2 OF
H3
K53B 40 MAIN CB
H4

ALSTOM T&D India


RL35
H5
K53C
H6

.
H8

ABCD
H9 RL36 P115C
P143C H7
42

PALLAVARAM CHENNAI 600043


H11 P117C LBB INITIATION
P143C
TO TBC CB BUSBAR PU
H12 RL37 H10 . 42

- Limited - AUTOMATION SAS


H14 P119C

H15 RL38 H13

H17 1K15A

H18 RL39 H16


1K15
PANEL TYPES: 2C1 2R1

43
SCHEMATIC DRAWING

RL40 A/R INITIATION


G1
1K15B TO TBC CB
G2
43
RL41
G3
1K15C
G4
RL42 TO TBC
P155
LK153 P153A
41 G5
P151B 41
1 G6 96 LBB TRIP RELAY
TITLE: 220KV LINE CONTROL & PROTECTION

G8 K453A
K51T BLKB .
41 RL43
S10 R10 G9 G7
FILE: DW852122

TO TC-2 OF
DISTANCE PROTECTION (MAIN-1) - OUTPUT CONTACTS

G11 K453B
TBC BKR
RL44 41
G12 G10
PREPARED BY:
CHECKED BY: JKK

G14
APPROVED BY: JKK

K453C
GKA

RL45
G15 G13

G17 K197A TB4


TO RELAY TEST KIT RESET
TB4 RL46 18
K195A G18 G16
REVISION:

SCALE: --

DRG. NO.: CPD KW85 SC21 SHT 22

17
Z
DATE: 19.03.2015

OF 67
EQPT 21M2
BUS SIDE 2R1
TYPE D60
P1 BMK LOC 2R1
TB1 BLKC
A21 A23 21M2 F1b
A85
13 S3 R3 F1c

14 BLKC
A41 A43
F2c F2b
15 S4 R4

16
BLKC
A61 A63 F3b
R5
F3c NOTE: NEUTRAL DR CURRENT
17 S5
CAN BE DERIVED INTERNALLY
18 BLKC .
A81 A83 A85
19 S6 R6
TB1
A87
20 F4c 21
A89
F4b
22 **

TB1
P2
23
LINE SIDE
TB1
CORE-3 24
RATIO :1200-600-300/1A D60 FOR MUTUAL
CLASS : PS COMPENSATION
E16 FS311 BLKC 21M2
VK >=350/700/1400 E118 E119 FROM PARALLEL LINE
F5a
Imag <= 100/50/25mA @ VK 1 2 S7 R7 E179
2A F7c (IF APPLICABLE)
Rct <= 3/6/12 Ohms FS331
220KV SELECTED BLKC E139
E36 E138
F6a F6c
E179
BUSVT SUPPLY 1 2 S8 R8
2A
10
E56
FS351 E158 BLKC E159
F7a E179
F5c
1 2 S9 R9
2A

E76 LK371 E178 BLKC E179


1 S10 R10 .
2

E121L FS26 E25 BLKD E27


220KV LINE F8a
1 2 S5 R5
VT SUPPLY 2A
15 E181L LK85 E85 BLKD E87
F8c
1 2 S6 R6

TO NO VOLT 2RP3
36 RELAY
X2
1
ITX2 TO TBC
E121T
TB2
A/R RELAY
67
ITX2 31 2
E181T REF. DWG. (4) - G719EA-
67 YC9029-WR203-B SHT. 10
32

NOTE:- ** SHORTING LINKS WILL BE REMOVED IN FUTURE IF PARALLEL LINE IS RUNNING

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852123
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DISTANCE PROTECTION (MAIN-2) - AC CIRCUIT DRG. NO.: CPD KW85 SC21 SHT 23 OF 67
OUTPUT CONFIGURATION

OUTPUT No. ASSIGNMENT INPUT CONFIGURATION

OUTPUT - RL1 A/R LOCKOUT -TO ANNUN INTPUT No. ASSIGNMENT


OUTPUT - RL2 DIST PROTN OPTD-TO ANNUN
SLOT- X31,32
OUTPUT - RL3 POWER SWING BLOCK- TO ANNUN
LED REF FUNCTION LED REF FUNCTION
OUTPUT - RL4 SOTF OPERATED - TO ANNUN INPUT - 1 MAIN / TBC CB R-PH OPEN
OUTPUT - RL5 OVER VOLTAGE OPTD - TO ANNUN INPUT - 2 MAIN / TBC CB Y-PH OPEN
R-PH FAULT SOTF OPTD.
OUTPUT - RL6 VT FUSE FAIL- TO ANNUN INPUT - 1 MAIN / TBC CB B-PH OPEN
OUTPUT - RL7 BROKEN CONDUCTOR ALARM - TO ANNUN Y-PH FAULT A/R OPTD. INPUT - 4 HMI BLOCK
OUTPUT - RL8 AUTO RECLOSE - TO ANNUN INPUT - 5 RESET LATCHED CONTACTS
B-PH FAULT A/R LOCKOUT/BLOCK
OUTPUT - RL9 POWER SWING TRIP - TO ANNUN INPUT - 6 BAY IN TRANSFER MODE
OUTPUT - RL10 CARRIER FAIL CH-2- TO ANNUN INPUT - 7 BAY IN INTER MODE
Z1 OPTD VT FUSE FAIL
OUTPUT - RL11 CARRIER SEND CH-2- TO ANNUN INPUT - 8 TC-2 FAULTY
OUTPUT - RL12 CARRIER RECEIVED CH-2- TO ANNUN Z2 OPTD SPARE INPUT - 9 SPARE
OUTPUT - RL13 SPARE INPUT - 10 DIRECT TRIP SEND CH-2
Z3 OPTD SPARE
OUTPUT - RL14 SPARE INPUT - 11 AUTO RECLOSE IN
OUTPUT - RL15 TC-1 R PH TRIP - MAIN CB INPUT - 12 MAIN-1 OPTD
DIRECT TRIP SPARE
OUTPUT - RL16 TC-1 Y PH TRIP - MAIN CB INPUT - 13 CARRIER HEALTHY CH-2
OUTPUT - RL17 TC-1 B PH TRIP - MAIN CB CARRIER AIDED TRIP INPUT - 14 CARRIER RECEIVED CH-2
OUTPUT - RL18 TC-1 R PH TRIP - TBC CB INPUT - 15 CARRIER HEALTHY CH-1
OUTPUT - RL19 TC-1 Y PH TRIP - TBC CB INPUT - 16 D/T RECEIVED CH-2
OUTPUT - RL20 TC-1 B PH TRIP - TBC CB INPUT - 17 MAIN / TBC CB READY FOR CLOSE
OUTPUT - RL21 TO CONTACT MULTI. INPUT - 18 MAIN / TBC CB SF6 LOCK OUT
OUTPUT - RL22 TO CONTACT MULTI. INPUT - 19 DC SOURCE-1 FAIL
OUTPUT - RL23 TO CONTACT MULTI. INPUT - 20 DC SOURCE-2 FAIL
OUTPUT - RL24 TO RESET TEST KIT INPUT - 21 SPARE
OUTPUT - RL25 DIRECT TRIP SEND CH-2- INPUT - 22 MAIN / TBC CB SOTF INI
OUTPUT - RL26 TO TBC CB AUTO RECLOSE LOCKOUT INPUT - 23 MAIN / TBC /BB PROTN OPTD/LBB TRIP RELAY OPTD
OUTPUT - RL27 GRP-B TRIP RELAY (A/R L/O, PS, MU.PH/Z2,Z3 FAULTS) INPUT - 24 3-PH TRIP RELAY OPTD
OUTPUT - RL28 CB AUTORECLOSE
OUTPUT - RL29 MAIN-2 OPTD TO MAIN-1
OUTPUT - RL30 TO BUSBAR PU TRIP RELAY
OUTPUT - RL31 DIRECT TRIP SEND CH-1
OUTPUT - RL32 CARRIER SEND (CHANNEL-2) PLCC PANEL
OUTPUT - RL33 TO MAIN-1 LBB START
OUTPUT - RL34 TO TBC CB BUSBAR PU LBB START

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852124
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DISTANCE RELAY LED CONFIGURATION (MAIN-2) DRG. NO.: CPD KW85 SC21 SHT 24 OF 67
2R1

27
86BX
K201 K253 3PH TRIP RELAY OPTD
35 28

86AX

34
FROM TBC PANEL

ITX3 86 TBC ITX4


K225 TB4A X4A X4A
TB4A
K225A
13 14
67 67
15 16
BB1
24PU
TB4 TB4
26 BB1 REF CPD KW85 SCXX SHT 25
22 23
PU ITX3
TB4A K251
K225B MAIN / TBC CB BB PROTN/
28
67 LBB TRIP RELAY OPTD
17
96A ITX4
X4A X4A TB4A K225C
31 32
67
18
REF. DWG. (4) - G719EA- 96
YC9029-WR203-B SHT. 14, 15
K201
37
2- 52
NIX2 TB4 X1-66 X1-65 TB4
K265 K241 CB READY FOR A/R
19 CB READY 20
66 54 53
28

X1-112 X1-111 TB4


26 K291 MAIN CB/TBC SF6 LOCK OUT
21 28
54 53
REF. DWG. (4) - G71AHS
DA403 W455-A- SHT. 03

2- 52 TBC CB
ITX4 ITX3
K299C TB4A TB4A K225E
19 CB READY 20
67 67

ITX3
TB4A K225F
21 67

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852125
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DISTANCE PROTECTION (MAIN-2) - DC OPTO I/P CKT DRG. NO.: CPD KW85 SC21 SHT 25 OF 67
2R1

25
FROM TBC PANEL
220KV TBC CB ITX3
K225
TB4A TB4A
K245
22 23

TB4A K247
24

TB4A K249
25

67

T N C ITX4
X4A X4A TB4A K205H
23 24 26
REF. DWG. (4) - G719EA- 67
YC9029-WC203-B SHT. 26
25
2C1
T N C
TB8 TB8 TB8 TB8 K297
9 9 10 10
28 MAIN / TBC CB SOTF INI
CS1 63

2-52
220KV MAIN CB
NIX2
S1LA-14 S1LA-13 TB4
K207A K207
27 MAIN / TBC CB R-PH OPEN
24
132 131

S1LB-14 S1LB-13 TB4 K209A K209


27 MAIN / TBC CB Y-PH OPEN
25
132 131

S1LC-14 S1LC-13 TB4


K211A K211
27 MAIN / TBC CB B-PH OPEN
26
132 131
66
REF. DWG. (4) - G71AHS
DA403 W455-A- SHT. 04

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852126
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DISTANCE PROTECTION (MAIN-2) - DC OPTO I/P CKT DRG. NO.: CPD KW85 SC21 SHT 26 OF 67
2R1

BASE FILE:
07 D60 07
+VE
21M2 -VE

FOR ALSTOM REF:


K201 - K202

SALES ORDER: -
+B5b -B6a

SCHEME TYPE: FEEDER


-

K207
26 H1a MAIN / TBC CB R-PH OPEN

ENGG.REF.NO.: KW85
K209 MAIN / TBC CB Y-PH OPEN
26 H1c

K211
26 H2a MAIN / TBC CB B-PH OPEN

Dated 08.10.2014
FS34 K217 H1b K202
2 H2c HMI BLOCK
1 4A
2C1
PB02
TB8 TB8 TB8 TB8
K223 H3bK202

P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779
H3a RESET LATCHED
11 2P3 2P4 12
11 12 CONTACTS

CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD


PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S
NIX1 K233
H3c BAY IN TRANSFER MODE
66

IX1
K231 BAY IN INTER MODE
H4a
47

ALSTOM T&D India


295R/Y/B
K235 TC-2 FAULTY
40
H4c

ABCD
RX2

PALLAVARAM CHENNAI 600043


K228 D/T RECEIVED CH-2
H5a
31

- Limited - AUTOMATION SAS


SX2
K226
H5c DIRECT TRIP SEND CH-2
33

IN OUT
PANEL TYPES: 2C1 2R1

K259
H6a AUTO RECLOSE IN
SCHEMATIC DRAWING

64
ARS

21M1
K229 H5b K202 MAIN-1 OPTD
H6c
22

PLCC PANEL- CARRIER CHANNEL-2


TITLE: 220KV LINE CONTROL & PROTECTION

TB4 CARRIER HEALTHY TB4


FS29 K237 H7a CARRIER HEALTHY
2 27 28 CH-2
1 4A
FILE: DW852127

IN OUT CARR.RECEIVE
TB4 TB4
K261 K239
H7c CARRIER RECEIVED
29 (CODE-2) 31 CH-2
CSS2
PREPARED BY:

64
PLCC PANEL- CARRIER CHANNEL-1
CHECKED BY: JKK
APPROVED BY: JKK
GKA

IN OUT CARRIER HEALTHY


K261B TB4 TB4 K243
H8a CARRIER HEALTHY
30 32 CH-1
CSS1
64
29
. K202AFS31
H8c H7b
1 2
REVISION:

4A
SCALE: --
DISTANCE PROTECTION (MAIN-2) - DC OPTO I/P CKT DRG. NO.: CPD KW85 SC21 SHT 27
Z

28 25 28
DATE: 19.03.2015

OF 67
2R1

BASE FILE:
K201
BIX=61
27
K202

FOR ALSTOM REF:

SALES ORDER: -
BI.01 27

SCHEME TYPE: FEEDER


K241
25 M5a MAIN / TBC CB READY FOR CLOSE

BI.02
25 K291
2C1 M5c MAIN / TBC CB SF6 LOCK OUT

80A BI.03

ENGG.REF.NO.: KW85
TB8 TB8
K297A M6a DC SOURCE-1 FAIL
06 14 14
TB8 TB8

13 13 80B BI.04
TB8 TB8 K297B M5b
M6c DC SOURCE-2 FAIL
06 15 15

BI.05
TB4 K299A M7a SPARE

Dated 08.10.2014
9

BI.06
K297 MAIN / TBC CB SOTF INI
26 M7c

BI.07

P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779
K251 MAIN / BC CB BB PROTN/
25 M8a
LBB TRIP RELAY OPTD

CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD


PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S
BI.08
K253 M7b 3-PH TRIP RELAY OPTD
25 M8c

ALSTOM T&D India


30
K202
30
D60

ABCD
K201 TO ANNUN
21M2

PALLAVARAM CHENNAI 600043


L201 W1b W1a
L215 57 A/R LOCKOUT
57
RL21

L205

- Limited - AUTOMATION SAS


W1c 57 DIST PROTN OPTD
RL22

L201 W2b W2a


L225 57 POWER SWING BLOCK
RL23

W2c
L227 58 SOTF OPTD
RL24
PANEL TYPES: 2C1 2R1

L201 W3b W3a


L229 58
58 O/V OPTD
RL25
SCHEMATIC DRAWING

W3c
L233 58
RL26
VT FUSE FAIL

L201 W4b W4a


L253 59
RL27
BROKEN CONDUCTOR ALARM
TITLE: 220KV LINE CONTROL & PROTECTION

W4c
L251 59 AUTO RECLOSE
RL28
FILE: DW852128

59 L201 W5b W5a


L211 57 POWER SWING TRIP OPTD.
RL29
DISTANCE PROTECTION (MAIN-2) - DC I/P & OUTPUTDRG.

W5c
L267 59 CARRIER FAIL CH-2
RL30
PREPARED BY:

L201 W6b W6a


L259 59 CARRIER SEND CH-2
CHECKED BY: JKK
APPROVED BY: JKK

RL31
GKA
ONCE ANNCIATOR IS GETTING RESET FROM PUSH BUTTON.

W6c
L261 59 CARRIER RECEIVED CH-2
RL32

TB7 TB7
U13 U14
W7b W7a SPARE
7 RL33 8
REVISION:
NOTE: RL21 - RL34 IN D60 RELAY IS LATCHABLE TYPE. THESE CONTACTS WILL BE RESET

SCALE: --
CKT NO.: CPD KW85 SC21 SHT 28
Z

W7c
RL34
DATE: 19.03.2015

OF 67
BASE FILE:
FOR ALSTOM REF:

SALES ORDER: -
SCHEME TYPE: FEEDER
2R1

D60

ENGG.REF.NO.: KW85
21M2
B1a B1b
21M2 L245 TO ANNUN.
58 L201 B2b 58
(RELAY FAULTY)
WD
BLKC K3D K3A
39 M1b M1c
S1 R1 RL1
TO TC-1 TRIP
M2b M2c K3B COIL CIRCUIT
RL2
(MAIN CB)

Dated 08.10.2014
M3b M3c K3C 39
RL3
K1T BLKC K1D M4b K403A
41 M4c
S2 R2 RL4
TO TC-1 TRIP
K403B (TBC CB)
P1b P1c
RL5

P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779
41
K403C
P2b P2c

CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD


RL6

PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S


K201 BLKD K205 K213A
30 P3b P3c
S1 R1 RL7
TO CONTACT
P4c K213B MULTI.
P4b RL8
K213C 30
P5b P5c
RL9
TB4 TB4
K187A

ALSTOM T&D India


P6b P6c K189A TO RESET TEST KIT
33 RL10 34

K701 K787
33 P7b P7c 33 DIRECT TRIP SEND CH-2
RL11

ABCD
1K15 1K17A TO TBC CB

PALLAVARAM CHENNAI 600043


43 P8b P8c 43
RL12 AUTO RECLOSE LOCKOUT
K201
BLKD K201B TO GRP-B TRIP RELAY
K203
35 U1b U1c 35

- Limited - AUTOMATION SAS


S2 R2 RL13 (A/R L/O, POWER SWING, MU.PH/Z2,Z3
K7 K14 FAULTS)
38 U2b U2c 38 TO CB AUTORECLOSE
RL14

K101 U3b K131 TO MAIN-1


17 U3c 17
RL15 ( MAIN-2 OPTD )
P143A U4b P121A TO MAIN CB BUSBAR PU
42 U4c 42
RL16 LBB START
PANEL TYPES: 2C1 2R1

K171 U5b K187


32 U5c 32 DIRECT TRIP SEND CH-1
SCHEMATIC DRAWING

RL17
K201D IN OUT
K239A K240 TB4
27 U6b U6c CARRIER SEND (CHANNEL-2)
64 RL18 35 PLCC PANEL
CSS2
K101 U7b K125
17 U7c 17 TO MAIN-1 LBB START
RL19
TITLE: 220KV LINE CONTROL & PROTECTION

42 P143C U8b P123C TO TBC CB BUSBAR PU


U8c 42
RL20 LBB START
FILE: DW852129

DISTANCE PROTECTION (MAIN-2) - OUTPUT CONTACTS


PREPARED BY:
CHECKED BY: JKK
APPROVED BY: JKK
GKA
REVISION:

SCALE: --

DRG. NO.: CPD KW85 SC21 SHT 29


Z
DATE: 19.03.2015

OF 67
EQPT 86R2
TYPE MVAJM11
2R1 2R1
LOC
EQPT 86Y2
TYPE MVAJM11
21M2
28 -VE 28 LOC 2R1
86R2
+VE R PH EQPT 86B2
K201 K213A K202
TYPE MVAJM11
27 28
LOC 2R1

86Y2
Y PH
K213B
27 28

86B2
B PH
K213C
27 28
29

86R2 86R2
K51A K53A 1K15 1K15A
40 1 3
43 5 7

86Y2 86Y2
K53B 1K15B TO A/R INITIATION
40 TO TRIP COIL-2 43
1 3 5 7 (TBC CB - MAIN-2 RELAY)
(MAIN CB)
86B2 86B2
K53C 1K15C
1 3 5 7

86R2 86R2
K51T K453A K101 K145
41 2 4
18 6 8

86Y2 86Y2
K453B K147 TO LBB INITIATION
41 TO TRIP COIL-2 18
2 4 6 8 (MAIN CB - MAIN-2 RELAY)
86B2 (TBC CB)
86B2
K453C K149
2 4 6 8

86R2
P141A P111A
42 9 11 86R2
P143C P115C
42 10 12
86Y2
P113A 42 TO MAIN CB BUSBAR PU 86Y2
9 11 P117C TO TBC CB BUSBAR PU
P117C
LBB INITIATION 10 12 42 LBB INITIATION
86B2
P115A 86B2
9 11 P119C
10 12
86R2
TB7 U101 TB7
86R2 86R2 86R2
U111
9 17 19 10 13 15 14 16
18 20
86Y2
TB7 U112 TB7 86Y2 86Y2 86Y2
U113
11 17 19 12 SPARE 18 20 13 15 14 16

86B2 86B2 86B2


TB7 U114 TB7 86B2
U115
13 15 14 16
13 17 19 14 18 20

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852130
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DISTANCE PROTECTION (MAIN-1) - DC I/P & OUTPUTDRG.
CKT NO.: CPD KW85 SC21 SHT 30 OF 67
EQPT RX1
2R1
TYPE MVAAM11
220V DC LOC 2R1
07 EQPT RX2
PLCC CHANNEL-1 TYPE MVAAM11
DIRECT TRIP TB4 K171 +VE -VE LOC 2R1

36 RX1
CODE 3 13 K172
LKRX1
K167 K169 14
1 2
11
** ** 37
.
5
K101 K139
17
3 1
17 TO 21M1
.
6
.
4 2

L201 L219
57 57 TO ANNUN
7 9

K101 K103 TO GRP-A TRIP RELAY


34 34
8 10

32

220V DC
07

PLCC CHANNEL-2
+VE -VE
DIRECT TRIP TB4 K701
38 RX2
CODE 4 13 K702
LKRX2
K767 K769 14
1 2
11
** ** 39
.
5
.
3 1
.
6
K201 K228
27 27 TO 21M2
4 2

L201 L219
57 57 TO ANNUN
7 9

K201 K203 TO GRP-B TRIP RELAY


35 35
8 10

33

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852131
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DIRECT TRIP COMMAND RECEIVE CKT DRG. NO.: CPD KW85 SC21 SHT 31 OF 67
EQPT SX1
2R1 MVAAM11
TYPE
LOC 2R1
PLCC
DIRECT TRIP COMMAND-1
K171 K172 TB4 TD1 TD7
+VE -VE
31 31 CS
40

TB8
57
2C1 2C1

1
LK187
N I T A/T A/C
T C

2
K171 TB8 TB8 K171 K185 K187 TB8 TB8
MANUAL TRIP OF
16 16 65 65 63 18 K187 18 SX1
MAIN CB CS1
TTS

K187
13 K172

N I T BB2C 14
LBB TRIP & N I T .
11PU
BUSBAR TRIP OF K189 TB4A TB4A K193
TBC CB 4 5
REF CPD KN76 SC01 SHT 42
TB7 TB7
U37 U38 SPARE
1 3
15 16

L201 L221 TO ANNUN


57 2 4
57

2CP3 K101 K127 TO 21M1 OPTO INPUT


2C1 17 5 7
17
A/T A/C
52X2 T C IX1
K521 TB4A TB4A K187B TB4A TB4A
44 6 27 28 8
CS52 6 8
47

9 11
IX1 T NC
TB8 TB8 TB4A 52X
K513
63 10 12
47 17 17 7
DIR. TRIP SEND
(CH-1)
MANUAL TRIP OF
DIR TRIP-1 A/T A/C
T C
NIX2 TB4A TB4A K191T NIX1
66 29 30 66
CS52
BB2E
PU REF. DWG. (4) - G719EA-
LBB TRIP & YC9029-WR203-B SHT. 21, 25
TB4 TB4
BUSBAR TRIP OF
41 REF CPD KW85 SCXX SHT 25 42
MAIN CB

21M2
O/V
29
TRIP

21M1
O/V /LBB
K187
TRIP 21

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852132
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DIRECT TRIP SEND CIRCUIT (CH-1) DRG. NO.: CPD KW85 SC21 SHT 32 OF 67
2R1 EQPT SX2
PLCC TYPE MVAAM11
DIRECT TRIP COMMAND-2 LOC 2R1
K701 K702 TB4 TD1 TD7
+VE -VE K702
31 31 CS
44

43
LK787 K786 TB4
2C1 2C1

1
N I T A/T A/C
T C

2
MANUAL TRIP OF K701 TB8 TB8 K701 K785 K787 TB8 TB8
SX2
MAIN CB 19 19 65 63 21 21
TTS CS1 13 K702

K787
BB2C 14
N I T N I T .
LBB TRIP & 11PU
K789 TB4A TB4A K793
BUSBAR TRIP OF
TBC CB 9 10 TB7 TB7
REF CPD KN76 SC01 SHT 42
TTS TTS U39 U40 SPARE
2CP3 1 3
17 18

2C1 A/T A/C L201 L221 TO ANNUN


57 57
52X2 T C IX2 2 4
K921 TB4A TB4A K787B TB4A TB4A
44 K201 K226
11 31 47 32 13 27 27 TO 21M2 OPTO INPUT
CS52 5 7

IX2 T NC
TB8 TB8 52TBC
K913 TB4A 6 8

47 20 20 63 12
DIR. TRIP SEND 9 11

(CH-2)
10 12
MANUAL TRIP OF
DIR TRIP-2
A/T A/C
NIX2 T C NIX2
K793T TB4A TB4A K791T
66 33 34 66
CS52
REF. DWG. (4) - G719EA-
YC9029-WR203-B SHT. 21, 25
BB2E
LBB TRIP & PU
K701 TB4 TB4 K787
BUSBAR TRIP OF
MAIN CB 45 46
REF CPD KW85 SCXX SHT 25
21M2
O/V K701 K787
TRIP 29

21M1
O/V /LBB K701 K787
TRIP 22

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852133
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 DIRECT TRIP SEND CIRCUIT (CH-2) DRG. NO.: CPD KW85 SC21 SHT 33 OF 67
2R1 EQPT 86A
TYPE MVAJM205
K101
LOC 2R1
07 K1A K3A EQPT 95/86A
K102 39 13 15
TYPE MVAXM21
+VE 07 39
LOC 2R1
21M1 K3B
17 19 TO TC-1 OF EQPT 86AX
DISTANCE PROTN -VE
K103 MAIN BKR TYPE MVAAM11
A/R LOCKOUT, PS 86A 28 K3C
27 LOC 2R1
MULTI PH./Z2,Z3, O/V 6 8

FAULTS 22 K1T K403A


41 10 12
PB01
K103D 41
K403B
1P3 1P4 25 26 14 16
TO TC-1 OF
K403C TBC BKR
18 20

DIRECT TRIP RECEIVE-CH-1


RX1
31 K51A K53A
40 33 35

40
TB4 TB4 K53B
FUTURE TRIP IF ANY 37 39 TO TC-2 OF
47 48
MAIN BKR
K53C
41 43
86A
K161A K102
5 7 25 28
K51T K453A
86A 41 45 47
K101 K163 86AX
9 11 41
K453B
34 36
TO TC-2 OF
95/86A
TBC BKR
K453C
A K103 38 40
21 22 K201 K253
25 25 TO 21M2 OPTO INPUT
1 3
95/86A K4A
K102 K4B K4A TO CLSG I/L
L201 L207 38 38
27 13 C 28 57 57 TO ANNUN 1 3 (MAIN CB)
2 4
K3H
K1C K3H TO CLSG I/L
42 42
2 4 (TBC CB)
K101 K155 19 TO 21M1 OPTO INPUT
19 5 7

TB7 U118
TB7
U117 SPARE
K101 K125 TO MAIN-1 LBB START 29 31
17 9 11
17 21 22
TB7 U120
TB7
U119 SPARE
P141A P117A TO MAIN CB BUSBAR PU 42 44
42 42 23 24
TB7 U23 U24 TB7 13 15 LBB INITIATION
SPARE S203
19 1 3 20 S201 TO RTU
56 56
P143A P121A TO MAIN BUSBAR PU 46 48
42 42
L201 L247
6 8 LBB START S205
58 58 TO ANNUN S201
2 4 TO TBC CB BUSBAR PU 56 30 32
56 TO RTU
P143C P121C
42 42 LBB INITIATION
10 12

5 7
P143C P123C TO TBC CB BUSBAR PU
42 14 16
42
LBB START

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852134
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 TRIP RELAY CIRCUIT - GROUP-A DRG. NO.: CPD KW85 SC21 SHT 34 OF 67
2R1 EQPT 86B
TYPE MVAJM205
K201
LOC 2R1
07 K1A K3A EQPT 95/86B
K202 39 13 15
TYPE MVAXM21
+VE 07 39
LOC 2R1
K3B
21M2 17 19 TO TC-1 OF EQPT 86BX
DISTANCE PROTN K203 -VE MAIN BKR TYPE MVAAM11
A/R LOCKOUT, PS, 27 86B 28 K3C
6 8 LOC 2R1
MULTI PH./Z2,Z3, O/V
FAULTS 29 K1T
41 K1T K403A
10 12
PB01
K203D 41
K403B
2P3 2P4 25 26 14 16
TO TC-1 OF
K403C TBC BKR
DIRECT TRIP RECEIVE-CH-2 18 20

RX2
31
K51A K53A
40 33 35
TB4 TB4 40
FUTURE TRIP IF ANY
49 50 K53B
37 39 TO TC-2 OF
MAIN BKR
K53C
41 43
86B
K204 K202
5 7 25 28
K51T K51T K453A
86B 41 45 47
K201 K263 86BX
9 11 41
K453B
34 36
TO TC-2 OF
95/86B
TBC BKR
K453C
A K203 K201 38 40
25 K253
21 22 1 3
25 TO 21M2 OPTO INPUT

95/86B
K202 L201 L209 TO ANNUN K4A K4A K5
57 57 38 38 TO CLSG I/L
27 13 C 28
2 4 1 3
(MAIN CB)
K6B
K7D K7D K6B TO CLSG I/L
K101 K155 42 42
19 19 TO 21M1 OPTO INPUT 2 4 (TBC CB)
5 7

K101 K125
TB7 TB7
17 17 TO MAIN-1 LBB START U44 U45 SPARE
TB7 U42 9 11
U43 TB7
42 44
SPARE 27 28
25 1 3 26 S207
P141A P117A TO MAIN CB BUSBAR PU S201 S201 S207
42 13 15
42 56 46 48
56 TO RTU
L201 L247
LBB INITIATION
58 58 TO ANNUN
2 4 TB7 TB7
P143A TO MAIN CB BUSBAR PU U121 U121 U123 SPARE
42 P121A 42 29 31
6 8 29 30
LBB START
S209
5 7 S201 S201 S209
P143C P121C TO TBC CB BUSBAR PU 56 30 32
56 TO RTU
42 42
10 12
LBB INITIATION

P143C P123C TO TBC CB BUSBAR PU


42 42
14 16
LBB START

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852135
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 TRIP RELAY CIRCUIT - GROUP-B DRG. NO.: CPD KW85 SC21 SHT 35 OF 67
EQPT 27RN
TYPE MVAGM11
LOC 2R1

2R1

27RN
E121L R
23 13 14
220KV
LINE CVT
SUPPLY
E181L N
23

1 3

K601 K671A
K671A
51 51 TO E/S INTERLOCK
2 4 2- 89LE

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852136
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 LINE UNDER VOLTAGE CKT DRG. NO.: CPD KW85 SC21 SHT 36 OF 67
EQPT 96
2R1
TYPE MVAJM205
FROM ADJACENT PANEL
LOC 2R1

ZB
+VE

ZA
5 7

-VE
.
9 11
P171

P173
P1
3

5
.

P2
BB2

BB2

BB2

6
13 15

BB2
P1

39 K1A K3A 39
17 19
89AX2 TO TC-1
LK33 P157B
-VE K3B
P157 39
1 2 96 28 6 8
45 27

K3C 39
89BX2 10 12

46
40 K51A K53A 40
14 16
TO TC-2
PB01 K53B 40
P103D 18 20
3P3 3P4 25 26
K53C 40
33 35

K101 K153 19
19 37 39 TO 21M1 OPTO INPUT
21M1 NIX1
P1 P153 .
41 43
22 66
TB7 TB7
U141 U142
45 47
SPARE
31 32

38 K6 K7 38 TO CLOSING INTERLOCK
TO ADJACENT PANEL 1 3

K3H
K3H K7D TO TBC CB
42 2 4
42
CLOSING INTERLOCK

L201 L223 TO ANNUN.


57 L223 57
34 36 LBB OPTD.

K201 K251
25 38 40
25 TO 21M2 OPTO INPUT

56 S201 S211 56 TO RTU


42 44

46 48

56 S201 S213 56 TO RTU


29 31
TB7 TB7
U169 U170 SPARE
30 32
33 34

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852137
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 LBB TRIP RELAY CIRCUIT DRG. NO.: CPD KW85 SC21 SHT 37 OF 67
2R1 2C1 CIRCUIT BREAKER
2-X52
07

TB4 X1
K1
1 +VE
1A
X1
K2
2 -VE
2A
39

BB
195R 195Y 195B 86B 86A K4B TB4 1PU TB8 TB8 FSC X1
K5C K5 K4 K17 K17
2 1 3
COMMON
39 35 34 51 22 22 6A 11
REF CPD KW85 SCXX SHT XX

295R 295Y 295B 96 89A2X TB8 TB8 89LX


K5C K6 K7 K8
40 37 45 23
23 47
89B2X
46

21M1

CHK SYN

BYPASS
K7
22

OFF
SS K12
REF. DWG. (4) - G71AHS
K10 K11 DA403 W455-A- SHT. 02
14 14 14
11 12
K7 21M2
29

SSS

N I T T NC
K16 K15 TB4 X1
REMOTE
65 63 4 CLOSE
TTS CS1 15

TB8 TB8 K14 TB4 * AUTO


24 5 RECLOSE
24 *

2-X89A 2-X89B 2-X89L


*
*
LOCAL
CLOSE I/L
*

* NOTE - TERMINAL NUMBER NOT IDENTIFIED IN THE DRAWING *

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852138
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 CIRCUIT BREAKER CLOSING CKT DRG. NO.: CPD KW85 SC21 SHT 38 OF 67
EQPT 195R,Y,B
TYPE MVAXM31
REF. DWG. (4) - G71AHS LOC 2R1
CIRCUIT BREAKER 2-952 (TC-1) DA403 W455-A- SHT. 01

MANUAL TRIP TC-1 PROTN TRIP PRE CLOSE SUPERVISION

121

123

125

122
124
126

19

21

23
X1

X1

X1

X1

X1

X1

X1
20

22

24
X1

13
TB4

K30A TB4

K30B TB4

K30C TB4

52

65

66

67

68

57

58

59

60
6

TB4

TO 21M1 OPTO
TB4
7

K31

K35
K32

K34
K33

K35A

TO ANNUN
K3C
K3A

K3B
K3

195Y
195R

195B
B

17

58
63

63

63

K123

L239
T NC

4
CS1

195Y

195B
195R

3
C

3
C

195R

195Y

195B
C

C
61

62

63
TB4

K101
2

2
K3B

L201
1

1
29

195Y
35

37

A
21

TB4X
2

4
34

K3C
K3A
N I T

21M1

21M2
86A

195B
195R
86B

96
TTS

K2

K2

K2
PU

A
TRIP ANY
FUTURE

K5C
38
195Y

195B
195R

K5A
BB2E
K1A
K30

21

34

35

37
29
65

7
C 7
195B
195R
A

A
B

195Y
TB4X
64
TB4

C
1

C
5

5
NIX1

5
K5B
66

K5
38
K1

K2
2C1

K1
25

TB8

TB8
26

27
2R1

TB8

TB8

26

27
25

TB8
TB8
+VE -VE
38
2C1

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852139
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 CIRCUIT BREAKER CONTROL CKT. (TC-1) DRG. NO.: CPD KW85 SC21 SHT 39 OF 67
EQPT 295R,Y,B
TYPE MVAXM31
LOC 2R1
REF. DWG. (4) - G71AHS
DA403 W455-A- SHT. 01
CIRCUIT BREAKER 2-952 (TC-2)

MANUAL TRIP TC-2 PROTN TRIP PRE CLOSE SUPERVISION

127

129

131

25

27

29
128
130
132
X1

X1

X1

X1

X1

X1

X1
14
X1

X1

26

28

30
2C1
TB4

TB4X
K53A TB4X

10

11

12

13
13

14

15
12

TO 21M2 OPTO
K61

K65
K62

K64
K63
K60C
K60A

K60B

K53C

K66

TO ANNUN
K53B
K53

295Y
295R

295B
B

B
63

63

63

27

58
T NC

CS1

K235

L241
4

4
295R

295Y

295B

295Y

295B
L201 295R
C

C
K201
K53B

2
TB4X

15

16

17

2
19

20

21

295Y
TB4X

A
N I T

K53C
K53A
TTS

REF CPD KW85 SCXX SHT 24

K5C
38
295R

295B
86R2/Y2/B2

K52

K52

K52
21M1

A
86A

FUTURE
TRIP ANY
86B

K5E
295Y

295B
295R
PU
96

7
K60

C 7
65

K51A

295B
295R
K51A
K51A

295Y
C

C
K51A

TB4X
BB2E

18
37
22

30
34

35

A
B

K5D
5

5
5
TB4X

14

K6
38
NIX2

K51

K52
66
K51

TB8
29

35
TB8
28
2R1

K52
TB8

K51
TB8

29

35
TB8
+VE -VE

28
TB8
07

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852140
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 CIRCUIT BREAKER CONTROL CKT. (TC-2) DRG. NO.: CPD KW85 SC21 SHT 40 OF 67
2R1
EXISTING TBC PANEL
EXISTING TBC PANEL
ITX3 ITX3 TB4A
K1T K1AT TB4A ** K51T K51AT **

35 67 39
67
86R2 ITX4
21M2 ITX4
TB4A
K1T K403A K3AT TB4A **
TO TBC
K51T K453A K53AT **
TO TBC
30 67 40 TRIP COIL-2
29 67 36 TRIP COIL-1 86Y2 ITX4
21M2 ITX4 TB4A
K403B K3BT TB4A ** K453B K53BT **
67 41
67 37 ITX4
21M2 ITX4 86B2
TB4A
K3CT TB4A K53CT
** K453C **
K403C
67 42
67 38

86B
86B
35
35

21M1
K1T
21 21M1
21M1
K51T
22
21M1 21M1

21M1
86A

34
86A
34

EXISTING TBC PANEL

P155 TB4A **

43
TO TBC PANEL
21M1 LBB TRIP RELAY
P155 P151B TB4A **
22 44

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852141
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 TBC BREAKER (TRIP) CONTACT DISTRIBUTION DRG. NO.: CPD KW85 SC21 SHT 41 OF 67
2R1
EXISTING BB PANEL ITX3 EXISTING BB PANEL
TB4X P143C P141C TB4X
22 67 67 29
21M1
21M1 TB4X
TB4X
22 22 30
22 22 23 TB4X
TB4X TO MAIN CB BUSBAR PU TO TBC CB BUSBAR PU
1-PH LBB INITIATION 22 31
22 1-PH LBB INITIATION
24 TB4X
TB4X
22 32
22 25

86AX
86AX P121CTB4X TO TBC CB BUSBAR PU
P117A TB4X TO MAIN CB BUSBAR PU 34 34 33 3-PH LBB INITIATION
34 34 26 3-PH LBB INITIATION

86R2
P115C
30 30
86R2 86Y2
P117C
P111A
30
30 30 86B2
86Y2 P119C
P113A
30
30
86B2
P115A 86BX
30
35 35
86BX

35
21M1
35 P123CTB4X LBB START
P143C
22 22 34
TO TBC CB BUSBAR PU
86A

34 34
21M2
EXISTING BB PANEL
P143ATB4X 29 29
86B
21M1 27 TO MAIN CB BUSBAR PU
TB4X 35 35
P121A LBB START
EXISTING TBC PANEL
22 22 28 ITX1
86AX TB4A
K1C K6C
34 34 67 67 45
TO TBC PANEL
CB CLOSING INTERLOCK
K6B TB4A
46
21M2

29 29 86A
86BX K3H 96 86B
34 37 35
35 35

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852142
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 TBC CONTACT DISTRIBUTION DRG. NO.: CPD KW85 SC21 SHT 42 OF 67
2R1 EXISTING TBC PANEL

1K15 NIX2 K6D TB4A X4A

66 47 9 COMMON

86R2
1K15 1K15A TB4A X4A

30 48 10

86Y2 TO TBC
1K15B TB4A X4A ( AUTO RECLOSE INITIATION )

30 49 11

86B2
1K15C TB4A X4A

30 50 12

21M2
1K15 1K17A TB4A X4A TO TBC
29 51 16 ( AUTO RECLOSE LOCKOUT )

21M1
1K15
22

21M1

22

21M1

22

21M1
1K15
22

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852143
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 TBC BREAKER (A/R) CONTACT DISTRIBUTION DRG. NO.: CPD KW85 SC21 SHT 43 OF 67
EQPT 52X1,2 & 3
2C1 VAJC11
TYPE
LOC 2C1
52X1
54 L1 L3 54
1 2 TO SEMAPHORE
07 (CB OPEN)
54 L1 L27 54
TO INDICATING LAMP
5 6 (CB OPEN)
BMK K601 K627
50 13 14
50 2-989B CLSG. CKT.
TB4 K801
2-952CBMB 23 K601 K641
(+)COM 51 17 18
51 2-989L CLSG. CKT.
52X1
52R 52Y 52B
S1LA-5 S1LA-6 S1LB-5 S1LB-6 S1LC-5 S1LC-6 TB4 7 8
R L1 L5 TO SEMAPHORE
24 11 12 54 54
112 111 112 111 112 111
OPEN 15 16 (CB CLOSED)
(2- 52CB OPEN) L1 L29
52R 54 54
52Y 52B 19 20 TO INDICATING LAMP
S1LA-1 S1LA-2 S1LB-1 S1LB-2 S1LC-1 S1LC-2
TB4 TB7 U129 TB7
U130 SPARE
25 9
O 10 5 3 4 6
104 103 104 103 104 103
CLOSE
(2- 52CB CLOSED)
REF. DWG. (4) - G71AHS
52X2
DA403 W455-A- SHT. 04 52X2
56 S201 S215 56 TO RTU
1 2
11 R 12

S201 S217
56 3 4
56 TO RTU
9
O 10

49 K601 K607 49 2-989A CLSG. CKT.


5 6
TB7 U151 TB7
U152 SPARE
52X3 7 7 8 8
32 K511 K521 32 TO DT CH-1
1 2 52X3 TB7 U153 TB7
U154 SPARE
9 15 16 10

3 4
11 R 12
TB7 TB7
U155 U156 SPARE
35 17 18 36

K911 K921 O
33 5 6
33 TO DT CH-2 9 10 . .
19 20

7 8
54 L1 L31 54 AUTO TRIP INDICATION
13 14

15 16

17 18
45

19 20

13 14

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852144
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 CIRCUIT BREAKER AUXILIARY RELAY CKT DRG. NO.: CPD KW85 SC21 SHT 44 OF 67
2C1 EQPT 89AX1
TYPE VAJC11
LOC 2C1
BMK 89AX1 TO SEMAPHORE
54 L1 L7 54 EQPT 89AX2
44 1 2 (2-989A OPEN)
TB4 TYPE MVAJM14
K801 2R1
26 L1 L41 TO INDICATION CKT LOC
2-989A ISOLATOR MB (+)COM 55 55
5 6 (2-989A OPEN)

K627 K625 ISOL 2-989B CLOSING CKT


50 13 14
50

89AX1
S221
56 17 18
56 TO RTU
TB4 K807
27 11
R 12
S219
OPEN 56 56
(OPEN) 3 4 TO RTU

L9 TO SEMAPHORE
54 L1 54
7 8 (2-989A CLOSED)
TB4 K808
O L1 L43 TO INDICATION CKT
28 9 10 55 15 16
55
(CLOSED) (2-989A CLOSED)
CLOSE

TB8
K625 K635
50 50 ISOL 2-989B CLOSING CKT

30

31

32
19 20

2R1

TB8
32
K101B89AX2 K276 VOLTAGE SELECTION
89AX2 09 1 3
09
TB8 K807
R
31 25 26 TB4 K673C TB4
K671C TO BUS E/S INTERLOCK
53 2 4 54
REF CPD KW85 SCXX SHTXX
K276 K276A
09 09 VOLTAGE SELECTION
5 7

89AX2 TB7 TB7


U131 U132
TB8 K808 K802 39 6 8 40
SPARE
30 27
O 28

9 11

K7 K8 CB CLOSING CKT
38 10 12
38

K101B K275
09 13 15
09 VOLTAGE SELECTION
46 P171 P157
37 14 16
37 TO LBB TRIP RELAY

TB7 TB7
U133 U134 SPARE
41 17 19 42

18 20

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852145
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ISOLATOR 2-989A AUXILIARY RELAY CKT DRG. NO.: CPD KW85 SC21 SHT 45 OF 67
2C1 EQPT 89BX1
TYPE VAJC11
LOC 2C1
BMK L1 89BX1 L11 TO SEMAPHORE
54 54 EQPT 89BX2
45 1 2 (2-989B OPEN) TYPE MVAJM14
TB4
K801 2R1
LOC
29 L1 L45 TO INDICATION CKT
2-989B ISOLATOR MB (+)COM 55 55
5 6 (2-989B OPEN)

K607 K605
49 13 14
49 ISOL 2-989A CLOSING CKT
89BX1
56 S201 S225 56
TB4 K809 17 18 TO RTU
30 11
R 12
OPEN S223
(OPEN) S201
56 3 4 56 TO RTU

L1 L13 TO SEMAPHORE
54 7 8
54 (2-989B CLOSED)
TB4 K810 L47
O 55
L1
55
TO INDICATION CKT
31 9 10 15 16 (2-989B CLOSED)
(CLOSED) CLOSE

TB8
K605 K615
49 19 20
49 ISOL 2-989A CLOSING CKT

33

34
2R1

K101C 89BX2 K285A VOLTAGE SELECTION


89BX2 09 1 3
09
TB8 K809
34 25
R 26 TB4 TB4
K675D K677D
55 2 4 56
TO BUS E/S INTERLOCK
REF CPD KW85 SCXX SHTXX
K285A K288 VOLTAGE SELECTION
09 5 7
09

89BX2 TB7 TB7


U158 U159 SPARE
TB8 K810 K802 37 6 8 38
33 27
O 28
. .
9 11

K7 K8
38 10 12
38 CB CLOSING CKT

K101C K286
09 13 15
09 VOLTAGE SELECTION

47 P173 P157
37 14 16
37 TO LBB TRIP RELAY

. .
17 19

TB7 TB7
U175 U176 SPARE
45 18 20 46

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852146
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ISOLATOR 2-989B AUXILIARY RELAY CKT DRG. NO.: CPD KW85 SC21 SHT 46 OF 67
EQPT 89LX
TYPE VAJC11
2C1
LOC 2C1
EQPT IX1
46
TYPE MVAJM14
L1 89LX L15
54 54 TO SEMAPHORE LOC 2R1
1 2 (2-989L OPEN)
BMK
TB4 K801 L1 L49 TO INDICATION CKT
55 5 6
55
33 (2-989L OPEN)
2-989L ISOLATOR MB 89LX
56 S201 S227 56 TO RTU
13 14
2-1-89L
K813
34 11
R 12 51
K675A K675B
51 TO E/S 2-989EL CLOSING CKT
17 18
(OPEN)
L1 L17 TO SEMAPHORE
54 3 4
54
(2-989L CLOSED)
2-1-89L L1 L51 TO INDICATION CKT
55 55
35 9 O 10
7 8 (2-989L CLOSED)
(CLOSED)
K8 K10 TO BKR CLOSING CKT
38 15 16
38

S201 S229
56 19 20 56 TO RTU

48

2R1

18

IX1
32 K187B K187 32
5 7 TO DT CH-1
IX1
33 K787 33
6 8 TO DT CH-1
2C1
IX1
N I T 27 K201 K231 27 TO 21M2 BAY IN
TB8 TB8 TB8 TB8 K157
K101 K157 K102 9 11 INTER MODE
O
48 48 65 50 50 27 28
TTS 17 K101 K119 17 TO 21M1 BAY IN
10 12 INTER MODE
K171 K511
32 13 15
32 TO DT CH-1
N I T IX1
TB8 TB8 TB8 TB8
K101S K701 K911
49 49 51 51 25 R 26 33 33 TO DT CH-2
65 14 16
TTS K851 K849
53 53 TO ISOLATOR 2-989C
N I T 17 19 INTERLOCK

65 53 K856 K858 53
TO ISOLATOR 2-989C
18
IX1 20 INTERLOCK
TTS
1 3

TB7 U139 U140


TB7
SPARE
47 2 4 48

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852147
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ISOLATOR 2-989L AUXILIARY RELAY CKT DRG. NO.: CPD KW85 SC21 SHT 47 OF 67
2C1 EQPT 89CX1
TYPE VAJC11
L1 89CX1 L19 2C1
47 TO SEMAPHORE (2-989C OPEN) LOC
BMK 54 1 2
54
TB4 EQPT 89CX2
K801 L1 L53 TYPE VAJC11
37 55 55 TO INDICATION CKT (2-989C OPEN)
2-989C ISOLATOR MB (+)COM 5 6
LOC 2C1
89CX1 K671A K675A
51 13 14
51 TO E/S 2-989EL CLOSING CKT EQPT 89LEX
TB4 K817
O TYPE VAJC11
38 9 10
17 18 LOC 2C1
CLOSE
(CLOSED)
3 4
TB4 K819
39
R 12
. .
11 7 8
(OPEN) OPEN L1 L21
54 54 TO SEMAPHORE (2-989C CLOSED)
15 16

L1 L55
55 19 20
55 TO INDICATION CKT (2-989C CLOSED)

K851 89CX2 K855


52 1 2
52 TO LADDER LOGIC
89CX2
K856 K854
52 52 TO LADDER LOGIC
O 5 6
9 10 S201 S235
56 56 TO RTU
13 14
TB7 U145 U146 TB7
41 17 18 42
SPARE
R 12
11 S201 S237
56 56 TO RTU
3 4
TB7 U149 U150 TB7
43 7 8 44
SPARE
. .
15 16

. .
19 20

2C1
BMK
TB4 89LEX
K801 L1 L23
41 54 54 TO SEMAPHORE (2-989EL OPEN)
1 2
2-989EL ISOLATOR MB (+)COM
L1 L57
55 5 6
55 TO INDICATION CKT (2-989EL OPEN)
K821
42 9 O 10 K641 K643
CLOSE
51 13 14
51 TO 2-989L CLOSING CKT
(CLOSED) 89LEX
K849 K851A
53 17 18
53 TO ISOLATOR 2-989C INTERLOCK
K823 R
43 11 12 TB7 U201 TB7
(OPEN) OPEN U203
11 3 4 12
SPARE

L1 L25 TO SEMAPHORE (2-989EL CLOSED)


54 7 8
54
L1 L59
55 15 16
55 TO INDICATION CKT (2-989EL CLOSED)
TB7 U147 U148 TB7
66 SPARE
13 19 20 14

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852148
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ISOLATOR 2-989C & E/S 2-989LE AUX. RELAY CKT DRG. NO.: CPD KW85 SC21 SHT 48 OF 67
ISOLATOR-2-989A
2C1 BMK
K601 K602
07 07
2KBC 89BX1
2KBC
TB4 52BC TB4 K615 TB4 2-889 PTES-I TB4
K601 K605 . +VE
45 *** 46 46 47 48

BUS-1 E/S I/L


52X2 K607 89BX1 K605
44 46

TB4
K602 - VE
49

K609 TB4
50 FROM L/R SWITCH

ONC
K609 K611 TB4
51
REMOTE CLOSING
62 62

K613 TB4
K601 K602 OPENING COIL
62 62 52
50 50
CS2

TRANSFER BUS 220KV, 3200A, 40KA, 3 sec

MAIN BUS-2 220KV, 3200A, 40KA, 3 sec

MAIN BUS-1 220KV, 3200A, 40KA, 3 sec

2-989A 2-989B 2-989C 2-1489A 2-1489B 2-1489C

2-952 2-1452

2-989L 2-1489L
2-989EL 2-1489EL

NOTE:
220KV LINE 220KV TBC
*** THUS MARKED CONTACT IS SERIES WITH BUSCOUPLER
MODE CMR (89A, 89B & 52 BREAKER)
FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z
SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852149
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ISOLATOR 2-989A CONTROL CKT DRG. NO.: CPD KW85 SC21 SHT 49 OF 67
ISOLATOR-2-989B
2C1 BMK

K601 K602 2KBC


49 49 89AX1 2KBC
52BC
**
K601 TB4 TB4 K625 TB4 2-889 PTES-II . TB4
+VE
53 *** 54 45 55 56

52X1 89AX1 BUS-2 E/S I/L


K627
44 44 45 45

TB4 **
K602 - VE
57

TB4 **
K629
58 FROM L/R SWITCH

ONC **
K629 K631 TB4
59 REMOTE CLOSING
62 62

K601 K602
51 51 TB4 **
K629 K633
OPENING COIL
62 62 60

CS3

TRANSFER BUS 220KV, 3200A, 40KA, 3 sec

MAIN BUS-2 220KV, 3200A, 40KA, 3 sec

MAIN BUS-1 220KV, 3200A, 40KA, 3 sec

2-989A 2-989B 2-989C 2-1489A 2-1489B 2-1489C

2-952 2-1452

2-989L 2-1489L
2-989EL 2-1489EL

NOTE:
220KV LINE 220KV TBC
*** THUS MARKED CONTACT IS SERIES WITH BUSCOUPLER
89A, 89B & 52 BREAKER

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852150
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ISOLATOR 2-89B CONTROL CKT DRG. NO.: CPD KW85 SC21 SHT 50 OF 67
2C1 BMK ISOLATOR-2-989L
K602 K601
50 TRANSFER BUS 220KV, 3200A, 40KA, 3 sec
50
MAIN BUS-2 220KV, 3200A, 40KA, 3 sec
52X1 89LEX
K601 K641 K643 TB4 MAIN BUS-1 220KV, 3200A, 40KA, 3 sec
+VE
44 48 61

2-989A 2-989B 2-989C 2-1489A 2-1489B 2-1489C

K602 - VE
62
2-952 2-1452

2-989L 2-1489L
K649
63 FROM L/R SWITCH 2-989EL 2-1489EL

ONC
K651
64
REMOTE CLOSING
62 62
220KV LINE 220KV TBC

K653
OPENING COIL
62 62 65

CS4

BMK EARTHSWITCH-2-989EL
2R1
(LINE DEAD)
27RN 89CX1 89LX
TB8 TB8 K601 K671A TB8 TB8 K671A K675A K675B TB4
I/C
52 52 36 36 53 53 66

K602 TB4
67

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852151
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ISOLATOR 2-989L CONTROL CKT DRG. NO.: CPD KW85 SC21 SHT 51 OF 67
BAY-2 BAY-3 BAY-4 BAY-6 BAY-7 BAY-8 BAY-10 BAY-11 BAY-12 BAY-13 BAY-15
89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN
TB8
K851 89CX2 K855 TB8
60 48 61

89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN TB8 89CX2 K856 TB8 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN
K854
62 48 63

ISOLATOR 2-289C ISOLATOR 2-389C ISOLATOR 2-489C ISOLATOR 2-689C ISOLATOR 2-789C ISOLATOR 2-1089C ISOLATOR 2-1189C ISOLATOR 2-1289C ISOLATOR 2-1389C ISOLATOR 2-1589C
53

2CP3
X14
52X2 +VE -VE 52X2
X14

30 32

REF. DWG. (4) - G719EA-


YC9029-WC203-B SHT. 15

BAY-28 BAY-27 BAY-26 BAY-24 BAY-23 BAY-21 BAY-20 BAY-19 BAY-18 BAY-17 BAY-16
89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN

89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN 89C OPEN

ISOLATOR 2-2889C ISOLATOR 2-2789C ISOLATOR 2-2689C ISOLATOR 2-2489C ISOLATOR 2-2389C ISOLATOR 2-2189C ISOLATOR 2-2089C ISOLATOR 2-1989C ISOLATOR 2-1889C ISOLATOR 2-1789C ISOLATOR 2-1689C

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852152
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ISOLATOR 2-989C CONTROL CKT (LADDER LOGIC) DRG. NO.: CPD KW85 SC21 SHT 52 OF 67
ISOLATOR-2-989C
2C1

LINE PANEL(2R1) BMK

IX1 89LEX
K851 TB8 TB8 K851 K849 TB8 TB8 K849 K851A TB4
+ VE
38 38 47 40 40 48 68

52
IX1 TB4
K856 TB8 TB8 K856 K858 TB8 TB8 K858 - VE
37 37 47 41 41 69

K673 TB4
70
FROM L/R SWITCH
O NC
K677 REMOTE CLOSING
62 71

K675 OPENING COIL


62 72
CS5

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852153
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ISOLATOR 2-989C CONTROL CKT (LADDER LOGIC) DRG. NO.: CPD KW85 SC21 SHT 53 OF 67
2C1
L1 L2
07 07

L3 CB OPEN
52X1 44 2
L5 CB CLOSED C
44 1
S1
89AX1
L7 2- 89A OPEN
89AX1 45 2
L9 2- 89A CLOSED C
45 1
S2
89BX1
L11 2- 89B OPEN
46 2
89BX1
2- 89B CLOSED C
1
S3
89LX
L15 2- 89L OPEN
47 2
89LX
L17 2- 89L CLOSED C
47 1
S4

89CX
L19 2- 89C OPEN
48 2
89CX
L21 2- 89C CLOSED C
48 1
S5
89LEX
L23 2- 89LE OPEN
48 2
89LEX
L25 2- 89LE CLOSED C
48 1
S6

52X1 SL01
L2
L27 CB OPEN
44 1 2

52X1 SL02
CB CLOSED L2
L29
44 1 2

A/T A/C CB AUTO TRIP


52X2 T N C
T C L33 SL03
L31 L2
44 1 2
L1 L2
CS1 CS1 55
55
63 63

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852154
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 INDICATION CKT DRG. NO.: CPD KW85 SC21 SHT 54 OF 67
2C1
L1 L2
54 2-952 CB MB 54
SL05
L1 TB5 X1-102 K41 X1-101 TB5 SPRING CHARGED L39
1 2 1 2
22 21

SL04
L1 TB5 X1-82 X1-81 TB5 SF6 GAS PRESSURE NORMAL L39A
3 4 1 2
22 21

SL06
89AX1 L41 L2
L41 2- 89A OPEN
45 1 2
89AX1 SL07
2- 89A CLOSED L43 L2
L43
45 1 2

89BX1 SL08
2- 89B OPEN L45 L2
L45
46 1 2
89BX1
L47 2- 89B CLOSED L47 SL09
L2
46
1 2
89LX SL10
2- 89L OPEN L49 L2
L49
47 1 2
89LX SL11
2- 89L CLOSED L2
L51 L51
47 1 2

SL12
89CX 2- 89C OPEN L53 L2
L53
48 1 2
89CX SL13
2- 89C CLOSED L2
L55 L55
48 1 2

89LEX SL14
L57 2- 89LE OPEN L57 L2
48 1 2
89LEX SL15
2- 89LE CLOSED L2
L59 L59
5
TB5

6
48 1

TB5
2R1

28
27

TB5
TB5

75A SL16
BUS-1 VT SELECTED L61 L2
L1
10 1 2

75B SL17
BUS-2 VT SELECTED L63 L2
1 2

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852155
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 INDICATION CKT DRG. NO.: CPD KW85 SC21 SHT 55 OF 67
EQPT FC
2R1 RTU TYPE ALAN
TBRTU
LOC 2C1
86A 1
S203
TBRTU
34 2

86A TBRTU
S205
34 3
86B TBRTU
S207
35 5
86B S209
TBRTU
35 4

96 TBRTU
S211
37 6

96 TBRTU
S213

44
37 7

TB8
2C1

44
TB8 89BX1 TBRTU
S223
46 1

89BX1 TBRTU
S225
46 2

89AX1 TBRTU
S219
45 3
89AX1 TBRTU
S221
45 4

89CX2 TBRTU
S235
48 5

89CX2
TBRTU
S237
48 6

52X2 TBRTU
S215
44 7
52X2
TBRTU
S217
44 8

89LX TBRTU
S227
47 9

89LX TBRTU
S229
47 10

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852156
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 RTU CKT. DRG. NO.: CPD KW85 SC21 SHT 56 OF 67
EQPT FC
TYPE ALAN
LOC 2C1

2R1 2C1

TB5 TB5
3 7
21M1
L203
21 4 8
21M2
L205
TB5
28 1 9
86AX
L207 L207
34 5 10
86BX
L209
35 2 21M1 11
L211
21M2 21
L211 6 12
28 21M1
L213
24PU 21 7 13

REF CPD KW85 SCXX SHT 25


L215
21 8 14
21M2 21M1 2-952
L215 A3
28
RX2 TB5 TB4 A8 TB4

15 23 K10 24 16
31 L201
RX1 X1-36 X1-37
L219 58
31 23 24
9 REF. DWG. (4) - G71AHS 17
SX 2 DA403 W455-A- SHT. 03
L221
SX 1 33 10 18

32

96 19
L223
37 11

21M2 20
L225
28 21M1
L225
L201 21 12
58

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852157
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ANNUNCIATION CKT DRG. NO.: CPD KW85 SC21 SHT 57 OF 67
EQPT FC
TYPE ALAN
LOC 2C1

2R1 2C1
L201
57
L201
57
21M2
L227
28 21M1
TB5
L227
21 13 21

21M2
L229 22
28 21M1
BB2E
24PU
21M2 L229 L231
21 14 50 23 REF. DWG. (4) - G71AHS
REF CPD KW85 SCXX SHT 25
DA403 W455-A- SHT. 02

24
K21
21M2 TB5 X1-61 X1-62

L233 25 14 13 22 26
21
28 21M1
L233
21 15
X1-46 X1-47

27 L12 L13 28 27
195R/Y/B REF. DWG. (4) - G71AHS
L239
DA403 W455-A- SHT. 03
39 16 28

295R/Y/B
L241
40 17 29

21M1 L243
21 18 30

21M2
31
29 19

95/86B L247 32
35
BB2E
95/86A L247 L247 24PU

34 20 33 34
REF CPD KW85 SCXX SHT 25

59

59

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852158
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ANNUNCIATION CKT DRG. NO.: CPD KW85 SC21 SHT 58 OF 67
EQPT FC
TYPE ALAN
LOC C1

2R1 2C1

58

21M2
L251
28 21M1
TB5 TB5
L251
21 21 35

21M2
L253 36
28 21M1 58 80A/B
L253 L255
21 22 BB2E 06
21M2 24PU
L259
37 38
28 21M1 REF CPD KW85 SCXX SHT 25
L259
21 23 39
21M2
L261
28 40
21M1
L261
21 24

21M1
41
L263
21 25 BB2E
24PU

42 43
21M2
L267
28 26 44
24PU

45
REF CPD KW85 SCXX SHT 25

INTERNALLY GEN INITIATION


FOR AC/DC FAIL

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852159
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ANNUNCIATION CKT DRG. NO.: CPD KW85 SC21 SHT 59 OF 67
2C1

H21
240V AC SUPPLY
H22 05

H21
PH +VE L101
220V DC SUPPLY
H22 NU
-VE L102 07
AT1A

TRIP
H26 AT2A
AN1A

N-TRIP
H28 PB03
AN2A
L113
AD1 TEST
1P3 1P4

DC FAIL
PB01
H35 AD2 ACCEPT
1P3 1P4
PB02
NON-TRIP TRIP
RESET
1P3 1P4

EBZ3 EBZ1
H26 -T2 + H21 L198 -T2 + L101

H28 L199
-T3 -T3

. H22
. . -T1 Ne

. PH

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852160
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ANNUNCIATION CKT DRG. NO.: CPD KW85 SC21 SHT 60 OF 67
203 205 207 209 211 213 LBB
DISTANCE DISTANCE GROUP-A GROUP-B
POWER SWING PROTN
PROTN PROTN TRIP RELAY TRIP RELAY
TRIP OPTD OPTD
MAIN-1 OPTD MAIN-2 OPTD OPTD. OPTD.
1 T 2 T 3 T 4 T 5 T 6 T

215 217 219 221 223 225


AUTO DIRECT TRIP DIRECT TRIP LBB POWER SWING
CB LOCKOUT TRIP RELAY
RECLOSE RECEIVED SEND BLOCKED
OPTD CHANNEL 1/2
LOCKOUT CHANNEL -1/2 OPTD
7 T 8 T 9 T 10 T 11 T 12 NT

227 229 231 233 235 237


OVER ISOLATOR DISTANCE
SOTF CB SF6 CB POLE
VOLTAGE DISCREPANCY PROTN GAS PRESSURE DISCREPANCY
OPTD ALARM
OPTD VT FUSE FAIL LOW OPTD
13 T 14 T 15 NT
T 16 NT 17 NT 18 T
239 241 243 245 247 249
TRIP CKT-1 TRIP CKT-2 DISTANCE DISTANCE GROUP-A/B CT CKT
FAULTY FAULTY RELAY MAIN-1 RELAY MAIN-2 TRIP RELAY FAULTY
ALARM ALARM FAULTY FAULTY FAULTY
19 NT
T 20 NT 21 NT 22 NT 23 NT 24 NT
251 253 255 257 259 261
BROKEN DC SUPPLY BUSBAR CARRIER CARRIER
AUTO RECLOSE SOURCE-1/2
CONDUCTOR SEND 1/2 RECEIVE 1/2
OPTD PU FAULTY
ALARM FAIL
25 NT
T 26 NT 27 NT 28 NT 29 T 30 NT
263 265 267 269
CARRIER CH-1 CARRIER CH-2 BUSBAR
BUSBAR
FAIL AC FAIL DC FAIL
PROTN OPTD FAIL INTERCON OPTD
31 NT
T 32 T 33 NT 34 T 35 NT 36 NT
OPERATING SEQUENCE
ALARM FAULT VISUAL AUDIBLE
LABELS CONDTITION CONTACT ANNUNCIATION ANNUNCIATION
3269PP728-7 - 2 NOS
FOR TRIP ALARM - BLACK LETTERS ON RED BACKGROUND 1. NORMAL OPEN OFF OFF
WINDOW SIZE: 72 x 34 mm FOR NON-TRIP ALARM - BLACK LETTERS ON YELLOW BACKGROUND
2. ABNORMAL CLOSE FLASHING ON
MAKE: ALAN
3. ACKNOWLEDGE A. CLOSE STEADY ON OFF
PUSH BUTTON IS PRESSED B. OPEN STEADY ON OFF
4. a). RESET PUSH BUTTON A. CLOSE STEADY ON OFF OFF
IS PRESSED
B. OPEN OFF OFF
b). IF ABNORMAL
CONDITION PERSISTS A. CLOSE FLASHING ON
LAMP PUSH BUTTON OPEN STEADY ON ON
IS PRESSED

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852161
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ANNUNCIATION INSCRIPTION DETAILS DRG. NO.: CPD KW85 SC21 SHT 61 OF 67
EQPT CS2/3/4/5
TYPE ODS
LOC 2C1

2C1
ODS/04/N/120/SR/PM/101
O N C
ODS/04/N/120/SR/PM/101
O N C
K609 K611
49 49
1P1 1P2 K629 K631
50 50
K609 K613
49 1P1 1P2
1P3 1P4 K629 K633
TB7 TB7 50
U77 U78
1P3 1P4
15 16 TB7 U81 U82
TB7
2P1 2P2
U79 U80 SPARE 19 20
2P1 2P2
17 18 U83 U84
SPARE
2P3 2P4
CS2 21 22
2P3 2P4
CS3

ODS/04/N/120/SR/PM/101
O N C
ODS/04/N/120/SR/PM/101
O N C
K649 K651
51 51
1P1 1P2 K673 K677
53 53
K649 K653
51 1P1 1P2
1P3 1P4 K673 K675
TB7 U85 U86
TB7 53
1P3 1P4
23 24 TB7 U89 U90
TB7
2P1 2P2
U87 U88
SPARE 27 28
2P1 2P2
25 26 U91 U92
SPARE
2P3 2P4
CS4 29 30
2P3 2P4
CS5

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852162
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 SWITCH CONTACT DISTRIBUTION DRG. NO.: CPD KW85 SC21 SHT 62 OF 67
EQPT CS1
TYPE ODS
LOC 2C1
2C1

ODS/22/N/120/SRL2/PM/108
T A/T A/C C

K501 K507
14 14 SYNCHRONISING CKT
1P1 1P2
K30 K30A
39 39 TO MANUAL TRIP TC-1
1P3 1P4
K177 K151
20 20 MAIN / TBC CB SOTF INI
2P1 2P2 ODS/12/LT/180/SP/PM/101
K30 K30B
39 39 TO MANUAL TRIP TC-1

CHK SYN

BYPASS
2P3 2P4
K277 K297

OFF
26 26 MAIN / TBC CB SOTF INI
3P1 3P2
K30 K30C G21 G22
39 39 TO MANUAL TRIP TC-1
3P4 1P1 1P2
TB4A 3P3 TB4A
P341A P119A G81 G72
14 15 CLOSE COMMAND TO BB PU
4P2 1P3 1P4
TB7 4P1 TB7
U191 U192 G11 G12
33 34 SPARE 2P1 2P2
4P3 4P4
G71 G72
5P2 2P3 2P4
5P1
K511 K513 K10 K11
32 32 DIR. TRIP-1 CKT.
5P4 3P1 3P2
5P3
K16 K15 CIRCUIT BREAKER K10 K12
38 38
6P2 REMOTE CLOSE 3P3 3P4
TB7 6P1 TB7 14
U193 U194 K501 K503
31 32
SPARE
6P4 4P1 4P2 SYNCHRONISING CKT
6P3
. .
K60 K60A
40 40 4P3 4P4
7P1 7P2 . .
K60B
40 TO MANUAL TRIP TC-2 5P1 5P2
7P3 7P4 K502 K504
K60C
40 5P3 5P4
8P1 8P2
K911 K913 . .
33 33 MANUAL TRIP OF DIR.TRIP-2 CKT. 6P1 6P2
8P3 8P4
K185 K187 K507 K505
32 32 MANUAL TRIP OF DIR.TRIP-1 CKT.
6P3 6P4
9P1 9P2
K785 K787 MANUAL TRIP OF DIR.TRIP-2 CKT.
33 33
9P3 9P4 SSS
54
L35 L33
54 TO INDICATION CKT.
10P1 10P2 (CB AUTO TRIP)
.
10P3 10P4
L31 L33
54
11P1 11P2
.
11P3 11P4

CS1

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852163
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 SWITCH CONTACT DISTRIBUTION DRG. NO.: CPD KW85 SC21 SHT 63 OF 67
2R1
ODS/08/N/90/SP/PM/102
ODS/08/N/90/SP/PM/102

OUT
IN

OUT
IN
. .
. .
1P1 1P2
K101
K101 K129 1P1 1P2
17 17 AUTO RECLOSE IN
K101D K145B
1P3 1P4 17 17
. . 1P3 1P4
. .
2P1 2P2
. . 2P1 2P2
K201D K261
2P3 2P4 27 27
. . 2P3 2P4
. .
3P1 3P2
K201 K259 3P1 3P2
27 27 AUTO RECLOSE IN
K201D K239A
3P3 3P4 29 29
. . 3P3 3P4
. .
4P1 4P2
. . 4P1 4P2
. .
4P3 4P4
4P3 4P4
ARS
CSS2

ODS/08/N/90/SP/PM/102
OUT
IN

. .

1P1 1P2
K201D K261B
27 27
1P3 1P4
. .

2P1 2P2
K101D K145A
17 17
2P3 2P4
. .

3P1 3P2
K101D K111B
21 21
3P3 3P4
. .

4P1 4P2
. .

4P3 4P4

CSS1

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852164
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 SWITCH CONTACT DISTRIBUTION DRG. NO.: CPD KW85 SC21 SHT 64 OF 67
EQPT TTS
2C1 ODS/30/LT/90/SP/PM/126 TYPE ODS

TRANSFER
2C1

NORMAL
LOC

INT
K101 K121 TO 21M1
17 17 BAY IN TRANSFER MODE K801 K832
1P1 1P2 67 67 TO I-T SWITCH CONTACT MULTI. RELAY CKT.
K701 K785 TO DIRECT TRIP SEND CIRCUIT (CH-2) 13P1 13P2
33 33
1P4 (MANUAL TRIP OF MAIN CB) K141T K109
1P3 20 20
. . 13P3 13P4
2P1 2P2 K143T K111 TBC CB STATUS
20 20
K101 K101S
47 47 IX1 MULTIPLICATION 14P1 14P2
2P3 2P4 K147T K113
K801 K891 20 20
66 66 TO N-I SWITCH CONTACT MULTI. RELAY CKT. 14P4
14P3
3P1 3P2
K801 K893
K171 K185 67 67 TO I-T SWITCH CONTACT MULTI. RELAY CKT.
32 32 TO DIRECT TRIP SEND CIRCUIT (CH-1)
3P4 (MANUAL TRIP OF TBC CB) 15P1 15P2
3P3
K101 K101S . .
47 47 IX1 MULTIPLICATION
4P1 4P2 15P3 15P4
. .
4P4
TTS
4P3
. .
5P1 5P2
K101 K157
47 47 IX1 MULTIPLICATION
5P3 5P4
. .
6P1 6P2
K12 K16
38 38 TO CB CLOSING CKT.
6P3 6P4
E111L E111T
14 14 TO SYNCHRONISING CKT.
7P1 7P2
K3 K30 39
39 TO CB CONTROL CKT. (TC-1)
7P3 7P4
E171L E171T
14 14 TO SYNCHRONISING CKT.
8P1 8P2
K53 K60
40 40 TO CB CONTROL CKT. (TC-2)
8P3 8P4
K193 K187
32 32 TO DIRECT TRIP SEND CIRCUIT (CH-1)
9P1 9P2 (LBB TRIP & BUSBAR TRIP OF TBC CB)
K801 K861
66 66 TO N-I SWITCH CONTACT MULTI. RELAY CKT.
9P3 9P4
K701 K789
33 33 TO DIRECT TRIP SEND CIRCUIT (CH-2)
10P1 10P2 (LBB TRIP & BUSBAR TRIP OF TBC CB)
TB7 U103 U104 TB7
39 10P4 40
10P3
K171 K189 TO DIRECT TRIP SEND CIRCUIT (CH-1)
32 32
11P1 11P2 (LBB TRIP & BUSBAR TRIP OF TBC CB)
. .
11P3 11P4
K793 K787 TO DIRECT TRIP SEND CIRCUIT (CH-2)
33 33
12P1 12P2 (LBB TRIP & BUSBAR TRIP OF TBC CB)
. .
12P3 12P4

TTS

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852165
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 SWITCH CONTACT DISTRIBUTION DRG. NO.: CPD KW85 SC21 SHT 65 OF 67
2C1 2R1 EQPT NIX1
48 TYPE MVAJM14
48 LOC 2R1
NIX1
N I T EQPT NIX2
K801 K861 TB8 TB8 K861 K802 MVAJM14
O TYPE
42 42 27 28
LOC 2R1
65

NIX2
K861 K802
27 O 28

NIX1
K891
25
R 26

NIX2
K891 TB8 TB8 K891
25
R 26
43 43

67
65
67

NIX1 NIX2
20 K141A K109 20 TO 21M1
5 7 9 11
MAIN / TBC CB R-PH OPEN

K143A K111 K201 K265 TO 21M2


20 6 8
20 TO 21M1 25 25 CB READY FOR A/R
MAIN / TBC CB Y-PH OPEN 13 15

K147A K113 TO 21M1


20 20 K51 K51A
9 11 MAIN / TBC CB B-PH OPEN 40 17 19
40 TO TC-2 CIRCUIT

P153 P157B
37
10 12
37 TO LBB TRIP RELAY CIRCUIT K207A K207 TO 21M2
26 10 12
26 MAIN / TBC CB R-PH OPEN
K1 K1A
39 13 15
39 TO TC-1 CIRCUIT K209 K209A TO 21M2
26 14 16
26 MAIN / TBC CB Y-PH OPEN

K101 K101B K211A K211 TO 21M2


09 14 16
09 VOLTAGE SELECTION CIRCUIT 26 26 MAIN / TBC CB B-PH OPEN
18 20

K101C
1K15 K6D TO TBC CB
K101 43 43
09 17 19
09 VOLTAGE SELECTION CIRCUIT 1 3 ( AUTO RECLOSER )

K101 K199A TRANSFER K701 K793T


19 19 33 DIRECT TRIP SEND CIRCUIT (CH-2)
18 20 CONTACT 2 4 33
(MANUAL TRIP OF TBC CB)
K191T K187 DIRECT TRIP SEND CIRCUIT (CH-1)
32 32 K791T K787
2 4 (MANUAL TRIP OF TBC CB) 33 DIRECT TRIP SEND CIRCUIT (CH-2)
TRANSFER 5 7 33
CONTACT MANUAL TRIP OF TBC CB)
K201 K233 TO 21M2
27 27
1 3 RELAY
K171 K193T DIRECT TRIP SEND CIRCUIT (CH-1)
32 32
6 8 (MANUAL TRIP OF TBC CB)

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852166
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 N-I SWITCH CONTACT MULTI. RELAY CKT. DRG. NO.: CPD KW85 SC21 SHT 66 OF 67
2C1 2R1 EQPT ITX1,2,3,4
66 TYPE MVAJM14
66 LOC 2R1
ITX1
N I T
K801 K832 TB8 TB8 K832 K802
O
46 46 27 28 ITX3
65
K832 K802
27
O 28

ITX4
K832 K802
27
O 28
ITX2 ITX1
K893 R
K832 K802 25 26 ITX2
O
27 28
K893 R
25 26 ITX3
K893
25 R 26 ITX4
K893 TB8 TB8
K893 R
47 47 25 26
65

ITX1 ITX2 ITX3


MAIN/TBC CB 3PH 86 ITX4
19 K113A K155 19 09 K275 K275A 09 K201 K225 TO TBC PROTN K403A K3AT TO TBC CB
OPTD(TO MAIN-1) 25 25 41 41
1 3 1 3 1 3 INITIATION 1 3 TRIP COIL-1 R-PH

K105G K141 CB READY K276A K276B K1T K1AT TO TBC CB K403B K3BT TO TBC CB
19 19 09 09 41 41 41 41
2 4 FOR A/R(TO MAIN-1) 2 4 2 4 TRIP COIL-1 CKT 5 7 TRIP COIL-1 Y-PH
VOLTAGE SELECTION
K105H K117 BB PROTN OPTD K285 K286 CIRCUIT K225E K241 CB READY K403C K3CT TO TBC CB
19 19 09 09 25 25 41 41
5 7 (TO MAIN-1) 5 7 5 7 FOR A/R(TO MAIN-2) 9 11 TRIP COIL-1 B-PH

K105J K153 MAIN/ TBC CB LBB K288 K286B K225F K291 TBC CB SF6 L/O K453A K53AT TO TBC CB
19 19 09 09 25 25 41 41
6 8 OPTD (TO MAIN-1) 6 8 6 8 (TO MAIN-2) 13 15 TRIP COIL-2 R-PH

K101 K159 TO TBC PROTN E121L E121T K245 K207 TBC CB R-PH OPEN K453B K53BT TO TBC CB
19 19 23 23 26 26 41 41
9 11 INITIATION 9 11
TO TBC 9 11 (TO MAIN-2) 17 19 TRIP COIL-2 Y-PH

K105M K151 TBC CB SOTF INI E181L E181T LINE VT EXTENSION CKT K247 K209 TBC CB Y-PH OPEN K453C K53CT TO TBC CB
20 20 23 23 26 26 41 41
10 12 (TO MAIN-1) 10 12 10 12 (TO MAIN-2) 2 4 TRIP COIL-2 B-PH

K105N K143 TBC CB SF6 L/O K249 K211 TBC CB B-PH OPEN K297 K205H TBC CB SOTF INI
19 19 09 09 26 26 26 26
13 15 (TO MAIN-1) 13 15 13 15 (TO MAIN-2) 6 8 (TO MAIN-2)

K101 K199C TO TBC CB K225B K251 MAIN/TBC BB PROTN/ K225A K253 MAIN/TBC CB 3PH 86
19 19 25 25 25 25
14 16 INITIATION 14 16 14 16 96 OPTD(TO MAIN-2) 10 12 OPTD(TO MAIN-2)

K101 K286C TO VT K51AT TO TBC CB K225C K251 MAIN/TBC BB PROTN/


09 09
SELECTION CKT 41 K51T 41 25 14 16
25
96 OPTD(TO MAIN-2)
17 19 17 19 17 19 TRIP COIL-2 CKT

K6C K1C TO TBC CB P141C TO MAIN CB K201 K299C TO TBC CB


42 42
CLOSING CKT 42 P143C 42 25 25
INITIATION
18 20 18 20 18 20 BUSBAR PU 18 20

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852167
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 I-T SWITCH CONTACT MULTI. RELAY CKT. DRG. NO.: CPD KW85 SC21 SHT 67 OF 67
R PHASE Y PHASE B PHASE R PHASE Y PHASE B PHASE

S3 S3 S3 S3 S3 S3 (2- 52CB OPEN)


S1LA-2 S1LA-1 S1LB-2 S1LB-1 S1LC-2 S1LC-1 S1LA-6 S1LA-5 S1LB-6 S1LB-6 S1LC-6 S1LC-6
(2- 52CB CLOSED) SHT 44 AUXILIARY RELAY CKT
SHT 44
20 29 20 29 20 29 112 111 112 111 112 111
21 MAIN-1 SHT 19
S1LA-4 S1LA-3 S1LB-4 S1LB-3 S1LC-4 S1LC-3 S1LA-10 S1LA-9 S1LB-10 S1LB-9 S1LC-10 S1LC-9

104 103 104 103 104 103 122 121 122 121 122 121
S1LA-8 S1LA-7 S1LB-8 S1LB-7 S1LC-8 S1LC-7 S1LA-14 S1LA-13 S1LB-14 S1LB-13 S1LC-14 S1LC-13
21 MAIN-2 SHT 26

114 113 114 113 114 113 132 131 132 131 132 131

S1LA-12 S1LA-11 S1LB-12 S1LB-11 S1LC-12 S1LC-11 S1LA-18 S1LA-17 S1LB-18 S1LB-17 S1LC-18 S1LC-17

124 123 124 123 124 123 142 141 142 141 142 141
S2 S2 S2 S2 S2 S2
S1LA-16 S1LA-15 S1LB-16 S1LB-15 S1LC-16 S1LC-15 S1LA-22 S1LA-21 S1LB-22 S1LB-21 S1LC-22 S1LC-21

134 133 134 133 134 133 152 151 152 151 152 151
S1LA-20 S1LA-19 S1LB-20 S1LB-19 S1LC-20 S1LC-19 S1LA-26 S1LA-25 S1LB-26 S1LB-25 S1LC-26 S1LC-25

144 143 144 143 144 143 162 161 162 161 162 161
S4 S4 S4 S4 S4 S4
S1LA-24 S1LA-23 S1LB-24 S1LB-23 S1LC-24 S1LC-23 S1LA-30 S1LA-29 S1LB-30 S1LB-29 S1LC-30 S1LC-29

154 153 154 153 154 153 72 71 72 71 72 71

S1LA-28 S1LA-27 S1LB-28 S1LB-27 S1LC-28 S1LC-27 S1LA-34 S1LA-33 S1LB-34 S1LB-33 S1LC-34 S1LC-33

94 93 94 93 94 93 82 81 82 81 82 81
S1LA-32 S1LA-31 S1LB-32 S1LB-31 S1LC-32 S1LC-31 S1LA-38 S1LA-37 S1LB-38 S1LB-37 S1LC-38 S1LC-37

184 183 184 183 184 183 102 101 102 101 102 101
S1LA-36 S1LA-35 S1LB-36 S1LB-35 S1LC-36 S1LC-35 S1LA-42 S1LA-41 S1LB-42 S1LB-41 S1LC-42 S1LC-41

174 173 174 173 174 173 172 171 172 171 172 171

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852168
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 CIRCUIT BREAKER CONTACTS DISTRIBUTION DRG. NO.: CPD KW85 SC21 SHT 68 OF 67
89Na

89Nb

FOR ALSTOM REF: ENGG.REF.NO.: KW85 PREPARED BY: GKA REVISION: Z


SCHEME TYPE: FEEDER
CUSTOMER: GUJARAT ENERGY TRANS. CORP.LTD
PROJECT: SUPPLY OF 400/220KV CRP PANELS AT VARIOUS S/S ABCD SCHEMATIC DRAWING
PANEL TYPES: 2C1 2R1 FILE: DW852169
CHECKED BY: JKK DATE: 19.03.2015
BASE FILE: P.O.NO.: CE(P)/Proc/E-2443/I/LOI/CRP/ALSTOM/779 ALSTOM T&D India
- Limited - AUTOMATION SAS TITLE: 220KV LINE CONTROL & PROTECTION APPROVED BY: JKK SCALE: --

SALES ORDER: - Dated 08.10.2014 PALLAVARAM CHENNAI 600043 ISOLATOR CONTACTS DISTRIBUTION DRG. NO.: CPD KW85 SC21 SHT 69 OF 67
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852C1


Cust. GETCO Panel type 2C1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


CIL 1 H3 FS2 2 K2 FS104 1 J22

CIL 2 H4 FS1 1 J15 FS104 2 J24

TH 1 H5 FS1 2 K1 FS103 1 J21

TH 2 H7 LK93 1 H2 FS103 2 J23

FSC 1 K17 LK93 2 H22 FS102 1 J12

FSC 2 K4 FS93 1 H1 FS102 2 J14

FS16 1 J16 FS93 2 H21 FS101 1 J11

FS16 2 K902 LK92 1 H2 FS101 2 J13

FS15 1 J15 LK92 2 H12 52X3 1 K511

FS15 2 K901 FS92 1 H1 52X3 2 K521

FS14 1 J26 FS92 2 H11 52X3 5 K911

FS14 2 K802 LK91 1 H2 52X3 6 K921

FS13 1 J25 LK91 2 H4 52X3 9 K805

FS13 2 K801 FS91 1 H1 52X3 10 K802

FS12 1 J16 FS91 2 H3 52X3 11 K804

FS12 2 K602 LK173 1 E71 52X3 12 K802

FS11 1 J15 LK173 2 E173 52X3 E01 EARTH

FS11 2 K601 FS153 1 E51 52X3 E02 ELOOP

FS10 1 J16 FS153 2 E153 89CX2 1 K851

FS10 2 K502 FS133 1 E31 89CX2 2 K855

FS9 1 J15 FS133 2 E133 89CX2 3 S201

FS9 2 K501 FS113 1 E11 89CX2 4 S237

FS8 1 J26 FS113 2 E113 89CX2 5 K856

FS8 2 L2 LK75 1 E171L 89CX2 6 K854

FS7 1 J25 LK75 2 G71 89CX2 7 U149

FS7 2 L1 FS75 1 E111L 89CX2 8 U150

FS6 1 J16 FS75 2 G11 89CX2 9 K817

FS6 2 L102 LK74 1 E71 89CX2 10 K802

FS5 1 J15 LK74 2 G81 89CX2 11 K819

FS5 2 L101 FS74 1 E11 89CX2 12 K802

FS4 1 J26 FS74 2 G21 89CX2 13 S201

FS4 2 K52 LK25 1 E171L 89CX2 14 S235

FS3 1 J25 LK25 2 E72 89CX2 17 U145

FS3 2 K51 FS25 1 E111L 89CX2 18 U146

FS2 1 J16 FS25 2 E12 89CX2 E EARTH

FS2 2 K2 FS104 1 J22 SL09 1 L47

Page 1 of 10
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852C1


Cust. GETCO Panel type 2C1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


SL09 2 L2 VART 4 D33 TB7 9 U153

S3 1 L13 VART 5 D52 TB7 10 U154

S3 2 L11 VART 6 D53 TB7 11 U201

S3 C L2 VART 7 S8 TB7 12 U203

SL08 1 L45 VART 8 S7 TB7 13 U147

SL08 2 L2 VART 9 E113 TB7 14 U148

S1 1 L5 VART 10 E133 TB7 15 U77

S1 2 L3 VART 11 E153 TB7 16 U78

S1 C L2 VART 12 E173 TB7 17 U79

SL07 1 L43 VART 13 S6 TB7 18 U80

SL07 2 L2 VART 14 S5 TB7 19 U81

S2 1 L9 VART 15 K902 TB7 20 U82

S2 2 L7 VART 16 K901 TB7 21 U83

S2 C L2 BB2 1 1H1 TB7 22 U84

SL06 1 L41 BB2 2 1H2 TB7 23 U85

SL06 2 L2 BB2 5 E111T TB7 24 U86

WT 1 D11 BB2 6 E171T TB7 25 U87

WT 2 D12 EBZ1 + L101 TB7 26 U88

WT 3 D31 EBZ1 Ne H22 TB7 27 U89

WT 4 D32 EBZ1 PH H35 TB7 28 U90

WT 5 D51 EBZ1 -T2 L198 TB7 29 U91

WT 6 D52 EBZ1 -T3 L199 TB7 30 U92

WT 7 S4 EBZ2 1 H25 TB7 31 U193

WT 8 S3 EBZ2 2 H22 TB7 32 U194

WT 9 E113 EBZ3 + H21 TB7 33 U191

WT 10 E133 EBZ3 -T2 H26 TB7 34 U192

WT 11 E153 EBZ3 -T3 H28 TB7 35 U155

WT 12 E173 TB7 1 U1 TB7 36 U156

WT 13 S2 TB7 2 U2 TB7 39 U103

WT 14 S1 TB7 3 U3 TB7 40 U104

WT 15 K902 TB7 4 U4 TB7 41 U145

WT 16 K901 TB7 5 U129 TB7 42 U146

VART 1 D12 TB7 6 U130 TB7 43 U149

VART 2 D13 TB7 7 U151 TB7 44 U150

VART 3 D32 TB7 8 U152 SL14 1 L57

VART 4 D33 TB7 9 U153 SL14 2 L2

Page 2 of 10
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852C1


Cust. GETCO Panel type 2C1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


SL15 1 L59 AT3 1 D53 A3 1 S21

SL15 2 L2 AT3 2 D55 A3 2 S22

S6 1 L25 AT3 9 S22 A2 1 S17

S6 2 L23 AT3 10 S21 A2 2 S18

S6 C L2 AT3 13 S24 A1 1 S13

SL10 1 L49 AT3 14 S23 A1 2 S14

SL10 2 L2 AT3 15 K902 VB 1 S25

S4 1 L17 AT3 16 K901 VB 2 S26

S4 2 L15 VBT 7 E378 FC AD1 H21

S4 C L2 VBT 8 E377 FC AD2 H35

SL11 1 L51 VBT 9 S26 FC AKN L109

SL11 2 L2 VBT 10 S25 FC AN1 L102

SL12 1 L53 VBT 13 S28 FC AN2 L199

SL12 2 L2 VBT 14 S27 FC AN1A H22

S5 1 L21 VBT 15 K902 FC AN2A H28

S5 2 L19 VBT 16 K901 FC AT1 L102

S5 C L2 VLT 7 E12 FC AT2 L198

SL13 1 L55 VLT 8 E72 FC AT1A H22

SL13 2 L2 VLT 9 S36 FC AT2A H26

AT1 1 D13 VLT 10 S35 FC C EARTH

AT1 2 D15 VLT 13 S38 FC 1C L203

AT1 9 S14 VLT 14 S37 FC 2C L205

AT1 10 S13 VLT 15 K902 FC 3C L207

AT1 13 S16 VLT 16 K901 FC 4C L209

AT1 14 S15 HS 1 H3 FC 5C L211

AT1 15 K902 HS 2 H5 FC 6C L213

AT1 16 K901 PS 1 H11 FC 7C L215

AT2 1 D33 PS 2 H12 FC 8C L225A

AT2 2 D35 PS E EARTH FC 9C L219

AT2 9 S18 VL 1 S35 FC 10C L221

AT2 10 S17 VL 2 S36 FC 11C L223

AT2 13 S20 VAR 1 S5 FC 12C L225

AT2 14 S19 VAR 2 S6 FC 13C L227

AT2 15 K902 W 1 S1 FC 14C L229

AT2 16 K901 W 2 S2 FC 15C L231

AT3 1 D53 A3 1 S21 FC 16C L233

Page 3 of 10
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852C1


Cust. GETCO Panel type 2C1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


FC 17C L235 TVM 3S D56 CS3 2P4 U84

FC 18C L237 TVM Y E134 CS2 1P1 K609

FC 19C L239 SL05 1 L39 CS2 1P2 K611

FC 20C L241 SL05 2 L2 CS2 1P3 K609

FC 21C L243 SL04 1 L39A CS2 1P4 K613

FC 22C L245 SL04 2 L2 CS2 2P1 U77

FC 23C L247 SL03 1 L35 CS2 2P2 U78

FC 24C L249 SL03 2 L2 CS2 2P3 U79

FC 25C L251 SL02 1 L29 CS2 2P4 U80

FC 26C L253 SL02 2 L2 CS1 1P1 K501

FC 27C L255 SL01 1 L27 CS1 1P2 K507

FC 28C L257 SL01 2 L2 CS1 1P3 K30

FC 29C L259 PB03 1P3 L107 CS1 1P4 K30A

FC 30C L261 PB03 1P4 L113 CS1 2P1 K177

FC 31C L263 PB02 1P3 L111 CS1 2P2 K151

FC 32C L265 PB02 1P4 L113 CS1 2P3 K30

FC 33C L267 PB02 2P3 K201 CS1 2P4 K30B

FC 34C L269 PB02 2P4 K223 CS1 3P1 K277

FC CC L113 PB01 1P3 L109 CS1 3P2 K297

FC COMM L201 PB01 1P4 L113 CS1 3P3 K30

FC E EARTH PB05 1P3 H23 CS1 3P4 K30C

FC N L102 PB05 1P4 H27 CS1 4P1 P341A

FC NU H22 SL51 1 H23 CS1 4P2 P119A

FC P L101 SL51 2 H22 CS1 4P3 U191

FC PH H21 PB04 1P1 J13 CS1 4P4 U192

FC RST L111 PB04 1P2 J17 CS1 5P3 K511

FC TEST L107 PB04 2P1 J23 CS1 5P4 K513

TVM B E154 PB04 2P2 J27 CS1 6P1 K16

TVM 1L D71 CS3 1P1 K629 CS1 6P2 K15

TVM 2L D71 CS3 1P2 K631 CS1 6P3 U193

TVM 3L D71 CS3 1P3 K629 CS1 6P4 U194

TVM N E174 CS3 1P4 K633 CS1 7P1 K60

TVM R E114 CS3 2P1 U81 CS1 7P2 K60A

TVM 1S D16 CS3 2P2 U82 CS1 7P3 K60

TVM 2S D36 CS3 2P3 U83 CS1 7P4 K60B

TVM 3S D56 CS3 2P4 U84 CS1 8P1 K60

Page 4 of 10
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852C1


Cust. GETCO Panel type 2C1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


CS1 8P2 K60C SS E EARTH TTS 7P1 E111L

CS1 8P3 K911 SSS 1P1 G21 TTS 7P2 E111T

CS1 8P4 K913 SSS 1P2 G22 TTS 7P3 K3

CS1 9P1 K185 SSS 1P3 G81 TTS 7P4 K30

CS1 9P2 K187 SSS 1P4 G72 TTS 8P1 E171L

CS1 9P3 K785 SSS 2P1 G11 TTS 8P2 E171T

CS1 9P4 K787 SSS 2P2 G12 TTS 8P3 K53

CS1 10P1 L35 SSS 2P3 G71 TTS 8P4 K60

CS1 10P2 L33 SSS 2P4 G72 TTS 9P1 K193

CS1 11P1 L31 SSS 3P1 K10 TTS 9P2 K187

CS1 11P2 L33 SSS 3P2 K11 TTS 9P3 K801

CS4 1P1 K649 SSS 3P3 K10 TTS 9P4 K861

CS4 1P2 K651 SSS 3P4 K12 TTS 10P1 K701

CS4 1P3 K649 SSS 4P1 K501 TTS 10P2 K789

CS4 1P4 K653 SSS 4P2 K503 TTS 10P3 U103

CS4 2P1 U85 SSS 5P3 K502 TTS 10P4 U104

CS4 2P2 U86 SSS 5P4 K504 TTS 11P1 K171

CS4 2P3 U87 SSS 6P3 K507 TTS 11P2 K189

CS4 2P4 U88 SSS 6P4 K505 TTS 12P1 K793

CS5 1P1 K673 TTS 1P1 K101 TTS 12P2 K787

CS5 1P2 K677 TTS 1P2 K121 TTS 13P1 K801

CS5 1P3 K673 TTS 1P3 K701 TTS 13P2 K832

CS5 1P4 K675 TTS 1P4 K785 TTS 13P3 K141T

CS5 2P1 U89 TTS 2P3 K101 TTS 13P4 K109

CS5 2P2 U90 TTS 2P4 K101S TTS 14P1 K143T

CS5 2P3 U91 TTS 3P1 K801 TTS 14P2 K111

CS5 2P4 U92 TTS 3P2 K891 TTS 14P3 K147T

SS 1 G12 TTS 3P3 K171 TTS 14P4 K113

SS 2 G72 TTS 3P4 K185 TTS 15P1 K801

SS 3 G22 TTS 4P1 K101 TTS 15P2 K893

SS 7 K503 TTS 4P2 K101S DCSS 1P1 J13

SS 8 K504 TTS 5P3 K101 DCSS 1P2 J25

SS 9 K505 TTS 5P4 K157 DCSS 2P1 J14

SS 11 K11 TTS 6P3 K12 DCSS 2P2 J26

SS 12 K12 TTS 6P4 K16 DCSS 2P3 J23

SS E EARTH TTS 7P1 E111L DCSS 2P4 J15

Page 5 of 10
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852C1


Cust. GETCO Panel type 2C1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


DCSS 3P3 J24 52X2 1 S201 89AX1 17 S201

DCSS 3P4 J16 52X2 2 S215 89AX1 18 S221

DCSS 4P1 J23 52X2 3 S201 89AX1 19 K625

DCSS 4P2 J25 52X2 4 S217 89AX1 20 K635

DCSS 4P3 J24 52X2 5 K601 89AX1 E EARTH

DCSS 4P4 J26 52X2 6 K607 89BX1 1 L1

DCSS 5P1 J13 52X2 7 U151 89BX1 2 L11

DCSS 5P2 J15 52X2 8 U152 89BX1 3 S201

DCSS 5P3 J14 52X2 9 K805 89BX1 4 S223

DCSS 5P4 J16 52X2 10 K802 89BX1 5 L1

VS B E153 52X2 11 K804 89BX1 6 L45

VS N E173 52X2 12 K802 89BX1 7 L1

VS R E113 52X2 13 L1 89BX1 8 L13

VS V1 E378 52X2 14 L31 89BX1 9 K810

VS V2 E377 52X2 15 U153 89BX1 10 K802

VS Y E133 52X2 16 U154 89BX1 11 K809

52X1 1 L1 52X2 17 U155 89BX1 12 K802

52X1 2 L3 52X2 18 U156 89BX1 13 K607

52X1 3 U129 52X2 E EARTH 89BX1 14 K605

52X1 4 U130 89AX1 1 L1 89BX1 15 L1

52X1 5 L1 89AX1 2 L7 89BX1 16 L47

52X1 6 L27 89AX1 3 S201 89BX1 17 S201

52X1 9 K805 89AX1 4 S219 89BX1 18 S225

52X1 10 K802 89AX1 5 L1 89BX1 19 K605

52X1 11 K804 89AX1 6 L41 89BX1 20 K615

52X1 12 K802 89AX1 7 L1 89BX1 E EARTH

52X1 13 K601 89AX1 8 L9 89CX1 1 L1

52X1 14 K627 89AX1 9 K808 89CX1 2 L19

52X1 15 L1 89AX1 10 K802 89CX1 5 L1

52X1 16 L5 89AX1 11 K807 89CX1 6 L53

52X1 17 K601 89AX1 12 K802 89CX1 9 K817

52X1 18 K641 89AX1 13 K627 89CX1 10 K802

52X1 19 L1 89AX1 14 K625 89CX1 11 K819

52X1 20 L29 89AX1 15 L1 89CX1 12 K802

52X1 E EARTH 89AX1 16 L43 89CX1 13 K671A

52X2 1 S201 89AX1 17 S201 89CX1 14 K675A

Page 6 of 10
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852C1


Cust. GETCO Panel type 2C1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


89CX1 15 L1 80A 5 L255 89LX 16 K10

89CX1 16 L21 80A 6 K201 89LX 17 K675A

89CX1 19 L1 80A 7 K297A 89LX 18 K675B

89CX1 20 L55 80A 8 J17 89LX 19 S201

89CX1 E EARTH 80A 10 J14 89LX 20 S229

89LEX 1 L1 80A 11 H23 89LX E EARTH

89LEX 2 L23 80A 14 U1 TTB 1 D16

89LEX 3 U201 80A 15 U2 TTB 2 D15

89LEX 4 U203 80A E EARTH TTB 3 D71

89LEX 5 L1 80B 1 L201 TTB 4 D36

89LEX 6 L57 80B 3 H21 TTB 5 D35

89LEX 7 L1 80B 5 L255 TTB 6 D71

89LEX 8 L25 80B 6 K201 TTB 7 D56

89LEX 9 K821 80B 7 K297B TTB 8 D55

89LEX 10 K802 80B 8 J27 TTB 9 D71

89LEX 11 K823 80B 10 J24 TTB A1 E114

89LEX 12 K802 80B 11 H23 TTB A2 E113

89LEX 13 K641 80B 14 U3 TTB B1 E134

89LEX 14 K643 80B 15 U4 TTB B2 E133

89LEX 15 L1 80B E EARTH TTB C1 E154

89LEX 16 L59 89LX 1 L1 TTB C2 E153

89LEX 17 K849 89LX 2 L15 TTB N1 E174

89LEX 18 K851A 89LX 3 L1 TTB N2 E173

89LEX 19 U147 89LX 4 L17 TB1 1 D11

89LEX 20 U148 89LX 5 L1 TB1 2 D71S

89LEX E EARTH 89LX 6 L49 TB1 3 D31

80C 1 H23 89LX 7 L1 TB1 4 D71S

80C 5 H25 89LX 8 L51 TB1 5 D51

80C 6 H23 89LX 9 K815 TB1 6 D71S

80C 7 H27 89LX 10 K802 TB1 7 D71

80C 8 H27 89LX 11 K813 TB1 8 D71S

80C 10 H22 89LX 12 K802 TB2 1 E111L

80C E EARTH 89LX 13 S201 TB2 2 E171L

80A 1 L201 89LX 14 S227 TB2 4 E11

80A 3 H21 89LX 15 K8 TB2 5 E31

80A 5 L255 89LX 16 K10 TB2 6 E51

Page 7 of 10
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852C1


Cust. GETCO Panel type 2C1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


TB2 7 E71 TBRTU 23 S37 TB4 47 K605

TB2 9 E111T TBRTU 24 S38 TB4 49 K602

TB2 10 E171T TB4 1 K1 TB4 50 K609

TB3 1 H1 TB4 2 K2 TB4 51 K611

TB3 1 1H1 TB4 3 K17 TB4 52 K613

TB3 2 1H2 TB4 4 K15 TB4 53 K601

TB3 2 H2 TB4 5 K14 TB4 54 K635

TB3 4 J11 TB4 6 K3 TB4 55 K625

TB3 5 J12 TB4 7 K30A TB4 57 K602

TB3 6 J21 TB4 8 K30B TB4 58 K629

TB3 7 J22 TB4 9 K30C TB4 59 K631

TB3A 1 1H1 TB4 12 K53 TB4 60 K633

TB3A 2 1H2 TB4 13 K60A TB4 61 K643

TBRTU 1 S223 TB4 14 K60B TB4 62 K602

TBRTU 2 S225 TB4 15 K60C TB4 63 K649

TBRTU 3 S219 TB4 23 K801 TB4 64 K651

TBRTU 4 S221 TB4 24 K804 TB4 65 K653

TBRTU 5 S235 TB4 25 K805 TB4 66 K675B

TBRTU 6 S237 TB4 26 K801 TB4 67 K602

TBRTU 7 S215 TB4 27 K807 TB4 68 K851A

TBRTU 8 S217 TB4 28 K808 TB4 69 K858

TBRTU 9 S227 TB4 29 K801 TB4 70 K673

TBRTU 10 S229 TB4 30 K809 TB4 71 K677

TBRTU 11 S3 TB4 31 K810 TB4 72 K675

TBRTU 12 S4 TB4 33 K801 TB5 1 L1

TBRTU 13 S7 TB4 34 K813 TB5 2 L39

TBRTU 14 S8 TB4 35 K815 TB5 3 L1

TBRTU 15 S15 TB4 37 K801 TB5 4 L39A

TBRTU 16 S16 TB4 38 K817 TB5 5 L1

TBRTU 17 S19 TB4 39 K819 TB5 6 L2

TBRTU 18 S20 TB4 41 K801 TB5 7 L201

TBRTU 19 S23 TB4 42 K821 TB5 8 L203

TBRTU 20 S24 TB4 43 K823 TB5 9 L205

TBRTU 21 S27 TB4 45 K601 TB5 10 L207

TBRTU 22 S28 TB4 46 K615 TB5 11 L209

TBRTU 23 S37 TB4 47 K605 TB5 12 L211

Page 8 of 10
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852C1


Cust. GETCO Panel type 2C1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


TB5 13 L213 TB4A 2 K143T TB8 22 K4

TB5 14 L215 TB4A 3 K147T TB8 23 K8

TB5 15 L201 TB4A 4 K189 TB8 24 K14

TB5 16 L225A TB4A 5 K193 TB8 25 K1

TB5 17 L219 TB4A 6 K521 TB8 26 K1

TB5 18 L221 TB4A 7 K513 TB8 27 K2

TB5 19 L223 TB4A 8 K187 TB8 28 K51

TB5 20 L225 TB4A 9 K789 TB8 29 K51

TB5 21 L227 TB4A 10 K793 TB8 30 K808

TB5 22 L229 TB4A 11 K921 TB8 31 K807

TB5 23 L231 TB4A 12 K913 TB8 32 K802

TB5 24 L233 TB4A 13 K787 TB8 33 K810

TB5 25 L201 TB4A 14 P341A TB8 34 K809

TB5 26 L235 TB4A 15 P119A TB8 35 K52

TB5 27 L237 TB8 1 J15 TB8 37 K856

TB5 28 L239 TB8 2 J16 TB8 38 K851

TB5 29 L241 TB8 3 J25 TB8 40 K849

TB5 30 L243 TB8 4 J26 TB8 41 K858

TB5 31 L245 TB8 5 K101 TB8 42 K861

TB5 32 L247 TB8 6 K121 TB8 43 K891

TB5 33 L201 TB8 7 K177 TB8 44 S201

TB5 34 L249 TB8 8 K151 TB8 46 K832

TB5 35 L251 TB8 9 K277 TB8 47 K893

TB5 36 L253 TB8 10 K297 TB8 48 K101

TB5 37 L201 TB8 11 K201 TB8 49 K101

TB5 38 L257 TB8 12 K223 TB8 50 K157

TB5 39 L259 TB8 13 K201 TB8 51 K101S

TB5 40 L261 TB8 14 K297A TB8 52 K601

TB5 41 L263 TB8 15 K297B TB8 53 K671A

TB5 42 L201 TB8 16 K171 TB8 54 K109

TB5 43 L265 TB8 17 K511 TB8 55 K111

TB5 44 L267 TB8 18 K187 TB8 56 K113

TB5 45 L269 TB8 19 K701 TB8 60 K851

TB5 50 L201 TB8 20 K911 TB8 61 K855

TB4A 1 K141T TB8 21 K787 TB8 62 K854

TB4A 2 K143T TB8 22 K4 TB8 63 K856

Page 9 of 10
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852C1


Cust. GETCO Panel type 2C1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


HT 1 H7
HT 2 H4
EBAR 1 EARTH
EBAR 2 ELOOP

Page 10 of 10
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2C1
Wire no. Colour Connection pattern
1H1 BB2(1)
1H2 BB2(2)
1H1 TB3(1)
1H2 TB3(2)
1H1 TB3A(1)
1H2 TB3A(2)
D11 RD WT(1)- TB1(1)
D12 RD WT(2)- VART(1)
D13 RD VART(2)- AT1(1)
D15 RD AT1(2)- TTB(2)
D16 RD TVM(1S)- TTB(1)
D31 YL WT(3)- TB1(3)
D32 YL WT(4)- VART(3)
D33 YL VART(4)- AT2(1)
D35 YL AT2(2)- TTB(5)
D36 YL TVM(2S)- TTB(4)
D51 BL WT(5)- TB1(5)
D52 BL WT(6)- VART(5)
D53 BL VART(6)- AT3(1)
D55 BL AT3(2)- TTB(8)
D56 BL TVM(3S)- TTB(7)
D71 BK TVM(1L)- TVM(2L)- TVM(3L)- TTB(3)- TTB(6)- TTB(9)- TB1(7)
D71S BK TB1(2)- TB1(4)- TB1(6)- TB1(8)
E11 RD FS113(1)- FS74(1)- TB2(4)
E111L RD FS75(1)- FS25(1)- TTS(7P1)- TB2(1)
E111T RD BB2(5)- TTS(7P2)- TB2(9)
E113 RD FS113(2)- WT(9)- VART(9)- VS(R)- TTB(A2)
E114 RD TVM(R)- TTB(A1)
E12 RD FS25(2)- VLT(7)
E133 YL FS133(2)- WT(10)- VART(10)- VS(Y)- TTB(B2)
E134 YL TVM(Y)- TTB(B1)
E153 BL FS153(2)- WT(11)- VART(11)- VS(B)- TTB(C2)
E154 BL TVM(B)- TTB(C1)
E171L BK LK75(1)- LK25(1)- TTS(8P1)- TB2(2)
E171T BK BB2(6)- TTS(8P2)- TB2(10)
E173 BK LK173(2)- WT(12)- VART(12)- VS(N)- TTB(N2)
E174 BK TVM(N)- TTB(N1)
E31 YL FS133(1)- TB2(5)
E377 BK VBT(8)- VS(V2)
E378 BK VBT(7)- VS(V1)
E51 BL FS153(1)- TB2(6)
E71 BK LK173(1)- LK74(1)- TB2(7)
E72 BK LK25(2)- VLT(8)
52X3(E01)- 89CX2(E)- PS(E)- FC(C)- FC(E)- SS(E)- 52X1(E)- 52X2(E)- 89AX1(E)- 89BX1(E)- 89CX1(E)- 89LEX(E)-
EARTH GN 80C(E)- 80A(E)- 80B(E)- 89LX(E)- EBAR(01)
ELOOP GN 52X3(E02)- EBAR(02)
G11 RD FS75(2)- SSS(2P1)
G12 RD SS(1)- SSS(2P2)
G21 RD FS74(2)- SSS(1P1)
G22 RD SS(3)- SSS(1P2)
G71 BK LK75(2)- SSS(2P3)
G72 BK SS(2)- SSS(1P4)- SSS(2P4)
G81 BK LK74(2)- SSS(1P3)
H1 BK FS93(1)- FS92(1)- FS91(1)- TB3(1)
H11 BK FS92(2)- PS(1)
H12 BK LK92(2)- PS(2)
H2 BK LK93(1)- LK92(1)- LK91(1)- TB3(2)
H21 BK FS93(2)- EBZ3(+)- FC(AD1)- FC(PH)- 80A(3)- 80B(3)
H22 BK LK93(2)- EBZ1(Ne)- EBZ2(2)- FC(AN1A)- FC(AT1A)- FC(NU)- SL51(2)- 80C(10)
H23 BK PB05(1P3)- SL51(1)- 80C(1)- 80C(6)- 80A(11)- 80B(11)
H25 BK EBZ2(1)- 80C(5)
H26 BK EBZ3(-T2)- FC(AT2A)
H27 BK PB05(1P4)- 80C(7)- 80C(8)
H28 BK EBZ3(-T3)- FC(AN2A)
H3 BK CIL(1)- FS91(2)- HS(1)
H35 BK EBZ1(PH)- FC(AD2)
H4 BK CIL(2)- LK91(2)- HT(2)
H5 BK TH(1)- HS(2)
H7 BK TH(2)- HT(1)

Page 1 of 6
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2C1
Wire no. Colour Connection pattern
J11 GY FS101(1)- TB3(4)
J12 GY FS102(1)- TB3(5)
J13 GY FS101(2)- PB04(1P1)- DCSS(1P1)- DCSS(5P1)
J14 GY FS102(2)- DCSS(2P1)- DCSS(5P3)- 80A(10)
J15 GY FS15(1)- FS11(1)- FS9(1)- FS5(1)- FS1(1)- DCSS(2P4)- DCSS(5P2)- TB8(1)
J16 GY FS16(1)- FS12(1)- FS10(1)- FS6(1)- FS2(1)- DCSS(3P4)- DCSS(5P4)- TB8(2)
J17 GY PB04(1P2)- 80A(8)
J21 GY FS103(1)- TB3(6)
J22 GY FS104(1)- TB3(7)
J23 GY FS103(2)- PB04(2P1)- DCSS(2P3)- DCSS(4P1)
J24 GY FS104(2)- DCSS(3P3)- DCSS(4P3)- 80B(10)
J25 GY FS13(1)- FS7(1)- FS3(1)- DCSS(1P2)- DCSS(4P2)- TB8(3)
J26 GY FS14(1)- FS8(1)- FS4(1)- DCSS(2P2)- DCSS(4P4)- TB8(4)
J27 GY PB04(2P2)- 80B(8)
K1 GY FS1(2)- TB4(1)- TB8(25)- TB8(26)
K10 GY SSS(3P1)- SSS(3P3)- 89LX(16)
K101 GY TTS(1P1)- TTS(2P3)- TTS(4P1)- TTS(5P3)- TB8(5)- TB8(48)- TB8(49)
K101S GY TTS(2P4)- TTS(4P2)- TB8(51)
K109 GY TTS(13P4)- TB8(54)
K11 GY SS(11)- SSS(3P2)
K111 GY TTS(14P2)- TB8(55)
K113 GY TTS(14P4)- TB8(56)
K12 GY SS(12)- SSS(3P4)- TTS(6P3)
K121 GY TTS(1P2)- TB8(6)
K14 GY TB4(5)- TB8(24)
K141T GY TTS(13P3)- TB4A(1)
K143T GY TTS(14P1)- TB4A(2)
K147T GY TTS(14P3)- TB4A(3)
K15 GY CS1(6P2)- TB4(4)
K151 GY CS1(2P2)- TB8(8)
K157 GY TTS(5P4)- TB8(50)
K16 GY CS1(6P1)- TTS(6P4)
K17 GY FSC(1)- TB4(3)
K171 GY TTS(3P3)- TTS(11P1)- TB8(16)
K177 GY CS1(2P1)- TB8(7)
K185 GY CS1(9P1)- TTS(3P4)
K187 GY CS1(9P2)- TTS(9P2)- TB4A(8)- TB8(18)
K189 GY TTS(11P2)- TB4A(4)
K193 GY TTS(9P1)- TB4A(5)
K2 GY FS2(2)- TB4(2)- TB8(27)
K201 GY PB02(2P3)- 80A(6)- 80B(6)- TB8(11)- TB8(13)
K223 GY PB02(2P4)- TB8(12)
K277 GY CS1(3P1)- TB8(9)
K297 GY CS1(3P2)- TB8(10)
K297A GY 80A(7)- TB8(14)
K297B GY 80B(7)- TB8(15)
K3 GY TTS(7P3)- TB4(6)
K30 GY CS1(1P3)- CS1(2P3)- CS1(3P3)- TTS(7P4)
K30A GY CS1(1P4)- TB4(7)
K30B GY CS1(2P4)- TB4(8)
K30C GY CS1(3P4)- TB4(9)
K4 GY FSC(2)- TB8(22)
K501 GY FS9(2)- CS1(1P1)- SSS(4P1)
K502 GY FS10(2)- SSS(5P3)
K503 GY SS(7)- SSS(4P2)
K504 GY SS(8)- SSS(5P4)
K505 GY SS(9)- SSS(6P4)
K507 GY CS1(1P2)- SSS(6P3)
K51 GY FS3(2)- TB8(28)- TB8(29)
K511 GY 52X3(1)- CS1(5P3)- TB8(17)
K513 GY CS1(5P4)- TB4A(7)
K52 GY FS4(2)- TB8(35)
K521 GY 52X3(2)- TB4A(6)
K53 GY TTS(8P3)- TB4(12)
K60 GY CS1(7P1)- CS1(7P3)- CS1(8P1)- TTS(8P4)
K601 GY FS11(2)- 52X1(13)- 52X1(17)- 52X2(5)- TB4(45)- TB4(53)- TB8(52)
K602 GY FS12(2)- TB4(49)- TB4(57)- TB4(62)- TB4(67)
K605 GY 89BX1(14)- 89BX1(19)- TB4(47)
K607 GY 52X2(6)- 89BX1(13)

Page 2 of 6
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2C1
Wire no. Colour Connection pattern
K609 GY CS2(1P1)- CS2(1P3)- TB4(50)
K60A GY CS1(7P2)- TB4(13)
K60B GY CS1(7P4)- TB4(14)
K60C GY CS1(8P2)- TB4(15)
K611 GY CS2(1P2)- TB4(51)
K613 GY CS2(1P4)- TB4(52)
K615 GY 89BX1(20)- TB4(46)
K625 GY 89AX1(14)- 89AX1(19)- TB4(55)
K627 GY 52X1(14)- 89AX1(13)
K629 GY CS3(1P1)- CS3(1P3)- TB4(58)
K631 GY CS3(1P2)- TB4(59)
K633 GY CS3(1P4)- TB4(60)
K635 GY 89AX1(20)- TB4(54)
K641 GY 52X1(18)- 89LEX(13)
K643 GY 89LEX(14)- TB4(61)
K649 GY CS4(1P1)- CS4(1P3)- TB4(63)
K651 GY CS4(1P2)- TB4(64)
K653 GY CS4(1P4)- TB4(65)
K671A GY 89CX1(13)- TB8(53)
K673 GY CS5(1P1)- CS5(1P3)- TB4(70)
K675 GY CS5(1P4)- TB4(72)
K675A GY 89CX1(14)- 89LX(17)
K675B GY 89LX(18)- TB4(66)
K677 GY CS5(1P2)- TB4(71)
K701 GY TTS(1P3)- TTS(10P1)- TB8(19)
K785 GY CS1(9P3)- TTS(1P4)
K787 GY CS1(9P4)- TTS(12P2)- TB4A(13)- TB8(21)
K789 GY TTS(10P2)- TB4A(9)
K793 GY TTS(12P1)- TB4A(10)
K8 GY 89LX(15)- TB8(23)
FS13(2)- TTS(3P1)- TTS(9P3)- TTS(13P1)- TTS(15P1)- TB4(23)- TB4(26)- TB4(29)- TB4(33)- TB4(37)- TB4(41)
K801 GY
FS14(2)- 52X3(10)- 52X3(12)- 89CX2(10)- 89CX2(12)- 52X1(10)- 52X1(12)- 52X2(10)- 52X2(12)- 89AX1(10)-
89AX1(12)- 89BX1(10)- 89BX1(12)- 89CX1(10)- 89CX1(12)- 89LEX(10)- 89LEX(12)- 89LX(10)- 89LX(12)-
K802 GY TB8(32)
K804 GY 52X3(11)- 52X1(11)- 52X2(11)- TB4(24)
K805 GY 52X3(9)- 52X1(9)- 52X2(9)- TB4(25)
K807 GY 89AX1(11)- TB4(27)- TB8(31)
K808 GY 89AX1(9)- TB4(28)- TB8(30)
K809 GY 89BX1(11)- TB4(30)- TB8(34)
K810 GY 89BX1(9)- TB4(31)- TB8(33)
K813 GY 89LX(11)- TB4(34)
K815 GY 89LX(9)- TB4(35)
K817 GY 89CX2(9)- 89CX1(9)- TB4(38)
K819 GY 89CX2(11)- 89CX1(11)- TB4(39)
K821 GY 89LEX(9)- TB4(42)
K823 GY 89LEX(11)- TB4(43)
K832 GY TTS(13P2)- TB8(46)
K849 GY 89LEX(17)- TB8(40)
K851 GY 89CX2(1)- TB8(38)- TB8(60)
K851A GY 89LEX(18)- TB4(68)
K854 GY 89CX2(6)- TB8(62)
K855 GY 89CX2(2)- TB8(61)
K856 GY 89CX2(5)- TB8(37)- TB8(63)
K858 GY TB4(69)- TB8(41)
K861 GY TTS(9P4)- TB8(42)
K891 GY TTS(3P2)- TB8(43)
K893 GY TTS(15P2)- TB8(47)
K901 GY FS15(2)- WT(16)- VART(16)- AT1(16)- AT2(16)- AT3(16)- VBT(16)- VLT(16)
K902 GY FS16(2)- WT(15)- VART(15)- AT1(15)- AT2(15)- AT3(15)- VBT(15)- VLT(15)
K911 GY 52X3(5)- CS1(8P3)- TB8(20)
K913 GY CS1(8P4)- TB4A(12)
K921 GY 52X3(6)- TB4A(11)
FS7(2)- 52X1(1)- 52X1(5)- 52X1(15)- 52X1(19)- 52X2(13)- 89AX1(1)- 89AX1(5)- 89AX1(7)- 89AX1(15)-
89BX1(1)- 89BX1(5)- 89BX1(7)- 89BX1(15)- 89CX1(1)- 89CX1(5)- 89CX1(15)- 89CX1(19)- 89LEX(1)- 89LEX(5)-
89LEX(7)- 89LEX(15)- 89LX(1)- 89LX(3)- 89LX(5)- 89LX(7)- TB5(1)- TB5(3)- TB5(5)
L1 GY
L101 GY FS5(2)- EBZ1(+)- FC(P)
L102 GY FS6(2)- FC(AN1)- FC(AT1)- FC(N)

Page 3 of 6
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2C1
Wire no. Colour Connection pattern
L107 GY FC(TEST)- PB03(1P3)
L109 GY FC(AKN)- PB01(1P3)
L11 GY S3(2)- 89BX1(2)
L111 GY FC(RST)- PB02(1P3)
L113 GY FC(CC)- PB03(1P4)- PB02(1P4)- PB01(1P4)
L13 GY S3(1)- 89BX1(8)
L15 GY S4(2)- 89LX(2)
L17 GY S4(1)- 89LX(4)
L19 GY S5(2)- 89CX1(2)
L198 GY EBZ1(-T2)- FC(AT2)
L199 GY EBZ1(-T3)- FC(AN2)
FS8(2)- SL09(2)- S3(C)- SL08(2)- S1(C)- SL07(2)- S2(C)- SL06(2)- SL14(2)- SL15(2)- S6(C)- SL10(2)- S4(C)-
L2 GY SL11(2)- SL12(2)- S5(C)- SL13(2)- SL05(2)- SL04(2)- SL03(2)- SL02(2)- SL01(2)- TB5(6)
L201 GY FC(COMM)- 80A(1)- 80B(1)- TB5(7)- TB5(15)- TB5(25)- TB5(33)- TB5(37)- TB5(42)- TB5(50)
L203 GY FC(1C)- TB5(8)
L205 GY FC(2C)- TB5(9)
L207 GY FC(3C)- TB5(10)
L209 GY FC(4C)- TB5(11)
L21 GY S5(1)- 89CX1(16)
L211 GY FC(5C)- TB5(12)
L213 GY FC(6C)- TB5(13)
L215 GY FC(7C)- TB5(14)
L219 GY FC(9C)- TB5(17)
L221 GY FC(10C)- TB5(18)
L223 GY FC(11C)- TB5(19)
L225 GY FC(12C)- TB5(20)
L225A GY FC(8C)- TB5(16)
L227 GY FC(13C)- TB5(21)
L229 GY FC(14C)- TB5(22)
L23 GY S6(2)- 89LEX(2)
L231 GY FC(15C)- TB5(23)
L233 GY FC(16C)- TB5(24)
L235 GY FC(17C)- TB5(26)
L237 GY FC(18C)- TB5(27)
L239 GY FC(19C)- TB5(28)
L241 GY FC(20C)- TB5(29)
L243 GY FC(21C)- TB5(30)
L245 GY FC(22C)- TB5(31)
L247 GY FC(23C)- TB5(32)
L249 GY FC(24C)- TB5(34)
L25 GY S6(1)- 89LEX(8)
L251 GY FC(25C)- TB5(35)
L253 GY FC(26C)- TB5(36)
L255 GY FC(27C)- 80A(5)- 80B(5)
L257 GY FC(28C)- TB5(38)
L259 GY FC(29C)- TB5(39)
L261 GY FC(30C)- TB5(40)
L263 GY FC(31C)- TB5(41)
L265 GY FC(32C)- TB5(43)
L267 GY FC(33C)- TB5(44)
L269 GY FC(34C)- TB5(45)
L27 GY SL01(1)- 52X1(6)
L29 GY SL02(1)- 52X1(20)
L3 GY S1(2)- 52X1(2)
L31 GY CS1(11P1)- 52X2(14)
L33 GY CS1(10P2)- CS1(11P2)
L35 GY SL03(1)- CS1(10P1)
L39 GY SL05(1)- TB5(2)
L39A GY SL04(1)- TB5(4)
L41 GY SL06(1)- 89AX1(6)
L43 GY SL07(1)- 89AX1(16)
L45 GY SL08(1)- 89BX1(6)
L47 GY SL09(1)- 89BX1(16)
L49 GY SL10(1)- 89LX(6)
L5 GY S1(1)- 52X1(16)
L51 GY SL11(1)- 89LX(8)
L53 GY SL12(1)- 89CX1(6)
L55 GY SL13(1)- 89CX1(20)
L57 GY SL14(1)- 89LEX(6)

Page 4 of 6
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2C1
Wire no. Colour Connection pattern
L59 GY SL15(1)- 89LEX(16)
L7 GY S2(2)- 89AX1(2)
L9 GY S2(1)- 89AX1(8)
P119A GY CS1(4P2)- TB4A(15)
P341A GY CS1(4P1)- TB4A(14)
S1 GY WT(14)- W(1)
S13 GY AT1(10)- A1(1)
S14 GY AT1(9)- A1(2)
S15 GY AT1(14)- TBRTU(15)
S16 GY AT1(13)- TBRTU(16)
S17 GY AT2(10)- A2(1)
S18 GY AT2(9)- A2(2)
S19 GY AT2(14)- TBRTU(17)
S2 GY WT(13)- W(2)
S20 GY AT2(13)- TBRTU(18)
89CX2(3)- 89CX2(13)- 52X2(1)- 52X2(3)- 89AX1(3)- 89AX1(17)- 89BX1(3)- 89BX1(17)- 89LX(13)- 89LX(19)-
S201 GY TB8(44)
S21 GY AT3(10)- A3(1)
S215 GY 52X2(2)- TBRTU(7)
S217 GY 52X2(4)- TBRTU(8)
S219 GY 89AX1(4)- TBRTU(3)
S22 GY AT3(9)- A3(2)
S221 GY 89AX1(18)- TBRTU(4)
S223 GY 89BX1(4)- TBRTU(1)
S225 GY 89BX1(18)- TBRTU(2)
S227 GY 89LX(14)- TBRTU(9)
S229 GY 89LX(20)- TBRTU(10)
S23 GY AT3(14)- TBRTU(19)
S235 GY 89CX2(14)- TBRTU(5)
S237 GY 89CX2(4)- TBRTU(6)
S24 GY AT3(13)- TBRTU(20)
S25 GY VBT(10)- VB(1)
S26 GY VBT(9)- VB(2)
S27 GY VBT(14)- TBRTU(21)
S28 GY VBT(13)- TBRTU(22)
S3 GY WT(8)- TBRTU(11)
S35 GY VLT(10)- VL(1)
S36 GY VLT(9)- VL(2)
S37 GY VLT(14)- TBRTU(23)
S38 GY VLT(13)- TBRTU(24)
S4 GY WT(7)- TBRTU(12)
S5 GY VART(14)- VAR(1)
S6 GY VART(13)- VAR(2)
S7 GY VART(8)- TBRTU(13)
S8 GY VART(7)- TBRTU(14)
U1 GY TB7(1)- 80A(14)
U103 GY TB7(39)- TTS(10P3)
U104 GY TB7(40)- TTS(10P4)
U129 GY TB7(5)- 52X1(3)
U130 GY TB7(6)- 52X1(4)
U145 GY 89CX2(17)- TB7(41)
U146 GY 89CX2(18)- TB7(42)
U147 GY TB7(13)- 89LEX(19)
U148 GY TB7(14)- 89LEX(20)
U149 GY 89CX2(7)- TB7(43)
U150 GY 89CX2(8)- TB7(44)
U151 GY TB7(7)- 52X2(7)
U152 GY TB7(8)- 52X2(8)
U153 GY TB7(9)- 52X2(15)
U154 GY TB7(10)- 52X2(16)
U155 GY TB7(35)- 52X2(17)
U156 GY TB7(36)- 52X2(18)
U191 GY TB7(33)- CS1(4P3)
U192 GY TB7(34)- CS1(4P4)
U193 GY TB7(31)- CS1(6P3)
U194 GY TB7(32)- CS1(6P4)
U2 GY TB7(2)- 80A(15)
U201 GY TB7(11)- 89LEX(3)
U203 GY TB7(12)- 89LEX(4)

Page 5 of 6
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2C1
Wire no. Colour Connection pattern
U3 GY TB7(3)- 80B(14)
U4 GY TB7(4)- 80B(15)
U77 GY TB7(15)- CS2(2P1)
U78 GY TB7(16)- CS2(2P2)
U79 GY TB7(17)- CS2(2P3)
U80 GY TB7(18)- CS2(2P4)
U81 GY TB7(19)- CS3(2P1)
U82 GY TB7(20)- CS3(2P2)
U83 GY TB7(21)- CS3(2P3)
U84 GY TB7(22)- CS3(2P4)
U85 GY TB7(23)- CS4(2P1)
U86 GY TB7(24)- CS4(2P2)
U87 GY TB7(25)- CS4(2P3)
U88 GY TB7(26)- CS4(2P4)
U89 GY TB7(27)- CS5(2P1)
U90 GY TB7(28)- CS5(2P2)
U91 GY TB7(29)- CS5(2P3)
U92 GY TB7(30)- CS5(2P4)

Page 6 of 6
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


CIL 1 H13 295B 5 K6 SX2 E EARTH

CIL 2 H14 295B 7 K5E RX2 2 K228

TH 1 H15 295B 13 K66 RX2 4 K201

TH 2 H17 295B 14 K65 RX2 7 L201

295R 1 L201 295B 21 K51A RX2 8 K201

295R 2 K201 295B 22 K53C RX2 9 L219

295R 3 L241 295B 27 K51 RX2 10 K203

295R 4 K235 295B 28 K52 RX2 11 K769

295R 5 K5D 295B E EARTH RX2 14 K702

295R 7 K5C SX1 1 U37 RX2 E EARTH

295R 13 K62 SX1 2 L201 195B 1 L201

295R 14 K61 SX1 3 U38 195B 2 K101

295R 21 K51A SX1 4 L221 195B 3 L239

295R 22 K53A SX1 5 K101 195B 4 K123

295R 27 K51 SX1 7 K127 195B 5 K5

295R 28 K52 SX1 13 K187 195B 7 K5A

295R E01 EARTH SX1 14 K172 195B 13 K35A

295R E02 ELOOP SX1 E EARTH 195B 14 K35

295Y 1 L201 RX1 1 K139 195B 21 K1A

295Y 2 K201 RX1 3 K101 195B 22 K3C

295Y 3 L241 RX1 7 L201 195B 27 K1

295Y 4 K235 RX1 8 K101 195B 28 K2

295Y 5 K5D RX1 9 L219 195B E EARTH

295Y 7 K5E RX1 10 K103 195Y 1 L201

295Y 13 K64 RX1 11 K169 195Y 2 K101

295Y 14 K63 RX1 14 K172 195Y 3 L239

295Y 21 K51A RX1 E EARTH 195Y 4 K123

295Y 22 K53B SX2 1 U39 195Y 5 K5B

295Y 27 K51 SX2 2 L201 195Y 7 K5A

295Y 28 K52 SX2 3 U40 195Y 13 K34

295Y E EARTH SX2 4 L221 195Y 14 K33

295B 1 L201 SX2 5 K201 195Y 21 K1A

295B 2 K201 SX2 7 K226 195Y 22 K3B

295B 3 L241 SX2 13 K787 195Y 27 K1

295B 4 K235 SX2 14 K702 195Y 28 K2

295B 5 K6 SX2 E EARTH 195Y E EARTH

Page 1 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


195R 1 L201 75D E EARTH 75B 16 L63

195R 2 K101 75C 1 K286 75B 17 E51

195R 3 L239 75C 3 K286D 75B 19 E251

195R 4 K123 75C 5 E121 75B 25 K285A

195R 5 K5B 75C 6 E141 75B 26 K102

195R 7 K5C 75C 7 E21 75B 27 K288B

195R 13 K32 75C 8 E41 75B 28 K102

195R 14 K31 75C 9 E161 75B E EARTH

195R 21 K1A 75C 10 E181 75A 1 K286

195R 22 K3A 75C 11 E61 75A 2 U9

195R 27 K1 75C 12 E81 75A 3 K288B

195R 28 K2 75C 13 E116 75A 4 U10

195R E EARTH 75C 14 E136 75A 9 E111

75D 1 K275 75C 15 E16 75A 10 E171

75D 3 K286A 75C 16 E36 75A 11 E11

75D 5 E21 75C 17 E156 75A 12 E71

75D 6 E41 75C 18 E176 75A 13 E131

75D 7 E221 75C 19 E56 75A 14 L1

75D 8 E241 75C 20 E76 75A 15 E31

75D 9 E61 75C 25 K276 75A 16 L61

75D 10 E81 75C 26 K102 75A 17 E151

75D 11 E261 75C 27 K286A 75A 19 E51

75D 12 E281 75C 28 K102 75A 25 K276

75D 13 E16 75C E EARTH 75A 26 K102

75D 14 E36 75B 1 K275 75A 27 K288A

75D 15 E216 75B 2 U11 75A 28 K102

75D 16 E236 75B 3 K288A 75A E EARTH

75D 17 E56 75B 4 U12 21M1 . K151A

75D 18 E76 75B 9 E11 21M1 +N2 K101

75D 19 E256 75B 10 E71 21M1 C2 A72

75D 20 E276 75B 11 E211 21M1 C3 A12

75D 25 K285A 75B 12 E271 21M1 C5 A72

75D 26 K102 75B 13 E31 21M1 C6 A32

75D 27 K286D 75B 14 L1 21M1 C8 A72

75D 28 K102 75B 15 E231 21M1 C9 A52

75D E EARTH 75B 16 L63 21M1 C11 A75

Page 2 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


21M1 C12 A74 21M1 E12 K135 21M1 H1 K55

21M1 C19 E124 21M1 E13 K102A 21M1 H2 K53A

21M1 C20 E144 21M1 E14 K137 21M1 H3 K55

21M1 C21 E164 21M1 E15 K102 21M1 H4 K53B

21M1 C22 E184 21M1 E16 K139 21M1 H5 K55

21M1 C23 E23 21M1 F1 K102 21M1 H6 K53C

21M1 C24 E83 21M1 F2 K141 21M1 H7 P115C

21M1 D1 K102 21M1 F3 K102 21M1 H9 P143C

21M1 D2 K109 21M1 F4 K143 21M1 H11 P117C

21M1 D3 K102 21M1 F5 K102 21M1 H12 P143C

21M1 D4 K111 21M1 F6 K145 21M1 H14 P119C

21M1 D5 K102 21M1 F7 K102 21M1 H15 P143C

21M1 D6 K113 21M1 F8 K147 21M1 H17 1K15A

21M1 D7 K102 21M1 F9 K102 21M1 H18 1K15

21M1 D8 K115 21M1 F10 K149 21M1 J1 K701

21M1 D9 K102 21M1 F11 K102 21M1 J2 K787

21M1 D10 K117 21M1 F12 K151 21M1 J3 1K15

21M1 D11 K102 21M1 F13 K102 21M1 J4 1K17A

21M1 D12 K119 21M1 F14 K153 21M1 J5 K101A

21M1 D13 K102 21M1 F15 K102 21M1 J6 K103

21M1 D14 K121 21M1 F16 K155 21M1 J7 K7

21M1 D15 K102 21M1 G1 1K15 21M1 J8 K14

21M1 D16 K123 21M1 G2 1K15B 21M1 J9 K201

21M1 E EARTH 21M1 G3 1K15 21M1 J10 K229

21M1 E1 K102 21M1 G4 1K15C 21M1 J11 P15C

21M1 E2 K125 21M1 G5 P153A 21M1 J12 P153

21M1 E3 K102 21M1 G6 P151B 21M1 J14 P123C

21M1 E4 K127 21M1 G8 K453A 21M1 J15 P143C

21M1 E5 K102 21M1 G9 K151A 21M1 J17 P121A

21M1 E6 K129 21M1 G11 K453B 21M1 J18 P143A

21M1 E7 K102 21M1 G12 K151A 21M1 K1 K13

21M1 E8 K131 21M1 G14 K453C 21M1 K2 K3C

21M1 E9 K102A 21M1 G15 K151A 21M1 K3 K407

21M1 E10 K133 21M1 G17 K197A 21M1 K4 K403A

21M1 E11 K102A 21M1 G18 K195A 21M1 K5 K407

21M1 E12 K135 21M1 H1 K55 21M1 K6 K403B

Page 3 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


21M1 K7 K407 21M1 M10 L229 89BX2 5 K285A

21M1 K8 K403C 21M1 M11 L201 89BX2 6 U158

21M1 K9 K171 21M1 M12 L233 89BX2 7 K288

21M1 K10 K187 21M1 M14 L253 89BX2 8 U159

21M1 K11 P141A 21M1 M15 L201 89BX2 10 K7

21M1 K12 P111A 21M1 M17 L251 89BX2 12 K8

21M1 K14 P113A 21M1 M18 L201 89BX2 13 K101C

21M1 K15 P141A 21M1 N11 L201 89BX2 14 P173

21M1 K17 P115A 21M1 N12 L243 89BX2 15 K286

21M1 K18 P141A 21M1 -N1 K102 89BX2 16 P157

21M1 L1 L201 89AX2 1 K101B 89BX2 18 U175

21M1 L2 L211 89AX2 2 K671C 89BX2 20 U176

21M1 L3 L201 89AX2 3 K276 89BX2 25 K809

21M1 L4 L263 89AX2 4 K673C 89BX2 26 K802

21M1 L5 L201 89AX2 5 K276 89BX2 27 K810

21M1 L6 L259 89AX2 6 U131 89BX2 28 K802

21M1 L7 L201 89AX2 7 K276A 89BX2 E EARTH

21M1 L8 L261 89AX2 8 U132 96 1 K6

21M1 L9 L201 89AX2 10 K7 96 2 K3H

21M1 L10 L213 89AX2 12 K8 96 3 K7

21M1 L11 K111B 89AX2 13 K101B 96 4 K7D

21M1 L12 K320 89AX2 14 P171 96 6 K1A

21M1 L14 K3A 89AX2 15 K275 96 8 K3B

21M1 L15 K13 89AX2 16 P157 96 10 K1A

21M1 L17 K3B 89AX2 17 U133 96 12 K3C

21M1 L18 K13 89AX2 19 U134 96 14 K51A

21M1 M1 L201 89AX2 25 K807 96 16 K53A

21M1 M2 L215 89AX2 26 K802 96 17 K1A

21M1 M3 L201 89AX2 27 K808 96 18 K51A

21M1 M4 L203 89AX2 28 K802 96 19 K3A

21M1 M5 L201 89AX2 E EARTH 96 20 K53B

21M1 M6 L225 89BX2 1 K101C 96 25 P103D

21M1 M7 L201 89BX2 2 K675D 96 26 P2

21M1 M8 L227 89BX2 3 K285A 96 27 P157B

21M1 M9 L201 89BX2 4 K677D 96 28 P2

21M1 M10 L229 89BX2 5 K285A 96 29 S201

Page 4 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


96 30 U169 21M2 F7c E179 21M2 M5c K291

96 31 S213 21M2 F8c E87 21M2 M6c K297B

96 32 U170 21M2 H1a K207 21M2 M7c K297

96 33 K51A 21M2 H2a K211 21M2 M8c K253

96 34 L201 21M2 H3a K223 21M2 P1b K1D

96 35 K53C 21M2 H4a K231 21M2 P2b K1D

96 36 L223 21M2 H5a K228 21M2 P3b K205

96 37 K101 21M2 H6a K259 21M2 P4b K205

96 38 K201 21M2 H7a K237 21M2 P5b K205

96 39 K153 21M2 H8a K243 21M2 P6b K187A

96 40 K251 21M2 H1b K202 21M2 P7b K701

96 42 S201 21M2 H3b K202 21M2 P8b 1K15

96 44 S211 21M2 H5b K202 21M2 P1c K403B

96 45 U141 21M2 H7b K202A 21M2 P2c K403C

96 47 U142 21M2 H1c K209 21M2 P3c K213A

96 E EARTH 21M2 H2c K217 21M2 P4c K213B

21M2 +B5b K201 21M2 H3c K233 21M2 P5c K213C

21M2 B1a L201 21M2 H4c K235 21M2 P6c K189A

21M2 -B6a K202 21M2 H5c K226 21M2 P7c K787

21M2 B2b L245 21M2 H6c K229 21M2 P8c 1K17A

21M2 E EARTH 21M2 H7c K239 21M2 U1b K201B

21M2 F5a E119 21M2 M5a K241 21M2 U2b K7

21M2 F6a E139 21M2 M6a K297A 21M2 U3b K101

21M2 F7a E159 21M2 M7a K299A 21M2 U4b P143A

21M2 F8a E27 21M2 M8a K251 21M2 U5b K171

21M2 F1b A85 21M2 M1b K3D 21M2 U6b K239A

21M2 F2b A85 21M2 M2b K3D 21M2 U7b K101

21M2 F3b A85 21M2 M3b K3D 21M2 U8b P143C

21M2 F4b A89 21M2 M4b K1D 21M2 U1c K203

21M2 F1c A23 21M2 M5b K202 21M2 U2c K14

21M2 F2c A43 21M2 M7b K202 21M2 U3c K131

21M2 F3c A63 21M2 M1c K3A 21M2 U4c P121A

21M2 F4c A87 21M2 M2c K3B 21M2 U5c K187

21M2 F5c E179 21M2 M3c K3C 21M2 U6c K240

21M2 F6c E179 21M2 M4c K403A 21M2 U7c K125

21M2 F7c E179 21M2 M5c K291 21M2 U8c P123C

Page 5 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


21M2 W1a L215 CSS2 1P4 K145B 95/86B 2 L201

21M2 W2a L225 CSS2 2P3 K201D 95/86B 3 U43

21M2 W3a L229 CSS2 2P4 K261 95/86B 4 L247

21M2 W4a L253 CSS2 3P3 K201D 95/86B 13 K263

21M2 W5a L211 CSS2 3P4 K239A 95/86B 21 K201

21M2 W6a L259 ARS 1P3 K101 95/86B 22 K203

21M2 W7a U14 ARS 1P4 K129 95/86B 27 K201

21M2 W1b L201 ARS 3P3 K201 95/86B 28 K202

21M2 W2b L201 ARS 3P4 K259 95/86B E EARTH

21M2 W3b L201 SL17 1 L63 86BX 1 K201

21M2 W4b L201 SL17 2 L2 86BX 2 L201

21M2 W5b L201 IX1 2 U139 86BX 3 K253

21M2 W6b L201 IX1 4 U140 86BX 4 L209

21M2 W7b U13 IX1 5 K187B 86BX 5 K101

21M2 W1c L205 IX1 6 K787B 86BX 6 P143A

21M2 W2c L227 IX1 7 K187 86BX 7 K155

21M2 W3c L233 IX1 8 K787 86BX 8 P121A

21M2 W4c L251 IX1 9 K201 86BX 9 K101

21M2 W5c L267 IX1 10 K101 86BX 10 P143C

21M2 W6c L261 IX1 11 K231 86BX 11 K125

SL16 1 L61 IX1 12 K119 86BX 12 P121C

SL16 2 L2 IX1 13 K171 86BX 13 P141A

CSS1 1P3 K201D IX1 14 K701 86BX 14 P143C

CSS1 1P4 K261B IX1 15 K511 86BX 15 P117A

CSS1 2P3 K101D IX1 16 K911 86BX 16 P123C

CSS1 2P4 K145A IX1 17 K851 86BX 25 K204

CSS1 3P3 K101D IX1 18 K856 86BX 28 K202

CSS1 3P4 K111B IX1 19 K849 86BX E EARTH

PB01 1P3 K101 IX1 20 K858 86B 1 K4A

PB01 1P4 K103D IX1 25 K101S 86B 2 K7D

PB01 2P3 K201 IX1 26 K102 86B 3 K5

PB01 2P4 K203D IX1 27 K157 86B 4 K6B

PB01 3P3 P1 IX1 28 K102 86B 5 K201

PB01 3P4 P103D IX1 E EARTH 86B 6 K1A

CSS2 1P3 K101D 95/86B 1 U42 86B 7 K204

CSS2 1P4 K145B 95/86B 2 L201 86B 8 K3C

Page 6 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


86B 9 K201 86B 48 S207 86A 5 K101

86B 10 K1T 86B E EARTH 86A 6 K1A

86B 11 K263 95/86A 1 U23 86A 7 K161A

86B 12 K403A 95/86A 2 L201 86A 8 K3C

86B 13 K1A 95/86A 3 U24 86A 9 K101

86B 14 K1T 95/86A 4 L247 86A 10 K1T

86B 15 K3A 95/86A 13 K163 86A 11 K163

86B 16 K403B 95/86A 21 K101 86A 12 K403A

86B 17 K1A 95/86A 22 K103 86A 13 K1A

86B 18 K1T 95/86A 27 K101 86A 14 K1T

86B 19 K3B 95/86A 28 K102 86A 15 K3A

86B 20 K403C 95/86A E EARTH 86A 16 K403B

86B 25 K203D 86AX 1 K201 86A 17 K1A

86B 26 K202 86AX 2 L201 86A 18 K1T

86B 27 K203 86AX 3 K253 86A 19 K3B

86B 28 K202 86AX 4 L207 86A 20 K403C

86B 29 U121 86AX 5 K101 86A 25 K103D

86B 30 S201 86AX 6 P143A 86A 26 K102

86B 31 U123 86AX 7 K155 86A 27 K103

86B 32 S209 86AX 8 P121A 86A 28 K102

86B 33 K51A 86AX 9 K101 86A 29 U117

86B 34 K51T 86AX 10 P143C 86A 30 S201

86B 35 K53A 86AX 11 K125 86A 31 U118

86B 36 K453B 86AX 12 P121C 86A 32 S205

86B 37 K51A 86AX 13 P141A 86A 33 K51A

86B 38 K51T 86AX 14 P143C 86A 34 K51T

86B 39 K53B 86AX 15 P117A 86A 35 K53A

86B 40 K453C 86AX 16 P123C 86A 36 K453B

86B 41 K51A 86AX 25 K161A 86A 37 K51A

86B 42 U44 86AX 28 K102 86A 38 K51T

86B 43 K53C 86AX E EARTH 86A 39 K53B

86B 44 U45 86A 1 K4B 86A 40 K453C

86B 45 K51T 86A 2 K1C 86A 41 K51A

86B 46 S201 86A 3 K4A 86A 42 U119

86B 47 K453A 86A 4 K3H 86A 43 K53C

86B 48 S207 86A 5 K101 86A 44 U120

Page 7 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


86A 45 K51T NIX2 6 K171 ITX1 18 K6C

86A 46 S201 NIX2 7 K787 ITX1 19 K286C

86A 47 K453A NIX2 8 K193T ITX1 20 K1C

86A 48 S203 NIX2 10 K207A ITX1 25 K893

86A E EARTH NIX2 12 K207 ITX1 26 K802

NIX1 1 K201 NIX2 13 K201 ITX1 27 K832

NIX1 2 K191T NIX2 14 K209 ITX1 28 K802

NIX1 3 K233 NIX2 15 K265 ITX1 E EARTH

NIX1 4 K187 NIX2 16 K209A ITX2 1 K275

NIX1 5 K141A NIX2 17 K51 ITX2 2 K276A

NIX1 6 K143A NIX2 18 K211A ITX2 3 K275A

NIX1 7 K109 NIX2 19 K51A ITX2 4 K276B

NIX1 8 K111 NIX2 20 K211 ITX2 5 K285

NIX1 9 K147A NIX2 25 K891 ITX2 6 K288

NIX1 10 P153 NIX2 26 K802 ITX2 7 K286

NIX1 11 K113 NIX2 27 K861 ITX2 8 K286B

NIX1 12 P157B NIX2 28 K802 ITX2 9 E121L

NIX1 13 K1 NIX2 E EARTH ITX2 10 E181L

NIX1 14 K101 ITX1 1 K113A ITX2 11 E121T

NIX1 15 K1A ITX1 2 K105G ITX2 12 E181T

NIX1 16 K101B ITX1 3 K155 ITX2 13 K101

NIX1 17 K101 ITX1 4 K141 ITX2 15 K286E

NIX1 18 K101 ITX1 5 K105H ITX2 25 K893

NIX1 19 K101C ITX1 6 K105J ITX2 26 K802

NIX1 20 K199A ITX1 7 K117 ITX2 27 K832

NIX1 25 K891 ITX1 8 K153 ITX2 28 K802

NIX1 26 K802 ITX1 9 K101 ITX2 E EARTH

NIX1 27 K861 ITX1 10 K105M ITX3 1 K201

NIX1 28 K802 ITX1 11 K159 ITX3 2 K1T

NIX1 E EARTH ITX1 12 K151 ITX3 3 K225

NIX2 1 1K15 ITX1 13 K105N ITX3 4 K1AT

NIX2 2 K701 ITX1 14 K101 ITX3 5 K225E

NIX2 3 K6D ITX1 15 K143 ITX3 6 K225F

NIX2 4 K793T ITX1 16 K199C ITX3 7 K241

NIX2 5 K791T ITX1 17 K101 ITX3 8 K291

NIX2 6 K171 ITX1 18 K6C ITX3 9 K245

Page 8 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


ITX3 10 K247 ITX4 20 K299C 86Y2 17 U112

ITX3 11 K207 ITX4 25 K893 86Y2 19 U113

ITX3 12 K209 ITX4 26 K802 86Y2 27 K213B

ITX3 13 K249 ITX4 27 K832 86Y2 28 K202

ITX3 14 K225B ITX4 28 K802 86Y2 E EARTH

ITX3 15 K211 ITX4 E EARTH 86B2 1 K51A

ITX3 16 K251 86R2 1 K51A 86B2 2 K51T

ITX3 17 K51T 86R2 2 K51T 86B2 3 K53C

ITX3 18 P143C 86R2 3 K53A 86B2 4 K453C

ITX3 19 K51AT 86R2 4 K453A 86B2 5 1K15

ITX3 20 P141C 86R2 5 1K15 86B2 6 K101

ITX3 25 K893 86R2 6 K101 86B2 7 1K15C

ITX3 26 K802 86R2 7 1K15A 86B2 8 K149

ITX3 27 K832 86R2 8 K145 86B2 9 P141A

ITX3 28 K802 86R2 9 P141A 86B2 10 P143C

ITX3 E EARTH 86R2 10 P143C 86B2 11 P115A

ITX4 1 K403A 86R2 11 P111A 86B2 12 P119C

ITX4 2 K453C 86R2 12 P115C 86B2 17 U114

ITX4 3 K3AT 86R2 17 U101 86B2 19 U115

ITX4 4 K53CT 86R2 19 U111 86B2 27 K213C

ITX4 5 K403B 86R2 27 K213A 86B2 28 K202

ITX4 6 K297 86R2 28 K202 86B2 E EARTH

ITX4 7 K3BT 86R2 E EARTH 27RN 2 K601

ITX4 8 K205H 86Y2 1 K51A 27RN 4 K671A

ITX4 9 K403C 86Y2 2 K51T 27RN 13 E121L

ITX4 10 K225A 86Y2 3 K53B 27RN 14 E181L

ITX4 11 K3CT 86Y2 4 K453B 27RN E EARTH

ITX4 12 K253 86Y2 5 1K15 BLKD R1 K205

ITX4 13 K453A 86Y2 6 K101 BLKD R2 K201B

ITX4 14 K225C 86Y2 7 1K15B BLKD R5 E27

ITX4 15 K53AT 86Y2 8 K147 BLKD R6 E87

ITX4 16 K251 86Y2 9 P141A BLKD S1 K201

ITX4 17 K453B 86Y2 10 P143C BLKD S2 K201

ITX4 18 K201 86Y2 11 P113A BLKD S5 E25

ITX4 19 K53BT 86Y2 12 P117C BLKD S6 E85

ITX4 20 K299C 86Y2 17 U112 BLKC R1 K3D

Page 9 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


BLKC R2 K1D BLKA S7 E123 BB1 20 1E281

BLKC R3 A23 BLKA S8 E143 BB1 21 1E216

BLKC R4 A43 BLKA S9 E163 BB1 22 1E236

BLKC R5 A63 BLKA S10 E183 BB1 23 1E256

BLKC R6 A85 BLKB R2 P15C BB1 24 1E276

BLKC R7 E119 BLKB R5 K407 BB2 1 1H1

BLKC R8 E139 BLKB R6 K55 BB2 2 1H2

BLKC R9 E159 BLKB R7 E23 BB2 3 P1

BLKC R10 E179 BLKB R8 E83 BB2 4 P171

BLKC S1 K1A BLKB R10 K151A BB2 5 P173

BLKC S2 K1T BLKB S2 P1 BB2 6 P2

BLKC S3 A21 BLKB S5 K1T PS 1 H19

BLKC S4 A41 BLKB S6 K51A PS 2 H18

BLKC S5 A61 BLKB S7 E22 PS E EARTH

BLKC S6 A83 BLKB S8 E82 HS 1 H13

BLKC S7 E118 BLKB S10 K51T HS 2 H15

BLKC S8 E138 BB1 1 1E111 LK153 1 P155

BLKC S9 E158 BB1 2 1E131 LK153 2 P153A

BLKC S10 E178 BB1 3 1E151 LKRX1 1 K167

BLKA R1 K13 BB1 4 1E171 LKRX1 2 K169

BLKA R2 K101A BB1 5 1E121 LKRX2 1 K767

BLKA R3 A12 BB1 6 1E141 LKRX2 2 K769

BLKA R4 A32 BB1 7 1E161 LK33 1 P157

BLKA R5 A52 BB1 8 1E181 LK33 2 P157B

BLKA R6 A72 BB1 9 1E116 LK787 1 K786

BLKA R7 E124 BB1 10 1E136 LK787 2 K787

BLKA R8 E144 BB1 11 1E156 LK187 1 K186

BLKA R9 E164 BB1 12 1E176 LK187 2 K187

BLKA R10 E184 BB1 13 1E211 LK811 1 E81

BLKA S1 K1A BB1 14 1E231 LK811 2 E183

BLKA S2 K101 BB1 15 1E251 LK85 1 E181L

BLKA S3 A11 BB1 16 1E271 LK85 2 E85

BLKA S4 A31 BB1 17 1E221 FS31 1 K202A

BLKA S5 A51 BB1 18 1E241 FS31 2 K202

BLKA S6 A73 BB1 19 1E261 FS33 1 K101

BLKA S7 E123 BB1 20 1E281 FS33 2 K115

Page 10 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


FS34 1 K201 TB7 38 U159 FS351 1 E56

FS34 2 K217 TB7 39 U131 FS351 2 E158

Page 11 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


TB7 1 U9 TB7 40 U132 FS331 1 E36

TB7 2 U10 TB7 41 U133 FS331 2 E138

TB7 3 U11 TB7 42 U134 FS311 1 E16

TB7 4 U12 TB7 45 U175 FS311 2 E118

TB7 7 U13 TB7 46 U176 FS611 1 E61

TB7 8 U14 TB7 47 U139 FS611 2 E163

TB7 9 U101 TB7 48 U140 FS411 1 E41

TB7 10 U111 FS29 1 K201 FS411 2 E143

TB7 11 U112 FS29 2 K201D FS211 1 E21

TB7 12 U113 FS28 1 K102A FS211 2 E123

TB7 13 U114 FS28 2 K102 LK181 1 E181L

TB7 14 U115 FS27 1 K101 LK181 2 E82

TB7 15 U37 FS27 2 K101D FS121 1 E121L

TB7 16 U38 FS26 1 E121L FS121 2 E22

TB7 17 U39 FS26 2 E25 LK95 1 H2

TB7 18 U40 FS24 1 J26 LK95 2 H18

TB7 19 U23 FS24 2 K702 FS95 1 H1

TB7 20 U24 FS23 1 J25 FS95 2 H19

TB7 21 U117 FS23 2 K701 LK94 1 H2

TB7 22 U118 FS22 1 J26 LK94 2 H14

TB7 23 U119 FS22 2 K202 FS94 1 H1

TB7 24 U120 FS21 1 J25 FS94 2 H13

TB7 25 U42 FS21 2 K201 TB1 1 A11

TB7 26 U43 FS20 1 J16 TB1 2 A71S

TB7 27 U44 FS20 2 K172 TB1 3 A31

TB7 28 U45 FS19 1 J15 TB1 4 A71S

TB7 29 U121 FS19 2 K171 TB1 5 A51

TB7 30 U123 FS18 1 J16 TB1 6 A71S

TB7 31 U141 FS18 2 K102 TB1 7 A71

TB7 32 U142 FS17 1 J15 TB1 8 A71S

TB7 33 U169 FS17 2 K101 TB1 9 A75

TB7 34 U170 LK371 1 E76 TB1 10 A74

TB7 37 U158 LK371 2 E178 TB1 11 A73

TB7 38 U159 FS351 1 E56 TB1 12 A71

TB1 13 A21 TB2 12 1E176 TB3 2 1H2

TB1 14 A271S TB2 13 1E211 TB3 2 H2

Page 12 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


TB1 15 A41 TB2 13 E211 TB3A 1 1H1

TB1 16 A271S TB2 14 E231 TB3A 2 1H2

TB1 17 A61 TB2 14 1E231 TB4 1 K145A

TB1 18 A271S TB2 15 1E251 TB4 2 K133

TB1 19 A81 TB2 15 E251 TB4 3 K145A

TB1 20 A271S TB2 16 1E271 TB4 4 K135

TB1 21 A87 TB2 16 E271 TB4 5 K145B

TB1 22 A89 TB2 17 1E221 TB4 6 K137

TB1 23 A83 TB2 17 E221 TB4 7 K101

TB1 24 A81 TB2 18 E241 TB4 8 K117

TB2 1 E111 TB2 18 1E241 TB4 9 K299A

TB2 1 1E111 TB2 19 1E261 TB4 10 K199A

TB2 2 E131 TB2 19 E261 TB4 11 K141

TB2 2 1E131 TB2 20 1E281 TB4 12 K143

TB2 3 1E151 TB2 20 E281 TB4 13 K141A

TB2 3 E151 TB2 21 1E216 TB4 14 K143A

TB2 4 E171 TB2 21 E216 TB4 15 K147A

TB2 4 1E171 TB2 22 E236 TB4 16 K320

TB2 5 1E121 TB2 22 1E236 TB4 17 K195A

TB2 5 E121 TB2 23 1E256 TB4 18 K197A

TB2 6 E141 TB2 23 E256 TB4 19 K265

TB2 6 1E141 TB2 24 1E276 TB4 20 K241

TB2 7 1E161 TB2 24 E276 TB4 21 K291

TB2 7 E161 TB2 25 E11 TB4 22 K201

TB2 8 E181 TB2 26 E31 TB4 23 K251

TB2 8 1E181 TB2 27 E51 TB4 24 K207A

TB2 9 E116 TB2 28 E71 TB4 25 K209A

TB2 9 1E116 TB2 29 E121L TB4 26 K211A

TB2 10 1E136 TB2 30 E181L TB4 27 K261

TB2 10 E136 TB2 31 E121T TB4 28 K237

TB2 11 E156 TB2 32 E181T TB4 29 K261

TB2 11 1E156 TB3 1 H1 TB4 30 K261B

TB2 12 E176 TB3 1 1H1 TB4 31 K239

TB2 12 1E176 TB3 2 1H2 TB4 32 K243

TB4 33 K187A TB4 68 K32 TB4A 35 K1AT

TB4 34 K189A TB4A 1 K286C TB4A 36 K3AT

Page 13 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


TB4 35 K240 TB4A 2 K275A TB4A 37 K3BT

TB4 36 K171 TB4A 3 K276B TB4A 38 K3CT

TB4 37 K167 TB4A 4 K285 TB4A 39 K51AT

TB4 38 K701 TB4A 5 K286B TB4A 40 K53AT

TB4 39 K767 TB4A 6 K159 TB4A 41 K53BT

TB4 40 K172 TB4A 7 K113A TB4A 42 K53CT

TB4 41 K171 TB4A 8 K105H TB4A 43 P155

TB4 42 K187 TB4A 9 K105J TB4A 44 P151B

TB4 43 K786 TB4A 10 K199C TB4A 45 K6C

TB4 44 K702 TB4A 11 K105G TB4A 46 K6B

TB4 45 K701 TB4A 12 K105N TB4A 47 K6D

TB4 46 K787 TB4A 13 K159 TB4A 48 1K15A

TB4 47 K101 TB4A 14 K105M TB4A 49 1K15B

TB4 48 K103 TB4A 15 K225 TB4A 50 1K15C

TB4 49 K201 TB4A 16 K225A TB4A 51 1K17A

TB4 50 K203 TB4A 17 K225B TB4A 52 K286E

TB4 51 K4B TB4A 18 K225C TB4X 1 K1A

TB4 52 K3A TB4A 19 K299C TB4X 2 K3A

TB4 53 K671C TB4A 20 K225E TB4X 3 K3B

TB4 54 K673C TB4A 21 K225F TB4X 4 K3C

TB4 55 K675D TB4A 22 K225 TB4X 5 K53A

TB4 56 K677D TB4A 23 K245 TB4X 6 K53B

TB4 57 K33 TB4A 24 K247 TB4X 7 K53C

TB4 58 K34 TB4A 25 K249 TB4X 8 K61

TB4 59 K35 TB4A 26 K205H TB4X 9 K62

TB4 60 K35A TB4A 27 K187B TB4X 10 K63

TB4 61 K3A TB4A 28 K187 TB4X 11 K64

TB4 62 K3B TB4A 29 K193T TB4X 12 K65

TB4 63 K3C TB4A 30 K191T TB4X 13 K66

TB4 64 K1A TB4A 31 K787B TB4X 14 K51A

TB4 65 K3B TB4A 32 K787 TB4X 15 K53A

TB4 66 K3C TB4A 33 K793T TB4X 16 K53B

TB4 67 K31 TB4A 34 K791T TB4X 17 K53C

TB4 68 K32 TB4A 35 K1AT TB4X 18 K51A

TB4X 19 K53A TB5 20 L247 TB8 28 K51

TB4X 20 K53B TB5 21 L251 TB8 29 K51

Page 14 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Equipment Wise Schedule File EW852R1


Cust. GETCO Panel type 2R1 Date 19/03/15

Equipment Terminal Wire no Equipment Terminal Wire no Equipment Terminal Wire no


TB4X 21 K53C TB5 22 L253 TB8 30 K808

TB4X 22 P141A TB5 23 L259 TB8 31 K807

TB4X 23 P111A TB5 24 L261 TB8 32 K802

TB4X 24 P113A TB5 25 L263 TB8 33 K810

TB4X 25 P115A TB5 26 L267 TB8 34 K809

TB4X 26 P117A TB5 27 L1 TB8 35 K52

TB4X 27 P143A TB5 28 L2 TB8 37 K856

TB4X 28 P121A TB8 1 J15 TB8 38 K851

TB4X 29 P141C TB8 2 J16 TB8 40 K849

TB4X 30 P115C TB8 3 J25 TB8 41 K858

TB4X 31 P117C TB8 4 J26 TB8 42 K861

TB4X 32 P119C TB8 5 K101 TB8 43 K891

TB4X 33 P121C TB8 6 K121 TB8 44 S201

TB4X 34 P123C TB8 7 K199A TB8 46 K832

TB5 1 L205 TB8 8 K151 TB8 47 K893

TB5 2 L209 TB8 9 K265 TB8 48 K101

TB5 3 L201 TB8 10 K297 TB8 49 K101

TB5 4 L203 TB8 11 K201 TB8 50 K157

TB5 5 L207 TB8 12 K223 TB8 51 K101S

TB5 6 L211 TB8 13 K201 TB8 52 K601

TB5 7 L213 TB8 14 K297A TB8 53 K671A

TB5 8 L215 TB8 15 K297B TB8 54 K109

TB5 9 L219 TB8 16 K171 TB8 55 K111

TB5 10 L221 TB8 17 K511 TB8 56 K113

TB5 11 L223 TB8 18 K187 TB8 57 K186

TB5 12 L225 TB8 19 K701 TBRTU 1 S201

TB5 13 L227 TB8 20 K911 TBRTU 2 S203

TB5 14 L229 TB8 21 K787 TBRTU 3 S205

TB5 15 L233 TB8 23 K8 TBRTU 4 S209

TB5 16 L239 TB8 24 K14 TBRTU 5 S207

TB5 17 L241 TB8 25 K1 TBRTU 6 S211

TB5 18 L243 TB8 26 K1 TBRTU 7 S213

TB5 19 L245 TB8 27 K2 HT 1 H17

TB5 20 L247 TB8 28 K51 HT 2 H14

EBAR 1 EARTH
EBAR 2 ELOOP

Page 15 of 15
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2R1
Wire no. Colour Connection pattern
1K15 21M1(G1)
1K15B 21M1(G2)
1K15 21M1(G3)
1K15C 21M1(G4)
1K15A 21M1(H17)
1K15 21M1(H18)- 21M1(J3)
1K17A 21M1(J4)
1K15 21M2(P8b)
1K17A 21M2(P8c)
1K15 NIX2(1)- 86R2(5)
1K15A 86R2(7)
1K15 86Y2(5)
1K15B 86Y2(7)
1K15 86B2(5)
1K15C 86B2(7)
1E111 BB1(1)
1E131 BB1(2)
1E151 BB1(3)
1E171 BB1(4)
1E121 BB1(5)
1E141 BB1(6)
1E161 BB1(7)
1E181 BB1(8)
1E116 BB1(9)
1E136 BB1(10)
1E156 BB1(11)
1E176 BB1(12)
1E211 BB1(13)
1E231 BB1(14)
1E251 BB1(15)
1E271 BB1(16)
1E221 BB1(17)
1E241 BB1(18)
1E261 BB1(19)
1E281 BB1(20)
1E216 BB1(21)
1E236 BB1(22)
1E256 BB1(23)
1E276 BB1(24)
1H1 BB2(1)
1H2 BB2(2)
1E111 TB2(1)
1E131 TB2(2)
1E151 TB2(3)
1E171 TB2(4)
1E121 TB2(5)
1E141 TB2(6)
1E161 TB2(7)
1E181 TB2(8)
1E116 TB2(9)
1E136 TB2(10)
1E156 TB2(11)
1E176 TB2(12)
1E211 TB2(13)
1E231 TB2(14)
1E251 TB2(15)
1E271 TB2(16)
1E221 TB2(17)
1E241 TB2(18)
1E261 TB2(19)
1E281 TB2(20)
1E216 TB2(21)
1E236 TB2(22)
1E256 TB2(23)
1E276 TB2(24)
1H1 TB3(1)
1H2 TB3(2)
1H1 TB3A(1)
1H2 TB3A(2)

Page 1 of 9
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2R1
Wire no. Colour Connection pattern
1K15A TB4A(48)
1K15B TB4A(49)
1K15C TB4A(50)
1K17A TB4A(51)
A11 RD BLKA(S3)- TB1(1)
A12 RD 21M1(C3)- BLKA(R3)
A21 RD BLKC(S3)- TB1(13)
A23 RD 21M2(F1c)- BLKC(R3)
A271S BK TB1(14)- TB1(16)- TB1(18)- TB1(20)
A31 YL BLKA(S4)- TB1(3)
A32 YL 21M1(C6)- BLKA(R4)
A41 YL BLKC(S4)- TB1(15)
A43 YL 21M2(F2c)- BLKC(R4)
A51 BL BLKA(S5)- TB1(5)
A52 BL 21M1(C9)- BLKA(R5)
A61 BL BLKC(S5)- TB1(17)
A63 BL 21M2(F3c)- BLKC(R5)
A71 BK TB1(7)- TB1(12)
A71S BK TB1(2)- TB1(4)- TB1(6)- TB1(8)
A72 BK 21M1(C2)- 21M1(C5)- 21M1(C8)- BLKA(R6)
A73 BK BLKA(S6)- TB1(11)
A74 BK 21M1(C12)- TB1(10)
A75 BK 21M1(C11)- TB1(9)
A81 BK TB1(19)- TB1(24)
A83 BK BLKC(S6)- TB1(23)
A85 BK 21M2(F1b)- 21M2(F2b)- 21M2(F3b)- BLKC(R6)
A87 BK 21M2(F4c)- TB1(21)
A89 BK 21M2(F4b)- TB1(22)
E11 RD 75B(9)- 75A(11)- TB2(25)
E111 RD 75A(9)- TB2(1)
E116 RD 75C(13)- TB2(9)
E118 RD BLKC(S7)- FS311(2)
E119 RD 21M2(F5a)- BLKC(R7)
E121 RD 75C(5)- TB2(5)
E121L RD ITX2(9)- 27RN(13)- FS26(1)- FS121(1)- TB2(29)
E121T RD ITX2(11)- TB2(31)
E123 RD BLKA(S7)- FS211(2)
E124 RD 21M1(C19)- BLKA(R7)
E131 YL 75A(13)- TB2(2)
E136 YL 75C(14)- TB2(10)
E138 YL BLKC(S8)- FS331(2)
E139 YL 21M2(F6a)- BLKC(R8)
E141 YL 75C(6)- TB2(6)
E143 YL BLKA(S8)- FS411(2)
E144 YL 21M1(C20)- BLKA(R8)
E151 BL 75A(17)- TB2(3)
E156 BL 75C(17)- TB2(11)
E158 BL BLKC(S9)- FS351(2)
E159 BL 21M2(F7a)- BLKC(R9)
E16 RD 75D(13)- 75C(15)- FS311(1)
E161 BL 75C(9)- TB2(7)
E163 BL BLKA(S9)- FS611(2)
E164 BL 21M1(C21)- BLKA(R9)
E171 BK 75A(10)- TB2(4)
E176 BK 75C(18)- TB2(12)
E178 BK BLKC(S10)- LK371(2)
E179 BK 21M2(F5c)- 21M2(F6c)- 21M2(F7c)- BLKC(R10)
E181 BK 75C(10)- TB2(8)
E181L BK ITX2(10)- 27RN(14)- LK85(1)- LK181(1)- TB2(30)
E181T BK ITX2(12)- TB2(32)
E183 BK BLKA(S10)- LK811(2)
E184 BK 21M1(C22)- BLKA(R10)
E21 RD 75D(5)- 75C(7)- FS211(1)
E211 RD 75B(11)- TB2(13)
E216 RD 75D(15)- TB2(21)
E22 RD BLKB(S7)- FS121(2)
E221 RD 75D(7)- TB2(17)
E23 RD 21M1(C23)- BLKB(R7)
E231 YL 75B(15)- TB2(14)

Page 2 of 9
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2R1
Wire no. Colour Connection pattern
E236 YL 75D(16)- TB2(22)
E241 YL 75D(8)- TB2(18)
E25 RD BLKD(S5)- FS26(2)
E251 BL 75B(19)- TB2(15)
E256 BL 75D(19)- TB2(23)
E261 BL 75D(11)- TB2(19)
E27 RD 21M2(F8a)- BLKD(R5)
E271 BK 75B(12)- TB2(16)
E276 BK 75D(20)- TB2(24)
E281 BK 75D(12)- TB2(20)
E31 YL 75B(13)- 75A(15)- TB2(26)
E36 YL 75D(14)- 75C(16)- FS331(1)
E41 YL 75D(6)- 75C(8)- FS411(1)
E51 BL 75B(17)- 75A(19)- TB2(27)
E56 BL 75D(17)- 75C(19)- FS351(1)
E61 BL 75D(9)- 75C(11)- FS611(1)
E71 BK 75B(10)- 75A(12)- TB2(28)
E76 BK 75D(18)- 75C(20)- LK371(1)
E81 BK 75D(10)- 75C(12)- LK811(1)
E82 BK BLKB(S8)- LK181(2)
E83 BK 21M1(C24)- BLKB(R8)
E85 BK BLKD(S6)- LK85(2)
E87 BK 21M2(F8c)- BLKD(R6)
295R(E01)- 295Y(E)- 295B(E)- SX1(E)- RX1(E)- SX2(E)- RX2(E)- 195B(E)- 195Y(E)- 195R(E)- 75D(E)- 75C(E)-
75B(E)- 75A(E)- 21M1(E)- 89AX2(E)- 89BX2(E)- 96(E)- 21M2(E)- IX1(E)- 95/86B(E)- 86BX(E)- 86B(E)- 95/86A(E)-
86AX(E)- 86A(E)- NIX1(E)- NIX2(E)- ITX1(E)- ITX2(E)- ITX3(E)- ITX4(E)- 86R2(E)- 86Y2(E)- 86B2(E)- 27RN(E)-
EARTH GN PS(E)- EBAR(01)
ELOOP GN 295R(E02)- EBAR(02)
H1 BK FS95(1)- FS94(1)- TB3(1)
H13 BK CIL(1)- HS(1)- FS94(2)
H14 BK CIL(2)- LK94(2)- HT(2)
H15 BK TH(1)- HS(2)
H17 BK TH(2)- HT(1)
H18 BK PS(2)- LK95(2)
H19 BK PS(1)- FS95(2)
H2 BK LK95(1)- LK94(1)- TB3(2)
J15 GY FS19(1)- FS17(1)- TB8(1)
J16 GY FS20(1)- FS18(1)- TB8(2)
J25 GY FS23(1)- FS21(1)- TB8(3)
J26 GY FS24(1)- FS22(1)- TB8(4)
K1 GY 195B(27)- 195Y(27)- 195R(27)- NIX1(13)- TB8(25)- TB8(26)
SX1(5)- RX1(3)- RX1(8)- 195B(2)- 195Y(2)- 195R(2)- 21M1(+N2)- 96(37)- 21M2(U3b)- 21M2(U7b)- PB01(1P3)-
ARS(1P3)- IX1(10)- 86BX(5)- 86BX(9)- 95/86A(21)- 95/86A(27)- 86AX(5)- 86AX(9)- 86A(5)- 86A(9)- NIX1(14)-
NIX1(17)- NIX1(18)- ITX1(9)- ITX1(14)- ITX1(17)- ITX2(13)- 86R2(6)- 86Y2(6)- 86B2(6)- BLKA(S2)- FS33(1)-
K101 GY FS27(1)- FS17(2)- TB4(7)- TB4(47)- TB8(5)- TB8(48)- TB8(49)
K101A GY 21M1(J5)- BLKA(R2)
K101B GY 89AX2(1)- 89AX2(13)- NIX1(16)
K101C GY 89BX2(1)- 89BX2(13)- NIX1(19)
K101D GY CSS1(2P3)- CSS1(3P3)- CSS2(1P3)- FS27(2)
K101S GY IX1(25)- TB8(51)
75D(26)- 75D(28)- 75C(26)- 75C(28)- 75B(26)- 75B(28)- 75A(26)- 75A(28)- 21M1(D1)- 21M1(D3)- 21M1(D5)-
21M1(D7)- 21M1(D9)- 21M1(D11)- 21M1(D13)- 21M1(D15)- 21M1(E1)- 21M1(E3)- 21M1(E5)- 21M1(E7)-
21M1(E15)- 21M1(F1)- 21M1(F3)- 21M1(F5)- 21M1(F7)- 21M1(F9)- 21M1(F11)- 21M1(F13)- 21M1(F15)- 21M1(-
N1)- IX1(26)- IX1(28)- 95/86A(28)- 86AX(28)- 86A(26)- 86A(28)- FS28(2)- FS18(2)
K102 GY
K102A GY 21M1(E9)- 21M1(E11)- 21M1(E13)- FS28(1)
K103 GY RX1(10)- 21M1(J6)- 95/86A(22)- 86A(27)- TB4(48)
K103D GY PB01(1P4)- 86A(25)
K105G GY ITX1(2)- TB4A(11)
K105H GY ITX1(5)- TB4A(8)
K105J GY ITX1(6)- TB4A(9)
K105M GY ITX1(10)- TB4A(14)
K105N GY ITX1(13)- TB4A(12)
K109 GY 21M1(D2)- NIX1(7)- TB8(54)
K111 GY 21M1(D4)- NIX1(8)- TB8(55)
K111B GY 21M1(L11)- CSS1(3P4)
K113 GY 21M1(D6)- NIX1(11)- TB8(56)
K113A GY ITX1(1)- TB4A(7)
K115 GY 21M1(D8)- FS33(2)

Page 3 of 9
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2R1
Wire no. Colour Connection pattern
K117 GY 21M1(D10)- ITX1(7)- TB4(8)
K119 GY 21M1(D12)- IX1(12)
K121 GY 21M1(D14)- TB8(6)
K123 GY 195B(4)- 195Y(4)- 195R(4)- 21M1(D16)
K125 GY 21M1(E2)- 21M2(U7c)- 86BX(11)- 86AX(11)
K127 GY SX1(7)- 21M1(E4)
K129 GY 21M1(E6)- ARS(1P4)
K13 GY 21M1(K1)- 21M1(L15)- 21M1(L18)- BLKA(R1)
K131 GY 21M1(E8)- 21M2(U3c)
K133 GY 21M1(E10)- TB4(2)
K135 GY 21M1(E12)- TB4(4)
K137 GY 21M1(E14)- TB4(6)
K139 GY RX1(1)- 21M1(E16)
K14 GY 21M1(J8)- 21M2(U2c)- TB8(24)
K141 GY 21M1(F2)- ITX1(4)- TB4(11)
K141A GY NIX1(5)- TB4(13)
K143 GY 21M1(F4)- ITX1(15)- TB4(12)
K143A GY NIX1(6)- TB4(14)
K145 GY 21M1(F6)- 86R2(8)
K145A GY CSS1(2P4)- TB4(1)- TB4(3)
K145B GY CSS2(1P4)- TB4(5)
K147 GY 21M1(F8)- 86Y2(8)
K147A GY NIX1(9)- TB4(15)
K149 GY 21M1(F10)- 86B2(8)
K151 GY 21M1(F12)- ITX1(12)- TB8(8)
K151A GY 21M1(.)- 21M1(G9)- 21M1(G12)- 21M1(G15)- BLKB(R10)
K153 GY 21M1(F14)- 96(39)- ITX1(8)
K155 GY 21M1(F16)- 86BX(7)- 86AX(7)- ITX1(3)
K157 GY IX1(27)- TB8(50)
K159 GY ITX1(11)- TB4A(6)- TB4A(13)
K161A GY 86AX(25)- 86A(7)
K163 GY 95/86A(13)- 86A(11)
K167 GY LKRX1(1)- TB4(37)
K169 GY RX1(11)- LKRX1(2)
K171 GY 21M1(K9)- 21M2(U5b)- IX1(13)- NIX2(6)- FS19(2)- TB4(36)- TB4(41)- TB8(16)
K172 GY SX1(14)- RX1(14)- FS20(2)- TB4(40)
K186 GY LK187(1)- TB8(57)
K187 GY SX1(13)- 21M1(K10)- 21M2(U5c)- IX1(7)- NIX1(4)- LK187(2)- TB4(42)- TB4A(28)- TB8(18)
K187A GY 21M2(P6b)- TB4(33)
K187B GY IX1(5)- TB4A(27)
K189A GY 21M2(P6c)- TB4(34)
K191T GY NIX1(2)- TB4A(30)
K193T GY NIX2(8)- TB4A(29)
K195A GY 21M1(G18)- TB4(17)
K197A GY 21M1(G17)- TB4(18)
K199A GY NIX1(20)- TB4(10)- TB8(7)
K199C GY ITX1(16)- TB4A(10)
195B(21)- 195Y(21)- 195R(21)- 96(6)- 96(10)- 96(17)- 86B(6)- 86B(13)- 86B(17)- 86A(6)- 86A(13)- 86A(17)-
K1A GY NIX1(15)- BLKC(S1)- BLKA(S1)- TB4(64)- TB4X(1)
K1AT GY ITX3(4)- TB4A(35)
K1C GY 86A(2)- ITX1(20)
K1D GY 21M2(M4b)- 21M2(P1b)- 21M2(P2b)- BLKC(R2)
K1T GY 86B(10)- 86B(14)- 86B(18)- 86A(10)- 86A(14)- 86A(18)- ITX3(2)- BLKC(S2)- BLKB(S5)
K2 GY 195B(28)- 195Y(28)- 195R(28)- TB8(27)
295R(2)- 295Y(2)- 295B(2)- SX2(5)- RX2(4)- RX2(8)- 21M1(J9)- 96(38)- 21M2(+B5b)- PB01(2P3)- ARS(3P3)-
IX1(9)- 95/86B(21)- 95/86B(27)- 86BX(1)- 86B(5)- 86B(9)- 86AX(1)- NIX1(1)- NIX2(13)- ITX3(1)- ITX4(18)-
BLKD(S1)- BLKD(S2)- FS34(1)- FS29(1)- FS21(2)- TB4(22)- TB4(49)- TB8(11)- TB8(13)
K201 GY
K201B GY 21M2(U1b)- BLKD(R2)
K201D GY CSS1(1P3)- CSS2(2P3)- CSS2(3P3)- FS29(2)
21M2(-B6a)- 21M2(H1b)- 21M2(H3b)- 21M2(H5b)- 21M2(M5b)- 21M2(M7b)- 95/86B(28)- 86BX(28)- 86B(26)-
K202 GY 86B(28)- 86R2(28)- 86Y2(28)- 86B2(28)- FS31(2)- FS22(2)
K202A GY 21M2(H7b)- FS31(1)
K203 GY RX2(10)- 21M2(U1c)- 95/86B(22)- 86B(27)- TB4(50)
K203D GY PB01(2P4)- 86B(25)
K204 GY 86BX(25)- 86B(7)
K205 GY 21M2(P3b)- 21M2(P4b)- 21M2(P5b)- BLKD(R1)
K205H GY ITX4(8)- TB4A(26)
K207 GY 21M2(H1a)- NIX2(12)- ITX3(11)

Page 4 of 9
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2R1
Wire no. Colour Connection pattern
K207A GY NIX2(10)- TB4(24)
K209 GY 21M2(H1c)- NIX2(14)- ITX3(12)
K209A GY NIX2(16)- TB4(25)
K211 GY 21M2(H2a)- NIX2(20)- ITX3(15)
K211A GY NIX2(18)- TB4(26)
K213A GY 21M2(P3c)- 86R2(27)
K213B GY 21M2(P4c)- 86Y2(27)
K213C GY 21M2(P5c)- 86B2(27)
K217 GY 21M2(H2c)- FS34(2)
K223 GY 21M2(H3a)- TB8(12)
K225 GY ITX3(3)- TB4A(15)- TB4A(22)
K225A GY ITX4(10)- TB4A(16)
K225B GY ITX3(14)- TB4A(17)
K225C GY ITX4(14)- TB4A(18)
K225E GY ITX3(5)- TB4A(20)
K225F GY ITX3(6)- TB4A(21)
K226 GY SX2(7)- 21M2(H5c)
K228 GY RX2(2)- 21M2(H5a)
K229 GY 21M1(J10)- 21M2(H6c)
K231 GY 21M2(H4a)- IX1(11)
K233 GY 21M2(H3c)- NIX1(3)
K235 GY 295R(4)- 295Y(4)- 295B(4)- 21M2(H4c)
K237 GY 21M2(H7a)- TB4(28)
K239 GY 21M2(H7c)- TB4(31)
K239A GY 21M2(U6b)- CSS2(3P4)
K240 GY 21M2(U6c)- TB4(35)
K241 GY 21M2(M5a)- ITX3(7)- TB4(20)
K243 GY 21M2(H8a)- TB4(32)
K245 GY ITX3(9)- TB4A(23)
K247 GY ITX3(10)- TB4A(24)
K249 GY ITX3(13)- TB4A(25)
K251 GY 96(40)- 21M2(M8a)- ITX3(16)- ITX4(16)- TB4(23)
K253 GY 21M2(M8c)- 86BX(3)- 86AX(3)- ITX4(12)
K259 GY 21M2(H6a)- ARS(3P4)
K261 GY CSS2(2P4)- TB4(27)- TB4(29)
K261B GY CSS1(1P4)- TB4(30)
K263 GY 95/86B(13)- 86B(11)
K265 GY NIX2(15)- TB4(19)- TB8(9)
K275 GY 75D(1)- 75B(1)- 89AX2(15)- ITX2(1)
K275A GY ITX2(3)- TB4A(2)
K276 GY 75C(25)- 75A(25)- 89AX2(3)- 89AX2(5)
K276A GY 89AX2(7)- ITX2(2)
K276B GY ITX2(4)- TB4A(3)
K285 GY ITX2(5)- TB4A(4)
K285A GY 75D(25)- 75B(25)- 89BX2(3)- 89BX2(5)
K286 GY 75C(1)- 75A(1)- 89BX2(15)- ITX2(7)
K286A GY 75D(3)- 75C(27)
K286B GY ITX2(8)- TB4A(5)
K286C GY ITX1(19)- TB4A(1)
K286D GY 75D(27)- 75C(3)
K286E GY ITX2(15)- TB4A(52)
K288 GY 89BX2(7)- ITX2(6)
K288A GY 75B(3)- 75A(27)
K288B GY 75B(27)- 75A(3)
K291 GY 21M2(M5c)- ITX3(8)- TB4(21)
K297 GY 21M2(M7c)- ITX4(6)- TB8(10)
K297A GY 21M2(M6a)- TB8(14)
K297B GY 21M2(M6c)- TB8(15)
K299A GY 21M2(M7a)- TB4(9)
K299C GY ITX4(20)- TB4A(19)
K31 GY 195R(14)- TB4(67)
K32 GY 195R(13)- TB4(68)
K320 GY 21M1(L12)- TB4(16)
K33 GY 195Y(14)- TB4(57)
K34 GY 195Y(13)- TB4(58)
K35 GY 195B(14)- TB4(59)
K35A GY 195B(13)- TB4(60)
K3A GY 195R(22)- 21M1(L14)- 96(19)- 21M2(M1c)- 86B(15)- 86A(15)- TB4(52)- TB4(61)- TB4X(2)
K3AT GY ITX4(3)- TB4A(36)

Page 5 of 9
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2R1
Wire no. Colour Connection pattern
K3B GY 195Y(22)- 21M1(L17)- 96(8)- 21M2(M2c)- 86B(19)- 86A(19)- TB4(62)- TB4(65)- TB4X(3)
K3BT GY ITX4(7)- TB4A(37)
K3C GY 195B(22)- 21M1(K2)- 96(12)- 21M2(M3c)- 86B(8)- 86A(8)- TB4(63)- TB4(66)- TB4X(4)
K3CT GY ITX4(11)- TB4A(38)
K3D GY 21M2(M1b)- 21M2(M2b)- 21M2(M3b)- BLKC(R1)
K3H GY 96(2)- 86A(4)
K403A GY 21M1(K4)- 21M2(M4c)- 86B(12)- 86A(12)- ITX4(1)
K403B GY 21M1(K6)- 21M2(P1c)- 86B(16)- 86A(16)- ITX4(5)
K403C GY 21M1(K8)- 21M2(P2c)- 86B(20)- 86A(20)- ITX4(9)
K407 GY 21M1(K3)- 21M1(K5)- 21M1(K7)- BLKB(R5)
K453A GY 21M1(G8)- 86B(47)- 86A(47)- ITX4(13)- 86R2(4)
K453B GY 21M1(G11)- 86B(36)- 86A(36)- ITX4(17)- 86Y2(4)
K453C GY 21M1(G14)- 86B(40)- 86A(40)- ITX4(2)- 86B2(4)
K4A GY 86B(1)- 86A(3)
K4B GY 86A(1)- TB4(51)
K5 GY 195B(5)- 86B(3)
K51 GY 295R(27)- 295Y(27)- 295B(27)- NIX2(17)- TB8(28)- TB8(29)
K511 GY IX1(15)- TB8(17)
295R(21)- 295Y(21)- 295B(21)- 96(14)- 96(18)- 96(33)- 86B(33)- 86B(37)- 86B(41)- 86A(33)- 86A(37)- 86A(41)-
K51A GY NIX2(19)- 86R2(1)- 86Y2(1)- 86B2(1)- BLKB(S6)- TB4X(14)- TB4X(18)
K51AT GY ITX3(19)- TB4A(39)
86B(34)- 86B(38)- 86B(45)- 86A(34)- 86A(38)- 86A(45)- ITX3(17)- 86R2(2)- 86Y2(2)- 86B2(2)- BLKB(S10)
K51T GY
K52 GY 295R(28)- 295Y(28)- 295B(28)- TB8(35)
K53A GY 295R(22)- 21M1(H2)- 96(16)- 86B(35)- 86A(35)- 86R2(3)- TB4X(5)- TB4X(15)- TB4X(19)
K53AT GY ITX4(15)- TB4A(40)
K53B GY 295Y(22)- 21M1(H4)- 96(20)- 86B(39)- 86A(39)- 86Y2(3)- TB4X(6)- TB4X(16)- TB4X(20)
K53BT GY ITX4(19)- TB4A(41)
K53C GY 295B(22)- 21M1(H6)- 96(35)- 86B(43)- 86A(43)- 86B2(3)- TB4X(7)- TB4X(17)- TB4X(21)
K53CT GY ITX4(4)- TB4A(42)
K55 GY 21M1(H1)- 21M1(H3)- 21M1(H5)- BLKB(R6)
K5A GY 195B(7)- 195Y(7)
K5B GY 195Y(5)- 195R(5)
K5C GY 295R(7)- 195R(7)

Page 6 of 9
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2R1
Wire no. Colour Connection pattern
K5D GY 295R(5)- 295Y(5)
K5E GY 295Y(7)- 295B(7)
K6 GY 295B(5)- 96(1)
K601 GY 27RN(2)- TB8(52)
K61 GY 295R(14)- TB4X(8)
K62 GY 295R(13)- TB4X(9)
K63 GY 295Y(14)- TB4X(10)
K64 GY 295Y(13)- TB4X(11)
K65 GY 295B(14)- TB4X(12)
K66 GY 295B(13)- TB4X(13)
K671A GY 27RN(4)- TB8(53)
K671C GY 89AX2(2)- TB4(53)
K673C GY 89AX2(4)- TB4(54)
K675D GY 89BX2(2)- TB4(55)
K677D GY 89BX2(4)- TB4(56)
K6B GY 86B(4)- TB4A(46)
K6C GY ITX1(18)- TB4A(45)
K6D GY NIX2(3)- TB4A(47)
K7 GY 21M1(J7)- 89AX2(10)- 89BX2(10)- 96(3)- 21M2(U2b)
K701 GY 21M1(J1)- 21M2(P7b)- IX1(14)- NIX2(2)- FS23(2)- TB4(38)- TB4(45)- TB8(19)
K702 GY SX2(14)- RX2(14)- FS24(2)- TB4(44)
K767 GY LKRX2(1)- TB4(39)
K769 GY RX2(11)- LKRX2(2)
K786 GY LK787(1)- TB4(43)
K787 GY SX2(13)- 21M1(J2)- 21M2(P7c)- IX1(8)- NIX2(7)- LK787(2)- TB4(46)- TB4A(32)- TB8(21)
K787B GY IX1(6)- TB4A(31)
K791T GY NIX2(5)- TB4A(34)
K793T GY NIX2(4)- TB4A(33)
K7D GY 96(4)- 86B(2)
K8 GY 89AX2(12)- 89BX2(12)- TB8(23)
89AX2(26)- 89AX2(28)- 89BX2(26)- 89BX2(28)- NIX1(26)- NIX1(28)- NIX2(26)- NIX2(28)- ITX1(26)- ITX1(28)-
K802 GY ITX2(26)- ITX2(28)- ITX3(26)- ITX3(28)- ITX4(26)- ITX4(28)- TB8(32)
K807 GY 89AX2(25)- TB8(31)
K808 GY 89AX2(27)- TB8(30)
K809 GY 89BX2(25)- TB8(34)
K810 GY 89BX2(27)- TB8(33)
K832 GY ITX1(27)- ITX2(27)- ITX3(27)- ITX4(27)- TB8(46)
K849 GY IX1(19)- TB8(40)
K851 GY IX1(17)- TB8(38)
K856 GY IX1(18)- TB8(37)
K858 GY IX1(20)- TB8(41)
K861 GY NIX1(27)- NIX2(27)- TB8(42)
K891 GY NIX1(25)- NIX2(25)- TB8(43)
K893 GY ITX1(25)- ITX2(25)- ITX3(25)- ITX4(25)- TB8(47)
K911 GY IX1(16)- TB8(20)
L1 GY 75B(14)- 75A(14)- TB5(27)
L2 GY SL16(2)- SL17(2)- TB5(28)
295R(1)- 295Y(1)- 295B(1)- SX1(2)- RX1(7)- SX2(2)- RX2(7)- 195B(1)- 195Y(1)- 195R(1)- 21M1(L1)- 21M1(L3)-
21M1(L5)- 21M1(L7)- 21M1(L9)- 21M1(M1)- 21M1(M3)- 21M1(M5)- 21M1(M7)- 21M1(M9)- 21M1(M11)-
21M1(M15)- 21M1(M18)- 21M1(N11)- 96(34)- 21M2(B1a)- 21M2(W1b)- 21M2(W2b)- 21M2(W3b)- 21M2(W4b)-
21M2(W5b)- 21M2(W6b)- 95/86B(2)- 86BX(2)- 95/86A(2)- 86AX(2)- TB5(3)
L201 GY
L203 GY 21M1(M4)- TB5(4)
L205 GY 21M2(W1c)- TB5(1)
L207 GY 86AX(4)- TB5(5)
L209 GY 86BX(4)- TB5(2)
L211 GY 21M1(L2)- 21M2(W5a)- TB5(6)
L213 GY 21M1(L10)- TB5(7)
L215 GY 21M1(M2)- 21M2(W1a)- TB5(8)
L219 GY RX1(9)- RX2(9)- TB5(9)
L221 GY SX1(4)- SX2(4)- TB5(10)
L223 GY 96(36)- TB5(11)
L225 GY 21M1(M6)- 21M2(W2a)- TB5(12)
L227 GY 21M1(M8)- 21M2(W2c)- TB5(13)
L229 GY 21M1(M10)- 21M2(W3a)- TB5(14)
L233 GY 21M1(M12)- 21M2(W3c)- TB5(15)
L239 GY 195B(3)- 195Y(3)- 195R(3)- TB5(16)
L241 GY 295R(3)- 295Y(3)- 295B(3)- TB5(17)
L243 GY 21M1(N12)- TB5(18)

Page 7 of 9
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2R1
Wire no. Colour Connection pattern
L245 GY 21M2(B2b)- TB5(19)
L247 GY 95/86B(4)- 95/86A(4)- TB5(20)
L251 GY 21M1(M17)- 21M2(W4c)- TB5(21)
L253 GY 21M1(M14)- 21M2(W4a)- TB5(22)
L259 GY 21M1(L6)- 21M2(W6a)- TB5(23)
L261 GY 21M1(L8)- 21M2(W6c)- TB5(24)
L263 GY 21M1(L4)- TB5(25)
L267 GY 21M2(W5c)- TB5(26)
L61 GY 75A(16)- SL16(1)
L63 GY 75B(16)- SL17(1)
P1 GY PB01(3P3)- BLKB(S2)- BB2(3)
P103D GY 96(25)- PB01(3P4)
P111A GY 21M1(K12)- 86R2(11)- TB4X(23)
P113A GY 21M1(K14)- 86Y2(11)- TB4X(24)
P115A GY 21M1(K17)- 86B2(11)- TB4X(25)
P115C GY 21M1(H7)- 86R2(12)- TB4X(30)
P117A GY 86BX(15)- 86AX(15)- TB4X(26)
P117C GY 21M1(H11)- 86Y2(12)- TB4X(31)
P119C GY 21M1(H14)- 86B2(12)- TB4X(32)
P121A GY 21M1(J17)- 21M2(U4c)- 86BX(8)- 86AX(8)- TB4X(28)
P121C GY 86BX(12)- 86AX(12)- TB4X(33)
P123C GY 21M1(J14)- 21M2(U8c)- 86BX(16)- 86AX(16)- TB4X(34)
P141A GY 21M1(K11)- 21M1(K15)- 21M1(K18)- 86BX(13)- 86AX(13)- 86R2(9)- 86Y2(9)- 86B2(9)- TB4X(22)
P141C GY ITX3(20)- TB4X(29)
P143A GY 21M1(J18)- 21M2(U4b)- 86BX(6)- 86AX(6)- TB4X(27)
21M1(H9)- 21M1(H12)- 21M1(H15)- 21M1(J15)- 21M2(U8b)- 86BX(10)- 86BX(14)- 86AX(10)- 86AX(14)-
P143C GY ITX3(18)- 86R2(10)- 86Y2(10)- 86B2(10)
P151B GY 21M1(G6)- TB4A(44)
P153 GY 21M1(J12)- NIX1(10)
P153A GY 21M1(G5)- LK153(2)
P155 GY LK153(1)- TB4A(43)
P157 GY 89AX2(16)- 89BX2(16)- LK33(1)
P157B GY 96(27)- NIX1(12)- LK33(2)
P15C GY 21M1(J11)- BLKB(R2)
P171 GY 89AX2(14)- BB2(4)
P173 GY 89BX2(14)- BB2(5)
P2 GY 96(26)- 96(28)- BB2(6)
S201 GY 96(29)- 96(42)- 86B(30)- 86B(46)- 86A(30)- 86A(46)- TB8(44)- TBRTU(1)
S203 GY 86A(48)- TBRTU(2)
S205 GY 86A(32)- TBRTU(3)
S207 GY 86B(48)- TBRTU(5)
S209 GY 86B(32)- TBRTU(4)
S211 GY 96(44)- TBRTU(6)
S213 GY 96(31)- TBRTU(7)
U10 GY 75A(4)- TB7(2)
U101 GY 86R2(17)- TB7(9)
U11 GY 75B(2)- TB7(3)
U111 GY 86R2(19)- TB7(10)
U112 GY 86Y2(17)- TB7(11)
U113 GY 86Y2(19)- TB7(12)
U114 GY 86B2(17)- TB7(13)
U115 GY 86B2(19)- TB7(14)
U117 GY 86A(29)- TB7(21)
U118 GY 86A(31)- TB7(22)
U119 GY 86A(42)- TB7(23)
U12 GY 75B(4)- TB7(4)
U120 GY 86A(44)- TB7(24)
U121 GY 86B(29)- TB7(29)
U123 GY 86B(31)- TB7(30)
U13 GY 21M2(W7b)- TB7(7)
U131 GY 89AX2(6)- TB7(39)
U132 GY 89AX2(8)- TB7(40)
U133 GY 89AX2(17)- TB7(41)
U134 GY 89AX2(19)- TB7(42)
U139 GY IX1(2)- TB7(47)
U14 GY 21M2(W7a)- TB7(8)
U140 GY IX1(4)- TB7(48)
U141 GY 96(45)- TB7(31)
U142 GY 96(47)- TB7(32)

Page 8 of 9
ALSTOM T&D INDIA LTD.

Job no. KW85 Wire Wise Schedule


Cust. GETCO
Panel type 2R1
Wire no. Colour Connection pattern
U158 GY 89BX2(6)- TB7(37)
U159 GY 89BX2(8)- TB7(38)
U169 GY 96(30)- TB7(33)
U170 GY 96(32)- TB7(34)
U175 GY 89BX2(18)- TB7(45)
U176 GY 89BX2(20)- TB7(46)
U23 GY 95/86A(1)- TB7(19)
U24 GY 95/86A(3)- TB7(20)
U37 GY SX1(1)- TB7(15)
U38 GY SX1(3)- TB7(16)
U39 GY SX2(1)- TB7(17)
U40 GY SX2(3)- TB7(18)
U42 GY 95/86B(1)- TB7(25)
U43 GY 95/86B(3)- TB7(26)
U44 GY 86B(42)- TB7(27)
U45 GY 86B(44)- TB7(28)
U9 GY 75A(2)- TB7(1)

Page 9 of 9