DIRIS A-30
Strong points
Functions
Multi-measurement • Kfactor • Individual harmonics up to 63rd Communications (1)
• Currents • Temperatures (1) - Currents: HI1, HI2, HI3, HIn • RS485 (Modbus)
- instantaneous: I1, I2, I3, In, Isystem - internal - Phase-to-neutral voltage: • Ethernet
- average/max average: I1, I2, I3, In - external via 3 PT100 probes HV1, HV2, HV3, (Modbus/TCP or Modbus RTU)
• Voltages & frequency Metering - Phase-to-phase voltages: • Ethernet with RS485 Modbus RTU
- instantaneous: V1, V2, V3, U12, HU12, HU23, HU31 gateway over TCP
• Active energy: +/- kWh
U23, U31, F, Vsystem, Usystem Load curve (1) • Profibus DP Sub-D9
• Reactive energy: +/- kvarh
- average/max average: V1, V2, V3, • Effective power: kVAh • Active & reactive power: Inputs/ Outputs(1)
U12, U23, U31, F ΣP+/- ; ΣQ+/- • Pulse counting
• Hours:
• Powers • Voltages & frequency: V1, V2, V3, • Checking / control of equipment
Harmonic analysis U12, U23, U31, F
- instantaneous: 3P, ΣP, 3Q, ΣQ, • Alarm report
• Level of harmonic distortion
3S, ΣS Events (1) • Pulse report
- Currents: thd I1, thd I2, thd I3, thd In
- max average: ΣP, ΣQ, ΣS • Alarms on all electrical parameters. Analogue output
- Phase-to-neutral voltage: thd V1, thd
- predictive: (ΣP), (ΣQ), (ΣS) • Analogue 0/4- 20 mA
V2, thd V3
• Power factors (1) A
vailable as an option
Phase-to-phase voltage: thd U12, thd
- instantaneous: 3PF, ΣPF U23, thd U31 (see following pages).
- average/max average: ΣPF
Front panel
1. Backlit LCD display
2. Pushbutton for currents and for connection correction function
3. Pushbutton for voltages and frequency..
4. Pushbutton for active, reactive and effective powers and for power factor.
5. Pushbutton for maximum and average values for currents and power levels.
6. Pushbutton for harmonics.
7. Pushbutton for electrical energy meters, timers and impulse counters
diris_984x_b_1_cat
1 2 3 4 5 6 7
Plug-in modules
Pulse outputs
diris_445_a_1_cat
DIRIS® A-30
MODBUS® communication
diris_447_a_1_cat
PROFIBUS® DP communication
SUB-D9 link with PROFIBUS® DP protocol (speed up to 12 Mbaud).
Analogue outputs
You can connect a maximum of 2 modules, i.e. 4 analogue outputs.
diris_448_a_1_cat
2 inputs - 2 outputs
DIRIS® A-41*
You can connect a maximum of 3 modules, i.e. 6 inputs / 6 outputs.
2 outputs can be allocated to:
diris_449_a_1_cat
- monitoring: 3I, In, 3V, 3U, F, ±ΣP, ±ΣQ, ΣS, ΣPFL/C, THD 3I, THD In, THD 3V, THD
3U, Ppred, Qpred, Spred, T°C internal, T°C 1, T°C2, T°C3 and of time counter,
- remote control,
- timed remote control,
- 2 inputs for pulse counting.
diris_774_a
diris_682_a_1_cat
Storage capability
• M emory function up to max. 62 days for P+, P-, Q+, Q- with a TOP for internal or
external synchronisation of 5, 8, 10, 15, 20, 30 and 60 minutes.
• Memory function for the last 10 timed and dated alarms.
* With current measurement module for Neutral • Memory function for the last min and max instantaneous values for 3U, 3V, 3I, In,
as standard. F, ΣP±, ΣQ±, ΣS, THD 3U, THD 3V, THD, 3U, THD, 3V, THD, 3I, THD In.
• Memory function of average values 3U, 3V et F as a function of synchronisation
(maximum 60 days).
diris_777_a_1_cat
Ethernet communication
• Ethernet link with MODBUS/TCP or MODBUS RTU over TCP.
diris_776_a_1_cat
Accessories
Current transformer IP65 protection
See “Current transformers” pages.
trafo_077_b_2_cat
trafo_024_a_2_cat
diris_720_a_2_cat
Terminals
DIRIS A-30
S1 - S2 : current inputs
diris_569_a_1_x_cat
V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2
AUX : auxiliary power supplies Us
I1 I2 I3 V1- V2 - V3 - VN : voltage inputs
DIRIS A-30
DIRIS A-41
S1 - S2 : current inputs
diris_570_a_1_x_cat
V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2 S1 S2
AUX: auxiliary power supplies Us
I1 I2 I3 IN
V1 - V2 - V3 - VN : voltage inputs
DIRIS A-41
diris_572_a_1_x_cat
1 2 3 4 5 6 7 8
diris_573_a_1_x_cat
0V - + 1
0n + - + -
RS485 R = 120 0/4-20 mA 0/4-20 mA
OUT 1 OUT 2 OUT 1 OUT 2
DIRIS A-30 / A-41 DIRIS A-30 / A-41 DIRIS A-30 / A-41
RS485 link. 1 - 2 : pulse output n°1. 5 - 6 : analogue output n°1.
R = 120 Ω : internal resistance for the RS485 link. 3 - 4 : relay output n°2. 7 - 8 : analogue output n°2.
diris_753_a_1_en_cat
19 20 21 22 23 24 25 26
9 10 11 12 17 18
sensor 1 sensor 2
OUT 1 OUT 2 + -
IN
diris_574_b_1_x_cat
A-Cd A-Cd
synchro 27 28 29 30
DIRIS A-30 / A-41 sensor 3
1 3 14 15 16
- + - + DIRIS A-30 / A-41
IN 1 IN 2 17 - 18 : synchronisation input. Probe 1 Probe 2 Probe 3
DIRIS A-30 / A-41 19 : red 23 : red 27: red
9 - 10 : relay output n°1. 20 : red 24 : red 28 : red
11 - 12 : relay output n°2. 21 : white 25 : white 29 : white
13 - 14 : optical input n°1. 22 : white 26 : white 30 : white
15 - 16 : optical input n°2.
10 BASE T 10 BASE T 0V - + 1
100 BASE T 100 BASE T 0n
RS485
RJ45 RJ45 gateway R = 120Ω
DIRIS A-30 / A-41 DIRIS A-30 / A-41
Electrical characteristics
Measurement of currents on insulated inputs (TRMS) Module 2 inputs - 2 outputs: outputs (alarms / control)
Via CT primary 9,999 A Number of relays 2(1)
Via CT secondary 1 or 5 A Type 250 VAC - 5 A - 1150 VA
Measurement range 0 … 11 kA Module 2 inputs - 2 outputs: optical coupler inputs
Input consumption ≤ 0,1 VA Number 2(1)
Measurement updating period 1s Power supply 10 … 30 VDC
Accuracy 0.2% Minimum width of signal 10 ms
Permanent overload 6A Minimum length between 2 pulses 18 ms
Intermittent overload 10 In for 1 s Type Optical couplers
Voltage measurements (TRMS) Pulse output module
Direct measurement between phases 50 to 1039 VAC Number of relays 2
Direct measurement between phase and neutral 28 to 600 VAC Type 100 VDC - 0.5 A - 10 VA
VT primary measurement 500,000 VAC Max. number of manoeuvres ≤ 108
VT secondary measurement 60, 100, 110, 173, 190 VAC Analogue output module
Frequency 50 / 60 Hz Number of outputs 2(2)
Input consumption ≤ 0,1 VA Type Insulated
Measurement updating period 1s Scale 0 / 4 … 20 mA
Accuracy 0.2% Load resistance 600 Ω
Current - voltage product Maximum current 30 mA
Limitation for TC 1 A 10,000,000 MODBUS communication module
Limitation for TC 5 A 10,000,000 Link RS485
Power measurement Type 2 to 3 half duplex wires
Measurement updating period 1s Protocol MODBUS® RTU
Accuracy 0.5% MODBUS® speed 4800 to 38400 baud
Power factor measurement PROFIBUS DP communication module
Measurement updating period 1s Link SUB-D9
Accuracy 0.5% Protocol PROFIBUS® DP
Frequency measurement PROFIBUS® speed 9.8 kbaud … 12 Mbaud
Measurement range 45 … 65 Hz Ethernet communication module
Measurement updating period 1s Connection technology RJ45
Accuracy 0.1% Baud rate 10 base T / 100 base T
Energy accuracy Protocol MODBUS TCP or MODBUS RTU on TCP
Active (according to IEC 62053-22) Class 0.5 S Temperature module (inputs)
Reactive (according to IEC 62053-23) Class 2 Type PT100
Auxiliary power supply Connection 2, 3 or 4 wires
Alternative voltage 110 …400 VAC Dynamic - 20°C ... 150°C
AC tolerance ± 10 % Accuracy ± 1 digit
Direct current 120 … 350 VDC / 12 … 48 VDC Maximum length 300 cm
DC tolerance ± 20 % / - 6 … + 20 % Operating conditions
Frequency 50 / 60 Hz Operating temperature range -10 to +55°C
Power consumption ≤ 10 VA
Storage temperature -20 to 85°C
Relative humidity 95%
(1) Max. 3 modules / DIRIS.
(2) Max. 2 modules / DIRIS.
Case
+ 0.8
92 - 0.0
35
45
15
96
Connections
Balanced low-voltage network for DIRIS A-30
Recommendation: When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried
out automatically by a SOCOMEC PTI, which can be found in the SOCOMEC catalogue: please consult us.
In TNC mode, it is advisable to connect the DIRIS A-30/A-41 to earth using the functional earth module.
3/4 wires with 1 CT Single-phase Two-phase
N P1 P1 L1
P1 L1
L1 S1 S2 S1 S2 L2
S1 S2 N
L2
L3
1 1 1
diris_392_d_1_x_cat
1 1 1
diris_393_e_1_x_cat
diris_394_d_1_x_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3
The use of 1 TC reduces by 0.5% the accuracy of the phases, 1. 0.5 A gG / 0.5 A class CC fuses. 1. 0.5 A gG / 0.5 A class CC fuses.
the current for which is worked out by vector calculation.
1. 0.5 A gG / 0.5 A class CC fuses.
diris_396_d_1_x_cat
diris_397_d_1_x_cat
1 1 1 1 1 1
1 1 1
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2
I1 I2 I3 I1 I2 I3 I1 I2 I3
1. 0.5 A gG / 0.5 A class CC fuses. The use of 2 TC reduces by 0.5% the accuracy of the phase, The use of 2 TC reduces by 0.5% the accuracy of the phase,
the current for which is worked out by vector calculation. the current for which is worked out by vector calculation.
1. 0.5 A gG / 0.5 A class CC fuses. 1. 0.5 A gG / 0.5 A class CC fuses.
1 1 1
diris_575_b_1_x_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 IN
1. 0.5 A gG / 0.5 A class CC fuses.
Additional information
Communication via RS485 link Connection of potential transformer for HV AC and DC auxiliary power supply
networks
110 / 400 VAC
L1 120 / 350 VDC
L2
L3
1 1
LIYCY-CY
diris_399_b_1_x_cat
diris_398_c_1_x_cat
A U X
diris_400_i_1_x_cat
0V - +
ON V1 V2 V3 N
RS485
1. 0.5 A gG / 0.5 A class CC fuses.
References
DIRIS A-41
Basic device DIRIS A-30
With CT on the neutral
Auxiliary power supply Us Reference Reference
110 ... 400 VAC / 120 ... 350 VDC 4825 0403 4825 0404
12 ... 48 VDC 4825 0405 4825 0406
Options
Plug-in modules(1) Reference Reference
Pulse outputs 4825 0090 4825 0090
RS485 MODBUS® communication 4825 0092 4825 0092
PROFIBUS® DP communication 4825 0205 4825 0205
Analogue outputs 4825 0093 4825 0093
2 inputs - 2 outputs 4825 0094 4825 0094
Storage capability 4825 0097 4825 0097
Ethernet communication(2) 4825 0203 4825 0203
Ethernet communication + RS485 gateway(2) 4825 0204 4825 0204
Temperature inputs. 4825 0206 4825 0206
(1) Ease of integration of additional functions (maximum 4 slots on A-30 and 3 on A-41).
(2) Dimensions: 2 slots.
To be ordered To be ordered
Accessories Reference Reference
in multiples of in multiples of
IP65 protection. 1 4825 0089 1 4825 0089
Integration kit for 144 x 96 mm cutout 1 4825 0088 1 4825 0088
Fuse holders to protect voltage inputs (type RM) 3 pole 4 5701 0018 4 5701 0018
Fuse holders to protect the auxiliary power supply (type RM) 1 pole + neutral 6 5701 0017 6 5701 0017
gG 10x38 0.5 A fuses 10 6012 0000 10 6012 0000
See “Current See “Current
Range of current transformers 1 1
transformers” pages transformers” pages
Ferrite for use with communication modules 1 4899 0011 4899 0011
PT100 temperature probe, M6 screw 1 4825 0208 1 4825 0208
PT100 temperature probe, M6 lug 1 4825 0209 1 4825 0209