DP2 BUILDINGS
The Buildings are RCC framed structure with Column, Beam, Slab construction using
M25/35 Grade Design Mix Concrete. For shear wall, Self compacting Concrete (as per IS
10262-2019 ) of design Mix M35 grade Concrete.
CPWD specifications shall be followed as per latest specifications and up-to-date
correction slips for all works execution unless noted otherwise.
Wherever not mentioned Item should be as per DSR 2018 & Specification of CPWD
(Latest with up to date correction slips) should be followed.
Contractor is liable to complete the building as per drawing & specification & make it
functional as per requirement & direction of Engineer-in-charge.
Shop drawings submitted by the contractor have to be approved for their design,
functionality and structural stability by concerned consultants appointed by IIT
Bhilai.So contractor should submit shop drawing well in advance so that work progress
doesn’t suffer.
Any minor changes (addition, omission and alteration) if required as per site condition
and as per IIT Bhilai requirement shall be done as per direction Engineer-in-charge;
nothing extra shall be paid against on this account.
Note: Floor height means from bottom of DPC to Top of slab in Level 1 and from top slab
to top of the slab above in upper Levels as per CPWD norms.
All necessary structural arrangements shall be provided at terrace to receive the solar
panels/ Fire Fighting/ water supply and other equipment’s as per requirement and as
per direction of Engineer-in-charge.
All material like Paints/ adhesives/ finishes, etc. shall be of low VOC meeting GRIHA
requirements.
All Concrete (PCC, RCC etc.) works shall be done with OPC 43 grade cement and
for all other works, PPC cement shall be used.
For all aluminium works, GRC works, dry stone cladding works, light-weight roofing
with MS sheeting or poly carbonate / multi-cell polycarbonate sheeting works, etc.,
wherever there are structural support system embedded within or exposed, the shop
drawings submitted by the contractor shall be duly vetted (structural) for their
structural stability and approved by concerned Consultant appointed by IIT Bhilai.
For all finishing works; especially - flooring, wall finishes (including exposed RCC, stone
cladding, etc.), fittings and fixtures, especially - hardware (for doors, windows, glazing,
aluminum works, all cupboards & cabinets), plumbing and sanitary CP fittings &
fixtures, lighting, etc. the contractor shall submit necessary sample board and prepare
necessary site mock-ups as per the direction of the Engineer-in-charge. Execution shall
be done only as per approved samples and mock-up approved by Engineer-in-charge.
For Mess Block all MEP work related to Kitchen and ancillary areas shall be done such
as to incorporate the functional requirements of the kitchen operations.
Detailed specifications:
A. Foundation:
Earthwork in excavation in foundation and trenches/ over areas for desired level as per
structural drawing for all kinds of soil and rock (if found) shall be as per CPWD
Specifications. Any deviation in earthwork in excavation as per site condition will be
ignored and nothing shall be paid extra. Top soil up to 300mm shall be preserved at site
premises (protected against erosion during rain) and reuse in future landscaping
development as per CPWD specifications and direction of Engineer-in-charge.
Filling with available excavated earth in sides of foundation & under floors shall be done
if soil found suitable. Otherwise filling shall be done by bringing Moorum of approved
quality and nothing extra shall be paid towards the same. Moorum of approved quality
shall be filled up to bottom of sand filling below flooring. Moorum filling may also be
done up to 3.00m from edge of building all-round the building up to proposed ground
level. Filling withavailable earthwork to be done as per CPWD specifications.
Excavation shall be undertaken to the width of the Basement / Retaining wall footing
including necessary margins for construction operation as per drawing or directed
otherwise. Where the nature of soil or the depth of the trench and season of the year, do
not permit vertical sides, the contractor at his own expense shall put up the necessary
shoring, strutting and planking or cut slopes with or without steps, to a safer angle or
both with due regard to the safety of personnel and works and to the satisfaction of the
Engineer. Nothing shall be paid extra
The rates are inclusive for all depths & nothing extra shall be paid for additional lift etc.
Filling with available excavated earth in sides of foundations & under floors shall be
done only if earth found suitable, otherwise filling shall be done by bringing Moorum of
approved quality from outside and nothing extra shall be paid towards the same.
Moorum of approved quality and quantity shall be filled from Natural ground level to
Proposed Made up ground level as per GFC drawing outside allround the building along
the perimeter to an extent of 3 m from building outer face. Outer area murrom filling is
included in scope of contractor for every building.
Landscape area
All Cutting and Filling of Earth coming to maintain the required finished level of
complete Landscape area as mentioned in the landscaping/building drawing is in the
scope of contractor. All filling should be done with available excavated earth and as per
CPWD specifications and if the earth is not available, the same of approved quality to be
Sand filling:
150mm thick (compacted) sand filling shall be provided over well compacted earth
/moorum of approved quality above which compacted 100mm thick PCC of mix 1:4:8
shall be provided. PCC of mix 1:4:8 (1 cement: 4 coarse sand: 8 20mm nominal size
aggregate) shall be provided below foundations/ footings, rafts, grade beams, plinth
beams, floors, grade slab, etc. with a minimum thickness of 100mm.
Foundation shall be with RCC isolated/ stripped/ combined, Raft type footings as per
approved structural drawings using the grade of concrete M25 Design mix. Minimum
cement content shall be 330kg/ cumand work shall be executed as per approved design
mix, no extra payment to be made if excess cement to be used for design mix. The
minimum footing depth below natural ground level shall be followed as per approved
structural drawings. The depth of footing is variable as per site condition. Columns are
connected by grade beams (external) and / plinth beams (Internal) below ground level
as per structural drawing and shall be of grade M35 Design mix, wherever necessary
additional tie beams shall be provided in between grade beams/ plinth beams and top
of footing based on the depth of footing. 100mm thick Grade slab / floating slab of RCC
grade M25 Design mix shall be provided with nominal reinforcement steel 8mm dia @
200mm c/c both ways. To maintain the Cover to reinforcement in structural members,
approved manufacture’s factory made cover blocks of required size for footings,
columns, beams, slabs mentioned in structural drawings shall be provided and Cover
block concrete grade not lesser than the grade of concrete shall be provided in
structural members.
a) Along external wall where the apron is not provided using chemical emulsion @ 7.5
litres / sqm. of the vertical surface of the substructure to a depth of 300 mm including
excavation channel along the wall & rodding etc. complete with Bayer Premise.
b) Treatment of soil under floors above sand filling using chemical emulsion by flooding
@ 15 litres per sqm
c)Along the expansion joints, surrounding of pipes & fittings and conduits @ 20litre per
building.
Plinth Protection:
The Plinth protection and ramp should be executed as per related Landscape
drawings only. If the same has been shown in Architectural drawing then
Landscape drawings will supersede.
B. Superstructure:
Reinforced cement concrete/ PCC:
RCC Columns, Shear walls, Beams including plinth beams /tie beams slabs etc. shall be
as per structural drawing (duly checked with relevant architectural drawings) with
concrete grade of M35 Design mix shall be used. For shear wall, Self compacting
Concrete (as per IS 10262-2019 ) of design Mix M35 grade Concrete. Minimum cement
content shall be 350kg/ cum and work shall be executed as per approved design mix, no
extra payment to be made if excess cement to be used for design mix. All
superstructures RCC shall be Form finished/ Fair faced concrete. Superstructure form
work shall be with 12 mm thick BWP grade film faced plywood of CSFF designation
confirming to IS: 4990 for form finished/ fair faced concrete surface / Aluminium
formwork duly designed for the work and as per Structural and Architectural drawing
and as per acceptance criteria where ever required .Form work shall be designed for
structural stability and safety by the contractor and contractor will be sole responsible
for any mishap happens during execution of work. The shuttering shall be repeated
after due cleaning and inspection by the authorized representative of Engineer-in-
charge.
Self compacting concrete (SCC) is highly flowable, non-segregating concrete that fills
uniformly and completely every corner of formwork by its own weight and encapsulate
reinforcement without any vibration whilst maintaining homogeneity.
a) Application Area
Self compacting concrete (SCC) may be used in precast concrete applications or for
concrete placed on site. SCC is used to cast sections with highly congested
reinforcement and in areas that present restricted access to placement and
consolidation and the casting of hybrid concrete- filled steel tubular columns. It may be
manufactured in a site batching plant or in a ready-mixed concrete plant and delivered
to site by truck mixer. It may be placed either by pumping or pouring into horizontal or
vertical forms.
b) Passing ability,
d) Viscosity
The above tests shall be carried out as per IS 1199 (Part 6).
This is the ability of fresh concrete to flow into and fill all spaces within the formwork,
under its own weight. Slump-flow test is performed to test the flowability. Slump-flow
value describes the flowablity of a fresh mix in unconfined condition. Visual observation
during the test can provide additional information on the segregation resistance and
uniformity.
a) SF1 (slump flow 550 mm - 650 mm). This class of SCC is appropriate for:
1) Unreinforced or lightly reinforced concrete structures that are cast from the
top with free displacement from the delivery point (For example, housing slabs).
3) Sections that are small enough to prevent long horizontal flow (for
example,piles and some deep foundations).
b) SF2 (slump flow 660 mm - 750 mm) is suitable for normal applications (for
example, walls, columns).
c) SF3 (slump flow 760 mm-850 mm) is used for vertical applications in heavily
reinforced structures, structures with complex shapes, or for filling under
formwork. SF3 will often give better surface finish than SF2 for normal vertical
applications but segregation resistance is more difficult to control.
Passing ability describes the capacity of the fresh mix to flow through confined spaces
and narrow openings such as areas of congested reinforcement without segregation. If
there is little or no reinforcement, there may be no need to specify passing ability as a
requirement. L-box test is preformed to check the passing ability. The minimum ratio of
the depth of the concrete in the horizontal section relative to the depth of concrete
vertical section is considered to be 0.8. If the SCC flows as freely as water, it will be
completely horizontal, and the ratio will be equal to 1.0.
This is the ability of fresh concrete to remain homogeneous in composition while in its
fresh state. Segregation resistance (Sieve) test is preformed to check this property of
fresh concrete.
After sampling, the fresh concrete is allowed to stand for 15 min and any separation of
bleed water is noted. The top part of the sample is then poured into a sieve with 4.75
mm square apertures. After 2 min, the weight of material which has passed through the
sieve is recorded. The segregation ratio (SR) is then calculated as the proportion of the
sample passing through the sieve.
There are two classes of segregation resistance, namely SR1 and SR2. SR1 is generally
applicable for thin slabs and for vertical applications with a flow distance of less than 5
m and a confinement gap greater than 80 mm. SR2 is preferred in vertical applications if
the flow distance is more than 5 m with a confinement gap greater than 80 mm in order
to take care of segregation during flow. For SR1 class segregation resistance shall be 15
to 20 percent and for SR2 it shall be less than 15 percent. SR2 may also be used for tall
vertical applications with a confinement gap of less than 80mm if the flow distance is
less than 5 m, but if the flow is more than 5 m, a target SR value of less than 10 percent
is recommended. Segregation resistance becomes an important parameter with higher
slump-flow classes and/or the lower viscosity classes, or if placing conditions promotes
4 .Viscosity
Viscosity can be assessed by the V-funnel flow time as per IS 1199 (Part 6). Concrete
with a low viscosity will have a very quick initial flow and then stop. Concrete with a
high viscosity may continue to creep forward over an extended time.
A V-shaped funnel is filled with fresh concrete and the time taken for the concrete to
flow out of the funnel is measured and recorded as the V-funnel flow time. The viscosity
is divided into two classes, that is, V1 and V2. V1 has good filling ability even with
congested reinforcement. It is capable of self-leveling and generally has the best surface
finish. V2 class viscosity is more likely to exhibit thixotropic effects, which may be
helpful in limiting the formwork pressure or improving segregation resistance. But it
may cause negative effects on surface finish and sensitivity to stoppages or delays
between successive lifts.
For V1 class, the time taken to pass the concrete from V-funnel shall be ≤ 8 s and for V2
class the time taken to pass the concrete from V-funnel shall be between 8 s and 25 s.
The forms shall be constructed so as to produce a uniform and consistent texture and
pattern on the face of the concrete. The formwork shall be placed so that all horizontals
are constructed of lumber and are not panelled and the formwork joints shall be
staggered.
To achieve a finish which shall be free of board marks, the formwork shall be faced with
plywood or equivalent material in large sheets. Whenever possible, joints between
sheets shall be arranged to coincide with architectural feature, sills, window heads or
change in direction of surface. All joints between panels shall be vertical or horizontal
unless otherwise directed. Suitable joints shall be provided between sheets. The joints
shall be arranged and fitted so that no blemish or mark is imparted to the finished
surfaces.
Forms for exposed concrete surfaces shall be constructed with grade strips (the
underside of which indicate top of pour) at horizontal constructions joints, unless the
use of groove strips is specified on the drawings. The reset forms shall be tightened
against the concrete so that the forms will not be spread and permit abrupt
For fair faced concrete, the position of through bolts will be restricted and generally as
indicated on the drawings.
Plywood and steel plates/ Aluminium sheetsused in the formwork for obtaining
exposed surfaces shall be got inspected by his authorized representativeEngineer-in-
charge on each use. However no forms will be allowed for reuse if it is doubtful to
produce desired texture of exposed concrete.
Cement of only approved shade shall be used preferably of single lot to achieve integrity
of texture.
The finish shall be uniform, dense and smooth. No grout, no grain pattern, no crazing
and no major blemishes shall be permitted. Abrupt irregularities not exceeding 3mm
and gradual irregularities less than 5mm in 2m length only shall be permitted.
For Columns/Wall/Fins:
The finish shall be uniform and smooth levelling the surface of the compacted concrete
shall be done with a screed board with power floating the surface and over that steel
trowelling the surface under firm pressure characteristics of finish shall be brush marks
< 3mm gradual irregularities less than 5mm in 2m.
The formwork shall be so made as to produce a finished concrete true to shape, lines,
level, plumb and dimensions as shown in the drawings subject to the following
tolerance unless otherwise specified in this specification or drawings.
WALL/COLUMN/FINS:
Variation from the level or from the specified grid for beam soffit before removal of
shores,
All the tolerances mentioned above shall apply to concrete dimensions only, and not to
positioning of vertical steel or dowels. The tolerances given above are specified for local
aberration in the finished concrete surface and should not be taken as tolerance for the
entire structure taken as whole for the setting and alignment of formwork. Any error,
within the above tolerance limits, or any other if noticed in any of the structure after
part or portion stripping of forms, shall be corrected in the subsequent work to bring
back the structure to its true line, level and alignment.
All shuttering brought at site should be new/fresh when used for the first time and
should not be allowed more than permissible repetition or quality of surface of
shuttering become uneven which ever is earlier
Dented, broken, cracked, twisted or rusted shuttering plates shall not be allowed to be
used on the work and Props of steel shall be provided with adequate horizontal
and cross - bracing. Steel props shall use steel pipes and steel couplers.
Form work including centering, shuttering, propping, staging shall be strong enough
to withstand the dead and live loads and forces caused by ramming and vibrations
of concrete and other incidental loads, imposed upon it during and after casting of
concrete. It shall be made sufficiently rigid by using adequate number of ties and
braces, screw jacks or hard board wedges where required shall be provided to make up
any settlement in the form work either before or during the placing of concrete.Form
work shall be properly designed for self- weight, weight of reinforcement, weight of
fresh concrete, and in addition, the various live loads likely to be imposed during the
construction process (such as workmen, materials and equipment). In case the height
of centering exceeds 3.50 meters, the prop may be provided in multi-stages.It is
important to note here that Designing of formwork/shuttering as per CPWD
specifications/relevant IS codes for RCC work i.e column/wall/beam/slab at all heights
and level as shown in GFC drawing is the responsibility of contractor and if any
mishap happens during execution of RCC work due to design/workmanship fault
etc, then it will be the sole responsibility of Contractor.
The shop drawing for centering and shuttering shall be prepared by the Contractor to
be submitted in advance (i.e., minimum 45 days) as per their work progress/ program
and same shall be submitted for approval by concerned Consultants appointed by IIT
Bhilai. (The ceiling of RCC slabs shall be shutter finished and plaster/ rendering shall
not be permitted). To maintain the Cover to reinforcement in structural member, only
factory made cover blocks of required size and grade not lesser than the M 35 deign mix
grade of concrete in RCC works shall be provided.
The parapet wall shall be in RCC/ Brick work as per structural / architectural drawing.
All external openings at unit and common areas and corridors shall have 600mm wide
projection (Sunshade/ Chajja) with both side minimum bearing of 230mm and drip
course of size 25x12mm in projections shall be provided in RCC.
Reinforcement:
Reinforcement bars shall be Thermo-Mechanically Treated (TMT) bars of grade Fe-
500D or more conforming to IS 1786of approved make (only primary producers of
steel). Workshop shall be installed at site for fabrication of steel. Couplers of approved
manufacturers/ brand of suitable length as per structural requirement to be provided
for columns reinforcement bars for more than 25mm dia.
Steel shall be fresh and new. It shall be free of defects and free of rust, oil, paints,
grease, loose mill scale or any other deleterious material undesirable for RCC or prevent
adhesion of concrete with reinforcement
Workmanship
Laps shall be strictly as per the GFC drawing or as per CPWD Specification. For
general guidance, the principles shall be followed as given in IS 456.
used by contractor for diameter 25mm and above in place of Lapping but nothing
extra will be paid for the same.
The reinforcement shall be done as per CPWD Specifications - 2009 - Vol.I& Vol. II
with upto date correction slips.
To avoid displacement of bars in any direction and to ensure proper cover, only
factory made round type/rectangular cover blocks of same block of parent concrete
shall be used by the contractor. Nothing extra shall be payable on this account.
CURING
Curing of concrete is most important. it is for the contractor to arrange for everything
necessary to make sure that the concrete is cured to the complete satisfaction of the
Engineer-in-Charge or his authorized representative. Concrete shall be protected from
quick drying with moist or damped hessian cloth or any other material approved by
the Engineer-in-Charge or his authorized representative. After 24 hours of laying of the
concrete, the surface shall be cured by flooding with water or covering with damp
hessian cloth for a period of 7 days to keep it moist and for the next 7 days the surface
shall be kept wet all the time by sprinkling water continuously or as per CPWD
specifications.
The 50mm wide expansion joint system for floor, wall and roof shall be with extruded
aluminum base member’s pre-engineered self-aligning/ self-centering arrangement and
support plates etc. as per ASTM B221-02. Material shall conform to ASTM 6063.
Provision of Moisture Barrier Membrane in the Joint System shall have watertight joint.
1.1. Internal walls shall be with 230/115 mm thick fly ash /fly ash Cement bricks
of class designation 7.5 and 200mm/150mm /100mm thick , Autoclaved
Aerated cement blocks (AAC blocks) of grade-1 & minimum compressive
strength 4.0 N/mm2 (IS 2185 Part3 ) in Cement mortar 1:4 (1 cement: 4
coarse sand) / Polymer modified cement mortar of approved company for
AAC block as per manufacturer’s specifications with RCC band (M 35) &duly
reinforced with GI flats of suitable section as per direction of Engineer-in-
charge ,properly anchored to the adjoining RCC columns & Masonary . RCC
band(M 35) shall contain 2no’s 8mm dia.reinforcement bar with 8mm dia.
single legged stirrup at spacing of 150 c/c as per IS 6041 to be provided at
the sill level/1metre and lintel level/2.1 metre.
1.2. Half brick masonry with cement mortar (1:4) including providing and placing
in position 2 Nos 8 mm dia reinforcement bars at every third course of Half
brick masonry work and RCC bands (M 35) of 100mm thick at the sill
level/1metre and lintel level/2.1 metre.RCC band (M 35) shall contain 2no’s
8mmdia.reinforcement bar with 8mm dia. single legged stirrup at spacing of
150 c/c .
1.3. 100mm AAC block of grade-1 & minimum compressive strength 4.0 N/mm2
(IS 2185 Part3 ) with approved block laying polymer modified adhesive
mortar all complete duly reinforced with GI flats of suitable section as per
direction of Engineer-in-charge ,properly anchored to the adjoining RCC
columns & Masonary , shall be provided with RCC bands(M 35) of 100mm
thick at the sill level/1metre and lintel level/2.1 metre .RCC band(M 35) shall
contain 2no’s 8mm dia. reinforcement bar with 8mm dia. single legged
stirrup at spacing of 150 c/c as per IS 6041to be provided at the sill
level/1metre and lintel level/2.1 metre.
All opening shall be with M-35 RCC ,lintels and bands over top of parapet walls shall be
with RCC (Corridor/ Terrace/ Balconies, etc.) with both side bearing minimum 230mm.
RCC bands at the interval of 1mts. shall be provided in half brick masonry.
D. Aluminium work:
All aluminum works shall be executed throughspecialized agency to be approved by
Engineer-in-charge. The works shall be protected as per direction of Engineer-in-charge
in suitable manner till completion / handing over of the building whichever is later. If
any scratches and damages occurs shall be replaced or rectified at contractors own cost
and nothing extra shall be paid against the same.
The contractor shall submit the shop drawings of doors. Windows, louvers, cladding and
other aluminum work, based on architectural drawings well in advance preferably 45
days before procurement to the Engineer-in-Charge for approval. The drawings shall
show full size sections of doors, windows etc. thickness of metal (i.e wall thickness),
details of construction, sub frame/ rough ground profile, anchoring details, hardware as
well as connection of windows, doors and other metal work to adjacent work.
All aluminum works shall be factory fabricated extruded sections and polyster powder
coated (Minimum 60 micron) as per approved shade, unless otherwise mentioned in
drawings.
All common lobby/ Lift lobby glazing, Main Entrance Door & common lobby doors, Lift
lobby doors at all levels include double action hydraulic floor spring of approved brand
and manufacture conforming to IS: 6315 with 6mm thick Heat Strengthened glass with
EPDM rubber/ neoprene gasket and Aluminium Fittings as per Drawing and schedule of
hardware fittings and as per direction of Engineer-in-charge.
Aluminium Louvers (factory fabricated powder coated) shall be provided for all
Electrical shaft, FHC’s doors at all levels & Plumbing shaft access doors at Level 1 as per
direction of Engineer-in-charge.
Windows shall be factory fabricated (factory established at site) with pure polyester
powder coated (minimum thickness 60 micron) Aluminum sections. Openable shutters
shall be with 300mm long adjustable stainless-steel friction stays. Glazed panel shall be
4mm thick glass (weight not less than 10 kg/sqm.) frosted in ventilators/ 6mm thick
float glass (weight not less than 15 kg/sqm.) except DWs are with 6mm thick Heat
strengthened glass with EPDM rubber/ neoprene gasket, aluminum fittings etc. as per
drawing.
faults. Optical faults to be within the limits set in BS EN 572-2. The visual quality would
be in conformance with EN 1096- part 2 & 3. Visual quality will be established with EN
1096 & EN 12150. The glass shall be ‘Saint Gobain Glass (SGG) - ST 167’ or from
approved equivalent make.
Light shelf with powder coated folded aluminum section to be integrated with room’s
windows. Toilet ventilators shall be with powder coated aluminum shutter (fixed/ top
hung/ louvers) as per drawing. All Windows and Corridor (common area) shall be
provided with MS Safety Grills as per design / drawing and direction of Engineer-in-
charge.
For Boys Hostel-1, Boys Hostel-2, Girls Hostel-1, all common toilet main doors at all
levels shall be powder coated aluminum with 6mm thick Heat Strengthened glasswith
3M frosted film with EPDM rubber / neoprene gasket in upper half and louvers in below
half with Aluminium Fittings as per Drawing.
The works shall be protected as per direction of Engineer in charge in suitable manner
till completion / handing over of the building whichever is later.
Stainless Steel 304 grade (18/8, Matt finish) railing for staircases, steps, at level 1, over
corridors and terrace parapet, etc. as per design and drawing. The section sizes and
thickness of handrail, main baluster and intermediate members of all railings shall be as
per requirement and as per direction of Engineer-in-charge. However, Balusters shall be
of wall thickness not less than 2.6mm and other members shall be of wall thickness not
less than 1.65mm.
the following specification. Recommended fire door shall be tested to IS 3614 part 2 /
ISO 834-1 Part 1 / BS476 Part 20 & 22, CBRI / Cerifire or third party certified or
equivalent lab, for maximum rating of 120mins with 30minutes of insulation, in
latched /unlatched condition (if used with deadbolts and pull handles). Labeled
doors with certification shall be with vision glass as a part of complete assembly.
Manufacturer test certificate shall cover doors both single and double leaf and all
doors supplied shall be within the tested specimen, deviation in specification and
sheet thickness other than what is mentioned in the test certificates are not allowed.
Proper label confirming the type of door and the hourly rating is mandatory from
Approved manufacturer or equivalent.
Size of door fame and shutter shall be as per the manufactures specification with 2
Hrs fire rating. Door frame shall be single rebate grooved profile of size 125 x 60mm
made out of 1.60mm (16gauge) minimum thick galvanized steel sheet. Frames shall
be mitered and field assembled with self-tabs. Frames to have in build grooved
sealing system and shall be site fitted with fire rated EPDM gasket as standard. All
provision should be mortised, drilled and tapped for receiving appropriate hardware.
Frames should be provided with back plate bracket and anchor fasteners for
installation on a finished plastered masonry wall opening. Frames shall be filled with
fire rated puff.
Door leaf shall be 46mm thick fully flush double skin door, insulated with or without
vision lite. Door leaf shall be manufactured from 1.2mm (18guage) minimum thick
galvanized steel sheet. The internal construction of the door should be rigid
reinforcement pads for receiving appropriate hardware. The infill material shall be
high density insulation material. Intumescent seals 15x2mm to be provided all
around the door in addition to the grooved smoke seal. All doors shall be factory
prepped for receiving appropriate hardware and provided with necessary
reinforcement for hinges, locks, and door closers. The edges should be interlocked
with a bending radius of 1.4mm. For pair of doors integrated astragals has to be
provided on the meeting stile for both active and inactive leaf. Vision lite wherever
applicable should be provided as per manufacturer’s recommendation with a clip-on
arrangement. The glass should be 6mm clear borosilicate fire rated glass of relevant
rating of the door.
All doors and frames shall be finished Powder coated and shall have passed
minimum 500 hours of salt spray test.
Item shall include supply and installation of door and hardware as a complete
assembly as mentioned in the door and hardware schedule. Once frame installed
should be filled with PUF as recommended by the manufacturer .
120Mins Fire Rated Door Double leaf of size : 1200-1500x2100-2200 with vision
panel 200x300 with hardware set 6no ball baring butt hinges, panic bar with trim for
double leaf door, 2no door closer HDC 35 with slide arm, door coordinator, groove &
intumescent seal for smoke, all hardware are as per List of preferred makes &
inclusive of PUFF Grouting.
Providing and fixing of Hollow metal Un-Insulated fire rated doors as per IS 3614
part-1, for stability and integrity. Pressed galvanized steel confirming to IS 277 with
the following specification. Recommended fire door shall be tested to IS 3614 part 2
/ ISO 834-1 Part 1 / BS476 Part 20 & 22, CBRI / Cerifire or third party certified or
equivalent lab, for maximum rating of 120mins, in latched /unlatched condition (if
used with deadbolts and pull handles). Labeled doors with certification shall be
with vision glass as a part of complete assembly. Manufacturer test certificate shall
cover doors both single and double leaf and all doors supplied shall be within the
tested specimen, deviation in specification and sheet thickness other than what is
mentioned in the test certificates are not allowed. Proper label confirming the type
of door and the hourly rating is mandatory from Approved manufacturer or
equivalent.
Size of door fame and shutter shall be as per the manufactures specification with 2
Hrs fire rating. Door frame shall be single rebate grooved profile of size 125 x
60mm made out of 1.60mm (16gauge) minimum thick galvanized steel sheet.
Frames shall be mitered and field assembled with self-tabs. Frames to have in build
grooved sealing system and shall be site fitted with fire rated EPDM gasket as
standard. All provision should be mortised, drilled and tapped for receiving
appropriate hardware. Frames should be provided with back plate bracket and
anchor fasteners for installation on a finished plastered masonry wall opening.
Door leaf shall be 46mm thick fully flush double skin door, Un-insulated with or
without vision lite. Door leaf shall be manufactured from 1.2mm (18guage)
minimum thick galvanized steel sheet. The internal construction of the door should
be rigid reinforcement pads for receiving appropriate hardware. The infill material
shall be resin bonded honeycomb core. All doors shall be factory prepped for
receiving appropriate hardware and provided with necessary reinforcement for
hinges, locks, and door closers. The edges should be interlocked with a bending
radius of 1.4mm. For pair of doors integrated astragals has to be provided on the
meeting stile for both active and inactive leaf. Vision lite wherever applicable
should be provided as per manufacturer’s recommendation with a clip-on
arrangement. The glass should be 6mm clear borosilicate fire rated glass of relevant
rating of the door.
All doors and frames shall be finished Powder coated and shall have passed
minimum 500 hours of salt spray test.
Item shall include supply and installation of door and hardware as a complete
assembly as mentioned in the door and hardware schedule. Once frame installed
should be filled with PUF as recommended by the manufacturer.
120Mins Fire Rated Door Single leaf of size: 1050-1200x2100-2400 with vision
panel 200x300mm with hardware set 3no ball baring butt hinges, D-type pull
handle of 300mm long on both side, mortise dead lock with both side cylinders, 1no
door closer HDC 35with slide arm, groove seal for smoke, all hardware are as per
List of preferred makes & inclusive of PUFF Grouting.
All hardware fittings should be minimum two hour fire rating.
MS Door : For Mumty, Common shaft & Plumbing shaft and lift machine room shall
be of MS doors shutters made with MS Door of 1mm thick M.S. sheet with frame of
40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all
necessary fittings complete using flats 30x6mm for diagonal braces and central piece.
Door frame shall be of T-iron frames for doors, windows and ventilators of mild steel
Tee-sections, joints mitered and welded, including fixing of necessary butt hinges and
screws fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block
15x10x10 cm of C.C. 1:3:6, Finished with primer and synthetic enamel paint.
For Boys Hostel-1, Boys Hostel-2, Girls Hostel-1, all staircases (as per drawing)
external side shall be provided with 3mm thick MS Rectangular Hollow Section or
Square Hollow Section as per IS:4923 up to beam/ slab bottom as per detail drawing
at all Levels. MS railing above terraces at all levels, MS works in Monkey ladder for
O.H.T.s and Stairs for Lift machine Room.
For Married Student Housing all balconies, corridors, staircases, etc. shall be
provided with MS grills up to beam/ slab bottom at Level 1. All balconies, corridors,
etc. shall be provided with MS railing at Levels 2, 3 & 4. Common shafts along
corridors, side grill of Staircase 1, etc. shall be provided with MS grills. MS works in
Monkey ladder for O.H.T.s and Stairs for Lift machine Room.
For Mess Block staircases 3 & 4 shall be provided with MS railing at all Levels. MS
works in Monkey ladder for O.H.T.s and Stairs for Lift machine Room.
For Boys Hostel-1, Boys Hostel-2, Girls Hostel-1, MS Pergola shall be provided at
front side of the block as per drawing with enamel paint as per specifications.
All window grills shall be powder coating (Minimum thickness 60mm) (All around
frame and vertical member is of flat 40x6mm @ 350 c/c and horizontal 12x12mm @
125mmc/c) shall be fixed with 100x8mm anchor fasteners in concrete / hold fast
with mix 1:2:4 concrete blocks in brick work in adequate no. (@500 c/c) of spacing.
MS Structural steel support/ base framing for stone cladding, GRC Screen, Concrete
jali, Polycarbonate roof sheeting, etc. works with priming coat of zinc primer and
painted with two or more coats of epoxy paint, all complete as per approved shop
drawing . All shafts shall be provided with MS ladder with chequered plate
(minimum 6mm thick) platform at floor levels with enamel paint with primer as per
specifications, all complete as per direction of engineer-in-charge.
MS support/ bracket (angle, tube, channel, plate, etc.) at wall/ ceiling for services line
(Plumbing, FF, Electrical, HVAC, etc.) shall be provided as per approved shop
drawing. The MS support to be fixed with 100x8mm anchor fasteners in concrete mix
of 1:1.5:3 / hold fast in brick work in adequate number at adequate spacing. The MS
works shall be finished with two or more coats of epoxy paint over a coat of zinc
primer.
For Boys Hostel-1, Boys Hostel-2, Girls Hostel-1- All door frames of size
125x65mm shall be factory made Phenol bonded Bamboo wood (Superior class,
interior use) of approved colour, texture and finish. The bamboo wood shall have
minimum density of 1000 Kg/cum, minimum hardness 1000 Kgf. The door frame
shall have tenon & mortise interlocking system, to be fixed to the wall with 100 mm
size. All complete as per directions of Engineer-in-charge.
For Married Student Housing- For All unit main entrance door frames of size
150x65mm (double rebate) and all internal door frames of size 125x65mm shall be
factory made Phenol bonded Bamboo wood (Superior class, interior use) of approved
colour, texture and finish. The bamboo wood shall have minimum density of 1000
Kg/cum, minimum hardness 1000 Kgf. The door frame shall have tenon & mortise
interlocking system, to be fixed to the wall with 100 mm size. All complete as per
directions of Engineer-in-charge.
For Mess Block-All door frames shall have factory made Pressed steel door frames
Profile section A/B/C conforming to IS: 4351, of approved manufacturers from
commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb,
bead, etc. including a coat of steel primer after pre-treatment and two or more coats
of approved brand and shade of painting and door frames profile inside should be
filled properly with CC 1:2:4( 1 cement: 2 coarse sand: 4 20mm graded stone
aggregate) and cured for seven days before fixing in position fixing shall be done as
per CPWD specification.
Toilet Cubicles and Doors: (Boys Hostel-1, Boys Hostel-2, Girls Hostel-1)
Providing and fixing Greenlam, Merino or equivalent, modular Box up toilet Toilet
cubicle(of following standard dimension which includes 600mm door size width)
made up of thermosetting resin treated high pressure ,self supporting decorative
compact laminates with permanently incorporate anti-bacterial agents during
manufacturing . The compact laminates should have the density >1.35kg/cm3 and
fulfilled the criteria of green guard gold certification and manufactured under
EN438-2&3:2005 standard. 12mm thick compact board should be heat resistant,
Chemical resistant, Moisture resistant, Impact resistant, termite resistant ,Scratch
resistant ,Weather and climatic shock resistant.
The top fitting should consist of SS round top rail of stainless steel(grade316) which
will get fixed with pilaster, with SS panel tube holder ,SS corner bend of stainless
steel(grade316) (connected with top rail ) will be use in corner of cubical in absence
of brick wall, SS wall fixing is used only on the wall which will hold the SS top rail.
All screw will of 304 grade in SS .All pilasters are supported by SS bottom cladding .
The base of the stainless steel bottom cladding will be anchored to the floor with a
clearance height upto 150 mm as per direction of Engineer-In-charge. Toilet Cubicle
with standard dimension of (Approx.) 2025mm Height, 1050 - 1250 mm Width and
1500mm Depth, which also includes 600mm door size width).
30mm thick pre-laminated factory-made PVC door shutter consisting of frame made
out of MS tube for style and for top & bottom rails. 30mm thick pre-laminated PVC
door shutters of approved design and colour. All complete as per specifications and
as directed by Engineer-in-charge. (9.120.2 / DSR 2018)
fixtures as per design and drawing. Loft shall be provided over cupboard as per
drawing. Heavy duty 25mm dia Stainless steel curtain rods with approved decorative
brackets shall be provided for all Windows.
All Doors, Windows, Cupboard, Cabinets, etc. shall be provided with all necessary
Stainless steel and Aluminium fitting and fixtures (such as hinges, Locks (Brass with
six levers), Mortice Lock, Safety Chain, Handles, sliding door bolt, Curtain rod, tower
bolt, night latch, cat eye, Twin rubber door stopper, door closer, drawer nob, vision
panel, double strip magnetic catcher, hanging rod, 300mm length stainless steel 304
friction stays at top and bottom, etc.) as per requirement & as per direction of
Engineer-in-charge.
All kitchens shall have built in type under-counter cabinets including drawers,
louvers door at gas cylinder and below sink as per drawing, over-head cabinets & loft
with necessary fitting and fixtures including auto hinges as per design and drawing.
All Doors, Windows, Cupboard, Cabinets, etc. shall be provided with all necessary
Stainless steel and Aluminium fitting and fixtures (such as hinges, Locks (Brass with
six levers), Mortice Lock, Safety Chain, Handles, sliding door bolt, Curtain rod, tower
bolt, night latch, cat eye, Twin rubber door stopper, door closer, drawer nob, vision
panel, double strip magnetic catcher, hanging rod for cupboard, 300mm length
stainless steel 304 friction stays at top and bottom, etc.) as per requirement and as
per direction of Engineer-in-charge.
Heavy duty 25mm dia Stainless steel curtain rods with approved decorative brackets
shall be provided for all Doors and Windows.
Door Stopper
lock 7 levers
Handle125
Handle300
Hinges
Buffer
DOOR
1800 x
D1a Main Entrance Glazed Door 8 4 1 1 1 2 2
2400
Indoor Sports & 1500 x
D1b Glazed Door 8 4 1 1 1 2 2
Washing 2400
HVAC Equipment
M.S Door with Including MS Door fittings and Fixtures, Handle,
D2 Room/ Mumty/ 1050x2400
M.S Frame Sliding door bolt, tower bolt, etc.
Machine Room
1200 X
FD-1 Electrical Room
2400
Fire Door As per fire Norms.
SD-1 Shaft Door 1200x2200 Louvered Door 6 2 1 1
SD-2 Shaft Door 600X2200 Louvered Door 3 1 1 1
DWG 1 Main Entry Door 5680x5800 Glazed Door 8 4 1 1 1 1 1
WINDOW
1500X190
W1 Room Aluminum 4 2 2
0
1500X190
W1a Guest Room Aluminum 4 2 2
0
W2 Guest Room 750X1900 Aluminum 2 1 1
1500X160
W3 Toilet Aluminum 4 2 2
0
1200X235
GL2 Warden Office Aluminum 4 2 2
0
1200X200
GL2a Warden Office Aluminum 4 2 2
0
Cupboards
Correction –Nil
&
Hardware Schedule
wide
Cabinetry
8
8
16
Self-Closing Hinge/ Auto Hinge (S.S. Matt finish)
Insertion –Nil
2
4
Handle 224mm (S.S. Matt finish)
Cupboard and Cabinetry Hardware Schedule
7
346
1
Cupboard Lock
Deletion –Nil
6
2 Drawer Channel for 30 kg load (Zinc plated)
Overwriting -Nil
Magnetic Catcher (load 4-5 kg)
347
Stay
Door Stopper
lock 7 levers
Handle125
Friction
Hinges
Hinges
Buffer
Lock
DOOR
1800 x
D1a Main Entrance Glazed Door 8 4 1 1 2 2
2400 1
Indoor Sports & 1500 x
D1b Glazed Door 8 4 1 1 2 2
Washing 2400 1
HVAC Equipment
1050x240 M.S Door with Including MS Door fittings and Fixtures. Handle, Sliding
D2 Room/ Mumty/
Machine Room
0 M.S Frame door bolt, tower bolt, etc.
1200 X
FD-1 Electrical Room
2400
Fire Door As per fire Norms.
1200x220 Louvered
SD-1 Shaft Door 3 2 1 1 1
0 Door
Louvered
SD-2 Shaft Door 600X2200 6 2 1 1 1
Door
5680x580
DWG 1 Main Entry Door Glazed Door 8 4 1 1 1 1 1
0
WINDOW
1500X190
W1 Room Aluminum 4 2 2
0
W2 Guest Room 750X1900 Aluminum 2 1 1
1500X160
W3 Toilet Aluminum 4 2 2
0
1200X235
GL2 Warden Office Aluminum 4 2 2
0
1200X200
GL2a Warden Office Aluminum 4 2 2
0
STAINLESS STEEL FITTING
1050 X
D3 Toilet Main Entry Paneled Door 4 2 1 1 1 1
2400
Pre-laminated
D4 Main Room Entry 900X2100 4 2 1 1 1 1
Flush Door
Main Room Entry -
Differently Abled 1050X210 Pre-laminated
D4a 4 2 1 1 1 1
Student Room & 0 Flush Door
Toilet Door
Kitchen
cupboard
cupboard
Cupboard
Cupboards
Correction –Nil
Rooms
&
Hardware Schedule
wide
8
8
16
Insertion –Nil
Self-Closing Hinge/ Auto Hinge (S.S. Matt finish)
2
4
Handle 224mm (S.S. Matt finish)
Cupboard and Cabinetry Hardware Schedule
7
348
1
2
Cupboard Lock
Deletion –Nil
6 Drawer Channel for 30 kg load (Zinc plated)
1
2
Overwriting -Nil
Magnetic Catcher (load 4-5 kg)
349
Stay
Door Stopper
lock 7 levers
Handle125
Friction
L-Drop
Hinges
Hinges
Buffer
Lock
DOOR
1800 x
D1a Main Entrance Glazed Door 8 4 1 1 2 2
2400 1
Indoor Sports & 1500 x
D1b Glazed Door 8 4 1 1 2 2
Washing 2400 1
HVAC
Equipment M.S Door with Including MS Door fittings and Fixtures. Handle, Sliding
D2 1050x2400
Room/ Mumty/ M.S Frame door bolt, tower bolt, etc.
Machine Room
1200 X
FD-1 Electrical Room
2400
Fire Door As per fire Norms.
Louvered
SD-1 Shaft Door 1200x2200 6 2 1 1 1
Door
Louvered
SD-2 Shaft Door 600X2200 3 1 1 1 1
Door
DWG 1 Main Entry Door 5200x5625 Glazed Door 8 4 1 1 1 1 1
DWG 2 Main Entry Door 1500x2650 Glazed Door 8 2 1 1 2 2
WINDOW
W1 Room 1500X1900 Aluminum 4 2 2
W2 Guest Room 750X1900 Aluminum 2 1 1
W3 Toilet 1500X1600 Aluminum 4 2 2
GL2 Warden Office 1200X2350 Aluminum 4 2 2
Multipurpose
GL2a 1200X2000 Aluminum 4 2 2
Hall
Cupboards
Correction –Nil
&
Hardware Schedule
8
8
16
Insertion –Nil
Self-Closing Hinge/ Auto Hinge (S.S. Matt finish)
2
4
Handle 224mm (S.S. Matt finish)
Cupboard and Cabinetry Hardware Schedule
350
7
Handle 96mm (S.S. Matt finish)
1
Cupboard Lock
Deletion –Nil
Drawer Recessed Handle (S.S. Matt finish)
6
2 Drawer Channel for 30 kg load (Zinc plated)
1
Tower Bolt (200mm) (S.S. Matt finish)
2
1
Tower Bolt (100mm) (S.S. Matt finish)
1
2
Overwriting -Nil
Magnetic Catcher (load 4-5 kg)
351
Handle300
Door Code
Location
Channel
Cat eye
Hinges
Buffer
levers
Catch
Knob
Lock
Size
1050x160 Aluminum
W2 Kitchen 4 1 2
0 Window
Electrical Aluminum
W3 900X1200 4 1 4
Room Window
Aluminum
V1 Toilet 750x1000 2 1 1
Window
Loft
+ Loft
Toilets
Kitchen
Cupboards
Correction –Nil
Overhead Cabinet
Under Counter Cabinet
Bedroom 1 Dress cupboard + Loft
Insertion –Nil
8
28
14
10
10
12
Self-Closing Hinge/ Auto Hinge (S.S. Matt finish)
4
2
CUPBOARD & CABINETRY HARDWARE SCHEDULE
353
4
7
5
5
6
2
Handle 96mm (S.S. Matt finish)
5
2 Cupboard Lock
2
1
Deletion –Nil
3
8
4
1
7
Overwriting -Nil
6
14
MESS BLOCK
Door and Window Hardware Schedule
1 2 3 4 5 6 7 8 9 10 11
Door leaf/
Door
Location Size Frame
Code
type
Door Stopper
Handle125
7 levers
L-Drop
Hinges
Buffer
Lock
STAINLESS STEEL FITTING
Entry (Loading/
1500x210 35mm Thk.
D1 Unloading), 8 4 1 1 1 1 1
0 Flush Door
Staircase
Clean Dish,
1200x210 35mm Thk.
D2 Garbage, Dish 4 2 1 1 1 1
0 Flush Door
Wash
1200x210 35mm Thk.
D2A Storage 4 2 1 1 1 1
0 Flush Door
1050x210 35mm Thk.
D3 PH Toilet 4 2 1 1 1 1
0 Flush Door
35mm Thk.
D4 Toilet 900x2100 4 2 1 1 1 1
Flush Door
PVC Frame
D5 W.C 750x2100 & Door 4 2 1 1 1 1
Shutter
1200x210 35mm Thk.
D6 Cold Storage 4 2 1 1 1 1
0 Flush Door
Ladies Rest 1000x210 35mm Thk.
D7 4 2 1 1 1 1
Room 0 Flush Door
Mumty/ 1000x210 Including MS Door fittings and Fixtures. Handle, Sliding
D8 M.S Door
Machine Room 0 door bolt, tower bolt, etc.
Dormitory 35mm Thk.
D9 900x2100 4 2 1 1 1 1 1
Locker Flush Door
Dormitory 1000x210 35mm Thk.
D10 4 2 1 1 1 1
Room 0 Flush Door
Staircase Fire 1500X220 As per fire Norms.
FD1 Fire Door
Door 0
Electrical Room 1050X220
FD2
(Fire Door) 0
Fire Door As per fire Norms.
Patch
8600x845
GL1 Main Entrance Fittin 8
0
g
ALUMINIUM FITTING
3030X270 Glazed
DW1 Garbage Exit 12 4 2 2 1 1 1 1
0 Door 1
Loading/ UN 3330X270 Glazed
DW2 8 4 1 1
Loading Area 0 Door 1
3010X270 Glazed
DW3 Rear Entry 8 4 1 1
0 Door 1
3010X270 Glazed
DW4 Private Dining 8 4 1 1 1 1
0 Door 1
1800x270 Glazed
DW5 Mess In-charge 4 2 1 1 1 1
0 Door 1
2400x270 Glazed
DW6 Mess In-charge 4 2 1 1 1 1
0 Door 1
GL2 Dining Entry 6810X330 Aluminum 16 8 2 8 2 2
0
5470X380
GL4 Aluminum 8 4 1 4 1 1
0
5470X350
GL5 Aluminum 8 4 4
0
WINDOW
Loading/ 2600X180
W1 Aluminum 8 4 4
Unloading Area 0
Loading/ 2745X180
W2 Aluminum 8 4 4
Unloading Area 0
2100X180
W3 Dining Area Aluminum 8 4 4
0
1500X180
W4 Machine Room Aluminum 4 2 2
0
1500X105
W6 Kitchen Area Aluminum 4 2 2
0
Hand Wash,
1200X180
W7 Ladies Rest, Ele. Aluminum 2 1 1
0
Room
Electrical Room 1200X180
W7A Aluminum 2 1 1
0
3030X180
W8 Garbage Arae Aluminum 8 4 4
0
Private Dining 2800X280
W9 Aluminum 8 4 4
Area 0
W11 750X750 Aluminum 4 2 2
Solid Waste/ 2700X180
W12 Aluminum 8 4 4
Waste Disposal 0
2230X180
W13 Rear Elevation Aluminum 8 4 4
0
2815X180
W14 Rear Elevation Aluminum 8 4 4
0
2520X180
W15 Rear Elevation Aluminum 8 4 4
0
2310X180
W16 Rear Elevation Aluminum 8 4 4
0
2030X180
W17 Kitchen Hood Aluminum 8 4 4
0
V Toilet 900X900 Aluminum 2 1 1
Hardware schedules are for guidance only. The fittings shall be provided as per actual
site requirements and direction of Engineer-in-charge.
The flooring works also protected by laying 2mm thick POP over the paper till
completion / handing over of the building whichever is later. If any scratches and
damages occur shall be replaced or rectified at their own cost and nothing shall be
paid against the same.
For Vitrified tiles, Rectified ceramic tiles and ceramic glazed tiles shall have not less
than 10% recycled material content to be used as per GRIHA norms for which
necessary certificate to be submitted by contractor.
For Boys Hostel-1, Boys Hostel-2, Girls Hostel-1 :- Flooring at Lobby & lift Lobby
area with combination of two colours of Kota stone and Tactile tile with 10mm wide
epoxy grout as per details in drawing shall be done as per CPWD specifications
Flooring in Corridors, passages etc. with combination of two colours of Kota stone
and Tactile tile with 10mm wide epoxy grout in a pattern as shown in drawing .
Flooring in connecting corridor/ wings (single loaded corridor at stilt) shall be
finished with combination of two colours of Kota stone and chisel dressed / rough
Kota stone with 10mm wide epoxy grout in a pattern as shown in drawing . Kota
stone flooring with 25 mm thick (average) slab over 20mm (average) thick base
mortar of 1:4 (1 cement : 4 coarse sand) and Skirting shall be with 20 mm thick kota
stones over 12mm (average) thick CM 1:3 (1 cement : 3 coarse sand).
Single piece Kota stone at staircase treads and risers up to 1500mm. Treads shall
have Kota stone with 15mm nosing projection as per approved design with 3 no’s
horizontal grooves for anti-skid purpose on treads as per CPWD specification.
Steps (Treads) shall be provided with Kota stone. Skirting and riser shall be
polished Kota stone as per per drawing and CPWD specifications.
Kota stone Flooring in Indoor sports area, Electrical room, Shop, Janitor, Security
room, Clothes washing, Lift machine room, all Staircases, Entrance steps, Stores,
Pump room, etc. as per drawing.
For Married Student Housing flooring at Common Lobby, lift Lobby, Corridors,
etc. with 10mm wide epoxy grout. Kota stone Flooring in Electrical room, Lift
machine room, all Staircases, Entrance steps, Stores, Pump room, etc. shall be done
as per CPWD specifications.
Steps, staircase treads and riser shall be finished with single piece Kota stone.
Treads shall have polished Kota stone with 15mm nosing projection as per design
and 3 no’s horizontal grooves for anti-skid purpose on treads as per CPWD
specification . Tread shall be single piece up to 1800mm.
For Mess Block: Flooring at Dining hall, corridors, passages, etc. shall be finished
with combination of Kota and Tactile tile with 10mm wide epoxy grout. Kota stone
flooring shall be provided in Garbage handling area, machine room, electrical room,
etc. as per drawing.
Staircases (2, 3, 4 & 5) shall be finished with Single piece Kota stone at treads and
risers up to 1700mm. Treads shall have Kota stone & 15mm nosing projection as
per design and 3 no’s horizontal grooves for anti-skid purpose on treads as per
CPWD specification.
For all staircases steps shall be provided with single piece of 25mm thick Kota stone
with 20mm thick base mortar 1:4 (1 cement: 4 coarse sand). Skirting and riser shall
be with 20mm thick Kota stone. Skirting shall be done with over 12mm (average)
thick base of CM 1:3 (1 cement: 3 coarse sand) as per CPWD specifications.
Flooring in Electrical room, Shop, Janitor, Security room, Clothes washing, Lift
machine room, all Staircases, Entrance steps, Stores, Pump room, etc. as per
drawing.
Tactile tile (for vision impaired persons as per standards) of required size with
9.8mm thickness having water absorption less than 0.5% and conforming to IS:
15622, of approved make in all colours and shades, laid on 20mm thick base of
cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns complete as
per drawing.
Polished Kota stone coping shall be provided over low height walls at Level 1 area
near steps, planters & terrace parapet including nosing as per drawing and design
for all buildings.
Granite flooring of Mirror polished, 18 mm thick gang saw cut pre-moulded and
pre-polished, machine cut of required size, approved shade, colour and texture laid
over 20 mm thick base cement mortar 1:4 (1 cement: 4 coarse sand), joints treated
with white cement, mixed with matching pigment, epoxy touch ups, including
rubbing, curing, moulding and polishing to edges to give high gloss finish etc.
complete at all levels.
Kitchen Counter, Toilet Counter, Window sills (single piece), etc. shall be laid with
18mm thick mirror polished, pre-moulded and pre-polished, Granite stone with
base of over cement mortar 20mm thick cm 1:4 (1 cement : 4 coarse sand)
moulding and nosing as per drawing. Window sill shall be provided with granite
stone over 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand) over PCC
1:3:6 ( 1 cement: 3 coarse sand: 6 stone aggregate of graded 20mm nominal size)
as per drawing. Counters shall be finished in Jet black granite.
18mm thick gang saw cut Granite Wall Cladding of full height shall be provided at
lift Facia in all floors as perarchitectural drawing and laid over 12mm thick cement
mortar 1:3 (1 cement : 3 coarse sand).
Granite stone divider for toilet and shower area shall be provided with nosing as
per drawing. The thickness of divider is 40mm thick (20+20mm).
Staircase-1 shall be finished with 18mm thick gang-saw-cut Single Piece Granite
stone at treads and risers up to 2150mm. Treads shall have flamed finish granite
stone & 15mm nosing projection as per design and 3 no’s horizontal grooves for
anti-skid purpose on treads as per CPWD specification .
Main Lobbies, lift lobby, etc. shall be finished with 18mm thick gang-saw-cut pre-
polished granite stone with combination of Tactile tile as per drawing.
NOTE: 18mm thick Gang saw Cut Granite slab while bringing to site minimum size
should be 2700mm X 1600mm and maximum size 3300mm X 2000mm. Less than
minimum size and thickness mentioned above shall not be allowed at site.
Dining hall, etc. wall shall be cladded with 600mm height of ceramic tiles at center
and a 200mm height band of Kota stone at top and bottom of tiles laid on minimum
12 mm thick mortar and finished surfaces to be flushed with each other with 50mm
polished Kota stone (25+25 with glue by araldite adhesive) stone mould on top as
per drawing, specifications .
Passages, etc. wall shall be cladded with 1000mm height of ceramic tiles as per
design with 50mm stone mould on top as per drawing, specifications.
Staircase-1 wall shall be cladded with 1000mm height full body vitrified tiles( High
traffic tiles) as per design, drawing, specifications.
Stainless steel Trough shall be provided for all 4 nos. hand wash areas as per profile
and requirement with base frame.
Stainless steel trough for the 2 nos. dish pre-wash areas shall be provided as per
profile and requirement with base frame.
Rectified Ceramic Floor Tiles (Satin Finish/ Matt Finish/ Anti-skid) and
Ceramic Wall Tiles:
For Married Student Housing :- Flooring for Living, Bedroom, etc. shall be with
600x600mm of thickness minimum 9mm Rectified Ceramic (Satin finish) laid on
20mm thick cement mortar with 3mm wide epoxy grout. Kitchen flooring shall be
with 300x300mm of thickness minimum 9mm Rectified Ceramic Tiles (Satin finish)
laid on 20mm thick cement mortar 1:4 (1 cement: 4 coarse sand). Balconies, Toilets,
etc. flooring shall be with 300x300mm of thickness minimum 9mm Rectified
Ceramic Tiles (Matt finish/anti-skid) laid on 20mm thick cement mortar 1:4 (1
cement: 4 coarse sand). Internal walls of Kitchen dado above counter and toilet
shall have 300x600mm ceramic wall tiles up to 2100mm laid over 12mm thick
cement mortar 1:3 (1 cement: 3 coarse sand) with PVC edge beading at corners.
Skirting shall be with same tiles laid over 12mm thick cement mortar.
For Mess Block :- Flooring for all Toilets, Hand wash area, rinse area, soil drop area,
Ladies and gent’s toilets, Dormitory toilets, etc. shall be with 300x300mm of
thickness minimum 9mm Rectified Ceramic Tiles (Matt finish/anti-skid) laid on
20mm thick cement mortar 1:4 (1 cement: 4 coarse sand). Flooring for Physically
challenged toilet with combination of 300x300mm of thickness minimum 9mm
Rectified Ceramic Tiles (Matt finish/anti-skid) & Tactile tile laid on 20mm thick
cement mortar 1:4 (1 cement: 4 coarse sand). Internal walls of all Toilets, PH toilets,
Hand wash area, rinse area, soil drop area, Ladies and gent’s toilets, Dormitory
toilets, Kitchen, dish wash, clean dishes storage area, Garbage handling area, etc.
shall have 300x600mm ceramic wall tiles up to 2100mm, laid over 12mm thick
cement mortar1:4 (1 cement: 4 coarse sand) with PVC edge beading at corners.
Skirting shall be with same tiles laid over 12mm thick cement mortar 1:3 (1 cement:
3 coarse sand).
Kitchen, dish wash area, clean dishes storage area, dormitory, etc. flooring shall be
with 15mm thick anti-skid Industrial tile laid on 20mm thick cement mortar with
3mm wide epoxy grout.
Internal floor and wall finish of Overhead Water Tanks shall be 300x300mm
Ceramic tiles (Glazed) over 12mm thick cement mortar 1:4 (1 cement: 4 coarse
sand) and laid over 12mm thick cement mortar 1:3 (1 cement: 3 coarse sand)
respectively.
All skirting shall be 100mm high with same material unless specified with base of
12mm cement mortar 1:3 (1 cement: 3 coarse sand). It should be flushed with wall
with groove 6x8mm.
Other balance areas if any left out shall be finished with Rectified Ceramic Floor
tiles Satin finish with 3mm epoxy grout and skirting with same tile with base of
12mm cement mortar 1:3 (1 cement: 3 coarse sand).
All tiles shall be of 1st quality as approved sample, brand, manufacture, colour and
shade.
Minimum base rate of Granite is Rs. 275 per sqft., Gwalior mint Stone is Rs. 150 per
sqft., Vitrified tile is Rs. 110 per sqft., Plain Ceramic tile is Rs. 45 per sqft., Rectified
Ceramic (Satin finish) tile is Rs. 75 per sqft., Rectified Ceramic (Matt/Anti-skid
finish) tile is Rs. 75 per sqft. (All above are approximate rates at Kutelabhata, Durg,
Chhattisgarh)
galvanized mild steel item (galvanised@80gsm) 50mm long 8mm outer diameter
M-6 dash fasteners, 6mm diameter fully threaded hanger rod up to 1000mm
length and L-shape level adjuster of size 85x25x2mm, spaced at 1200mm center to
center along main ‘T’. The system should rest on periphery walls /partitions with
the help of GI perimeter wall angle of size24x24X3000mm made of 0.40mm thick
sheet, to be fixed to the wall with help of plastic rawl plug at 450mm center to
center & 40mm long dry wall S.S. screws. The exposed bottom portion of all T-
sections used in false ceiling support system shall be pre-painted with polyester
baked paint, for all heights. The work shall be carried out as per specifications,
drawings. With 16mm thick beveled tegular mineral fibre Anti-microbial false
ceiling tile confirming to ISO 5 (class 100) specifications (DSR 2018 26.27.3).
Tiled false Ceiling (grid false Ceiling) tiles of approved texture in the grid including
required cutting/ making, opening for services like diffusers, grills, light fittings,
fixtures, smoke detectors etc. as per drawing.
For Boys Hostel-1, Boys Hostel-2, Girls Hostel-1 :- (Corridor areas, etc. First
floor, Second floor and Third floor and as per drawing)
Metal false ceiling:
Corridor areas as per drawing shall be finished with Providing and fixing Gl Clip in
Metal Ceiling System of 300x1200mm module which includes providing and fixing
'C' wall angle of size 20x30x20 mm made of 0.5mm thick pre painted steel along
the perimeter of the room with help of nylon sleeves and wooden screws at 300
mm center to center, suspending the main C carrier of size 10x38x10 mm made of
G.I steel 0.7 mm thick from the soffit with help of soffit cleat 37x27x25x1.6 mm,
rawl plugs of size 38x12 mm and C carrier suspension clip and main carrier
bracket at 1000 mm c/c. Inverted triangle shaped Spring Tee having height of 24
mm and width of 34 mm made of Gl steel 0.45 mm thick is then fixed to the main C
carrier and in direction perpendicular to it at 600 mm centers with help of
suspension brackets with 6mm dia GI fully threaded hanger rod upto 1000mm
length @1200 mm c/c spacing. Wherever the main C carrier and spring T have to
join, C carrier and spring T connectors have to be used. All sections to be
galvanized @ 120 gms/sqm (both side inclusive), fixing with clip in tiles into
spring T with :
GI Metal Ceiling Clip in plain Beveled edge global white color tiles of
size300x1200mmand 0.5 mm thick with 25 mm height, made of G I sheet having
galvanizing of 100 gms/ sqm (both sides inclusive) and 20% perforation area with
1.8 mm dia holes and having NRC of 0.5, electro statically polyester powder coated
of thickness 60 microns (minimum), including factory painted after bending and
perforation. (DSR item2018 12.54.2)
For Boys Hostel-1, Boys Hostel-2, Girls Hostel-1 :- (Corridor areas, etc. First
floor, Second floor and Third floor and as per drawing)
Side Wall Panelling ( Services covering)
Corridor areas as per drawing shall be finished with Providing and fixing Gl Clip in
Metal wall cladding System of 600x700 module which includes providing and
fixing 'C' wall angle of size 20x30x20 mm made of 0.5mm thick pre painted steel
with help of nylon sleeves and wooden screws at 300 mm center to center, main C
carrier of size 10x38x10 mm made of G.I steel 0.7 mm thick from the wall with
help of cleat 37x27x25x1.6 mm, rawl plugs of size 38x12 mm and C carrier
suspension clip and main carrier bracket at 1000 mm c/c. Inverted triangle
shaped Spring Tee having height of 24 mm and width of 34 mm made of Gl steel
0.45 mm thick is then fixed to the main C carrier and in direction perpendicular to
it at 600 mm centers with help of suspension brackets. Wherever the main C
carrier and spring T have to join, C carrier and spring T connectors have to be
used. All sections to be galvanized @ 120 gms/sqm (both side inclusive), fixing
with clip in tiles into spring T with :
GI Metal Clip in plain Beveled edge global white color tiles of size 600x700mm and
0.5 mm thick with 25 mm height, made of G I sheet having galvanizing of 100 gms/
sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and
having NRC of 0.5, electro statically polyester powder coated of thickness 60
microns (minimum), including factory painted after bending and perforation.
The Strut framework systems includes Strut CC50 Cross Channel having thickness
0.7mm, length 3600mm, knurled web 50, depth 50mm and equal flanges 15mm is
fastened to wall positioned horizontally in a regular manner at 600mm c/c. Strut
H-Spline having sectional thickness 2mm and length 2400mm to be fixed
perpendicular to the Strut CC50 Cross Channel at 600mm centers. The Kerfed edge
panels shall be then inserted into the Strut H-spline along their long edges of
2400mm against framework to perfect fit with staggered short edges.
The system is backlined with the acoustical infill Anutone SynthPF 10x50 or
equivalent
Technical Parameters
• Fire (Class) – 1 & P
• Acoustics – NRC 0.91 (For 50mm E250* Mounting)
• Thermal conductivity (W/mk)– 0.08
• Climate (°C, RH) – 50, 90
• Light reflectance (%) – 75
• Green (VoC, RC %) – Low, 30
Waterproofing:
Waterproofing compound material shall be mixed in concreting and plastering in
proportion recommended by manufactures.
All waterproofing works shall be commenced after completion of all RCC and
cementitious works like mumty rooms, water tanks, parapet walls and
supporting pillars of water supply line, firefighting lines and solar heater
supporting system and plastering of all works at terrace. Insulation system shall
start after initial surface cleaning, removal of debris, surface cleaning by wire
brush/ air blower and ready for the surface preparation and surface should be
dust free .
Making khurras 45cm x 45cm with average minimum thickness of 5cm cement
concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate of 20mm
nominal size) over PVC sheet 1mx1mx400 micron finished with 12mm cement
plaster 1:3 (1 cement: 3 fine sand) and a coat of neat cement rounding the edges
and making and finishing the outlet complete.
Aluminium edge beading shall be provided / fixed to the parapet wall at the
end of PU coating and above that cement mortar 1:2 (1 cement: 2 Fine sand)
band of size 50mm height and 25mm width/ depth to be provided to prevent
entry of water as shown in terrace water proofing treatment drawing.
The terrace top finish with Heat Resistant tiles (300 mm x 300mm x 20 mm)
with SRI (solar refractive index) > 78, solar reflection > 0.70 and initial emittance
> 0.75 on water proof and sloped surface of terrace, laid on 20 mm thick cement
sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints
with mix of white cement & marble powder in ratio of 1:1, including providing
skirting up to 150 mm height along the parapet walls.
Providing and laying integral cement based treatment for water proofing on
horizontal surface at all depth below ground level for underground structures
and consisting of:
1st layer of 22 mm to 25 mm thick approved and specified rough kota stone slab
over a 25 mm thick base of cement mortar 1:3 (1 cement: 3 coarse sand) mixed
with water proofing compound conforming to IS:2645 in the recommended
proportion over the leveling course Joints sealed and grouted with cement slurry
mixed with water proofing compound.
2nd layer of 25 mm thick cement mortar 1:3 (1 cement: 3 coarse sand) mixed
with water proofing compound in recommended proportions.
(b)Vertical surface:
Providing and laying integral cement based treatment for water proofing on the
vertical surface by fixing specified rough kota stone slab 22 mm to 25 mm thick
with cement slurry mixed with water proofing compound conforming to IS:2645
in recommended proportions with a gap of 20 mm (minimum) between stone
slabs and the receiving surfaces and filling the gaps with neat cement slurry
mixed with water proofing compound and finishing the exterior of stone slab
with cement mortar 1:3 (1 cement: 3 coarse sand) 20 mm thick with neat cement
punning mixed with water proofing compound in recommended proportion
complete at all levels as per CPWD specifications :Using rough Kota stone.
Initially surface cleaning, removal of debris, surface cleaning by wire brush/ air
blower and ready for the surface preparation.
Making ‘V’ groove shall be made at all construction joints. In cracks and hairline
cracks etc. on mother slab treated with Injection grouting (Cementitious
grouting) shall be done at all weaker sections in construction joints. In cracks
and hairline cracks filling the groove, the polymer mortar with cement and sand
mortar 1:4 admixed with SBR latex @ 1lt. per 50kg of cement. Angle fillets
(50x50mm) at junction of slab and vertical walls prepared with cement and sand
mortar 1:4 admixed with integral water proofing admixture (as per IS 450-
2000)” @ 200ml. per 50kg of cement.
After jointing flood test for 7 days for full depth of sunken portion. Leaking point
if any to be pressure grout after fixing PVC nipples and 40PSI grout pump using
cement slurry mixed with non-shrink admixture Dr. Fixit Pidicrete AM/cebex
100 or equivalent @ 225 gms per 50 kg of cement.
M. Finishing:
All paint finishing 1st quality material should have VOC (Volatile Organic
Compound) content less than 50 grams / litre of approved brand, manufacture,
colour and shade.
All internal brick wall /AAC wall shall be finished with 12mm thick cement
plaster of 1:6 (1 cement: 6 fine sand) and 15mm cement plaster 1:6 (1
cement: 6 fine sand) on rough side. The plastering shall be finished within line of
groove provided in door frame. No Plastering to be done at Ceiling.
External walls shall be finished with 15mm thick cement plaster of 1:4 (1 cement
: 4 fine sand)
All junctions of concrete and masonry work and other locations shall be
provided with approved galvanized chicken wire mesh (24 gauge, 12mm size)
fixing in position with galvanized wire nails as per specifications. Groove of size
10x8mm shall be provided at the junctions wherever required. Wherever
chicken mesh provided there will not be any groove and grooves (if provided)
shall be finished with neat cement floating coat. External areas shall be provided
with grooves (Horizontal & Vertical) as per design.
All internal walls of units, Corridors, Lift lobby, Staircases, etc. shall be finished
with premium acrylic emulsion paint of interior grade two or more coats on new
work including priming coat to achieve even colour and shade, and All internal
Ceiling area of units shall be finished with Acrylic Distemper two or more coats
on new work including priming coat to achieve even colour and shade including
applying additional coats wherever required to achieve even shade and colour.
The painting works shall be commenced after base preparation by white cement
based putty (1mm) of approved brand and manufacture over plaster for even
and smooth surface.
All external sloping slabs above chajja projection in elevation shall be finished
with 15mm thick cement plaster 1:4 (1 cement: 4 fine sand) mixed with water
proofing compound in recommended proportion complete at all levels.
All internal walls shall be finished with premium acrylic emulsion paint of
interior grade two or more coats on new work including priming coat to achieve
even colour and shade. All internal Ceiling area shall be finished with Acrylic
Distemper two or more coats on new work including priming coat to achieve
even colour and shade including applying additional coats wherever required to
achieve even shade and colour. The painting works shall be commenced after
base preparation by white cement based putty (1mm) of approved brand and
manufacture over plaster for even and smooth surface.
All shafts (Lift, Plumbing, electrical, etc.) internal areas shall be finished with
waterproofing cement paint over water thinnable cement primer as per
specifications.
Electrical room, Kitchen, Common Shafts, lift machine room, etc. wall and ceiling
shall be finished with Acrylic Distemper, including applying additional coats
wherever required, to achieve even shade and colour. The painting work
commencing after base preparation by white cement based putty (1mm) of
approved brand and manufacture over plaster for even and smooth surface.
Wood works (frame, Beading, lipping, etc.) shall be finished with French spirit
polish and coated with melamine as per specifications.
MS Steel work on other balance works shall be finished with two or more coats
on new work with synthetic enamel painting over the coat of approved red oxide
zinc chromatic steel primer having VOC content less than 250 grams/ litre.
External wall shall be painted with premium Acrylic smooth exterior paint with
silicone additives at locations specified in the Elevation drawings.
All paints shall be procured directly from company of 1st quality as approved
sample, brand, manufacture, colour and shade.
External walls shall be finished with non-pigmented stone based texture paint
with natural mineral, at locations specified in the Elevation drawings. It is a
mixture of Water based natural sand stone, granite and marble chips powder
providing natural colour and shade. The finish is water repellent, anti-fungal,
anti-bacterial, etc. has a unique property of flexibility.
Providing and applying silicone based water repellent coating confirming to BS:
6477-1984 in 2 coats with a consumption of 6 sqm/litre per coat over the
exposed RCC surface including cleaning the surface making it free from dirt, oil
grease, wax and all other contamination using mechanical tool, wire brush,
compressed air followed by water washing and as per the manufacturer
specification .
The silicone-based water repellent coating should have the below mentioned
technical properties-
SURFACE PREPARATION
Surface should be dry and free from all debris, dirt, oil, grease, wax and all other
contamination, which could prevent penetration.
Clean the saturated dirt of surface by thorough wire brushing, cleaning with
compressed air followed by water washing.
De grease oil & grease by using appropriate solvents.
Allow the surface to dry completely before the application.
Thorough wire brushing followed by sanding with emery paper is recommended
APPLICATION
Apply one liberal coat of silicone coating confirming to BS: 6477-1984 simply by
brushing evenly on the prepared surface.
Allow the surface to dry for a minimum of 24 hrs for best results.
Allow it to dry for 24 hrs.
Apply second coat wet on wet, to improve the penetration rate & performance.
Allow it to dry for 24 hrs.
Do not dilute with water or by any other means.
External faces of RCC shear wall (below texture finish) shall be insulated with
50mm thick EPS insulation board having density 15-18 kg/sqm. And thermal
conductivity of 0.030-0.033W/mK fixed with fire rated polymer modified
adhesive layer @2.8kgs/sqm. conforming to standard BS8414 and mechanical
fasteners. PVC corner bead and Glass fiber mesh installed with the polymer
modified base coat. Primer applied at 0.2kgs/sqm. to reinforcement base coat
layer.
Step-1. Supply & application of fire rated Polymer Modified Adhesive layer
@2.8kgs/sqm confirming to standard BS8414 resulting in BR135, duly certified
by LPCB to LPS1581 and holds BBA certification.
Step-2. Supply and application of 50mm thick EPS Insulation board having the
density of 15-18kg/m3 and Thermal Conductivity of 0.030-0.033W/mK over the
adhesive layer.
Step-3. Supply & application of fire rated Polymer Modified Base coat layer
@2.0kgs/sqm over the EPS board confirming to standard BS8414 resulting in
BR135, duly certified by LPCB to LPS 1581 and holds BBA certification.
Step-4. Providing & application of Fibre Reinforcing Mesh, installed within the
polymer modified base coat including an additional layer of High grade Glass
Fibre Reinforcing Mesh for high impact areas at finishes.
TEXTURE PAINT
It is a mixture of natural granite & marble chips powder providing natural stone
colours in approved shade. The finish shall be colourfast, water repellant,
resistant to condensate formation, cover hairline cracks/ crazing, UV & alkali
resistant & ensure good breathability `Protective and decorative coating for
exterior surfaces such as, concrete, plaster, masonry, brickwork, gypsum,
The surface must be dry and mature, new plasters should have been left to
mature at least 30 days to allow complete carbonation. Clean the surfaces and
remove detaching and flaking parts. Surface should be free of water leaks and
humidity.
Protection top coat- one coat of primer and sealer mixed in equal ratio followed
by one coat of basecoat with steel trowel made of natural stone crushed powder.
2nd coat to be applied with steel trowel and finished by acrylic trowel or spray
gun of natural stone crushed powder added with granite chips. Final coat of
ultra-protect shall be applied with roller/ spray diluted with water, the above
procedure must be carried out following closely all application instructions
according to the desired finish.
Application recommendation-
-Apply on putty surface.
-Apply two coat of acrylic putty.
-Apply 1 coat of Primer/wall sealer
-Level the surface and sand until smooth.
-Apply 1 – coats -one coat of basecoat with steel trowel made of natural stone
crushed powder.
-Apply 2 – coats- 2nd coat to be applied with steel trowel and finished by acrylic
trowel or
Spray gun
-Final coat of ultra-protect shall be applied with roller/spray diluted with water.
manufactured by ‘JK Cement’ or equivalent, White Quartz graded fine Silica Sand,
Alkali Resistant Glass Fiber manufactured by 'NEG , Owen Corning ‘Saint Gobain’
or equivalent, Super Plasticizers manufactured by ‘Karochem’ or equivalent,
Polymers manufactured by ‘Nova Polychem’ or equivalent and U.V resistant
Synthetic inorganic pigments should be used for pigmentation manufactured by
‘Phenochem industries or equivalent.
The screens casting shall take place with layering methodology using- Direct
Power Spray machines. The GRC screens flexural strength average Limit Of
Proportionality (LOP) should be above or equivalent to 6 N/mm2 & M.O.R should
be above or equivalent to 15 N/mm2 for tests done on 28 days cured samples.
The fixing of screens should be done using ‘Dry fixing’ method onto structural
support members i.e. R.C.C, Brick work or epoxy primer and epoxy paint treated
mild steel frame works. The fixtures SS 304 grade CLAMPS & SS 304 grade PINS
to be used and Self drilling Screw, fasteners to be used for dry fixing should be
Hilti / Fischer or equivalent. The quantity of fasteners or self-drilling/ tapping
screws shall be calculated in accordance to weight of screen and actual site fixing
conditions. Welding Rod (grade 309) to be used ESAB or equivalent MS to SS.
All Shafts shall provide orange colour safety foot rest 6mm thick plastic
encapsulated as per IS:10910, on 12mm dia steel bar conforming IS:1786, having
cross section as 23mmx25mm over all minimum length 263mm and width
163mm with minimum 112mm space between protruded legs. including fixing in
manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement: 3 coarse
sand: 6 graded stone aggregate 20 mm nominal size) complete as per design,
drawing and specifications.
Q. ROOF SHEETING
4. Reinforcement steel – (Primary RINL, SAIL, TATA Steel Ltd., JSW Steel
Producers)- (Fe500D or more) Ltd., Jindal Steel & Power Ltd.
6. Ready Mix Concrete (RMC) Plant Ultra Tech, ACC, RMC Ready Mix (India)
9. Structural Steel Sections TATA, SAIL, RINL, Jindal Steel & Power
Ltd.,
JSW
10. M.S. Pipe (Railing) Jindal / Tata/ RINL/SAIL
11. Hollow Steel Sections TATA, Jindal, RINL, Jindal Steel & Power
Ltd.,
JSW, SAIL
12. Autoclaved Aerated Concrete M/s. Hyderabad Industries Ltd., M/s. Ultra
Blocks (AAC) Tech India Limited, M/s. Siporex India
Ltd., NCL, ECOREX, DLITE Block, ECOLITE
13. Binding Wire TATA, JSW or equivalent.
14. Factory Made Cement Concrete A.S.R. Cover Blocks, JK, Conbextra, KGM,
Cover Blocks grade M25 and M35 KK Manhole
15. Flush Door Shutters 1S:2202, ply Green ply, Archid Ply, Kitply (Swastic),
wood and block boards Century Ply, DURO
16. Fire Rated Doors (Metal) and Navair, Shakti Hormann, MPP Schrodder,
hardware fiitings.
17. Ply wood / Laminate Greenply, Merino, Archid ply, Centuryply,
Kitply, Greenlam
18. Veneers Greenlam, Merino, Centuryply,Archid
29. Metallic Floor Hardners/ Floor Fosroc, SIKA, Pidilite, ironite, Ferrok,
hardners Hardonate, BASF
30. Polyurethane floorings, wall Fosroc, Ardex endura, BASF, Pidilite.
coats, covings, sealant
31. Precast Cement Concrete Tiles NITCO, Eurocon, Ultra.
32. Factory made Cement Concrete Nitco, Ultra, Rigid tiles, Raj tiles
Interlocking Paver Blocks-
33. Grass Pavers Unistone, Ultra, NITCO
37. High Density Fibre (HDF) Pre- Armstrong, GreenLam, Merino, Action-
laminated Flooring boards Tessa
38. Unglazed Heavy Duty Vitrified Somany (Dura Gres ), Johnson (Endura) or
Tiles equivalent
39. Unglazed Heavy Duty Paver/ Johnson (Endura), Somany ( Dura Stone )
Parking Tiles or equivalent
40. Tile Adhesives, Epoxy Grout, Laticrete, Roff, SIKA, Ardex, Endura,
Silicone Spray, Polysulphide Pidilite, Weber
Sealant
41. Ready Mix Plaster Ultratech/ Fomous Crete/ Saint Gobain
46. Water proofing compound with FOSROC (Conplast 421)/ Dr. fixit: LW+/
cement (for plaster & mortar) Sika: sikacim/ BASF/ Ardex Endura/ CICO
47. Crystalline waterproofing Fosroc crystalline/ Pidilite Dr
compound. Fixitcrystalline/ Sika/ Crystalline/ BASF/
CICO/Ardex endura
48. Polymer Modified Cementitious Bal Endura/ Pidilite Kero Koal/
grout Ultratech/ Ardex/ Ferrous Crete
49. Damp proof material CICO, FOSROC, SIKA
78. Float/ Plain/ Tinted/ Tempered pilkington, Saint Gobain, TATA, AIS
Glass/ Annealed Float Glass/
Float Glass Profile Sheet
(transparent)
79. Mirror Glass. Modi Guard, Saint Gobain, AIS
80. Hydraulic Door Closers / Floor Ozone, Godrej, Hardwyn, Everite, Dorma,
Springs - Hafele, Dorset
81. Ball Bearing Hinges and Spring Dorma, Hafele, Dorset, ozone
Hinges
82. Clamping System Using Dash / Hilti (SS 316 grade ), Fischer, Bosch
Anchor Fastners, Expansion bolt,
stone cladding clamps
83. Locks in Cabinets, Furniture. Hettich, Dorset, Godrej, Harrison, Ozone,
Mortice locks, Multipurpose locks IPSA
84. Four Point / Multi Point Locking Hefele, Dorma, Godrej
Handle.
85. Stainless Steel Friction stay Hafele, Geze, Earl Bihari
hinges
86. Door closer lock/ Panic exit Ozone, Dorma, Monarch, Doortech, Geze,
device Kich, Hafele,Dorset
87. Door Coordinator UL Listed, Monarchor equivalent
88. Precoated galvalume Iron Profile TATA Blue scope, NCL, Lloyd Superdeck,
Sheets JSW, Jindal
89. Multi Walled Polycarbonate Lexan GE, Coxwell, DPI Day lighting
Roofing Sheets System, poly gal, DanPalon
90. Bitumen IOCL, HPCLor equivalent
102. Stainless steel hardware fittings KICH, Ozone, Dorma, Haffle, Hettich
103. Exterior ready mix Plaster Ferrous Crete, Gyproc, Ultratech, saint
gobain
104. Rolling Shutters Shakti Hormann, Toshi Automation, Rama
Rolling Shutters, Jyoti Rolling Shutters
105. Reflective Glass Saint Gobain, AIS Asahi India Glass Ltd.,
pilkington
106. Hermetically-sealed double GSC Trutuf, AIS Asahi India Glass Ltd, ,
Saint Gobain, pilkington
insulated glass
2) Products not mentioned in the above list shall be brought by the contractor
after sample approval by the Engineer-in-charge. Equivalent material and
finishes of any other specialized make may be used provided brand specified
above are not available in the market. These equivalent material and finishes
may be used only after approval of Engineer-in-charge.