0% found this document useful (0 votes)
90 views2 pages

Feeder Protection M1 - NGCP Side - Test Report

1. A feeder protection relay test was conducted on the relay installed at Zamboanga S/S. 2. The test involved injecting current and voltage signals at the secondary of CTs and VTs to check the performance and accuracy of the relay. 3. All tests including CT ratio, VT ratio, directional overcurrent protection stages, and time curves were satisfactory and within acceptance criteria, demonstrating the proper functioning of the relay.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views2 pages

Feeder Protection M1 - NGCP Side - Test Report

1. A feeder protection relay test was conducted on the relay installed at Zamboanga S/S. 2. The test involved injecting current and voltage signals at the secondary of CTs and VTs to check the performance and accuracy of the relay. 3. All tests including CT ratio, VT ratio, directional overcurrent protection stages, and time curves were satisfactory and within acceptance criteria, demonstrating the proper functioning of the relay.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TESTING & COMMISSIONING

FEEDER PROTECTION RELAY


TEST REPORT

F-PMS-CTC-48, Rev 0,08-Aug-2022

Company National Grid Corporation of the Philippines


Plant/Substation Zamboanga S/S
Location Sangali, Zamboanga City, Zamboanga del Sur
Test Date December 06,2023

INSTRUMENT DATA
Make/Brand Omicron
Model No. CMC 356
Serial No. AN148E/102005943
Calibration Date September 21, 2023-2024

RELAY DATA
Relay Function 67P, 67G
Make NR Electric
Model No. PCS-9611s
Serial No. NRJB2153382210012
Settings & Calculation NGCP

RELAY SETTING
Line CT Pri 1000 Line PT Pri 69kV L-L
Line CT Sec 5 Line PT Sec 115V L-L

NOTE: See complete final Relay Setting on a separate sheet.

TEST DATA
1.1 CT MEASUREMENTS (Metering Secondary Injection)
Phase Current Injected (A) Expected Value (A) Measured Value (A) REMARKS

PHASE A 0.1 0.1 0.0997 OK


PHASE B 0.2 0.2 0.1992 OK
PHASE C 0.3 0.3 0.2993 OK
Acceptance Criteria: ±0.2% of I at 0.5×In<I<4.0×In

1.2 VT MEASUREMENTS (Metering Secondary Injection)


Phase Voltage Injected Expected Value Measured Value REMARKS

PHASE A 10 10 9.994 OK
PHASE B 20 20 19.981 OK
PHASE C 30 30 29.986 OK
Acceptance Criteria: 0.2% of V at 5V<U<300V

2.1 DIRECTIONAL OVERCURRENT (67P) Stage 1: I_Set = 8 , t_Op = 0


Measured Time (ms) Measured Time (ms) Measured Time (ms) Measured Time (ms)
PHASE Pickup (A) Drop Off (A) @ 106.3% TAP @ 112.5% TAP @ 118.8% TAP @ 125.0% TAP REMARKS
0ms 0ms 0ms 0ms
PHASE A 8 7.56 46.2 44.9 39.4 38.7 OK
PHASE B 8 7.6 45.1 44.6 39.5 38 OK
PHASE C 8.04 7.598 45.3 44.6 38.9 38.8 OK
Trip Region: Counterclockwise Rotation: from -29° to 150°

Acceptance Criteria: ≤1%×Setting or 40ms (at 2 times current setting)

2.2 DIRECTIONAL OVERCURRENT (67P) Stage 4: I_Set = 1.30A , TMSp = 0.08


Measured Time (ms) Measured Time (ms) Measured Time (ms) Measured Time (ms)
PHASE Pickup (A) Drop Off (A) @ 150% TAP @ 200% TAP @ 300% TAP @ 400% TAP REMARKS
1376ms 802.3ms 504.2ms 398.4ms
PHASE A 1.25 0.975 1398 822.9 523.9 417.3 OK
PHASE B 1.25 0.975 1399 823.6 523.5 417.3 OK
PHASE C 1.25 0.975 1398 822.8 523.4 417.7 OK
Trip Region: Counterclockwise Rotation: from -29° to 150°

Acceptance Criteria: ≤1%×Setting or 40ms (at 2 times current setting)

3.1 DIRECTIONAL OVERCURRENT (67G) Stage 1: I_Set = 13A , t_Op=0


Measured Time (ms) Measured Time (ms) Measured Time (ms) Measured Time (ms)
PHASE Pickup (A) Drop Off (A) @ 103.9% TAP @ 107.7% TAP @ 111.5% TAP @ 115.4% TAP REMARKS
0ms 0ms 0ms 0ms
3IO 13.07 12.35 54.3 44.8 44.4 44.2 OK
Trip Region: Clockwise Rotation: from 30° to -149°

Acceptance Criteria: ≤1%×Setting or 40ms (at 2 times current setting)

3.2 DIRECTIONAL OVERCURRENT (67G) Stage 4: I_Set = .31A , TMSg=0.05


Measured Time (ms) Measured Time (ms) Measured Time (ms) Measured Time (ms)
PHASE Pickup (A) Drop Off (A) @ 161.3% TAP @ 483.9% TAP @ 806.5% TAP @ 1129% TAP REMARKS
728.7ms 218.5ms 164.2ms 140.9ms
3IO 0.3 0.25 768.1 239.9 184 161.3 OK
Trip Region: Clockwise Rotation: from 30° to -149°

Acceptance Criteria: ≤1%×Setting or 40ms (at 2 times current setting)

Remarks:
TESTING & COMMISSIONING
FEEDER PROTECTION RELAY
TEST REPORT

F-PMS-CTC-48, Rev 0,08-Aug-2022

Signatories:
MIESCOR Client
Tested by: RAFAEL M. CUNANAN Reviewed by: JARETTE S. FERNANDO Witnessed by:

Tested by: JOHN CARLO B. IGNACIO Approved by: PORTIA O. IBIAS Approved by: