Is 732
Is 732
( Reafffinned 199.5 )
( Reaffirmed 2005 )
Indian Standard
CODEOFPRACTTCEFOR
ELECTRICALWIRINGINSTALLATIONS
(Third Revision )
Second Reprint FEBRUARY 1999
0 Copyright 1989
Indian Standard
CODE OF PRACTICE FOR
ELECTRICAL WIRING INSTALLATIONS
( Third Revision )
Electrical Installations Sectional Committee, ETDC 20
Chuifmun
SHBI M. L. DONQ~E
M-3 Satyam, 88 Sion Circle, Bombay 400 022
Members Re#resenti&
SHRI P. ANANTHARAMAN Engineet-in-Chief’s Branch, Army Headquarters ( Ministry of
Defence ), New Delhi
Q Copyright 1989
BUREAU OF INDIAN STANDARDS
This publication is protected under the Indian CopyrightAct ( XIV of‘1957 ) and production in whole or in part by
any means except with written permission of the publisher shall be deemed to be an infringement of copyright
under the said Act. I
?Sr7SZ-MM9 .
2
IS t ‘132- 1989
CONTENTS
Page
0. FOREWORD’ .. . 5
1. SCOPE ... 6
SECTION 1 TERMINOLOGY
2. TERMINOLOQY ... 6
3. ASSESSMENT
OF CHARACTERISTICS
- GENERAL ... 12
5. REQUIREMENTS
FOR PROTECTIONFOR SAFETY ,.. 19
6. FUNDAMENTALREQUIREMENTS ... 39
7. COMMON RULES ... 41
8. CABLES,CONDUCTORS
AND WIRING MATERIALS .. . 43
9. SWITCHGEAR *. . 49
10. EARTHINGARRANQEMEMTAND PROTECTIVECONDUCTORS ... 51
11. SUPPLIESFOR SAFETY SERVICES ... 51
Indian Standard
CODE OF PRACTICE FOR
ELECTRICAL WIRING INSTALLATIONS
( Third Revision )
0. FOREWORD
0.1 This Indian Standard was adopted by the account in that the information has been called
Bureau of Indian Standards on 25 January 1989, from various Indian Standard specifications and
after the draft finalized by the Low Voltage other literature available and presented as a single
5
IS I 732.~1989
SECTION 1 TERMINOLOGY
2. TERMINOLOGY 2.2 Ambient Temperature - The temperature
of the air or other medium where the equipment
2.0 For the purposes of this standard, the follow- is to be used.
ing definitions shall apply.
2.1 Accessory - A device, other than current- 2.3 Appliance - An item of current using
using equipment, associated with such equipment equipment other than a luminaire or an inde-
or with the wiring of an installation. pendent motor.
6
2.4 Arm’s Reach - A zone extending from any N-2 - Specially formed building voids are
point on a surface where persons usually stand or also known as ducts.
move about, to the limits which a person can 2.9 Buried Direct - A cable laid in the ground
reach with the hand in any direction without in intimate contact with the soil.
assistance.
2.10 Bonchtd - Cables are said to be bunched
NOTE - Thir space is by convention, limited a~
shown in Fig.1. when two or more are contained within a single
conduit, duct, ducking, or tnmking cr, if not
enclosed, are not -rated from each &her:
2.11 Cable BLnnntl - An enclosure situated
above o; ,111the ground, open or ventilated or
clo&; and having dimensions which do not
prmit the access of persons but allow access to
the conductors and/or cabks throughout their
length during and after installation.
NATE - A cable channel may or may not form
part of the building construction
7
IS 1732 -1989
,device(s). Certain types of circuit are categorised 2.26 Connector - The part of a cable coupler
as follows: or of an appliance coupler which is provided
with female contact and is intended to be attached
4 Category 1 Circuit - A circuit ( other than to the flexible cable connected to the supply.
a fire alarm or emergency lighting circuit )
operating at low voltage and supplied 2.27 Conventional Touch Voltage Limit -
directly from a mains supply system. Maximum value of the touch voltage which is
Category 2 Circuit - With the exception of permitted to be maintained indefinitely in specified
W conditions of external influences.
fire alarm and emergency lighting circuits,
any circuit for telecommunication ( for 2.28 Conventional Operating Current ( of a
example, radio, telephone, sound distri- Protective Device )- A specified value of the
bution, intruder alarm, bell and call and current which causes tht protective device to
data transmission circuits ) which is sup- operate within a specifiqd time, designated
plied from a safety source. conventional time.
4 C&egory 3 Circuit - A fire alarm circuit or
NOTE - For fuses this current is called the ‘ con-
an emergency lighting circuit. ventional fusing current ‘. For circuit breakers this
current ia called the ‘ conventional operating current ‘.
2.21 Circuit Breaker - A mechanical switching
device capable of making, carrying and breaking The conventional operating current is greater than
2.40 Earth Electrode Resistance - The resis; 2.52 Enclorure - A part providing protection of
tance of an earth electrode to earth. equipment againstc ertain external influences and,
in any direction, protection against direct contact.
2.41 Earth Fault Loop Impedance - The
impedance of the earth fault current loop ( phase 2.53 Equipment - See2.47.
to earth loop ) starting and ending at the point of
earth fault. 2.54 Equipotential Bonding - Electrical con-
nection putting various exposed conductive parts
2.42 Earth Leakage Current - A current and extraneousconductive parts at a substantially
which flows to earth, or to extraneous conductive equal potential.
parts, in a circuit which is electrically sound.
NOTE- In a building installation equipotential
NOW - This current may ‘have a capacitive com- bonding conductors ahall interconnect the following
ponent including that resulting from the deliberate conductive parts:
use of capacitors. a) Protective conductor,
2.43 Earthing Resistance, Total - The resis- b) Earth continuity conductor, and
tance between the main earthing terminal and c) Risers of air-conditioning system and beating
the earth. systems ( if any ).
2.44 Earthed Concentric Wiring - A wiring 2.55 Exposed Conductive Part - A conductive
2.47 Elect&al Equipment ( 466: Equip- 2.59 Final Circuit - A circuit connected direct-
ment ) - Any item for such purposes as genera- ly to current using equipment, or to a socket
tion, conversion, transmission, distribution or outlets or other outlet points for the connection of
utilization of electrical energy, such as machines, such equipment.
transformers, apparatus, measuring instruments,
protective devices, wiring materials, accessories, 2.60 Fixed Equipment - Equipment fastened
and appliances. to a support or otherwise secured.
2.50 Electrode Boiler (or Electrode Water 2.64 Hand-Held Equipment - Portable equip-
Heater ) - Equipment for the electrical heating ment intended to ‘be held in the hand during
of water or electrolyte by the passage of an normal use, in which the motor, if any, forms an
electric current between electrodes immersed in integral part of the equipment.
the water or electrolyte. NOTE- A hand-held equipment is an item of
equipment, the functioning of which requires constant
2.51 Emergency Switching - Rapid cutting manual support or guidance.
off of electrical energy .to remove any hazard to
*Specification for factory built assemblies of switchgear
persons, livestock, or property which may occur and controlgear for volt es upto and including 1 000~ volt
unexpectedly. ac and I 200 volt dc: P 3 t 1 General requirements.
9
fS : 732 -‘1383
2.65 Indirect Contact - Contact of ‘persons or 2.78 Overcmrreat - A current exceeding the
livestock with exposed conductive parts made live rated value. For conductors the rated value is the
by a fault and which may result in electric shock. current carrying capacity.
2.66 Installations - See2.48. 2.79 Overcurrent Detection - A method of
establishing that the value of current in a circuit
2.67 Insulating Floor ( or WalJ ) - A floor exceeds a. predetermined value for a specified
( or wall ) such that, in the event of direct con- length of time.
tact with a live part, a person standing on the
floor ( or touching the wall ) cannot be traversed 2.80 Ovetload Corrent ( of a Circuit ) - An
by a shock current flowing to the floor (or wall). overcurrent occurring in a circuit in the absence
of an electrical fault.
2.66 Insulation-Suitable non-conductive mate-
rial enclosing surrounding, or supporting a 2.81 PEN Condactor -A conductor combining
conductor. the functions of both protective conductor and
neutral conductor.
Norm -See also the definitions for basic insulation,
double insulation, reinforced insulation and supplemen- 2.82 Phase Conductor - A conductor of an ac
tary insulation.
system for the transmission of electrical energy,
2.69 Isolation - Cutting off an electrical instal- other than a neutral conductor.
lation, a circuit, or an item of equipment from NOTE - The term also means the equivalent con-
10
IS:732:1989
2.90 Residual Cyrrent Device ( RCD ‘) - A circle of diameter equal to the major axis of the
mechanical switchrng device or association of cable.
devices intended to cause the opening of the con-
tacts when the residual current attains a given 2.99 Spur - A branch cable connected to a ring
value under specified conditions. or radial final circuit.
2.91 Residual Operating Current - ResiduaI 2.100 Standby Supply System - A system
current which causes the residual current device intended to maintain supply to the installation or
to operate under specified conditions. part thereof, in case of interruption of the normal
supply, for reasons other than safety of persons.’
2.92 Resistance Area (for an Earth Electrode
NOTE - Standby supplies are necessary, for exam-
only) - The surface area of ground ( around an ple, to avoid interruption of continuous industrial
earth electrode ) on which a significant voltage processes or data processing.
gradient may exist.
2.101 Stationary Equipment - Either fixed
2.93 Ring Pinal Circuit - A final circuit equipment or equipment not -provided with a
arranged in the form of a ring ‘and connected to carrying handle and having such a mass that it
a single point of supply. cannot easily be moved.
2.94 Shock Current-A current passing through 2.102 Supplementary Insulation - Indepen-
the body of a person or an animal and having dent insulation applied in addition to basic
11
on the earths surface separated by a distance 2.109Voltage, Nominal (of an Installation)-
equal to the normal maximum horizontal reach Voltage by which an installation or part of an
approximately 1 metre. installation is designated.
3.1.3 Arrangement of Live Conductors and Tyke of NOTE- For further reqtiitementsfor suppliesfor
Earthing safety servicessee3.4.
12
18873291%?9
clecttically separate from that of every other final Cl generator sets independent of the normal
circuit, so as to prevent indirect energisation of a supp1.y , and
final circuit intended to be isolated.
d) a separate feeder effectively independent
3.2 Compatibility . of the normal feeder.
3.2.1 An assessment shall be made of any NOTE- The use of separate independent feeders
character@@ .ofequi$ment likely to have harmful should be based on an assessment that the two supplies
are unlikely to fail concurrently.
effects upon other electrical equipment or other
services, or likely to impair the supply. The 3.4.2 ClassiJication - A safety service is either:
characteristics include, for example: a non-automatic supply, the starting of
4 transient overvoltages; which is initiated by an operator, or
b) rapidly fluctuating loads; an automatic supply, the starting ol
which is independent of an operator.
4 ‘starting currents;
d) harmonic currents ( such as with fluores- An automatic supply is classified according to
cent lighting loads and thyristor drives ); changeover time:
e>mutual inductance; a) no-break - an automatic supply which can
f) dc feedback; ensure a continuous supply within specified
13
JS t 732 - 1989
c) Contact of persons with earth potential, For the time being, the characteristics of influences.
( co1 2, Table 1 ) are given in descriptive laagu8ge
d) y;;ditions of evacuation in an emergency, only. Codification for the same .( SW Note 1 above ),
as recommended by IEC are given in co1 4 for infor-
mation. It is hoped that in due course the users of the
e) Nature of processed or stored material. Code would be familiar with the codification in terma-
ofwhich the requirements would be stated in future
3) Construction of Buildings’ editions.
a) Constructional materials, and
4.2 Compatibility - An assessment shall be-
b) Building design.
made of any characteristics of equipment likely
4.1.2 Table I suggests the classification and to have .harmful effects upon other electrical.
codification of external influences which require equipment or other services or likely to impair
assessment in-the design and erection of electrical the supply. Those characteristics include, for
installation. example:
NOTE 1 - Each condition of external influence is a) transient overvoltages,
designated by a code comprising a group of two capital
letters and a number as follows: b) rapidly fluctuating loads,
ThaJirSt letter relates to rhe general category of external c) starting currents,
inJkence : d) harmonic currents,
14
L..”
IS : 732 - 1989
15
IS:732-1889
16
_” _ _ _.
ISr732-Ml9
-
TABLE I ASSESSMENT OF GENERAL CHARACTERISTICS OF BUILDINGS - Cod
( Confinwd
17
18:732-19a9
18
IIt1989
b) Limiting the fault current which can pass capable of carrying that current without assuming
through a body to a value lower than the excessive temperature, until the protective gear
shock current; and operates.
c) Automatic disconnection of the supply on
the occurrence of a fault likely to cause a NOTE 1 - Particular attention should be given to
current to flow through a body in contact earth fault currents.
with exposed conductive parts, where the NOTE 2 - For live conductors, compliance with 5
value of that current is equal to or greater assures their protection against any fault currents,
than the shock current. including overcurrents.
5.0.3 Protection Against Thermal E@cts in .Nonal 5.0.5.1 Precautions against earth leokoge and
Service - The electrical installation shall be so metalwork of electrical
earth fault currents -Where
arranged that there is no risk of melting besides equipment, other than current-carrying conduc-
ignition of flammable materials due to high tem- tors, may become charged with electricity in such
perature or electric arc. Also during normal a manner as to cause danger if the insulation of a
operation of the electrical equipment, there shall conductor should become defective or if a fault
be no risk of persons or livestock suffering burns. should occur in any equipment:
5.0.4 Protection Against Overcurrent - Persons or a>the metalwork shall be earthed in such a
NOTE - Where the supply undertaking pro- 5.0.6 Protection Against Overvoltage - Persons or
vides switchgear or fusegear-at the origin of-the livestock shall be protected against injury and
installation it may not be necessary to duplicate property shall be protected against any harmful
the means of overcurrent protection for that part
of the installation between its origin and the main effects of a fault between live parts of circuits
distribution point of the installation where the supplied at different voltages.
next step for overcurrent protection is provided.
In domestic installations the protection and isolat-
ing functions are combined in the same device. Persons or livestock shall be protected against
injury and property *shall be protected against
5.0.5 Protection Against Fault Currents - Conduc- damage from any excessive voltages likely to arise
tors, other than live conductors, and any other due to other causes ( for example, atmospheric
parts intended to carry a fault current shall be phenomena or switching voltages ).
.. _ “_._
_“_.._,..~.._
IS I 732 - 1989
21
IS I 732 l 19119
voltage cvcuits shall be insulated, parts may be touched by a &rson having a con-
individually or collectively, for the ventionalty normal body resistance, and shall be
highest voltage present. appropn*atcly reduced in conditions where reductd
or very low body resistance ir to be exjtcted.
.NCWl - In arrangements (2) and (3)
basic insulation of any conductor need be NOTE - Conventionally normal body resistance
sufficient only for the voltage of the circuit relates to a contact involving one hand and both
of which it is a part. feet, the skin being dry or moist wlth perspiration
( but not wet ). Reduced body’ resistance may be
v) Plugs and socket outlets of safety extra expected in situations where the hands and/or feet
low voltage circuits shall comply with are likely to be wet or where the shock current
all of the following requirements: path may not be through the extremities, and
very low body resistance ( of the order of one
1) The plugs shall not be capable of quarter of the conventionally normal body reair-
tance ) is KO be expected in locationa where a
entering socket outlets of other person is immersed in water or working in confined
voltage systems in use in the same conductive locations.
premises.
2) The socket outlets shall exclude 5.1.1.3 Functional extra low voltage systems
plugs of other voltage systems in use 4 If for functional reasons extra low voltage
in the same premises. is used but not all the requirements
22
ii) Insulation corresponding to the mini- 5.1.1.4 Prokction by limitation of discharge of
mum test voltage required for the energy - For equipment complying with the
primary circuit. appropriate standard, protection against electric
shock is afforded when the equipment incorporates
In addition, protection against means of limiting the current which can pass
indirect contact shall be provided in through the body of a person or livestock to a
accordance with (d) below. value lower than the shock current. Circuits rely-
The extra low voltage circuit may be ing on this protective measure shall be separated
used to supply factory built equipment from other circuits in a manner similar to that
whose insulation does not comply with specified in !5.1.1.2(2)(iii) and (iv) for safety extra
the minimum test voltage required for low voltage circuits.
the primary circuit provided that the
accessible insulation of that equipment Application of protective measure-Limitation
is reinforced during erection to with- of discharge of energy
stand a test voltage of 1 500 V rms for
one minute. This measure shall be applied only lo individual
If the primary circuit of the functional items of current-using equipment complying with an
IS : 732 - 1989
IS : 732 - 1989
5.1.3 Protection Against Indirect Contact iii) The provisions of (ii) above are consi-
dered to be satisfied if the automatic
5.1.3.0 General - One or more of the follow-
disconnection provided for occurs with-
ing basic protective measures for protection against
in the duration not permitting the
indirect contact shall be used:
touch voltage to exceed the safe value.
4 Earthed equipotential bonding and auto- iv) Where protection is afforded by an
matic disconnection of supply, overcurrent protective device, and the
b) Use of Class II equipment or equivalent nominal voltage to earth (V, ) is
insulation, 240 V rms ac, the earth fault loop im-
pedance ( & ), for compliance with
C>Non-conducting location,
25
IS:732-1989
ii) The protective devices shall be of one such magnitude and duration between simultane-
or more of the following type: ously accessible conductive parts that danger could
arise. Il includesall methods involving the earth-
1) Overcurrent protective devices, and
ing of exposed conductive parts. The limiting
2) Residual current devices. values of earth fault loop impedance speciJied
Provided that where the neutral in 5.1.3.1 (a)(iv) shall be applied. where the
and the protective functions are combi- conditions are such that conventionally normal
ned in one conductor (PEN conductor) body resistance applies. In conditions where
a residual current device shall not be reduced or very low body resistance is to be
used. expected, either the earth fault loop impedance
values shall be appropriately reduced or another
c) Installations which are part of a TT system: protective measure shall be used.
i) Where protection is afforded by over-
NOTE -Conventionally normal body resistance
current protective devices or residual relates to a contact involvine cjne band and both
current devices, exposed conductive feet, the skin being dry or Goist with perspiration
parts shall be connected by protective ( but not wet ). Reduced body resistance may be
conductors individually, in groups or expected in situations where tile hands and/or. feet
are likely to be w&or where the shock current
collectively to an earth electrode or path may not.& through the extremities. and very
electrodes. low body resistance (of the order of one quarter of
the conventionally normal body resistance ) is to
ii) The protective dt.4ces shall be of one
NOTE -To reduce overvoltage or to damp Where a circpit originating in that zone is
voltage oscillations, it may be necessary to pro- specijically intended to supply equipment to be
vide earthing through impedances or artificial
used outside the zone, and that equipment may be
neutral points and the characteristics of these
should be appropriate to the requirements of touched by a person in contact directly with thd
the installation. general mass of earth, the following requirements
ii) Exposed conductive parts shall be apply:
earthed either individually, in groups or i) For solidly grounded system it shall be suji-
collectively. Simultaneously accessible cient to check whether de provisions of
exposed conductive parts and associated 5.1.3.1 are complied with in general;
extraneous conductive parts shall be ii) It shall be veriJed whether the main over-
connected only to an earth electrode current protection drvice afords the degree of
common to those parts. protection envisaged by 5.1.3.1 (a) (iv);
iii) The protective devices shall be residual iii) Where the overcurrent protective device did not
current devices. aford the degree of protection in 5.1.3.1(a)
iv) An insulation monitoring device shall (iv) and where the earthing is inadequate, a
be provided to indicate the occurrence separate residual current device shall be *ins-
of first fault from a live part to exposed talled, afordind a protection in compliance
conductive parts or to earth. The device Gth 5.1.3.l(a)(iv); and
shall automatically disconnect the iv) The automatic disconnecting device shall be
supply, or initiate an audible and/or so installed that proper discrimination between
visual signal. the circuits being protected is available.
NOTE- First fault should be eliminated as 4 Where the measure is used in a househsld or
quickly aa practicable. similar installation forming part of a TT system
or where the earthing is not effective, every socket
v) After the occurrence of first fault, condi- outlet circuit shall be protected by a residual
tions for disconnection of supply, as
current device having a rated residual operating
specified for TN and TT systems, shall
current not exceeding 30 mA.
apply*
d) Automatic disconnection using residual current
Application of protective measure - Automa- devices shall not be applied to circuits itlcorpordt-
tic disconnection of supply ing a PENoenductor. The measure is otherwise
a) This measure is gensrally applicable, and is generally applicable, provided that the deviee is
intended to prevent the occurrence of voltage of selected to have a residual operating current
26
b... _. .” _.. .___. -.
ISr732-1989
ensuring compliance with 5.1.3.1 (a)(ii) and of the installation and exposed metalwork
(v). The use of s&h devices is preferred where of that equipment.
the value of earth fault loop impedance prevents
4 The electrical equipment being ready for
the use of overeurrent devices to obtain compli-
operation, all conductive parts separated
ance with the disconnection times specified
from live parts by basic insulation only
in 5.1.3.l(a)(iii).
shall be contained in an insulating
NOTE - If a residual current device affording enclosures affording at least the degree of
protection against indirect contact has a rated protection IP 2X.
residual current equal to or less than 30 mA and
an operating time of 40 msor less at a residual 4 The insulating enclosure shall be capable
current of 250 mA, it may also be used to reduce of resisting the mechanical, electrical and
the risk associated with direct contact in case of thermal stresses to which it is likely to be
failure of other protective measures. Such a device
subjected.
cannot be used as a sole means of protection
against direct contact and does not obviate the NOTE - Coatings of paint, varnish and similar
need to apply one of the protective measure speci- products are generally considered not to comply
fied in 5.1.2.0.
with (d).
e) Automatic disconnection using fault voltage opera- If the insulating enclosure has not previ-
ted protective devices is recogniscdfor use in TT
e)
ously been tested, a suitable test shall be
and IT systems and is suitabte where the impe- carried out ( see Section 5 ).
27
IS ; 732 - 1989
of electrical equipment through a fault in the basic ii) 100 kQ where the supply voltage exceeds
insulation. It is generally applicable to items of 500 V but does not exceed 1 000 V.
equipment, either by the selection of equipment
complying with an appropriate Indian Standard If at any point the resistance is less
where that standard provides for the use of than the specified value, the floors and
Class N construction or total insulation, or by the walls are extraneous conductive parts for
application of suitable supplementary insulation the purposes of protection against shock.
during erection.
NOTX- Stepa may need to be taken SOthat
b) Where a circuit supplies items of Class II equip- humidity will not effect the resistance of Boom
ment, a means of connection to the protective and walk to such an extent that they do not com-
ply with 5.1.3.S(c).
conductor of the circuit shall nevertheless be provi-
ded at every point for the supply of current-using The arrangements
equipment likely to be changed by the user, and
4 made shall be perma-
nent. They shall also afford protection
at terminations for accessories similarly likely to where the use of mobile or portable equip
be changed by the user. This requirement need ment is envisaged.
not be observed where (c) below applies.
NOTE - Attention is drawn to the risk that
NOTE- Exposed metalwork of Class II equip-
where electrical installations are not under effec-
ment should preferably be mounted so that it is
tive supervision, further conductive parts may be
4 The resistance of insulating floors and walls This measure is intended to prevent simultaneoy
at every point of measurement under the con&et with parts which may be at di&ent potentials
conditions specified in 12.3 shall be not less through failure of the basic irt.sulationof live parts. It 1s
than: not recognised in these clauses for general use, but may
i) 50 kQ where the supply voltage does not be apfiied in special situations under e&tive supeririJ,iun,
exceed 500 V, or where spectfied by a suitably qualijisd rlectn’cal engineer.
28
Protection by earth frcG
5.1.3.4 local equigotential 2) such that the output is separated
bonding from the input and from the tnclo-
sure by an isolation satisfying the
Equipotential bonding conductors shall
conditions of 5.1.3.2(a) to (j). If such
connect together all simultaneonsly accessi-
a source supplies several items of
ble exposed conductive parts and extraneous
equipment, exposed metalwork of
conductive parts.
that equipment shall not be conntc-
The local equipotential bonding conductors ted to the metallic enclosure of the
shall not be in electrical contact with earth source.
directly, or through exposed conductive
parts or through extraneous conductive c) The separated circuit shall comply with the
following requirements:
parts.
NOTE -Where (b) caunot be obrerved, i) Live parts of the separated circuit shall
requirements far protection by automatic discon- not be connected at any point to another
nection of supply are applicable [ sse 5.1.3.1 (a)
circuit or to earth and to avoid the risk
to(d) 1.
of a fault to earth, particular attention
Precautions shall be taken so that persons shall be given to the insulation of such
entering the equipotential location carmot parts from earth, especially for flexible
be exposed to ,dangerous potential diffe-
cables and cords.
ii) All socket’outlets shall be provided with 4 Exposed conductive parts, which owing to
protective contacts which’shall be con- their reduced dimensions or their disposition
nected 0 cquipotcntial bonding cannot be gripped or cannot be contacted
conducto f provided in accordance with by a major surface of the human body,
(i) above. provided that connection of these parts to
iii) All flexible cables of equipment other a protective conductor cannot readily be
than Class II equipment shall embody made or cannot be reliably maintained.
a protectiv conductor for use as an NOTE- This clause applies to small isolated
equipotent e 1 bonding conductor. metal Darts such as bolts. rivets. nameolates and
cable ciips. For the purposes of (c) above a major
iv) It shall be verified that, if two faults to surface of the human body is considered to be
exposed me alwork occur and these are 50 mm x 50 mm.
fed by con x uctors of different polarity,
an associated protective device will meet 4 Fixing screws for non-metailic accessories
the requirements of 5.1.3.l(a)(ii). provided that there is no appreciable risk
of the screws coming into contact with live
Application of Protective Measure- Electrical parts.
separation Short lengths of metal conduit for mechani-
4
This measure is intended, in the individual circuit, cal protection of cables having a non-
metallic sheath, or other metal enclosures
5.1.4.3 For areas which are accessible only 5.1.5.4 The neutral (star) point of the
to skilled persons by the use of a safety ward lock secondary windings of three-phase transformers
key or tools, the measures of protection against and generators, or the midpoint of the secondary
electric shock specified in this section may be windings of single-phase trtisformers and genera-
totally dispensed with, where this is permitted by tors, shall be connected to earth.
the appropriate authority. 5.1.5.5 Protection against direct contact shall
5.1.4.4 Areas reserved for skilled or instruc- be provided by insulation or by barriers or enclo-
ted persons shall be clearly and visibly indicated sures.
by suitable warning signs.
5.1.5.6 Protection against indirect contact
5.1.4.5 It is permissible to dispense with by automatic disconnection shall be provided by
measures of protection against indirect contact in means of an overcurrent protective device in each
the following instances: phase conductor or by a residual current device,
and all exposed conductive parts of the reduced
4 Overhead line insulator wall brackets and low voltage system shall be connected to earth.
metal parts connected to them if such parts The earth fault loop impedance at every point of
are not situated within arm’s reach. utilisation, including socket outlets, shall be such
b) Steel reinforced concrete poles in which the that the disconnection time does not exceed
steel reinforcement is not accessible. 5 seconds. Where a residual current device is used,
30
-._ _,.__
___..
_._
,I X._I
IS : 732 - l!MJ!9
the productof the rated residual operating current supply unit shall be connected to the pro-
in amperes and the earth fault loop impedance in tective conductor of the final circuit from
ohms shall not exceed 50. which the supply is derived.
5.1.5.7 Plugs, socket outlets and cable coup- e) In a room containing a fixed bath or
shower cubicle, parts of a lampholder with-
lers of reduced low voltage systems shall have a in a distance of 2.5 m from the bath or
protective conductor contact and shall not be shower cubicle shall be. constructed of
inter-changeable with plugs, socket outlets- and or shrouded in insulating material. Bayonet
cable couplers for use at other voltages in the type (B22) lampholder shall be fitted with
same installation. a protective shield. As an alternative,
totally enclosed luminaries may be used.
5.1.6 Protective Measures for ParticuLar Locations-
In certain locations the susceptibility of persons, f 1 Every switch or other means of electrical
and livestock where present, to electric shock may control or adjustment shall be so situated
be so high as to necessitate special combinations as to be normally inaccessible to a person
of protective measures and supplementary precau- using a fixed bath or shower. This require-
tions as specified in the following clauses. ment does not apply to electric shaver
supply units installed in accordance with
5.2 Reqairements for Protection Against provided by the appropriate measures specified in
Thermal Effects this section.
5.2.1.2 All switchgear shall be selected and
5.2.1 General erected in accordance with the requirements
of Section 4 so as to prevent danger from
5.2.1.1 Protection against thermal effects overheating, arcing, or the scattering of hot
caused by fixed electrical equipment shall be particles during operation.
31
5.2.2 Protection Against Fire Application of Protective Measure .- U&r
considiiation.
5.2.2.1 Fixed equipment shall be selected,
located and erected so that its intended heat dissi-
pation is not inhibited and it does not present a
c- .
.\
1
fire hazard to adjacent building materials. \\
5.2.2.2 Fixed equipment which in normal \\
operation has a surface temperature exceeding
90°C shall be adequately ventilated and be moun-
\\
ted so that no material constituting ,a fire hazard
is within 300 mm above or 150 mm laterally from ’,\
or below the equipment ( see Fig. 2 ), except that I
these distances may be reduced if a suitable fire- 600
resistant shield or enclosure is installed between I
I
the equipment and any such material.
k
This does not apply to lamps, luminaires and
appliances installed in accordance with the manu-
facturer’s instructions and considered to comply
5.3.1.2 The protection against overload and NOTE- The use of a projective device having a.
rated breaking capacity below the due of the prospe
the protection against short circuits shall be co- tive short circuit current at its lace of installation
ordinated in accordance with 5.3.5. subject to the requiremenu of 5. B.4.3.bL
32
br732-1999
33
5.13.4 Protection Against Short-Circuit Curreti - NOTE For certain types of circuit breakers,
This clause deals only with the case of short especially aontcurrent-limiting types, this. assump-
tion may not btixalid for the whole range of short-
circuits anticipated between conductors belonging circuit currenta; ‘Zo case of doubt, itr validity
to the same circuit. should be checked in 2tccordance with the require-
ments of(d) below.
5.3.4.1 General - Protective devices shall be
provided to break any short-ciruit current in the Where (c) above does not apply, it shall be
conductors of each circuit before such current verified as follows that al.1 currents caused
could cause danger due to thermal and mechani- by a short-circuit occurring,,?t any point of
cal effects produced.in conductors and connections. the circuit shall bq interrupted in a time
The nominal current of such a protective device not exceeding that which brings the cable
may be greater than current-carrying capacity of conductors to the admissible limiting tem-
the conductor being protected. perature. In addition it shall be verified for
larger installations that the cable is unlikely
563.4.2 D6tannination of pros~cti~c short-circuit to be damaged mechanically.
CWY6flt- The prospective short-circuit current at
every relevant point of the complete installation
For short-circuits of duration up to 5 seconds
shall be determined. This may be done either by
34
NOTE.- For very short durations (len b) Omission of devices for sho&&c& prutectian
than O-1 second ) where a symmetry of the
current ir of importance and for current i) Devices for protection against shoti circuit
limiting devices, the value of PS’ for the need not be proti’dedfw:
cable rbould ba greater than the value of
let-through energy ( Pt ) of the device aa 1) conductorsconnecting generators, trmfw-
quoted by the manufacturer.
mers, recti@rs or batteries with their
5.3.4.4 Protection of conductors inparallel - A controlpanel& where short-circuitprotec-
single device may protect several conductors in tive devices are placed on thosepaneis,
parallel against short circuit provided that the
operating’ characteristics of the device and the 2) cartain maaswing circuits, and
method of installation of the parallel conductors 3) circuits where disconnection could cause
are suitably coordinated. danger in the opera& the installation
NATE- Account should be taken of the conditions concerned.
that would occur in tb; event of a short circuit which
does not affect all of the conductors.
Provided that the conductors thur not
protected against short circuit compll with
Applica’tion of protective measure 53.4 $) ~nditions speciJed in (a)@)(2) and
a ove.
a) Position of devices for short-circuit protect&m
5.3.5 Coordination d Overload and Short-Chit
i) A devices forprotectivn against short&rcuit
35
18 : 732 - 1989
,b) Where either or both of the conditions arrangements described in (b) below are
specified in (b) above are not met, over- adopted.
current detection shall be provided for the b) In IT systems where the neutral is distribu-
neutral conductor, appropriate to the cross- ted, means of detection of overcurrent for
sectional area of that conductor, and the the neutral conductor need not be provided
means of detection shall cause the discon- if either of the following conditions is
nection of the phase conductors but not satisfied:
necessarily of the neutral conductor.
i> the neutral conductor concerned is
NOTE - The cross-sectioal area of the neutral effectively protected against short circuit
conductor should in any event comply with by a protective device placed on the
Section 4.
supply side, for example at the origin of
5.3.1.3 N6utral conductor-IT systems the installation, in accordance with the
a) In IT systems, the distribution of the requirements of 5.3.4.3(b); and
neutral conductor shall be avoided wbere- ii) the circuit concerned is protected by a
ver practicable. Where distribution of the residual current device having a rated
neutral conductor is unavoidable, means of residual operating current not exceeding
detection of overcurrent shall be provided 0.15 times the current-carrying capacity
for the neutral conductor of every circuit, of the neutral conductor concerned and
which shall cause disconnection of all the the device is arranged to disconnect all
5.4 Requirements for Protection Agaimrt could be due to reveral reasons such as:
’ Overvoltage - hhr consideration. a) insulation fault between live parts of circuitd
supplied at different voltages, and
NOTE - This clause is set aside to cover rules con-
ceming protective measures against overvoltage which b) atmospheric phenomena or switching voltages.
5.5 Requirements for Protection Against tbe appliance protected allows without danger a
Undervoltage brief interruption or loss of voltage.
5.5.1 Gmcrol R6quir6mcntJ
5.5.1.3 If use is made of contractors, delay
5.5.1.1 Where a drop in voltage, or a loss in their opening and reclosing shall not impede
and subsequent restoration of voltage could imply instantaneous disconnection by control or protec-
dangerous situations for persons or property, suit- tive devices.
able precautions shall be taken, Also, precautions
shall be taken where a part of the installation or 5.5.1.4 The cmracteristics of the undervol-
current-using equipment may be damaged by a tage protective device ShalI be compatible with the
drop in voltage. requirements of the Indian Sandards for starting
and use of equipment.
An undervoltage protective device is not
required if damage to the installation or to current-
5.5.1.5 Where the reclosure of a protective
using equipment is considered to be an acceptable
device is likely to create a dangerous situation, the
risk, provided that no danger is’ caused to
persons. reclosure shall not be automatic.
5.5.1.2 The o ation of undervoltage pro- Application of protective measuke .5b T Under
tective d&c& qy Cr delayed if the operation of conridrratiw,
36
IS I 732 - 1369
5.6 Requirements for Isolation and Switch- 5.6.1.5*All devices used for isolation shall be
% clearly identifiable for example, by marking, to
indicate the circuit which they isolate.
5.6.0 General
5.6.0.1 _Means shall (be provided for non- Application for protective measure-Isolation
automatic isolation and switching to prevent or
remove hazards associated with the electrical 4 Means of isolation complying with 5.6.1 shall
installation or electrically powered equipment and be provided at a point as near as practicable to
machines, These means shall comply with the the origin of every installation,without the inter-
appropriate requirements of this section. vention of any other equipment on which work
might need to be done.
5.6.0.2 In TN-C systems the PEN conductor
shall not incorporate means of isolation or switch- b) Where an isolator is to be used in conjunction
ing. In TN-S systems the protective conductor with a circuit-breaker as a means of isolating
shall not incorporate a means of isolation or main switchgear for maintenance, it shall be
switching and provision need not be made for interlockedwith the circuit-breaker; alternatively,
isolation of the neutral conductor except where it shall be so placed and/or guarded that it can
this is specifically required. be operatedonly by skilledpersons.
37
I$i732-1989
5.6.2.2 Devices for &itching off for mecha- 4 Means of emergency switching shall be provided
nical maintenance shall be suitably placed, readily in everyplace where a machine driven by tlectric
identifiable (for example by marking if necessary) means may give rise to danger, and shall
and
, convenient for their intended use. be readily accessible and easily operated by the
5.6.2.3 Suitable me&s shall be provided so person in charge of the machine. Where more
that precautions can be taken to prevent any than one means of manually stopping the machine
equipment from being unintentionally or inadvei- isprovided and danger might be caused by unex-
tently reactivated. pected restarting, means shall be provided to
prevent such restarting.
Application of protective measure prescribed
in 5.6.2 4 A jireman’s emergency sivitch shall be provided
A means of switching o$for mechanical maintenance f or:
shall beprovided- for every circuit supplying an electric - exterior discharge lighting installations opera-
motor, or equipment having electrically heated surfaces ing at a voltage exceeding low voltage, and
which can be touched, or electromagnetic equipment for
o#erations from which mechanical accidents could arise. - interior discharge lighting installations operat-
Wherg a switch mounted on an appliance or luminaire ing unattended at a voltage exceeding low
is in&a& to serve as a means of switching @for voltage.
38
IS : 732 l 1966
5.6.4 Other Requirements for Switching for Safe0 the installation and the consumer’s main switch-
gear.
5.6.4.1 In situations where the requirements
of 5.6.3 for emergency switching are not applica- 5.6.4.4 Every appliance or luminaire con-
ble, the requirements of 5.6.4.2 to 5.6.4.7 shall be nected to the supply other than by means of a
satisfied, either: plug and socket outlet complying with Section 4,
-
shall be provided with a means of interrupting the
by means of isolation and/or the means of supply on load. The means of interruption shall
switching off for mechanical maintenance be separate from the appliance and in a readily
provided ior compliance with 5.6.1 and accessible position, subject to the provisions
5.6.2, or of 5.6.4.5 and 5.6.4.6 where applicable. For an
- by the arrangements for switching of equip- appliance fitted with heating elements which can
ment for its normal service ( functional be touched, the means of interruption shall be a
switching ), or linked switch arranged to break all the circuit
conductors including the neutral. For the purpose
- by the provision of suitable additional of this regulation the sheath of silica-glass sheathed
means of switching. element is regarded as part of the element.,Where
the means of interruption is also intended to serve
5.6.4.2 A main switch or circuit-breaker as a means of switching off for mechanical main-
shall be provided for every installation which
39
-. _.._-_... __.
18 I 132-1999
f) Particular requirements of the supply respect to their function which may be for
undab@aking. example, protection against the effects of:
g) PaRietilar requirements of the load. a) overcurrent ( overload and short circuit ),
6.1.2 JVature of Demand - The number and b) earth-fault current,
type of the circuits required for lighting, heating, c) overvoltage, and
power, control, signalling, telecommunication, etc, d) undervoltage and no-voltage.
are to be determined by:
The protective devices shall operate at values
a) location of points of power demand, of current voltage and time which are suitably
b) loads to be expected on the various circuits, related to the characteristics of the circuits and to
c) daily and yearly variation of demand, the possibilities of danger.
d) any special conditions, and 6.1.7.1 Position of protective deuiccs and switches
e) requirements for control, signalling, tele-
communication, etc.
a>No fuse, or circuit-breaker
linked circuit-breaker, shall
other than a
be inserted in
6.1.3 Emergency Supply or Supplies an earthed neutral conductor, and any
linked circuit-breaker inserted in an earthed
a) Source of supply ( nature, characteristics ), neutral conductor shall be arranged t@
and break also all the related phase conductors.
40
- ... ”_ - . _.-__
I9 ~132-1989
6.1.11 Accessibility of Electrical Equipment - The cause harmful effects on other equipment or
electrical equipment shall be arranged SO as to impair the supply during normal service including
afford: switching operations. In this context, the factors
which may have an influence include, for exam-
a) sufficient space for the initial installation
ple:
and later replacement of individual items of
electrical equipment; and a) power factor,
4 inrush current,
‘b) accessibility for operation, testing, inspec-
tion, maintenance and repair. 4 asymmetrical load, and
6.2 Fundamental Requirements for Selection 4 harmonics.
of Electrical Equipment 6.3 Fundamental Requirements for Erection
and Initial Testing of Electrical Installations
6.2.0 Every item of electrical equipment used
in electrical installations shall comply with rele- 6.3.1 Erection
vant Indian Standard specifications.
6.3.1.1 For the erection of the electrical
6.2.1 Characteristics - Every item of electrical installation good workmanship by suitably quali-
equipment selected shall have suitable characteris- fied personnel and the use of proper materials shall
tics appropriate to the values and conditions on be provided for.
41
- I .._ __.
ISr732.1989
7.2.6 External In@encesS- All equipment shall be Means of access to all live parts of switchgear
of a design appropriate to the situation in which and other fixed live parts where different nominal
it is to be used and its mode of installation shall voltages exist shall be marked to indicate the
take into account the conditions likely to be voltage present.
encountered.
7.5 Mutual DetrimcntaI InHaence
7.3 Accessibility
7,3.I All equipment shall be arranged so as to 7.5.1 All electrical equipment shall be selected
facilitate its operation, inspection and maintenance and erected so as to avoid any harmful influence
and access to its connections. Such facilities shall between the electrical l%stallation and any non-
not be significantly impaired by mounting equip- electrical installations-envisaged.
ment in enclosures or compartments.
7.5.2 Where equipment carrying currents of
different types or at different voltages is grouped
7.4 IdentI&ation and Notices
in a common assembly, all equipment using any
7.4.1 General - Labels or other suitable means one type of current or w_.qne voltage shall,
of identification shall be provided to indicate the wherever necessary, be effeei%vely segregated from
purpose of switchgear and controlgear, unless equipment of any other type, to avoid mutual
there is no possibility of confusion. detrimental influence.
Where the operation of switchgear and control- *Recommendations for direction of movement for con-
gear cannot be observed by the operator and trol devices operating electrical apparatus.
where this might cause a danger, a suitable tDanger notice plates (first re&en ).
42
“___
__.--_.
r--- - ___^_“_^__
IS : 732 - 1989
8.1.1.3 Busbars and busbar connections shall 8.1.7.1 Methods of installation of cables and
comply with IS : 8623 ( Part 1 )-1977t. conductors in common use for which this code
specifically provide are described in Appendix A.
43
NOTE - It is recommended that the maximum 8.2.3 Minimum Cross-Sectional Area of Neutrals
operating temperature of bare conductors should not Condwtors - For polyphase circuits in which
exceed 90%.
imbalance may occur in normal service, through
8.2.1.5 Where cables are to be connected to significant inequality of loading or of power
bare conductors or busbars it shall be verified that factors in the various phases, or through the
their type of insulation and/or sheath is suitable presence of significant harmonic currents in the
for the maximum operating temperature of the various phases, the neutral conductor shall have a
bare conductors or busbars. Alternatively the insu- cross-sectional area adequate to afford compliance
lation and/or sheath of the cables shall be removed with 8.2.1.1 for the maximum current likely to
for a distance of 150 mm from the connection and flow in it.
replace if necessary by suitable heat-resisting
insulation. For polyphase circuits in which serious
imbalance is unlikely to be sustained in normal
8.2.1.6 Where a cable is to be run for a service, other than discharge lighting circuits, the
significant length in a space to which thermal use of multicore cables incorporating a reduced
insulation is likely to be applied, the cable shall, neutral conductor in accordance with the appro-
wherever practicable, be fixed in a position such priate Indian Standard is recognised. Where
that it will not be covered by the thermal insula- single-core cables are used in such circuits, the
44
L _,... ._ .
I8 : 732 0 1989
8.3.1.3 In determining the normal opera- 8.3.2.5 In any situation, the exposed conduc-
tional conditions of conductors and cable, account tor and insulation at terminations and joints of
need not be taken of the minimum ambient tem- cables insulated with impregnated paper shall be
perature likely to occur. However, precautions shall protected from ingress of moisture by being suit-
-be taken to avoid risk of mechanical damage to ably sealed.
cables susceptible to low temperatures.
8.3.2.6 The ends of mineral-insulated cables
8.3.1.4 The enclosures of wiring systems for shall be protected from moisture. by being suitably
conductors and cables shall be selected and instal- sealed and the insulation shall be thoroughly dry
led so that they are suitable for the extremes of before the sealing material is applied. Such seal-
ambient temperature to which they are likely to ing material, and any material used to insulate
-be exposed in normal service. If a nonmetallic or the conductors where they emerge from the
composite outlet box is used for the suspension of, insulation, shall have adequate insulating and
or is in contact with, a luminaire and where a moisture-proofing properties, and shall retain those
thermoplastic material ( for example PVC ) is the properties throughout the range of temperatures to
principal load-bearing member, care shall be which they may be subjected in service.
taken that the temperature of the box does not
exceed 60°C and that the mass suspended from
8.3.2.7 In damp situations, enclosures for
the box does not exceed 3 kg.
cores of sheathed cables from which the sheath has
45
me...... ^.. .___^ _ .__
IS t 732 - 1989
8.3.5.2 Where cables are installed under 8.3.5.9 Flexible cords, where they are
floors or above ceilings they shall be run in such exposed to risk of mechanical damage, shall be of
positions that they are not liable to be damaged a type sheathed with rubber or PVC, and where
by contact with the floor or the ceiling or their necessary, shall also be armoured; provided that
fixings. Where the cable passes through a timber for domestic and similar applications where flexi-
joint within a floor or ceiling construction ( for ble cords are subject only to moderate bending
example, under floorboards ), the cable shall be and/or wear, unkinkable flexible cords may be
50 mm, measured vertically, from the top or used.
bottom, as appropriate, of the joist. Alternatively,
cables not protected by an earthed metallic sheath 8.3.5.10 Braided circular twin and- three-
shall be protected by enclosure in earthed steel core flexible cords insulated with glass fibre shall
conduit securely supported, or by equivalent be used only for luminaires or for other applica-
mechanical protection sufficient to prevent pene- tions where the cord is not subject to abrasion or
tration of the cable by nails, screws, and the undue flexing.
like.
8.3.5.11 Flexible cords shall not be used as
8.3.5.3 Where cables pass through holes in fixed wiring, except as permitted by 8.3.5.13,
metalwork, precautions shall be taken to prevent unless contained in an enclosure affording mecha-
abrasion of the cables on any sharp edges. nical protection.
46
IS : 732 - 1989
8.3.7 Solar Radiation- Cables and wiring systems any other category, these circuits, shall be segrega-
installed in positions which may be exposed to ted from the latter by continuous partitions such
direct sunlight shall be * of a type resistant to that the specified integrity of the category 3
damage by ultra-violet light. circuits is not reduced. These partitions shall also
be provided at any common outlets in a trunking
8.4 Identification system accommodating category 3 circuits and cir-
8.4.1 Reference is drawn to IS : 11353-1986* cuits of other categories. Where mineral-insulated
on marking of conductors and apparatus terminals cables are. used for category 3 circuits such
by colours and alphanumeric code. partitions are not normally required. Where parti-
tions are not used, the mineral-insulated cables
8.5 Prevention of Mutual Detrimental shall be rated for exposed-to-touch conditions.
l&hence
8.5.1.7 In conduit, duct, ducting or trunking
8.5.1 BetweenLow Voltage Circuits and Circuits of
systems, controls or outlets for category 1 and
Other Categories
category 2 circuits shall not be mounted in or
8.5.1.1 Low voltage circuits shall be segrega- on common boxes, switchplates or blocks. Where
ted from extra-low voltage circuits. it becomes unavoidable the cables and connections
of the two categories of circuit shall be partitioned
8.5.1.2 Where an installation comprises
by means of rigidly fixed screens or barriers.
48
.
provided that all other bends on the conduit 4U.1.2 For;?TT systemg, :d?kde cxp6seP
run are not more than the equivalent of conductive parts are connectedRogether ,and over-
one right angle. current protective devices are tobecused to provide
protection, against electric shock in the&em of a
8.9.2.3 The radius of every conduit bend second fault, the requirements for the protective
shall be such as to allow compliance with 8.9.2.1 devices are similar to those for TN systems as
for bends in &bles and, in any event, the inner specified in 9.1.1.1.
radius of the bend shall be not less than 2-5 times
the outside diameter of the conduit. 9.1.1.3 The overcurrent protective devices
shall conform to. the relevant .Indian Standards.
8.9.2.4 Every bend in a closed duct or duct-
ing shall be of an inner radius allowing compliance 9.1.1.4 When semi-enclosed fuse units are
with 8.9.2.1. used for overcurrent protection, the nominal
current rating of the circuit being protected to be
8.9.3 Space Factors - The number of cable indicated adjacent to the fuse.
drawn into, or laid in, an enclosure of a wiring
system shall be such that no damage is caused to 9.1.2 Residual Current Devicts
the cable or to the enclosure during their installa- 9.1.2.1 Residual current devices shall be
tion . capable of disconnecting all the phase conductors
9. SWITCHGEAR of the circuit.
so
Is a 732 - 1989
51
IS I 732 -.1989
11.3.3 The protection against overload may be 11.5.1 Precautions shall be taken to prevent
omitted. the paralleling of the sources, for example, by
mechanical interlocking.
11.3.4 Overcurrent protective device shall be
selected and erected so as to avoid an overcurrent 11.5.2 The requirements of these clauses for
in one circuit imparing the correct operation of protection against short circuit and indirect
other circuits of safety services, contact shall be met for each source.
11.3.5 Switchgear and controlgear, except
alarm devices, shall be clearly identified and 11.6 Special Requirements for Safety
grouped in locations accessible only to, skilled or Services Having Sour&s Capable of Opera-
instructed persons. Alarm devices shall be clearly tion in Parallel
identified.
NOTE - Ser also 4.1.3.2.
11.4 Utilisation Equipment - In equipment
supplied by two different circuits, a fault occurring 11.6.1 The requirements of these clauses for
in one circuit shall not impair the protection protection against short circuit and against
against electric shock nor the correct operation of indirect contact shall be met whether the installa-
the other circuit. Such equipment shall be selec- tion is supplied by either of the two sources or by
ted to the protective conductors of both circuits, both in parallel.
if necessary.
12. INITIAL INSqECTION AND TESTING Appendix C, the use of other methods is not pre-
cluded provided that they give no less effective
12.1 General results:
12.1.1 Every installation shall, on completion Continuity of ring final circuit conductors,
and before being energised, be inspected and 4
tested in accordance with the requirements of this W Continuity of protective conductors? includ-
section to verify, as far as practicable, that the ing main and supplementary equrpotential
requirements of these clauses have been met. bonding,
Cl Earth electrode resistance,
The methods of test shall be such that no
danger to persons or property or damage to 4 Insulation resistance,
equipment can occur even if the circuit tested is 4 Insulation of site-built assemblies,
defective.
f 1 Protection by electrical separation,
12.2 Visual Inspection I31Protection by barriers or enclosures provi-
ded during erection,
12.2.1 A visual inspection shall be made to
verify that the installed electrical equipment is: h) Insulation of non-conducting floors and
walls,
- in compliance with the applicable Indian
Standards ( this may be ascertained by 3 Polarity, I
mark or by certification furnished by the k) Earth fault loop impedance,
installer or by the manufacturer ), n-4 Operation of residual current devices and
- correctly selected and erected in accord- fault-voltage operated protective devices.
ance with this code, and
- not visibly damaged so as to impair safety. In the event of any test indicating failure to
comply, that test and those preceding, the results
NOTE - Appendix E lists the principal features of of which may have been influenced by the fault
an installation to be visually inspected in order to
verify compliance with this code.
indicated, shall be repeated after the fault has
been rectified.
12.3 Testing
12.3.1 General - The following items, where 12.3.2 Continuity of Ring Final Cihit Con-
relevant, shall be tested in the sequence indicated. ductors - A test shall be made to verify the con-
Standard methods of testing, in respect of some of tinuity of all conductors ( including the protec-
the following clauses of this section, ‘&e given in tive conductor ) of every ring final circuit.
52
-_ _ __ _-_...-.
IS : 732 - 1989
53
IS : 732 - l!b89
shall be able to withstand a test voltage of at least relevant impedance shall be measured, or deter-
2 kV, and shall not pass a leakage current exceed- mined by an equally effective method.
ing 1 mA in‘normal conditions of use.
12.3.12 Ofieration of Residual Current Ojerated
and Fault- Voltage Operated Protective Devices -
12.3.10 Polarity - A test of polarity shall be Where protection against indirect contact is to be
made and it shall be verified that all fuses and provided by ,a residual current device or a fault-
single-pole control devices are connected in the voltage operated protective device, its effecti-
phase conductor only, that centre-contact veness shall be verified by a test simulating an
bayonet and Edison-type screw lampholders in appropriate fault condition and independent of
circuits having an earthed neutral conductor, any test facility incorporated in the device.
have their outer or screwed contacts connected to
that conductor, and that wiring has been 13. ALTERATIONS TO INSTALLATIONS
correctly connected to socket outlets.
13.1 In case of an alteration to an existing ins-
tallation, it shall be verified that the installation
12.3.11 Earth Fault Loop Impedance - Where after the alteration complies with this code and
protective measures are used which require a does not impair the safety of the existing installa-
knowledge of earth fault loop impedance, the tion.
NOTE -Other types ofwiring systems,not covered A-2. The method of installation of a wiring system
ii this Appendix, may be used provided they comply in relation to the situation concerned shall be in
with the general rules of this code.
accordance with Table 3.
A-I. The method of installation of a wiring system
in relation to the type of conductor cable used A-3. Examples of wiring systems are shown
shall be in accordance with Table 2. in Tables 2, .3 and 4.
Insulated conductors X X : d 4 X 4 X
Sheathed cables
(including armour-
ed and mineral
insulated)
Multi-core
Single-core
4 : Permitted
x : Not permitted
-: Not applicable, or not normally used in practice
54
em. ..I, .,._ .L I_..
._--
ISr732-l!m
MOTE - The illustrations are not intended to depict actual product or installation practice but are indicative
of the method described.
( Confirwd )
ISt732-1989
On unperforated tray8 12
On brackets 14
On cleats 15
On ladder 16.
( Continurd )
56
18 I 732 - 1989
;/
Bare or insulated conductors on insulators 18
D 0
&
L
Sh;e;tsed single core or multicore cables in building 21
.D
b) in suspended floor
. Insulated conductors
a) Run horizontally
in cable trunkink on a wall:
31
m b) Run vertically
33
( Continued )
-..
IS:732-1989
( Continurd )
58
TABLE 4 EXAMPLES OF WIRING SYSTEMS - Contd
63 l
l
e
.,
\\
,
\ Insulated conductors in conduits or sheathed single 7;
core of multicore cables in architravts
( Continued
-29
TABLE 4 EXAMPLES OF WIRING SYSTEMS - %fu’
B-I. CLEATED WIRING SYSTEM B-1.6.2 Where practicable the same method
shall be adopted in the cases of stone walls, but
B-l.1 General - This system shall not be when owing to irregular coursing or other reasons
employed for wiring on damp walls or ceiling. it is impracticable to fix the cleats in a regular and
workman like manner, a wood batten shall be
B-l.2 Accecsibility - All cleated wiring shall provided and fixed with not less than one plug per
be run, as far as practicable, so as to be visible 1.25 m run. The batten shall be of seasoned teak
except in positions where they would be liable to or other suitable seasoned hardwood 2 cm thick
mechanical injury and where they are less than and 2.5 cm wider than the cleat used, it shall be
1.5 m above the floor, in which cases they shall be chamfered on the edges, wrought all over and
adequately protected. varnished with two coats of varnish conforming
B-1.3 Types of Cables - Vulcanized rubber to IS : 347-1975* or painted as may be required.
insulated cables; plastic ( PVC and polyethylene ) B-l.7 Distance Between Wires - @or voltages
insulated cables, braided or unbraided; and any up to 250 volts, cleats shall be of such dimensions
other approved insulated cables shall be used that in the case of branch loads, conductors shall
without any further protection. not be less than 2.5 cm apart centre to centre and
B-l.4 Cleats - All cleats shall consist of two in the case of submains not less than 4 cm apart
parts, a base piece and a cap. A special pattern of centre to ‘centre, provided that this shall not
cleat may be used, if necessary, where conductors apply, if the cable used is twin-core. Care shall be
pass round cornen, so that there may be no risk taken in select&g size of cleats particularly for
of the cductors touching the wall owing to the branch distribution wiring where two-way and
sagging or stretching. Cleats shall be fixed at three-way porcelain cleats are essential, and the
distances not greater than 60 cm apart and at difference in size shall be reasonable. Care shall
regular intervals. also be taken that grooves of porcelain cleats do
not compress the insulation nor be too wide for a
B-l.5 Where cleated wiring is laid along iron very loose fit. Under no circumstances two wires
joist or any metal, spacing between such metal shall be placed in one groove of porcelain cleats.
and porcelain cleats shall be inserted either with
varnished wood fillet or varnished, wood clamp
El.8 Cramming of Conductors
securely fixed as would be approved so as to B-1.8.1 Where cleated conductors cross each
prevent conductors coming in contact with such other they shall be separated by an insulating
metal along which they are passing. bridging piece, which will rigidly maintain a
distance of at least I.3 cm between the conductors
El.6 Fixing of Cleatm except when the cable used is twin-core.
B-1.6.1 In ordinary cases, cleats shall be *Specificationfor varnish, shellac, for general purposes
attached to plugs arranged in a suitable manner, ( jirsl rrDirion
).
60
B-1.8.2 In open type wiring, joint cut-outs B-2.4 Bunching of Circuits - Conductora, of
or fuse or fuse cut-outs shall not be inserted for opposite polarity or different phases shall not be
any purpose, but where joints are required for bunched in one groove in wood casing.
connecting bifurcating wires, junction boxes of
Nom - Length8 of conductors of the same polarity
wooden or-other insulating material with porcelain or phase, and free joints, may be buncbtd, if so
connectors inside shall be used. desired,
61
IS:732 -1989
B-2.9 Passing Through Floors - Where con- B-3. TOUGH RUBBER-SHEATHED OR PVC
ductors pass through floors, they shall be carried SHEATHED WIRING SYSTEM
in an approved heavy gauge con&it properly
bushed at both ends. The conduit shall be carried B-3.1 General - Wiring with tough rubber-
1.5 m above floor level and 2.5 cm below ceiling sheathed cables is suitable for low voltage installa-
level and neatly entered into the casing, which tions, and shall not be used in places exposed to
shall, if so required, be suitably protected at the sun and rain nor in damp places, unless wires are
floor level. The conduit pipe shall be securely sheathed in protective covering against atmosphere
earthed. and well protected to withstand dampness. Wiring
with PVC-sheathed cables is suitable for medium
B-2.10 Casing Round Mouldings or Decora- voltage installation and may be installed directly
tions - This shall be considered as special under exposed conditions of sun and rain or damp
decoration work and carried out in consultation places. This system of wiring is suitable in situa-
with the architect or the engineer-in-charge of tions where acids and alkalis are likely to be
construction work and with his approval. present. Where attack from whiteants (termite) is
prevalent, anti-termite treatment shall be-given.
B-2.11 Painting and Varnishing - All casing
and capping shall be given, before erection, inter- All sheathed cables on brick walls, stone or
nally and on the back, two coats of varnish plaster walls and ceilings, steel joists, or any
conforming to IS : 347;1975*. In addition all structural steel work shall be run on well-seasoned
casing together with capping after erection shall be and vasnished, straight teak wood battens finished
painted or varnished to the desired finish. not less than 10 mm thick and the width of which
*Specificationfor varnish, shellac for general purposes
is such as to suit total width of cables laid on the
( .,frd ralision ). batten. Prior to erection, these shall be painted
62
IS:732- 1989
with one coat of varnish or suitable paint match- B-3.8 Stripping of Outer Covering - While
ing with the surroundings. These battens shall be cutting and stripping of the outer covering of the
secured to the walls and ceilings by flat-head wood cables, care shall be taken that the sharp edge of
screws to wood plugs or other plugs at an interval the cutting instrument does not touch the rubber
not exceeding 75 cm; the flat-head wood screws or <PVC sheathed insulation of conductors. The
shall be countersunk within wood batten and protective outer covering of the cables shall be
smoothed down with file. stripped off near connecting terminals, and this
protective covering shall be maintained up to the
B-3.2 Link Clips - Link clips shall conform close proximity of connecting terminals as far as
to IS : 2412-1975*. Link clips shall be so arranged practicable. Care shall be taken to avoid hammer-
that one single clip shall not hold more than two ing on link clips with any metal instruments, after
twin-core TRS or PVC-sheathed cables up to the cables are laid. Where junction boxes are
l-5 mm* above which a single clip shall hold a provided, they shall be made moisture-proof with
single twin-core cable. The clips shall be fixed on an approved plastic compound.
varnished wood battens with any rust resisting pins
or screws and spaced at intervals of 10 cm in the B-3.9 Painting - If so required, the tough
case of horizontal runs and 15 cm in the case of rubber-sheathed wiring shall, after erection, be
vertical runs. For the wiring and runs of mains painted with one coat of oil-less paint or distemper
exposed to heat and rain, clips specially made for of suitable colour over a coat of oil-less primer,
outdoor use from a durable metal, resistant to and the PVC-sheathed wiring shall be painted
B-3.3.1 In cases where there are chances of B-4.1 General - Metal-sheathed wiring system is
any damage to the wirings, such wirings shall be suitable for IGWvoltage installations, and shall not
covered with sheet metal protective covering, the be ustd in situations where acids and alkalis are
base of which is made flush with the plaster or likely to be present. Metal-sheathed wiring may be
brickwork, as the case may be, or the wiring shall used in places exposed to sun and rain provided
be drawn through a conduit complying with all no joint of any description is exposed; this system
requirements of conduit wiring system ( see B-5 ). may be installed in damp places with approved
protection against dampness coming in contact
B-3.3.2 Such protective covering shall in all with open ends of cables.
cases be fitted on all downdrops within 1.5 m from
the floor. B-4.2 Link Clips - Link clips shall conform to
IS : 2412.1975* and shall be so arranged that one
B-3.4 Bends in Wiring - The wiring shall not single clip shall not hold more than two twin-core
in any circumstances be bent so as to form a right metal-sheathed cables up to 1.5 mms, above which
angle but shall be rounded off at the corners to a a single clip shall hold a single twin-core cable.
radius not less than six times the overall diameter The clips shall be fixed on varnished wood battens
of the cable. with brass pins or brass screws and placed at
B-3.5 Passing Through Floors - All cables intervals of 10 cm in the case of horizontal runs
taken through floors shall be enclosed in an and 15 cm in the case of vertical runs, For the
insulated heavy gauge steel conduit extending wiring and runs of mains exposed to heat and rain,
l-5 m above the floor and flush with the ceiling clips specially made for the outdoor use from a
below, or by means of any other approved type of durable metal, resistant to weather and atmos-
metallic covering. The ends of all conduits or pipes pheric corrosion, shall be used.
shall be neatly bushed with porcelain, wood or B-4.3 Attachment to Walls and Ceilings-All
other approved material. metal-sheathed cables on brick walls, stone walls
B-3.6 Passing Through Walls - The method or plastered walls and ceilings; steel joists or any
to be adopted shall be according to good practice. structural steel work shall be run on well-seasoned
There shall be one or more conduits of adequate and perfectly straight teak wood battens of not less
size to carry the conductors ( see Table 6 and than 10 mm finished thickness, which have been
Table 7 ). The conduits shall be neatly arranged well varnished on four sides. The width of teak
so that the cables enter them straight without wood. battens shall be such as to suit the total
bending. width of cableslaid on the batten. Prior to erection
B-3.7 Buried Cables - The tough rubber- these shall be painted with one coat of varnish
( see IS : 347-1975t) or suitable paint of colour to
sheathed cables shall not be buried directly in
match with the surroundings These battens shall be
plaster; where so specified, tbey may be taken in
secured to the walls and ceilings by flat-head wood
teak wood channelling of ample capacity or _
cement chase or conduit buried in the wall. *Specification for link clips for electrical wiring (brat
f&&m ).
*Specification for link clipi for electrical wiring ( jrst @pecification for varnish, shellac, for general purposps
rmisin ). (first reoision ) .
63
IS I 732 - 1989
screwsto wood plugs or other approved plugs at by means of any other approved type of metallic
an interval not exceeding 75 cm; the flat-head covering. The ends of all conduits or pipes shall be
wood screws shall be countersunk within wood neatly bushed with porcelain, wood or other
batten and smoothed down,with file. approved material.
B-4.4 Wiring on Rolled Steel Jojsts - Where B-4.9 Passing Through Walls - The method
wiring is ‘to be carried along the face of rolled to be adopted shall be in accordance with good
steel joists, a batten shall first be laid on the joists practice. There shall be one or more conduits of
and clipped to it as inconspicuously as possible. adequate size to carry the conductors (see Tables 6
The wiring shall be fixed to the batten in the and 7 ). The conduit(s) shall be neatly arranged so
ordinary way. that the cables enter them straight without bend-
ing.
Bi4.5 Protection of Wiring from Mechanical
B-4.10 Burried Cables - Metal sheathed cables
Damage
shall in no case be hurried directly in the plaster
B-4.5.1 In cases where there are chances of any or under any masonry work.
damage to the wiring, such wiring shall be covered B-4.11 Earthing - Precautions shall be taken to
with sheet metal protective covering, the base of ensure that all lead sheathing including portable
which is made flush with the plaster of brickwork, appliance with exposed metal parts, together with
as the case may be, or the wiring shall be drawn all joint-boxes and other similar receptacles are
through a steel conduit pipe by complying with all efficiently earthed and made electrically continu-
requirements of conduit system of wiring ous throughout their lengths by means of soldered
64
IS:732-1969
r l/l’80 7 - - - _ -
2’5 3 2 0 5 10 8 18 12 -
(I 3/1’06* I)
r l/2*24 1 4 7 - - - - -
4 3 2 3 8 12 10 -
1 7/0’85+ J)
2 - 5 4 8 7 - - - - I
10 - 4 - - -
2 3 6 5 8 6 -
16 711’70 - 2 - 4 3 7 6 - - - -
25 712’24 - - - - 3 2 5 4 8 6 9 7
35 7/2’50 - -_ - - 2 - 4 3 7 5 8 6
I 7/3*oot -l - - - - - -
50 - 2 - 5 4 6 5
‘I. 19/1’80 ]
NO’I’E 1 - The table shows the maximum capacity of conduits for the simultaneouly drawing
of cables. The columns headed S apply to runs of conduit which have distance not exceeding
4’25 m between drawn-in boxes, and which do not deflect from the straight by an angle of more
than 15O. The columns headed B apply to runs of conduit which deflect from the straight by an
angle of more than 15”.
NOTE 2 - In case an inspection type draw-in box has been provided and if the cable in first
drawn through one straight conduit, then through the draw-in box, and then through the second
straight conduit, such systems may be considered as that 01 a straight conduit even if the conduit
deflects through the straight by more than 15”.
B-5.1.3 Conduit Joints - Conduit pipes shall be tube, all outlets of conduit system shall be properly
joined by means of screwed couplers and screwed drained and ventilated, but in such a manner as
accessories only ( see IS : 2667-1976* ), In long to prevent the entry of insects as far as possible.
distances straight runs of conduit, inspection type B-5.1.5 Protection of Conduit Against Rust - The
couplers at reasonable intervals shall be provided outer surface of the conduit pipes, including all
or running threads with couplers and jam-nuts ( in bends, unions, tees, junction boxes, etc, forming
the latter case the bare threaded portion shall be
part of the conduit system shall be adequately
treated with anti-corrosive preservative ) shall be
protected against rust particularly when such
provided. Threaded on conduit pipes in all cases
system is exposed to weather. In all cases, no bare
shall be between 11 mm to 27 mm long sufficient
threaded portion of conduit pipe shall be allowed
to accommodate pipes to full threaded portion of
unless such bare threaded portion is treated with
couplers or accessories. Cut ends of conduit pipes anti-corrosive preservative or covered with suitable
shall have no sharp edges nor any burrs left to plastic compound.
avoid damage to the insulation of conductors while
pulling them through such pipes. B-5.1.6 Fixing of Conduit - Conduit pipes shall
be fixed by heavy gauge saddles, secured to suit-
B-5.1.4 Protection Against Dampwss - In order able wood plugs or other plugs with screws in an
to minimize condensation or sweating inside the approved manner at an interval of not more than
one metre, but on either side of couplers or bends
*Specificationfor fittings for rigid steel conduits for elec- or similar fittings, saddles shall be fixed at a
trical wiring ( JFrst r8ai.ri0a ) distance of 30 cm from the centre of such fittings.
65
ib t 732 --I989
B-5.1.7 Beno5 in Conduit - All necessary bends by bending the conduit pipe itself with a long
in the system including diversion shall be done by radius which will permit easy drawing-in of con-
bending pipes; or by inserting suitable solid or ductors. All threaded joints of rigid steel conduit
inspection type normal bends, elbows or similar shall be treated with preservative compound to
fittings; or fixing cast-iron inspection boxes which1 secure protection against rust.
ever is more suitable. Conduit fittings shall be
avoided as far as possible on conduit system B-5.2.3 Inspection Boxes - Suitable inspection
exposed to weather; where necessary, solid type boxes shall be provided to permit periodical
fittings shall be used. Radius of such bends in inspection and to facilitate removal of wires, if
conduit pipes shall not be less than 7.5 cm. No necessary. These shall be mounted flush with the
length of conduit shall have more than the equiva- wall. Suitable ventilating holes shall be provided
lent of four quarter bends from outlet to outlet, the in the inspection box covers. The minimum sizes
bends at the outlets not being counted. of inspection boxes shall be 75 mm x 75 mm.
B-5.1.8 Outlets-All outlets for fittings, switches, B-5.2.4 Types of Accessories to be Used - All
etc, shall be boxes of suitable metal or any other outlet, such as switches and wall sockets, may be
approved outlet boxes for either surface mounting either of flush mounting type or of surface mount-
or flush mounting system. ing type.
B-5.1.9 Conductors - All conductors used in
B-5.2.4.1 Flush mounting gpe - All flush
66
IS:732-1989
2’5 ( l/1*80) 3 5 10 14 - -
( 3/1’06e )
4 ( 112.24 ) 2 3 6 10 14 -
( 7/0’85+ )
6 ( 112’80 ) - 2 5 9 11 -
50 lY/%z
. - 2’ s
*For copper conductors only,
tFor aluminium conducton only.
B-5.3.3 Conduit Joints - Conduits shall be join- B-5.3.9 Heat may be used to soften the conduit
ed by means of screwed or plain couplers depend- for bending and forming joints in case of plain
ing on whether the conduits are screwed or plain. conduits. As the material softens when heated,
Where there are long runs of straight conduit, sitting of conduit in close proximity to hot surfaces
inspection type couplers shall be provided at should be avoided. Caution should be exercised in
intervals. For conduit fittings and accessories the use of this conduit in locations where the-
reference may be made to IS : 3419-19766. ambient temperature is 50’C or above. Use of imch
conduits in places where ambient temperature is
B-5.3.4 Fixing of Conduits -The provisions
60°C or above is prohibited.
, of B-5.1.6 shall apply except that the spa&g be-
tween saddles or supports is recommended to be
60 cm for rigid non-metallic conduits, B-5.3.10 Non-metallic conduit systems shall be
used only where it is ensured *t they are:
B-5.3.5 Bends in Conduits - Wherever necessary,
bends or diversions may be achieved by bending 4 suitable for the extremes of ambient tem-
the conduits (see B-5.3.9 ) or by employing normal perature to which they are likely to be
bends, inspection bends, inspection boxes, elbows subjected in service,
or similar fittings.
B-5.3.6 Conduit fittings shall be avoided, as far b) resistant to moisture and chemical atmos-
pheres, and
as possible, on outdoor systems.
4 resistant to low temperature and sunlight
B-5.3.7 Outlets - In order to minimize conden-
effects.
sation or sweating inside the conduit, all outlets of
conduit system shall be properly drained and
ventilated, but in such a manner as to prevent the For use underground, the material shall be
entry of insects. resistant to moisture and corrosive agents.
67
IS ‘: 732 - 1989
APPENDIX C
( Clauses11.7 and 12.3 )
C-O. GENERAL between the earth terminal of plug and the body
of current-consuming devices.
C-O.1 All equipment, fittings and accessories,
materials, em, selected for the, wiring installation
In industrial premises three phase and neutral
shall conform to the relevant Indian Standards socket-outlets shall be provided with a earth
wherever these exist.
terminal either of pin type or scrapping type in
C-l. CEILING ROSES AND SIMILAR addition to the main pins required for the
ATTACHMENTS purpose.
C-l.1 A ceiling rose or any other similar attach- C-2.6 In wirirg installations, metal clad switch,
ment shall not he used on a circuit, the voltage of socket-outlet and plugs shall be used for power
which normally exceeds 250 V. wiring.
~-2.2 Each socket-oulet shall also be controlled Nominal &oss- Number and Maximum
by a switch which shall preferably be located Sectional Area of Diameter in Permissible
immediately adjacent thereto or combined there- Twin Flexible mm of Wires Weight
witb. Cord
mms kg
C-2.3 The switch controlling the socket-outlet
shall be on the live side of the line. o*s 1610.2 2
o-75 2410.2 3
C-2.4 Ordinary socket-outlet may be fixed at any
convenient place at a height dove 20 cm from l*O 3210.2 5
the floor level and shall be away from danger of l-5 4810.2 5.3
mechanical injury. 80/o-2
2.5 a-8
NOTE- In situations where a socket-outlet is 4 128/o-2 14.0
accassible to children, it ia necessary to install an in-
terlocked plug and socket or alternatively a socket-
outlet which automatically gets screened by the with- C-3.3 No flammable shade shall form a part of
drawal of plug. In industrial premises socket-outlet of lighting fittings unless such shade is well protected
rating 20A and above shall preferably be provided against all riska of fire. Celluloid shade or lighting
with interlocked type switch.
fitting shall not be used under any circumstances.
C-2.5 In an earthed system of supply, a socket-
outlet with plug shall be of three-pin type with C-4. FITTING-WIRE
the third terminal connected to the earth. When
such socket-outlets with plugs are connected to C-4.1 The use of fittings-wire shall be restricted
any current consuming device of metal or any to the internal wiring of the lighting fittings.
non-insulating material or both, conductors Where fittings-wire is used for wiring fittings, the
connecting such current-consuming devices shall sub-circuit loads shall terminate in a ceiling rose
be of flexible cord with an earthing core and the or box with connectors from which they shall be
earthing core shall be secured by connecting carried into the fittings.
-_._ _., .,_^ I_ “^_- -
18 t 732.1989
69
ISt732.1999
hole shall be neatly plastered with cement and The size of such boards shall depend on the
brought to the original finish of the wall. The number of accessories that could conveniently
nhaust fan shall be connected to exhaust fan and neatly be arranged. Where there is danger of
point which shall be wired as near to the hole as attack by termite, the boards shall be treated wit6
possible by means of a flexible cord, care being suitable anti-termite compound and painted on
taken that the blades rotate in the proper direc- both sides.
tion.
C-10. INTERCHANGEABXLITY
C-9. ATTACHMENT OF FITTINGS AND
ACCESSORIES C-10.1 Similar part of all switches, lampholders,
distribution fuse-boards, ceiling roses, brackets,
C-9.1 In wiring other than conduit wiring, all pendants, fans and all other fittings shall be so
ceiling roses, brackets, pendants and accessories chosen that they are of the same type and inter-
attached to walls or ceilings shall be mounted on changeable in each installation.
substantial teak wood blocks twice varnished after
all fixing holes are made in them. Blo&s shall C-11. EQUIPMENT
not be less than 4 cm deep. Brass screivs shall
only be used for attaching fittings and accessories
C-11.1 Electrical equipment which form integral
APPENDIX D
( Cluws 11.7)
SPECIFIC GUIDANCE ON SELECTION OF EQUIPMENT WITH REGARD TO
EXTERNAL INFLUENCES
70
IS : 732 - 1989
A EnvironmentaI conditions
AA Ambient lemperaiure
AA1 - 60°C to + 5% Specially designed equipment or appropriate
AA2 - 40°C to + 5OC arrangements*
AA3 - 25°C to -l- 5°C
AA4 - 5°C to + 40°C Normal ( in certain cases special precautions
may be necessary )
AA5 + 5OC to + 40°C Normal
AA6 + 5°C to + 60°C Specially designed equipment or appropriate
arrangements*
( Continued )
71
IS:732 - 1989
72
I8 : 732.1989
*Classification of electrical and electronic equipment with regard to protection against electric shock.
( Continuri )
73
-__
APPENDIX E
( Itern 12.2.1 )
CHECKLIST OF INITIAL INSPECTION
74
.
-
IS :732 - 1989
8) 11cable trenches are provided with non- 29) Connections to gas relay in transformers
i flammable covers;
A, are in order;
9) Free accessibility is provided for all equip- 30) Oil and winding temperature are set for
ments for normal operation; specific requirements in transformers;
10) All name plates are fixed and the equip- 31) In case of cable cellars, adequate arrange-
ments are fully painted; ments to pump out water that hasentered
due to seepage or other reason; and
11) All construction materials and temporary
connections are removed; 32) All incoming and outgoing circuits of HT
and LT panels are clearly and indelibly
12) Oil-levels, busbar tightness, transformer
top position, etc, are in order; labelled for identifications.
13) Adequate precautions are taken to ensure 3) The plug points in the lighting circuit are
that no live parts are so exposed as to cause all of 3-pin type, the third pin being
danger; suitably earthed;
14) Ammeters and voltmeters are tested; and 4) Tiampe.r-proof interlocked switch socket and
p!ug are used for locations easily accessible;
15) The relays are inspected visually by moving
covers for deposits of dust or other foreign 5) Lighting wiring in factory area is taken
matter. enclosed in conduit and conduit properly
earthed, or alternatively, armoured cable
E-1.1.3 Overhead Lines - For overhead lines it wiring is used;
shall be checked whether:
6) A separate earth wire is run in the lighting
1) All conductors and apparatus including live installation to provide earth@g for plug
parts thereof are inaccessible; points, fixtures and equipments;
2) The types and size of supports are suitable
7) Proper connectors and junction bores are
for the overhead lines/conductors used and used wherever joints are to be made in
are in accordance with approved drawing conductors or cross over of conductors takes
7) Stays are provided suitably on the overhead 12) The ends of conduits enclosing the wiring
lines as required and are efficiently earthed leads are provided with ebonite or other
or provided with suitable stay insulators of suitable bushes;
suitable voltages; 13) The fittings and fixtures used for outdoor
use are all of weatherproof construction,
8) Anti-climbing devices and Danger Board/ and similarly, fixtures, fittings and switch-
Caution Board/Notices are provided on all
HT supports; gears used in the hazardous area are of
flame-proof application;
9) Clearances along the route are checked and
all obstructions such as trees/branches and 14) Proper terminal connectors are used for
shrubs are cleared on the route to the termination of wires ( conductors and earth
leads ) and all strands are inserted in the
required distance on either side;
terminals;
10) Clearance between the live conductor and
the earthed metal parts are adequate; and 15) Flat ended screws are used for fixing con-
ductor to the accessories; and
11) For the service connections tapped-off from
the overhead lines, cut-outs of adequate 16) Use of flat washers backed up by spring
capacity are provided. washers for making end connections ia
desirable.
76
c_ ___ _^_ ... -. -.
I8 : 732 - 19119
77
IS t 732-1989
resistance the working voltage shall be Such a test shall be made after removing
deemed to be that which is maintained all metallic connections between the two
between the outer or phase conductor and poles of the installation and in these
the neutral. circumstances the insulation resistance be-
The insulation resistance in megohms of an tween conductors of the installation shall
b) be not less than that specified in (b).
installation measured as in (a) shall not be
less than 50 divided by the number of
points on the circuit, provided that the On completion of an electrical installation ( or
whole installation need not be required to an extension to an installation ) a certificate shall
have an insulation resistance greater than be furnished by the contractor, countersigned by
one megohm. the certified supervisor under whose direct super-
vision the installation was carried out. This
4 Control rheostats, heating and power appli- certificate shall be in a prescribed form as required
ances and electric signs, may, if desired, be by the local electric supply authority.
disconnected from the circuit during the
test, but in that event the insulation resis- E-2.1.6 Earthing - For checking the efficiency
tance between the case or framework, and of earthing the following tests are done:
all live parts of each rheostat, appliance
and sign shall be not less than that specified a) The earth resistance of each electrode shall
in the relevant Indian Standard Specifica- be measured.
78