Operation Manual
Operation Manual
Legal notice
Technical specifications and availability subject to change without notice.
© 2006-2014 Copyright by Siemens Switzerland Ltd
Issued by:
Siemens Switzerland Ltd.
Infrastructure & Cities Sector
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724-2424
www.siemens.com/buildingtechnologies
Edition: 2014-02-18
Document ID: 008838_p_en_--
2
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Table of contents
3
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
4 Operation functions...................................................................................... 35
4.1 Selection and opening / execution .................................................................. 35
4.2 Scrolling ......................................................................................................... 35
4.3 Indication of the position and length of the list ................................................. 36
4.4 Shortcut.......................................................................................................... 36
4.5 Favorites ........................................................................................................ 36
4.6 Entry of numbers and letters ........................................................................... 37
4.7 SintesoView operation modes......................................................................... 38
4.8 Sinteso Mobile operation modes ..................................................................... 39
5 Operation ...................................................................................................... 40
5.1 Log in / Change access level .......................................................................... 40
5.1.1 Polling reports.................................................................................. 41
5.2 ALARM Procedure.......................................................................................... 42
5.3 Procedure in case of Fault .............................................................................. 45
5.4 Switching off / Switching on ............................................................................ 46
5.4.1 Switching a detector zone off / on .................................................... 47
5.4.2 Switching a detector off / on ............................................................. 50
5.4.3 Temporary switching-off ................................................................... 53
5.4.4 Switching off / on the remote transmission Fire ................................ 56
5.4.5 Switching off alarm activation ........................................................... 60
5.4.6 Switching off sabotage evaluation [DE] ............................................ 61
5.5 Logging out from an access level .................................................................... 61
5.6 Switching between 'Manned' / 'Unmanned' operation modes ........................... 62
5.7 Changing visibility ........................................................................................... 63
5.7.1 Deactivating standby........................................................................ 63
5.7.2 Activating / deactivating expanded visibility ...................................... 64
5.8 Main menu / Open menu item ......................................................................... 65
5.9 Execute commands – Basics .......................................................................... 66
5.9.1 Execute commands – General ......................................................... 67
5.9.2 Execute commands – object-oriented .............................................. 68
5.9.3 Executing commands – function-oriented ......................................... 71
5.9.4 Hide command confirmation message.............................................. 71
5.10 Selecting elements or events .......................................................................... 72
5.10.1 Select events ................................................................................... 72
5.10.2 Selection in the topology .................................................................. 73
5.10.3 Searching for elements .................................................................... 75
5.11 Testing ........................................................................................................... 77
5.11.1 Testing detectors ............................................................................. 77
5.11.2 Carry out 'Walk test' ......................................................................... 78
5.11.3 Carry out 'Installation test' ................................................................ 79
5.11.4 Control test ...................................................................................... 79
5.11.5 Testing indicators............................................................................. 81
4
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
5.12 Enabling detector exchanger and tester communication.................................. 81
5.13 Activation / Deactivation / Reset ...................................................................... 83
5.13.1 Activating an alarm indicator (AI)...................................................... 83
5.13.2 Deactivating / Activating alarm devices ............................................86
5.13.3 Activating / resetting zone ................................................................ 87
5.13.4 Activating / deactivating universal control ......................................... 89
5.13.5 Activating evac controls ................................................................... 91
5.14 Show information ............................................................................................ 93
5.14.1 Polling alarm counters / remote transmissions.................................. 93
5.15 Polling reports ................................................................................................ 94
5.16 Entering the configuration ............................................................................... 95
5.17 Auto-configure station ..................................................................................... 96
5.18 Auto-configure line.......................................................................................... 97
5.19 Enabling / blocking SintesoView ..................................................................... 99
5.20 Connecting SintesoView ............................................................................... 101
5.21 Setting up SintesoView link with integrated IP ............................................... 102
5.22 Operating SintesoView ................................................................................. 102
5.23 Specifying the operation mode for Sinteso Mobile ......................................... 103
5.24 Enabling a smartphone ................................................................................. 104
5.25 Removing a smartphone ............................................................................... 105
5.26 Polling / Deleting the event memory .............................................................. 105
5.27 Settings / Administration ............................................................................... 106
5.27.1 Change language .......................................................................... 106
5.27.2 PIN administration.......................................................................... 107
5.27.3 Setting the buzzer volume.............................................................. 108
5.27.4 Adjusting the display brightness ..................................................... 109
5.27.5 Setting time and date ..................................................................... 109
5.28 Entering/Changing customer text .................................................................. 110
5.29 Insert printing paper ...................................................................................... 111
5.30 Switching off the printer ................................................................................114
5.31 Show version ................................................................................................ 114
6 System functions........................................................................................ 115
6.1 Note on the configuration of the local fire detection installation ...................... 115
6.2 Operating condition....................................................................................... 116
6.3 Operation modes .......................................................................................... 116
6.4 Normal operation .......................................................................................... 116
6.5 Test .............................................................................................................. 117
6.5.1 'Detector test' ................................................................................. 117
6.5.2 'Walk test' ...................................................................................... 118
6.5.3 'Installation test' ............................................................................. 118
6.5.4 Control test .................................................................................... 118
6.5.5 Test variants .................................................................................. 119
6.6 Isolation........................................................................................................ 119
6.7 Renovation ................................................................................................... 119
5
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
6.8 Access level and access rights ..................................................................... 120
6.8.1 Managing PINs .............................................................................. 121
6.8.2 PIN input dialog ............................................................................. 121
6.8.3 Logout timeout ............................................................................... 121
6.8.4 SintesoView enabling..................................................................... 122
6.9 Visibility ........................................................................................................ 122
6.9.1 Standby visibility ............................................................................ 122
6.9.2 Expanded visibility ......................................................................... 123
6.10 Sabotage ALARM [DE] ................................................................................. 123
7 Commands with required access levels.................................................... 124
7.1 'Switching on/off' command group................................................................. 124
7.2 Command zone 'Test' ................................................................................... 125
7.3 'Activating/deactivating' command group....................................................... 126
7.4 Command group 'Information' ....................................................................... 127
7.5 'Configuration' command group..................................................................... 128
7.6 'Maintenance' command group ..................................................................... 128
7.7 'Report' command group ............................................................................... 129
7.8 Other commands .......................................................................................... 129
8 List of elements .......................................................................................... 130
9 System description..................................................................................... 132
9.1 Overview ...................................................................................................... 132
9.2 Topology ...................................................................................................... 134
9.2.1 Hardware tree ................................................................................ 134
9.2.2 Detection tree ................................................................................ 135
9.2.3 Control tree.................................................................................... 140
9.2.4 Operating tree................................................................................ 142
9.2.5 Assigning with the hardware tree ................................................... 145
9.2.6 Functional allocation ...................................................................... 146
9.2.7 Network tree .................................................................................. 147
9.3 Acquisition .................................................................................................... 148
9.4 Evaluation .................................................................................................... 149
9.5 Control ......................................................................................................... 153
9.5.1 Universal control ............................................................................ 154
9.5.2 Evacuation control ......................................................................... 155
9.5.3 Extinguishing control with sprinkler................................................. 157
9.5.4 Extinguishing control with extinguishing control unit XC10 .............. 158
9.6 Alarm verification concept (AVC) .................................................................. 159
9.6.1 Attendance check .......................................................................... 160
9.6.2 Investigation time ........................................................................... 160
9.6.3 Example of a verification process ................................................... 160
9.6.4 Fire alarming.................................................................................. 162
6
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
9.7 Intervention concept (IC)............................................................................... 163
9.7.1 Attendance check .......................................................................... 164
9.7.2 Intervention monitoring................................................................... 164
9.7.3 Example of an intervention process................................................ 165
9.7.4 Intervention alarming ..................................................................... 167
9.8 Events .......................................................................................................... 168
9.8.1 Event categories ............................................................................ 168
9.8.2 Event status identification............................................................... 169
9.8.3 Event memory ............................................................................... 169
9.8.4 Message overview ......................................................................... 170
9.9 List representation and list types ................................................................... 170
9.9.1 Event lists ...................................................................................... 171
9.9.2 Element lists ..................................................................................172
9.9.3 Selection lists................................................................................. 172
9.10 Version display for station / configuration data .............................................. 173
10 Faults / Troubleshooting ............................................................................ 174
11 System maintenance .................................................................................. 175
11.1 Maintenance recommendation ...................................................................... 175
11.2 Opening the control panel [DE] ..................................................................... 175
12 Glossary ...................................................................................................... 176
Index............................................................................................................ 181
7
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
8
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
About this document
How displays are represented in the document
1
Scope
This document applies to the fire control panels and the fire terminal of type
Fx20xx, market package MP5.
Target groups
The information in this document is intended for the following target groups:
Operating personnel l Carries out procedures to correctly l No particular basic training is needed.
operate the product. l Has been instructed by the
commissioning personnel.
Commissioning personnel l Configure the product at the place of l Has obtained suitable specialist training
installation according to customer- for the function and for the products.
specific requirements. l Has attended the training courses for
l Check the product operability and commissioning personnel.
release the product for use by the
operator.
l Searches for and corrects malfunctions.
Maintenance personnel l Carries out all maintenance work. l Has obtained suitable specialist training
l Checks that the products are in perfect for the function and for the products.
working order.
l Searches for and corrects malfunctions.
Document identification
The document ID is structured as follows:
ID code Examples
ID_ModificationIndex_Language_COUNTRY A6V10215123_a_de_DE
-- = multilingual or international A6V10215123_a_en_--
A6V10315123_a_--_--
Date format
The date format in the document corresponds to the recommendation of
international standard ISO 8601 (format YYYY-MM-DD).
9
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
About this document
1 How displays are represented in the document
The 'i' symbol identifies supplementary information and tips for an easier way of
working.
10
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
About this document
How displays are represented in the document
1
Zone (1)
Section (2)
Area (3)
Sounder (4)
Physical channel (5)
The table representation has the following key deviations from the
original:
l Font and representation (not inverted)
l Windows are indicated separately without display background
l No bars to indicate the position and list length
l No frame around selection
11
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
About this document
1 Applicable documents
You will also find information about search variants and links to mobile
applications (apps) for various systems on the home page.
See also
2 Glossary [➙ 176]
12
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
About this document
History of changes
1
The first edition of a language version or a country variant may, for example, be
version 'd' instead of 'a' if the reference document is already this version.
p 2014-02-10 Chapters 'Commands with required access levels' and 'LEDs' updated
o 2013-11-14 Edition for MP5
Change to date format according to ISO 8601
New:
PIN administration
Sinteso Mobile
Sinteso Mobile operation modes
Specifying the operation mode for Sinteso Mobile
Enabling a smartphone
Removing a smartphone
Polling the switching-off time
Expiry reminder for temporary switching-off
Polling reports
'Report' command group
Revised:
'Temporary switching-off' for levels 'Zone' and 'Detector', 'Override for different settings' in
'Temporary switching-off', information on 'Temporary switching-off' in 'Switching off a
detector zone' and 'Switching off a detector', menu structure, information on license keys,
operating SintesoView with a PC keyboard, country-specific pre-configuration for 'Counter
control', 'Commands with required access levels'
n 2012-08 Revised: Polling the alarm counter, command group 'Information'
m 2012-05 Edition MP-EN 4.0
Commands revised, Test chapter revised, 'Walk test' new, note concerning buzzer volume
according to EN 54-2 Para. 2.10.2
l 2010-08 Minor corrections in the following chapters: 'Example of a verification process', 'Example of
an intervention process'
k 2010-05 Glossary revised
j 2010-03 MP3.0 edition
History of changes redefined and standardized, GAP new, router station new, CAP
removed, commands revised
i 2009-04 'Auto-configuring station' chapter revised
h 2009-01 edition MP2.1
Sabotage monitoring, maintenance, commands revised, IC fault transfer revised
g 2008-08 Edition for field test
f 2008-07 Safety chapter revised, Expanded Visibility, Standby Visibility, Commands revised
e 2007-09 EVAC changed
d 2007-08 Visualizer renamed SintesoView, details added to how to connect SintesoView
c 2007-07 Commands revised
b 2007-02 Visualizer, EVAC, FBA added
a 2006-09 First edition
13
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Safety
2 Safety instructions
2 Safety
Battery Heat
Signal word
The signal word classifies the danger as defined in the following table:
DANGER DANGER identifies a dangerous situation, which will result directly in death or
serious injury if you do not avoid this situation.
WARNING WARNING identifies a dangerous situation, which may result in death or serious
injury if you do not avoid this situation.
NOTICE NOTICE identifies possible damage to property that may result from non-
observance.
14
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Safety
Safety instructions
2
WARNING
NOTICE
15
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Safety
2 Safety regulations for the method of operation
Electrical installations
WARNING
Electrical voltage
Electric shock
● Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
l Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
l Lock volt-free areas to prevent them being switched back on again by mistake.
l Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
l Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
l Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
l Produce earthing as stated in local safety regulations.
16
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Safety
Safety regulations for the method of operation
2
17
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Safety
2 Standards and directives complied with
NOTICE
WARNING
NOTICE
18
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
Release Notes
3
3 PMI
The following figure shows the PMI of a station (fire control panel or fire terminal).
PMI Station
You can use inscription strips to inscribe the PMI. You will find a template for this
in document 009026.
19
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
3 Buttons on the PMI
<Silence buzzer>
Switches the 'Station' buzzer off.
<Acknowledge>
l Acknowledges all events that can be acknowledged.
l Confirms presence ('AVC', 'IC')
l Switches the buzzer off
<Reset>
Resets all events that can be reset (password required).
20
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
Buttons on the PMI
3
<Premises manned>
l Switches between 'Manned operation' and 'Unmanned operation' operation
modes (password required).
l Opens the event list in case of a "mixed" condition (i.e., visibility on several
'Areas' with different 'Manned operation' and 'Unmanned operation' settings)
<Alarm device>
Deactivates the alarm devices in the event of alarm (password required).
Configurable buttons
The two buttons a and b in the figure above are configurable standard buttons.
You can, for example, configure these two buttons with the following functions:
l 'Poll RT counter'
l 'Non-MCP zones OFF'
21
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
3 Buttons on the PMI
3.1.3 Softkeys
The figure below shows the part of the PMI including the softkeys.
Softkeys are buttons which you can use to carry out functions and which are
displayed in the three fields of the softkey line on the display. These three black
fields contain the names of the functions in white font.
The functions of the softkeys change dynamically depending on the situation and
the contents of the display.
Always the most important functions are assigned to the softkeys 1 and 2.
When the user navigates through the topology, the softkey allocation does not
change depending on the context; the assignment remains fixed. If a softkey
function cannot be executed at a point in the topology, the inscription in the field is
hidden.
'Show intervention text' 1 Shows the intervention text of the selected event.
'Jump back' Displays the list the selected event has been taken from. Back from the view
Intervention text or Details.
'Execute command' Opens the 'Select command' window.
'More options' Opens the 'Select option' window.
'Show details' 2 Shows details of the selected event or element.
'Lower level' Changes to the next lower hierarchy level.
'Upper level ' Changes to the next higher hierarchy level.
'Jump to begin' / 'Jump to end' Within a list, jumps to the top or end of the list
'Show topology ' 3 Jumps to the selected element in the topology.
'Show active detectors' Shows a list of all active detectors, corresponding to an event list.
1 Softkey / Option is only displayed when intervention text is available at this point
2 Softkey / Option available only in 'Access level 3'
3 Softkey / Option available only as of 'Access level 2.1'
See also
2 Normal view [➙ 28]
22
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
Buttons on the PMI
3
Navigation buttons
l The navigation buttons work in the same way as the arrow keys on a PC
keyboard.
l The next entry in a list can be highlighted with the buttons <▲> and <▼>.
l It is possible to change to a higher or lower hierarchy level with the buttons <◄>
and <►>.
l In a command list, the highlighted command can be executed with the button
<►>.
l When characters are entered, the character to the left of the cursor position is
deleted by pressing the button <▲>.
23
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
3 Buttons on the PMI
3.1.5 Keypad
The following figure shows the keyboard and <MENU>, <ok> and <C> (Cancel)
buttons:
2
4 3
1 Keypad 3 <ok>
2 <MENU> 4 <C> (Cancel button)
Numeric entry
Numeric entry is applicable in the following cases:
l PIN entry (password)
l Shortcuts (Menus)
l Address entry (Element ID)
l Parameter entry
Alphanumeric entry
The alphanumerical input is for entering customer text.
See also
2 Log in / Change access level [➙ 40]
24
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
Fire department control and display (FBA) CH
3
1 4
2 5
3 6
FBA
Position Function
1 LED fire alarm (red) Lights up as long as the fire control panel is in the status Fire
alarm.
2 LED fault (yellow) Lights up as long as the fire control panel is in the status Fault.
3 LED remote alarm Lights up when the remote alarming is actuated, until the fire
(red) control panel is reset.
4 Button Silence The acoustic signaling of alarms and faults is switched off upon
audible pressing this button.
5 Button Reset Resets the fire control panel (detector zones incl. alarming
equipment)
6 Key switch Selects operating access for buttons in positions 4 and 5
l Vertical position: locked
l Horizontal position: operations enabled
The 'LED test' function of the fire control panel also activates the LEDs of the FBA
during the test.
25
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
3 EVAC NL
3.3 EVAC NL
Ontruimingsalarm b
Bedrijf
a Uitgeschakeld c
1 Totaal Storing d
Alarm
Zoemer Zone 1
2 uit 7
3 Zone 2
4 Zone 3
Zone 4
5 IN/UIT Zone 5
6 Zone 6
g
Zone 7
f
Zone 8
Selecteer
Zone 9
i Start
e
Zone 10
Stop 2x
Button LED
26
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
EVAC NL
3
LED Function
27
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
3 Display
3.4 Display
The display of the station has two displaying variants:
l Display without window
– Normal view
– Expanded visibility
– Fire department view
l Display with window for following representations
– Lists
– Input fields
– Command responses
001 AAA 1
001 ABC YYYY 1
ABC
2
Identification of messages
Events occurring in the fire detection installation are indicated on the display. A
special identification informs on the status of an event.
You will find details on the identification in the chapter 'Event status identification'.
See also
2 Event status identification [➙ 169]
28
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
Display
3
With the <Switch to Extended view> and the <Switch to Standard view> softkeys,
you can switch from 'Standard view' to 'Extended view' and vice versa.
Alternatively, the navigation buttons <►> and <◄> can be used to switch over.
29
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
3 LEDs
3.5 LEDs
The LEDs on the Person Machine Interface signal 'Events' and conditions. In
addition, the LEDs support the operator's orientation. The LEDs can light up in red,
yellow, or green. The LEDs can be configured according to customer-specific
requirements.
The LED colors can, for example, signal the following information:
Red l ALARM
l Activations, e.g. remote transmission, alarm devices,
control function
Yellow l Fault
l Isolation
l Deactivation, e.g. remote transmission, alarm devices,
control function
Green l System is in operation
Additional information on the conditions of the LEDs (steady on, steady off or
flashing) can be found in the relevant chapter.
30
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
Key switch (optional)
3
See also
2 Logout timeout [➙ 121]
31
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
3 Menu structure
1 Configurable
See also
2 Settings / Administration [➙ 106]
32
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
SintesoView
3
3.8 SintesoView
SintesoView is software for the PC which can be used to display the Person
Machine Interface of a 'Station' on the PC. For example, it can be used to access
the system for maintenance purposes.
Depending on the operation mode, SintesoView can either be used for display
purposes or for display and operation purposes.
The link between SintesoView and a 'Station' can be structured as follows:
l Local connection via any 'Station' in the system
l Connection via the Global Access Point (GAP)
SintesoView is an integrated part of SintesoWorks but may also be installed on a
PC as a stand-alone application 'FXS2009'.
You will need an installed license key and appropriate authorization for the 'Station'
in order to use SintesoView. The license key must support the SintesoView
function. The license key need only be installed in the 'Station' that has the Person
Machine Interface that is to be displayed in SintesoView.
You will find more information about license keys in document 008843. See
chapter 'Applicable documents'.
The connection to a 'Station' with a license key is also possible via a 'Station'
without a license key.
SintesoView has the same visibility as the connected 'Station'. You can use
SintesoView in a system with networked 'Stations' to gain global visibility. Just
one license key is needed for this per network if the license key is installed in a
'Station' with global visibility.
See also
2 SintesoView operation modes [➙ 38]
2 Operating SintesoView [➙ 102]
2 Enabling / blocking SintesoView [➙ 99]
33
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
PMI
3 Sinteso Mobile
You will find more information about 'Sinteso Mobile' in document A6V10415916.
See chapter 'Applicable documents'.
You will need an installed license key and appropriate authorization for the 'Station'
in order to use Sinteso Mobile. The license key must support the 'Sinteso Mobile'
function.
You will find more information about license keys in document 008843. See
chapter 'Applicable documents'.
See also
2 Sinteso Mobile operation modes [➙ 39]
2 Enabling a smartphone [➙ 104]
2 Specifying the operation mode for Sinteso Mobile [➙ 103]
2 Removing a smartphone [➙ 105]
34
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation functions
Selection and opening / execution
4
4 Operation functions
The following chapters contain descriptions of important functions for directly
operating the system.
You will find information on the system functions in the corresponding chapter.
See also
2 System functions [➙ 115]
Button Consequence
See also
2 List representation and list types [➙ 170]
4.2 Scrolling
You can use the navigation keys to scroll through a displayed list in the display.
You can scroll to the start/end of the lists (limited function) and back in the following
lists:
l Option lists
l Command lists
l Element category lists
In all other lists, you can scroll beyond the end of the list to the start of the list and
back.
35
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation functions
4 Indication of the position and length of the list
See also
2 Event status identification [➙ 169]
4.4 Shortcut
A shortcut serves for the direct execution of an entry in a selection list by pressing
a numeric key.
In a command list, for example, you can execute a command directly by entering
the corresponding number.
The numbers for the shortcut are shown in the list entry line, on the right and in
brackets.
4.5 Favorites
You can use favorites to execute several operation sequences or one operating
sequence in an operation sequence.
A maximum of 8 favorites are configured and you can select them from the favorite
list in the 'Favorites' main menu item.
36
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation functions
Entry of numbers and letters
4
Numeric entry
l The number of underscores corresponds to the number of possible positions
for the entry.
l The overwrite mode is set by default; there is no insert mode.
l Horizontal navigation within the input field is possible with the keys <◄> and
<►>.
l Use <▲> to delete the character to the left of the cursor position.
l Use <ok> to save the entered value and exit the input field.
– When there are several input fields in the window, the cursor jumps to the
next field by pressing <ok>.
– If the cursor position is in the last or only input field, close the input dialog
by pressing <ok>.
l Use <C> to cancel the input and close the dialog without saving.
Alphanumeric entry
l Alphanumeric entries are only possible in particular input fields, e.g. for
customer text.
l Letters are entered in the same way as letters on telephones. You can select
the corresponding letter by pressing a key several times.
l Switching between lower and upper case letters is possible with the key <*>
and only applies for the next character.
In input fields with more than one line, you cannot change back to a line above
the cursor position.
37
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation functions
4 SintesoView operation modes
You will find more information about license keys in document 008843. See
chapter 'Applicable documents'.
The LED test also tests the display. However, the LEDs are not displayed in
'SintesoView'.
See also
2 Enabling / blocking SintesoView [➙ 99]
2 Operating SintesoView [➙ 102]
38
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation functions
Sinteso Mobile operation modes
4
You will find more information on configuring 'Visibility' for 'Sinteso Mobile' in
document 009078.
See also
2 Specifying the operation mode for Sinteso Mobile [➙ 103]
39
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Log in / Change access level
5 Operation
In this part of the document you will find brief descriptions and detailed operation
sequences for important functions of the fire detection installation. In addition, you
can find your preferred procedures in the representation of exemplary operation
sequences.
Login/logout
The present 'Access level' is indicated in the main menu in the header of the
display.
40
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Log in / Change access level
5
41
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 ALARM Procedure
42
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
ALARM Procedure
5
1 Press <Acknowledge> on the Person ⇨ With 'AVC' countdown t2 for examination of the
Machine Interface cause of 'ALARM' starts
5 Optional: press <Alarm device> on the ⇨ Deactivates the acoustic alarm devices
Person Machine Interface (password
required)
43
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 ALARM Procedure
Fire department has been Save people Try to prevent fire department
called Guide the fire department to the fire deployment
location
'Fire Brigade in' mm:ss Trigger the manual call point <Press <Reset> (password required)
or
'Call Fire Brigade !' Call the fire department on the phone! <Press <Reset> (password required)
No automatic transmission to
the fire department
44
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Procedure in case of Fault
5
A list of possible 'Faults' and how they are eliminated can be found in the chapter
'Faults / Troubleshooting'. If you cannot eliminate 'Fault', please contact your
service provider.
Acknowledging 'Fault'
1. Press <Acknowledge> before the expiry of t1.
2. Read the 'Fault'location on the display.
3. Go to the 'Fault' location.
4. Rectify 'Fault'.
See also
2 Intervention concept (IC) [➙ 163]
2 Faults / Troubleshooting [➙ 174]
45
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Switching off / Switching on
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
● Deploy staff to monitor the deactivated area.
● You must switch deactivated parts of the 'Site' back on as soon as possible.
46
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Switching off / Switching on
5
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
● Deploy staff to monitor the deactivated area.
● You must switch deactivated parts of the 'Site' back on as soon as possible.
You will find information on temporarily switching off detector zones in chapter
'Temporary switching-off [➙ 53]'.
The fastest method for switching off or on is to enter a known address in the
'Enter address' window.
In the configuration, a standard button can be given the function of directly
opening the menu with the 'Enter address' input dialog to select a detector zone.
In the following exemplary operating sequence the process is shown without a
known address.
47
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Switching off / Switching on
Zone (1)
Area (2)
Section (3)
Sounder (4)
Fire control group (5)
Enter address
Zone ---------
48
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Switching off / Switching on
5
021 Zones
Select command
OFF (2)
OFF/timer (4)
Execute command
OFF
Command executed
See also
2 Execute commands – object-oriented [➙ 68]
49
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Switching off / Switching on
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
● Deploy staff to monitor the deactivated area.
● You must switch deactivated parts of the 'Site' back on as soon as possible.
50
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Switching off / Switching on
5
Area 1 Portaphone AG
Lower Execute
level Commands
51
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Switching off / Switching on
l Select element 'Zone 1', continue with 'Lower level' <softkey 2>
Upper More
level Options
Selecting option
Select command
OFF (1)
Activate alarm indicator (3)
Deactivate alarm indicator (4)
Execute command
OFF
Command executed
52
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Switching off / Switching on
5
Select command
ON (2)
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
● Deploy staff to monitor the deactivated area.
● You must switch deactivated parts of the 'Site' back on as soon as possible.
If a detector has been temporarily isolated and its 'Zone' has been permanently
isolated, the detector is also permanently isolated.
If a detector has been temporarily isolated and its 'Zone' has been temporarily
isolated, the time limit for the isolation of the 'Zone' also applies for the detector.
If all detectors in a 'Zone' have been isolated and the time limit for the isolation of
a detector elapses, the 'Zone' is displayed as switched on.
The 'Temporary switching-off' function can be used to set a time limit for 'Isolation'.
The switched off part of the 'Site' is switched back on automatically after the time
period entered.
53
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Switching off / Switching on
The figures below show an exemplary operation sequence to temporarily switch off
'Section':
1. In the 'Main menu', select the 'Element search' menu item.
2. Select 'Start with category'.
Zone (1)
Area (2)
Section (3)
Detector (4)
RT control (5)
Enter address
Section 1--------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
Select command
54
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Switching off / Switching on
5
Enter duration
05:00
(hh:mm)
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
Execute command
All zones OFF/timer
Command executed
Execute command
Show remaining off time
55
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Switching off / Switching on
The expiry reminder must be configured in 'SintesoWorks' > task card 'Operation'
> 'Global system configuration' > 'Global behaviour' > 'Details' tab.
You will find more information about configuring the expiry reminder in document
'009078'. See chapter 'Applicable documents'.
WARNING
When the remote transmission Fire has been switched off, the fire brigade cannot
be called up in the event of fire!
Fire may spread unhindered.
● Deploy staff to monitor the 'Site'.
● You must switch the 'RT Fire' back on as soon as possible.
The 'RT Fire' is normally switched on and may only be switched off in particular
cases, e.g. for a function check of controls.
56
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Switching off / Switching on
5
LED statuses:
l Off
l Steady on with isolation
l Flashing with fault
Example of switching off 'RT Fire' using 'Topology' main menu item:
Topology Access level 2.1
Exit with <C>
Detection tree (1)
Hardware tree (2)
Control tree (3)
Lower Execute
level Commands
57
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Switching off / Switching on
RT ch. 1
Upper More
level Options
Selecting option
Select command
OFF (1)
Set customer text (3)
Activate (5)
Time limited activation (6)
Execute command
OFF
Command executed
58
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Switching off / Switching on
5
Example of switching off 'RT Fire' using 'On / Off' menu item in
'Functions' menu:
Selecting element category
Zone (3)
Sounder (4)
Fire control group (5)
RT control (6)
Alarming control group (7)
Enter address
Alarmg. ---------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
Select command
59
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Switching off / Switching on
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
● Deploy staff to monitor the deactivated area.
● You must switch deactivated parts of the 'Site' back on as soon as possible.
You can switch off the fire detection installation alarm activation for specific
elements with this function.
Faults such as the removal of a detector are nevertheless evaluated and displayed.
You can only run the 'Alarm evaluation OFF' command on the following
elements:
'XC10 zone'
'Section'
'Automatic zone'
'Technical zone'
60
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Logging out from an access level
5
NOTICE
61
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Switching between 'Manned' / 'Unmanned' operation modes
When there is at least one 'Premises manned' event, the 'Premises manned' LED
is on.
By means of configured switching from 'Manned operation' to 'Unmanned
operation' at predefined times, the operation mode may switch although no
manual switching has been performed.
There is no possibility of an automatic switching from 'Unmanned operation' to
'Manned operation'.
See also
2 Operation modes [➙ 116]
62
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Changing visibility
5
See also
2 Standby visibility [➙ 122]
63
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Changing visibility
See also
2 Expanded visibility [➙ 123]
64
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Main menu / Open menu item
5
Without PIN entry, the 'Main menu' only includes the menu items that are
available without logging-in. To view an extended menu list in the 'Main menu',
you need to log in on a corresponding access level.
See also
2 Menu button [➙ 24]
65
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Execute commands – Basics
Depending on the 'Access level', the possible selection of commands via softkeys
or the 'Main menu' is extended or restricted.
See also
2 Selection in the topology [➙ 73]
2 Searching for elements [➙ 75]
2 Commands with required access levels [➙ 124]
66
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Execute commands – Basics
5
Area (1)
Section (2)
Zone (3)
Sounder (4)
Fire control group (5)
67
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Execute commands – Basics
Enter address
Zone ---------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
021 Zones
Select command
OFF (2)
OFF/timer (4)
Execute command
OFF
Command executed
68
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Execute commands – Basics
5
l Select 'Topology' menu item in the main menu, continue with <ok>
Area 2 Portaphone AG
Lower Execute
level Commands
69
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Execute commands – Basics
Upper Execute
level Commands
Select command
OFF (1)
Activate alarm indicator (3)
Deactivate alarm indicator (4)
Execute command
OFF
Command executed
70
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Execute commands – Basics
5
'Functions' menu
Regarding the following commands with longer execution durations, the window
with the command confirmation messages does not disappear automatically:
l Auto configuration functions
l 'Accept replaced devices'
l 'Read in installed devices'
l 'Read current topology'
l 'Detector line ON'
l 'Restart line'
l 'Detector line OFF'
71
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Selecting elements or events
Selecting events
1. In the 'Main menu', select the 'Event memory' menu item.
a A list with 'Stations' is displayed. The 'Station', where the selection is made
is identified accordingly.
2. Select the 'Station'.
a A list of all events is displayed.
3 0008/0069 AAAAA bb STST 01 4
2 ttt 06-05-19 00:00:01 ttt 06-05-25 08:48:29
06-05-23 09:25:36 GGGGGG
YY 13 VVVVV
1 06-05-22 08:16:05 GGGGGG
ZZ 13 VVVVV
1 Event list
2 Timespan
3 Highlighted entry (0008) of the total number of entries (0069)
4 Selected 'Station'
ALARM (0)
Pre-ALARM (1)
Fault (2)
Isolation (3)
72
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Selecting elements or events
5
You can use the 'Select Date/time range' softkey to enter the timespan.
Whole range
From / to (1)
Today (2)
Yesterday (3)
Last 7 days (4)
Selecting option
73
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Selecting elements or events
Lower Execute
level Commands
Select command
OFF (1)
Deactivate (2)
Poll RT counter (3)
74
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Selecting elements or events
5
75
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Selecting elements or events
Search by category
The tables below indicate steps of the 'Element search' with 'Start with category':
Area (1)
Section (2)
Zone (3)
Sounder (4)
Fire control group (5)
Enter address
Zone 2--------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
Zone 2 Corridor
76
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Testing
5
Search by address
The tables below indicate steps of the 'Element search' with 'Start with address':
Enter address
Address 2--------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
050 Elements
Area 2 Portaphone AG
Section 2 1. floor
Zone 2 Corridor
RT fire 2 RT channel Fire
Execute Execute commands
Commands Topology
5.11 Testing
The following chapters with operation sequences for testing include sample tests.
See also
2 Test [➙ 117]
77
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Testing
See also
2 Enabling detector exchanger and tester communication [➙
81]
78
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Testing
5
WARNING
During the system test, the alarming and fire control are activated!
Personal injury resulting from extinguishing activation
The fire brigade is called up unnecessarily.
● Set the 'Fire controls' to 'Control test' in advance.
● Inform the fire brigade in advance.
Before the 'Installation test' you can set 'Fire controls' to 'Control test'.
See also
2 Testing detectors [➙ 77]
2 Control test [➙ 79]
During the 'Control test', the controls function in the same way as during normal
operation; however, the hardware is not actuated.
The effects of the controls, e.g. the actuation of digital outputs and the sounders or
the execution of commands is ensured, but the respective hardware receives no
signal and is thus not activated.
79
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Testing
Testing a control
1. In the main menu, select the 'Functions' menu item.
a The 'Functions' window is open.
2. Select the 'Test' menu item.
a A list of all element categories on which a command of the 'Test' command
group can be executed is indicated.
3. Select the 'Fire control group' element category.
a The 'Enter address' window is open.
4. Press <ok> without entering an address.
a A list of all 'Fire control groups' is displayed.
5. Select the desired 'Fire control group' and press <softkey 1>.
a The 'Select command' window is open.
6. Select 'Control test'.
a The control test is performed.
Section (2)
Zone (3)
Sounder (4)
RT control (5)
Fire control group (6)
Select command
See also
2 Testing detectors [➙ 77]
80
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Enabling detector exchanger and tester communication
5
You can use the detector exchanger and tester to set a device to ALARM without
enabling detector exchanger and tester communication.
81
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Enabling detector exchanger and tester communication
Canceling enabling
l Proceed as with the enable above but select the 'Disable MC link' command.
82
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Activation / Deactivation / Reset
5
WARNING
WARNING
Activated parts of the system may actuate alarming and universal control devices!
Personal injury resulting from extinguishing activation.
The fire brigade is called up unnecessarily.
● Set the 'Fire controls' to 'Control test' in advance.
● Inform the fire brigade in advance.
83
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Activation / Deactivation / Reset
The example below shows navigation in 'Detection tree' to select a detector and
activate the alarm indicator:
Area 1 Portaphone AG
Lower More
level Options
l Select element 'Section 3', continue with 'Lower level' <softkey 2>
l Select element 'Zone 11', continue with 'Lower level' <softkey 2>
84
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Activation / Deactivation / Reset
5
l Select element 'Detect. 1', continue with 'More Options' <softkey 3>
Selecting option
Select command
OFF (1)
Set customer text (3)
Activate alarm indicator (5)
Select PS MANNED (6)
Select PS UNMANNED (7)
Execute command
Activate alarm indicator
Command executed
85
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Activation / Deactivation / Reset
PMI
When activated alarm devices have been deactivated after an alarm event, they
are automatically re-activated when a new alarm event occurs.
86
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Activation / Deactivation / Reset
5
Activating 'Zone'
1. In the main menu, select the 'Functions' menu item.
a The 'Functions' menu is open.
2. Select the 'Activate / Deactivate' menu item.
a A list of all element categories on which a command of the 'Activate /
Deactivate' command group can be executed is indicated.
3. Select the 'Zone' element category.
a The 'Enter address' window is open.
4. Press <ok> without entering an address.
a A list with all 'Zones' is open.
5. Select an 'Zone' and press <softkey 1>.
a The 'Select command' window is open.
6. Select 'Activate'.
a 'Zone' is activated.
a The window with the command response is open.
l Select 'Activate / Deactivate' function in the main menu, continue with <ok>
Area (1)
Zone (2)
Sounder (3)
RT control (4)
Alarming control group (5)
87
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Activation / Deactivation / Reset
Enter address
Zone ---------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
004 Zones
Zone 1 FSE Zone1
Zone 2 Manual Zone 2
Zone 3
Zone 4
Execute Execute commands
Commands Topology
Select command
Activate (1)
Execute command
Activate
Command executed
After successful activation of a 'Zone', the event 'ALARM' is shown on the display:
'ALARM' event
88
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Activation / Deactivation / Reset
5
Acknowledging 'ALARM'
l Press <Acknowledge>.
a The alarming equipment is switched off.
Execute command
Acknowledge
Command executed
Command response
Reset 'Zone'
1. Press <Reset>.
a The 'Login/logout' window is open.
2. Enter an admissible PIN.
a 'Zone' is reset.
89
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Activation / Deactivation / Reset
Enter address
Fire ct 1--------
OUTFire 1--
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
009 OUTFire
90
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Activation / Deactivation / Reset
5
Select command
OFF (1)
Activate (4)
Execute command
Activate
Command executed
91
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Activation / Deactivation / Reset
Area (1)
Zone (2)
Sounder (3)
Evac control group (4)
Fire control group (5)
Enter address
Evac gr --------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
Select command
Activate/ALERT+EVAC (1)
Activate/EVAC (2)
Activate/ALERT (3)
Deactivate (4)
Execute command
Activate/EVAC
Command executed
92
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Show information
5
Execute command
Poll alarm counter
93
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Polling reports
Poll RT counter
1. Press 'Functions' > 'All functions' in the main menu.
a The 'Select element category' window is open.
2. Select the 'RT control' element category.
a The 'Enter address' window is open.
3. Press <ok> without entering an address.
a A list with all elements of the 'RT' type is open.
4. Select an element and press <softkey 1> 'Execute commands'.
a The 'Select command' window is open.
5. Select the 'Poll RT counter' command.
a The number of remote transmissions is shown.
94
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Entering the configuration
5
95
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Auto-configure station
NOTICE
96
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Auto-configure line
5
NOTICE
Auto-configuring a line:
1. In the main menu, select the 'Topology' menu item.
a The 'Topology' window is open.
2. Select 'Hardware tree'.
a The 'Element' window is open.
3. Select a 'Station' and press the 'Lower level' <softkey>.
a The elements of 'Station' are displayed.
4. Select the corresponding 'FDnet line card (onboard/FCL2001)' module and
press the 'Lower level' <softkey>.
a All lines of 'FDnet line card (onboard/FCL2001)' are indicated.
5. Select a line and press 'More Options' <softkey>.
a The 'Select option' window is open.
6. Select 'Execute commands' and confirm with <ok>.
a The window including the possible commands is displayed.
7. Select the 'Auto-configure line' command and confirm with <ok>.
a The line is auto-configured.
Example of auto-configuration
Main menu Access level 3
Exit with <C>
Message summary (1) Element search (5)
Functions (2) Event memory (6)
Favorites (3) Login/logout (7)
Topology (4) Settings/administration (8)
Function Function LED
On/Off All test
97
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Auto-configure line
Lower More
level Options
98
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Enabling / blocking SintesoView
5
Selecting option
Select command
You will find more information about license keys in document 008843. See
chapter 'Applicable documents'.
99
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Enabling / blocking SintesoView
Enabling SintesoView
w License key is installed.
1. In the 'Main menu', select the 'Functions' menu item.
a The 'Functions' window is open.
2. Select 'Maintenance' and confirm with <ok>.
a A list of all element categories on which a command of the 'Maintenance'
command group can be executed is indicated.
3. Select 'SintesoView'.
a The 'Enter address' window is open.
4. Enter the number of the 'Station on which SintesoView is to be enabled and
confirm with <ok>.
a The 'Select command' window is open.
5. Select the 'Enable full access' command and confirm with <ok>.
a Enabling for viewing and operating the 'Station' with SintesoView is granted.
or
l Select the 'Enable view access' command and confirm with <ok>.
a Enabling for viewing the 'Station' with SintesoView is granted.
The 'Enable full access' and 'Enable view access' commands cannot be selected
when enabling has already been granted. For the purpose of disabling
SintesoView, the 'Disable access' command is available instead in the command
section.
Disabling SintesoView
If SintesoView is enabled but there is no link to SintesoView, you can disable the
enable with the 'Disable access' command. Proceed as described above and select
the corresponding command.
When SintesoView is enabled for operation and the connection with the
SintesoView has been established, each operating attempt on the 'Station' opens
the following window:
l Press <ok>
a Connection with SintesoView is broken.
a Enabling for SintesoView is disabled.
100
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Connecting SintesoView
5
SintesoView has the same visibility as the connected 'Station'. You can use
SintesoView in a fire detection installation with networked 'Stations' to gain global
visibility. Just one license key is needed for this per network if the license key is
installed in a 'Station' with global visibility.
You will find more information about license keys in document 008843. See
chapter 'Applicable documents'.
The possible 'Enable full access' or 'Enable view access' operation modes must be
enabled before connecting to the 'Station'. The possible operation modes can also
be permanently enabled in the configuration with SintesoWorks.
Establishing connection
1. Select in SintesoWorks the task card 'SintesoView'.
2. Select 'SintesoView' > 'Connect' from the menu bar.
101
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Setting up SintesoView link with integrated IP
Option
l Execution of 'SintesoView' with additional parameters (IP address and PIN).
l Save modified program execution as link.
Procedure
w Start 'SintesoView' as own application (FX2020) and not from the
corresponding register in 'SintesoWorks' (FX2030).
1. Right-click on link in 'Start' > 'Siemens' > 'FX2020' > … to go to the executable
'SintesoView' file and copy the link to the clipboard or an editor.
2. Add following parameters to program execution:
- IP address for GAP.
- Host ID for 'FCnet'-'Station' to be viewed with 'SintesoView'.
- PIN for 'Access level' 3.
a Modified program execution with integrated IP is created.
Example:
C:\Program Files\Siemens\F-FX2020\XL_en_1-V2.1>F-FXS2009.exe"
-visualizer ip=192.168.200.1 host=1 pin=0000
l Test program execution command using 'Start' > 'Execute'
102
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Specifying the operation mode for Sinteso Mobile
5
Proceed as for 'Specification of operation mode on the 'Station'' and select the
Select command' command in the 'Disable access' window.
See also
2 Enabling a smartphone [➙ 104]
103
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Enabling a smartphone
You will find more information about 'Sinteso Mobile' in document A6V10415916.
See chapter 'Applicable documents'.
See also
2 Removing a smartphone [➙ 105]
104
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Removing a smartphone
5
105
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Settings / Administration
Depending on the country-specific BDV, either one or two firmware languages are
integrated.
'Change language'
1. In the 'Main menu', select the 'Settings/administration' menu item.
2. Select the 'Change language' command.
a If a second language is not integrated, this information is displayed: 'Only 1
language is available'.
a The language will be changed.
106
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Settings / Administration
5
'Change PIN'
1. In the 'Main menu', select the 'Settings/administration' > 'Manage PINs' menu
item.
2. Select the 'Change PIN' menu item.
3. Enter the PINs in accordance with the input fields and confirm with <ok>.
a The PIN has been changed.
Change PIN
'Create PIN'
w You have the required authorization level.
1. In the 'Main menu', select the 'Settings/administration' > 'Manage PINs' menu
item.
2. Select the 'Create PIN' menu item.
3. Enter an admissible access level.
4. Enter the PIN in accordance with the input fields and confirm with <ok>.
a A new PIN has been created.
Create PIN
Access level: __
Enter PIN: ****
Verify PIN: ****
107
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Settings / Administration
'Delete PIN'
w PIN is present.
w You have the required authorization level.
1. In the 'Main menu', select the 'Settings/administration' > 'Manage PINs' menu
item.
2. Select the 'Delete PIN' menu item.
3. Enter the PIN in accordance with the input fields and confirm with <ok>.
a PIN has been deleted.
Delete PIN
NOTICE
As per EN54-2, the minimum sound level at a distance of 1 m must reach the
following values, measured under open air conditions:
-60 dB (A) for announcing fire alarm signals
-50 dB (A) for announcing fault messages
108
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Settings / Administration
5
25-04-09 12:42:58
(dd-mm-yy) (hh:mm:ss)
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
109
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Entering/Changing customer text
Once customer text has been entered or changed, the updated display is only
shown the next time the element is accessed.
Entering or changing customer text does not lead to a reboot.
See also
2 Entry of numbers and letters [➙ 37]
2 Selecting elements or events [➙ 72]
110
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Insert printing paper
5
111
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Insert printing paper
Please make sure that the side that will be unwound is at the back of the drum,
corresponding to the dashed line in the figure below.
112
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
Switching off the printer
5
Closing printer
1. Pull some of the paper out of the printer.
2. Hold the paper end upwards.
3. Close the printer by holding the bracket upwards until the clips audibly engage.
a The printer is ready.
Closing printer
Printer is ready
113
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Operation
5 Switching off the printer
Version indication
1. In the main menu, select the 'Topology' menu item.
a The three partial trees of the topology tree are indicated.
2. Select 'Hardware tree'.
3. Select the 'Station'.
4. Press the 'More Options' softkey.
a The 'Select option' window is open.
5. Select 'Show details'.
a The version of the 'Station' and configuration data are indicated.
114
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System functions
Note on the configuration of the local fire detection installation
6
6 System functions
See also
2 Event categories [➙ 168]
Parameter Configuration
115
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System functions
6 Operating condition
'Manned operation'
In the 'Manned operation' operating mode, events can be processed via 'AVC' or
'IC'.
The remote transmission of an 'ALARM' may be delayed, for example, and an
operator may verify 'ALARMS' or 'Faults' that have occurred.
116
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System functions
Test
6
'Unmanned operation'
In 'Unmanned operation' operating mode events are directly handled in accordance
with the configuration, without taking into account the 'AVC' or 'IC'.
This means e.g. that remote transmission of an 'ALARM' is effected without delay.
Global alarming is activated immediately.
See also
2 Intervention concept (IC) [➙ 163]
2 Alarm verification concept (AVC) [➙ 159]
6.5 Test
FS20 offers various test functions for efficient testing of instruments and logical
functions. Some test methods can be combined, others have to be carried out
individually.
The fire detection installation is in 'Test' operating mode if one of the following test
modes is activated:
l 'Detector test'
l 'Walk test'
l 'Control test'
l 'Installation test'
l Test variants
See also
2 Testing [➙ 77]
117
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System functions
6 Test
118
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System functions
Isolation
6
Alarm simulation
An alarm can be simulated by activating a detector zone via a command. With this,
'Pre-ALARM' and alarm can be activated.
6.6 Isolation
You can switch off 'Zones' with automatic or non-automatic detectors in special
situations, e.g. during construction work.
When parts of the fire detection installation are switched off, the fire detection
installation is in 'ISOLATION' condition and operating mode.
The 'ISOLATION' LED on the Person Machine Interface is on.
In 'ISOLATION' operating mode neither 'ALARMS' nor 'Faults' from the parts that
have been switched off can be evaluated.
See also
2 Switching off / Switching on [➙ 46]
6.7 Renovation
In ' --Renovation mode' operating mode the detector parameter sets are changed
as follows:
l No evaluation possible by the optical part of the detector.
l A static evaluation by the thermal part of the detector is possible, however,
without the evaluation of the temperature difference.
The 'ISOLATION' LED on the PMI is on as soon as a part of the installation has
been set to ' --Renovation mode'.
119
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System functions
6 Access level and access rights
A list of all commands and the required access levels can be found in the
corresponding chapter.
The following table shows examples of main menu items and the access levels
needed for execution
'Message summary' 1
'Functions' 1, 2.1, 2.2, 3, depending on the function
'Favorites' 1, 2.1, 2.2, 3, depending on the favorite
'Topology' 1
'Element search' 1
'Event memory' 2.1
'Login/logout' 1
'Settings/administration' 3
120
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System functions
Access level and access rights
6
When the key switch is in position 'On', the logout timeout function is deactivated.
See also
2 Logout timeout [➙ 121]
2 Commands with required access levels [➙ 124]
The PIN input dialog is indicated automatically if the activation of a button on the
PMI requires a higher access level.
See also
2 Log in / Change access level [➙ 40]
121
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System functions
6 Visibility
See also
2 Enabling / blocking SintesoView [➙ 99]
6.9 Visibility
Several fire control panels and fire terminals ('Stations') can be integrated into a fire
detection installation. The visibility defines which part of a fire detection installation
on 'Station' is visible and can be operated.
The visibility for a fire control panel can be configured in the following topology
levels of a fire detection installation:
l 'Site'
l 'Station'
l 'Area'
The visibility for this 'Station' is configured by selecting and assigning event
categories from the topology to the visibility for this 'Station'.
For example, all the 'ALARMS' for the 'Site' or just the 'Faults' for the 'Area' of a
'Station' are indicated.
Two other modes are available for configuring the visibility:
l 'PMI standby visibility'
l 'PMI expanded visibility'
See also
2 Changing visibility [➙ 63]
2 Event categories [➙ 168]
See also
2 Deactivating standby [➙ 63]
2 Expanded visibility [➙ 123]
122
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System functions
Sabotage ALARM [DE]
6
Possible dependencies
l 'PMI expanded visibility' can only be activated if a monitored 'Station' fails.
See also
2 Activating / deactivating expanded visibility [➙ 64]
See also
2 Opening the control panel [DE] [➙ 175]
2 Switching off sabotage evaluation [DE] [➙ 61]
123
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Commands with required access levels
7 'Switching on/off' command group
124
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Commands with required access levels
Command zone 'Test'
7
125
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Commands with required access levels
7 'Activating/deactivating' command group
126
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Commands with required access levels
Command group 'Information'
7
127
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Commands with required access levels
7 'Configuration' command group
128
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Commands with required access levels
'Report' command group
7
129
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
List of elements
8
8 List of elements
Element short text / long text Definition
'Zone' / 3. level of the 'Detection tree'; decision on alarm is taken on this level
'Zone'
'Detect.' / Lowest level in 'Detection tree'
'Detector'
'Control' / General control
'Control'
'Evac ct' / 3. level in 'Control tree'
'Evac control'
'Evac gr' / 2. level in 'Control tree'
'Evac control group'
'Fire ct' / 3. level in 'Control tree'
'Fire control'
'Fire gr' / 2. level in 'Control tree'
'Fire control group'
'RT fire' / 3. level in 'Control tree'
'RT fire control'
'RTfault' / 3. level in 'Control tree'
'RT fault control'
'RT 1' … 'RT 8' / 3. level in 'Control tree'
'RT 1 control' … 'RT 8 control'
'Alarmg.' / 2. level in 'Control tree'
'Alarming control group'
'Sounder' / 3. level in 'Control tree'
'Sounder control'
'Sounder' / 2. level in 'Control tree'
'Sounder'
'Phased' / Lowest level in 'Control tree'
'Phased sounder '
'Evac' / Lowest level in 'Control tree'
'Evac sounder'
'Sounder' / Lowest level in 'Control tree'
'Sounders' alarming control
'Sounder' / Lowest level in 'Control tree'
'Sounders' fire control
'Station' / Highest level in 'Hardware tree'
'Station'
'Station' / 'Station' network
'Station'
130
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
List of elements
8
131
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Overview
9 System description
This part of the document includes information on the setup and functions of the
fire detection installation.
9.1 Overview
Acquisition ►► Evaluation ►► Alarming and control
Remote transmission
Acquisition
Fire detectors detect fire phenomena, e.g. smoke, heat or carbon monoxide, and
transmit signals to the control panel in the form of different danger levels.
132
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Overview
9
133
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Topology
Alarming
The different fire alarms and system events are verified independently from one
another. Depending on the configuration, local alarming or direct or delayed global
alarming is actuated.
l Local alarming:
Local alarming equipment (e.g. acoustic or optical alarm devices) is actuated in
order to call up immediately available intervention personnel (e.g. in-house
staff) and to alert people of a possible fire hazard.
l Global alarming:
Global alarming equipment (e.g. remote transmission) is actuated and external
intervention forces (e.g. the fire brigade) are alerted.
The following points influence the type of alarming:
l Configuration of the alarming process
l Position of 'Manned operation'/'Unmanned operation' operation mode
– 'Manned operation': Personnel present on site
– 'Unmanned operation': No personnel present on site
l Type of alarm activation (automatic or manual)
Control
In the event of fire it makes sense to initiate first, decisive actions automatically.
Automatic measures are carried out by controls, e.g. by the control of building
services, evacuation or extinguishing.
9.2 Topology
The configuration of an 'FS20' fire detection installation is created in the following
structure trees:
l 'Hardware tree'
l 'Detection tree'
l 'Control tree'
l 'Operation tree'
l 'Network tree'
The structure is created by installing in the building and configuring the fire
detection installation. The elements of the individual structure trees are assigned to
one another via channels.
Thanks to a hierarchical topology and arrangement into zones, events can be
assigned geographically and shown accordingly. This enables commands to be
given to consolidated parts of the site, for example.
134
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Topology
9
1 'Station'
2 'Module'
3 'Device'
Dotted line 'Line'
135
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Topology
1 'Area'
2 'Section'
3 'Zone'
4 'Channel'/ 'Detector'
'Area'
l 'Area' typically corresponds to a building.
l 'Area' combines 'Sections' which are subject to the same 'Manned
operation'/'Unmanned operation' operation mode.
l 'Area' actuates the alarming equipment (acoustic and optical alarming devices
as well as remote transmission).
l 'Area' is assigned the following functions:
– 'Manned operation'/'Unmanned operation' operation mode
– Switching assigned 'Sections' on/off
Several 'Areas' are possible per control panel:
l FC2020, FC2030, FC2040: up to four 'Areas'
l FC2060: up to eight 'Areas'
There is an 'Area' that groups together the functions of alarm verification (AVC),
e.g. collective alarms and degraded mode operation.
136
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Topology
9
'Section'
l 'Section' combines 'Zones' to form logical units. Such a unit can be e.g. a floor
or a staircase.
l 'Section' is assigned the following function:
– Switching assigned 'Zones' on/off
'Zone'
l 'Zone' generally combines the detectors in a room.
l 'Zone' evaluates the danger levels transmitted by the detectors. The configured
combination of different danger levels defines the conditions upon which an
'ALARM' is triggered.
l The following fire alarm zone types exist:
– 'Automatic zone'
– 'Manual zone'
– 'Technical zone'
– 'FSE zone'
– 'Flow switch zone' (sprinkler)
– 'Sub-system zone'
l The following extinguishing zone types exist:
– 'Sprinkler zone'
– 'XC10 zone'
'Channel'
The 'Channel' in 'Detection tree' represents the functionality of the inputs and
outputs of an FDnet device.
'Area'
l 'Manned operation'
In 'Manned operation' operating mode, operating personnel are present and
can investigate the fire location. The detectors are set to normal sensitivity, in
accordance with the selected parameter set.
l 'Unmanned operation'
In the 'Unmanned operation' operating mode, there are no operating personnel
present to investigate the fire location. The sensitivity level of the detectors or
their parameter sets are typically increased by switching to 'Unmanned
operation' operating mode.
The settings for the 'Manned operation'/'Unmanned operation' operation modes are
defined in the chapter Alarm Verification Concept (AVC).
137
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Topology
'Zone'
l Switched on (normal operation)
Danger levels are evaluated and 'ALARMS' produced in normal operation. The
detectors have a normal sensitivity level, in accordance with the selected
parameter set.
l Switched off
If a 'Zone' is switched off, the channels assigned to the 'Zone' are isolated. No
signals are evaluated, neither danger levels nor 'Faults'.
There are two isolation functions:
– Isolation without time limits
– Isolation with time limits
l 'Renovation'
To avoid false alarms during renovation work (when emissions may be
generated), the 'Renovation' parameter set can be selected for the 'Zone'. In
this mode, the detectors are operated at a low sensitivity level. In the
'Renovation' operating mode, danger levels are evaluated.
l 'Detector test'
In the 'Detector test' operating mode, detectors can be actuated for test
purposes. When a detector is triggered, a test activation message is generated.
Alarm devices or controls are not activated.
The following devices are activated:
– Internal alarm indicators
– External alarm indicators in accordance with the configuration
– Base sounders if they are in the base of the activated detector
During testing the detectors must react quickly so that the holding times are
short. During the 'Detector test', the detectors are switched to increased
sensitivity with the 'Test' parameter set for this purpose.
After terminating the 'Detector test' operating mode, the detectors and
'Zones'are reset to the condition they were in before the 'Detector test'.
l 'Installation test'
An 'Installation test' can be performed during normal operation. The alarm
devices and controls are activated.
In the test the detectors must react quickly so that the holding times are short.
During the 'Installation test', the detectors are switched to increased sensitivity
with the 'Test' parameter set for this purpose.
After terminating the 'Installation test' operating mode, the detectors and
'Zones'are reset to the condition they were in before the 'Installation test'
operating mode.
'Channel'
l Switched on (normal operation)
In the normal operation, the danger levels of the detector as well as any 'Faults'
are transmitted to the 'Zone' for evaluation.
l Switched off
If a 'Channel' is switched off, no signals are forwarded to the 'Zone', neither
danger levels nor 'Faults'.
138
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Topology
9
139
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Topology
140
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Topology
9
C 'Control tree'
1 5 control groups (a - e)
2 Controls
3 Devices and remote transmission, 2 circuits
Lines Logical link
Arrows Signal transfer
a 'Evac control group'
b 'Fire control group' e.g. for door controls
c 'Fire control group' for alarm indicators (external AI)
d 'Fire control group' for commands
X E.g. isolation, commands to other installation parts
e 'Alarming control group' for alarm devices and remote transmission
Y Local or global alarming
141
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Topology
142
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Topology
9
Mimic display
There are two possible ways of configuring the LED indicator (internal) FTO2002
and the LED module FTO2008-A1:
l Visibility of the 24 LED groups (red/yellow) or (red/green, yellow) on a Section
or Zone.
l Visibility of each of the 48 LEDs on any event.
Event printer
The event printer logs all system events in the configured view.
143
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Topology
144
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Topology
9
Geographical allocation
Each device in the 'Hardware tree' has a unique address. In 'Detection tree', it is
possible to allocate room x on floor y to the device, for example.
D 'Detection tree'
L Link
HW 'Hardware tree'
The physical and the logical channel of a device are assigned between the
'Detection tree' and 'Hardware tree'.
The physical channel is the lowest level in the 'Hardware tree' and maps the
physical function of a device.
The logical channel is the lowest level in the 'Detection tree' and maps the logical
function of a device.
145
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Topology
D 'Detection tree'
C 'Control tree'
L Link
HW 'Hardware tree'
a-e Control groups
f Controls
X E.g. isolation, commands to other installation parts
L Local alarming
Alarming equipment (e.g. acoustic or optical alarm devices) is actuated in order
to call up immediately available intervention personnel (e.g. in-house staff) and to
alert people of a possible fire hazard.
G Global alarming
Alarming equipment (e.g. remote transmission) is actuated and external
intervention forces (e.g. the fire brigade) are alerted.
Visualization of the link from causes and effects via controls
Lines Signal transfer or logical link
146
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Topology
9
Networking types
The stations in the fire detection system can be networked in the following ways:
l SAFEDLINK (system bus)
l SAFEDLINK, extended: coupling of several SAFEDLINK sub-nets via
FCnet/LAN (optical Ethernet)
l Electric Ethernet (does not comply with EN 54)
l SAFEDLINK and Ethernet mixed (does not comply with EN 54)
Connection types/functions
The stations in the network can have the following connection types/functions:
l Stand-alone station
l SAFEDLINK station: station in the SAFEDLINK network
l Router station: station in the SAFEDLINK sub-net connected to the FCnet/LAN
l Ethernet station: station in the Ethernet sub-network to which no more stations
are connected via SAFEDLINK
l GAP station: Station in the network for connecting to a management station
(BACnet client)
– The GAP station has the function of a DHCP server (configurable)
– The DHCP server automatically issues IP addresses to the clients from a
defined IP address space. This enables a PC to receive local access, for
example
l A route to an external IP router can be defined for the GAP station
Extended networking
Extended networking is the merging of several SAFEDLINK sub-nets via
FCnet/LAN, which is managed as optical Ethernet in loop topology.
The sub-networks communicate via the router stations.
Private/external network
l Private network: FS20fire detection installations have their own cabling. The IP
addresses come from a reserved range for private networks
l External network: Fire detection installations can be incorporated in an existing
IT infrastructure as sub-nets
l Integration in an external network does not comply with EN 54
You will find more information about license keys in document 008843. See
chapter 'Applicable documents'.
147
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Acquisition
9.3 Acquisition
The detectors detect the fire phenomena, e.g. smoke, heat or carbon monoxide,
and transmit the danger level to the 'Zone'.
D 'Detection tree'
a Detector / channel
b 'Zone'
0…3 Danger levels
Automatic Manual
0 No danger No danger No danger No danger (entry contact opened)
1 Possible danger Button not Detector line resetting –
pressed
2 Probable danger – Alarm verification of the Danger
first alarm is running l Input contact closed
l Input configured as not relevant for
degraded mode
3 Highly probable Button pressed, Highly probable danger Danger
danger danger l Input contact closed
l Input configured as not relevant for
degraded mode
Danger levels
148
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Evaluation
9
9.4 Evaluation
The evaluation of the danger level and the decision to trigger an 'ALARM' or not
takes place on 'Zone'.
The danger levels of several alarming detectors are combined in the 'Zone'. The
following zone types exist:
l 'Manual zone'
l 'Automatic zone'
l 'Technical zone'
l 'FSE zone'
l 'Sprinkler zone'
l 'XC10 zone'
D 'Detection tree'
1 'Area'
2 'Section'
3 'Zone'
m 'Manual zone'
ax Automatic detector group with multi-detector dependency
a1 Automatic detector zone with single-detector dependency
I/O 'Technical zone'
Dashed arrows 'ALARM'/'Pre-ALARM'
149
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Evaluation
'Manual zone'
A 'Manual zone' combines the 'Manual call points'. Danger signals are evaluated by
means of an OR relation. Each detector of a 'Manual zone' can generate 'ALARM',
but not 'Pre-ALARM'.
'Automatic zone'
A 'Automatic zone' combines 'Automatic detectors'. The 'Automatic zone' can
generate 'Pre-ALARM' and 'ALARM'. A distinction is made between the following
detector dependencies:
l Multi-detector dependency
With multi-detector dependency, the danger levels of several detectors are
linked (AND relation) and evaluated. A 'Pre-ALARM' or 'ALARM' is generated
when the defined danger levels have been reached.
Several evaluation variants are possible in multi-detector dependency.
l Single-detector dependency
With single-detector dependency the danger levels of one or more detectors
are linked (OR relation). A 'Pre-ALARM' or 'ALARM' is generated as soon as at
least one detector has reached the defined danger level.
Alarm levels
'Technical zone'
In a 'Technical zone', inputs for technical messages are combined, e.g. fault or
danger by extraneous equipment.
'FSE zone'
A release element is assigned to this zone. With the release element, a fire alarm
is generated manually, which in turn releases the lock to the 'Key depots' with the
keys for the building. To operate the release element, a key is required which is
exclusively in the possession of the fire department.
150
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Evaluation
9
'Sprinkler zone'
A sprinkler system is a piping system that is terminated at several locations with
sprinkler heads. It is normally fed by the public network of hydrants.
The sprinkler station is installed directly after the house feed. It separates the
sprinkler network from the hydrant network due to overpressure in the sprinkler
network.
The sprinkler station signals when the sprinkler network is opened somewhere and
water begins to flow. This condition is reported to the fire control panel via a
contact (or two as an option) and triggers an alarm with immediate response from
the fire brigade.
In larger sprinkler systems, the piping system is distributed over several floors and
the supply network has an outlet on every floor. Flow rate indicators are built into
each outlet.
The flow rate indicators generate a signal when there is a flow.
D 'Detection tree'
F Flow rate indicator
S Sprinkler station with one or two contacts (cause)
H Hydrant network
ZF 'Flow switch zone'
ZS 'Sprinkler zone'
Arrows Signal transfer
151
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Evaluation
'XC10 zone'
Extinguishing is actuated and monitored by the autonomous extinguishing control
unit XC10.
An interface to the extinguishing control unit makes it possible to send
extinguishing control unit functions to the fire control panel, and to transmit
commands from the fire control panel to the extinguishing control unit.
D 'Detection tree'
XC10 Extinguishing control unit
I Extinguishing control unit inputs: 'Extinguishing activated', 'Fault', 'Pre-alarm',
'Autom. + manual extinguishing OFF'
O Extinguishing control unit outputs: 'Reset', 'Autom. Blocking extinguishing
activation, 'Autom. + manual extinguishing activation blocked'
Z 'XC10 zone'
You will find detailed information in the Technical manual for the extinguishing
control unit XC10, document 008399.
152
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Control
9
9.5 Control
Alarm events and system events may occur in a fire detection installation. It is the
task of the fire control unit to alert people and/or initiate appropriate actions based
on the different event categories. This is achieved with the different control types:
l Alarming control
l 'Fire control'
l 'Evac control'
l Extinguishing control
The alarming control is described in the chapter "Alarm Verification Concept
(AVC)".
Sample control
I Causes
F Control
O Effects
E Events ('ALARM', 'Fault', 'Isolation', test mode, etc.)
act / deact Activate / deactivate
com Command
Causes are any events such as 'ALARM', 'Fault', 'Isolation', test mode as well as
signal inputs (contacts).
The control has an "OR / AND / NOT" combination of the causes that have
occurred.
The effects of the control are the activation or deactivation of outputs. The actuated
outputs can be combined with inputs for confirmation.
Effects are also commands within the fire detection system, e.g. for the isolation of
a 'Zone' or for changing a detector parameter set.
153
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Control
D 'Detection tree'
C 'Control tree'
b 'Fire control group'
f 'Fire control'
HW 'Hardware tree'
154
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Control
9
D 'Detection tree'
C 'Control tree'
a 'Evac control group'
f 'Evac control'
HW Hardware
155
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Control
3 'Alert' → → → 'Evac' → → →
2 'Alert' → → → 'Evac' → → →
1 'Alert' → → → 'Evac' → → →
EG 'Alert' → → → 'Evac'
UG 'Alert' 'Evac' → → →
156
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Control
9
D 'Detection tree'
F Flow rate indicator
S Sprinkler station with one or two contacts (cause)
H Hydrant network
ZF 'Flow switch zone'
ZS 'Sprinkler zone'
Arrows Signal transfer
157
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Control
C 'Control tree'
b 'XC10 zone'
f Extinguishing control
XC10 Extinguishing control unit
I Extinguishing control unit inputs: 'Extinguishing activated', 'Fault', 'Pre-alarm',
'Autom. + manual extinguishing OFF'
O Extinguishing control unit outputs: 'Reset', 'Autom. Blocking extinguishing
activation, 'Autom. + manual extinguishing activation blocked'
158
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Alarm verification concept (AVC)
9
159
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Alarm verification concept (AVC)
If the 'ALARM' is not reset within the given time t2, 'Immediate global alarming' is
activated.
160
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Alarm verification concept (AVC)
9
mx m
t1.. q t2.. r
?
qx rx
..t1 X ..t2 X
GA
Alarm verification
161
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Alarm verification concept (AVC)
Alarm devices
For local and global alarming, acoustic alarm devices, strobes, digital outputs, etc.
can be used. The tone of the alarm devices can be configured differently for local
and global alarming (the alarm devices must be suitable for this).
Remote transmission
The alarm message is transmitted to an intervention station. In the case of local
alarming, this is usually the company fire brigade and for global alarm usually the
state fire brigade. A remote transmission device must be used to transmit alarm
messages via the public telephone network.
The alarm devices and the remote transmission can be separately configured for:
l Alarm type (only with automatic zones)
– 'Pre-ALARM'
– 'ALARM'
l Zone type (only with 'ALARMS')
– Manual alarm
– Automatic alarm
– Degraded fire alarm
162
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Intervention concept (IC)
9
l Operating mode:
– 'Manned operation'
– 'Unmanned operation'
l Alarming type:
– 'Local alarming only'
– 'Delayed alarming'
– 'Global alarming only'
D 'Detection tree'
HW 'Hardware tree'
IC 'Intervention Concept'
a Events from 'Hardware tree'
b Events from 'Detection tree' and 'Control tree'
L Link
163
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Intervention concept (IC)
The 'Intervention Concept' ('IC') is an integral part of the fire control panel and
takes into account the interaction of the operating personnel. The 'Intervention
Concept' can be used to define an intervention process which is initiated should an
event occur or once a particular delay time has lapsed.
For each of the following event categories the behavior can be defined separately:
l 'Fault'
l 'Isolation'
l Test
l 'Technical message'
l 'Activation'
l 'Information'
The 'Intervention Concept' has two independent, parallel intervention processes:
l Attendance check (t1)
l Intervention monitoring (ts)
The intervention process can be configured according to the 'Manned
operation'/'Unmanned operation' operating mode.
164
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Intervention concept (IC)
9
165
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Intervention concept (IC)
The figure below shows an exemplary intervention process for the 'Fault' event
category.
A B
t1.. ts..
! !
..t1 X ..ts X
G S
166
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Intervention concept (IC)
9
Alarm devices
Alarm devices, strobes, digital outputs, etc. can be used for local and global
alarming. The tone of the alarm devices can be configured differently for local and
global alarming.
Remote transmission
For service intervention the event message is transmitted to intervention forces, in
general the maintenance personnel. A remote transmission device must be to
transmit event messages via the public telephone network.
Intervention alarming
167
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 Events
The alarm devices and the remote transmission can be separately configured for:
l Operating mode:
– 'Manned operation'
– 'Unmanned operation'
l Immediate intervention:
– 'Local intervention only'
– 'Delayed intervention'
– 'Global intervention only'
l Service intervention:
– 'Delayed intervention'
– 'Direct intervention'
9.8 Events
See also
2 Event memory [➙ 169]
168
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Events
9
Labeling Meaning
See also
2 Select events [➙ 72]
169
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 List representation and list types
In the 'Message summary' main menu item only those message categories in
which messages (events) have actually occurred are indicated.
After pressing the short-cut button (2) the detailed view of the 'Pre-ALARM'
message category is indicated:
170
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
List representation and list types
9
In the 'Message summary' main menu item only those event categories are
indicated in which events have actually occurred.
In accordance with the event categories, there are the following event lists:
l 'ALARM'
l 'Pre-ALARM'
l 'Fault'
l 'Isolation'
l Test
l 'Technical message'
l 'Activation'
l 'Information'
All events are also included in the event list in the 'Event memory'. This 'Event
memory' list has a different layout as well as additional functions. For this reason,
a separate chapter 'Event memory' is included.
See also
2 Event memory [➙ 169]
171
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
9 List representation and list types
025 Elements
station 1
Area 1
PMI 1
Network 1
Execute Execute commands
Commands Topology
Details of Station 1
Select command
172
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System description
Version display for station / configuration data
9
See also
2 Show version [➙ 114]
173
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Faults / Troubleshooting
10
10 Faults / Troubleshooting
If the site displays 'Fault', you will find in the table below a list with possible 'Faults'
including information on possible causes.
If a 'Fault' cannot be rectified with the help of these operation instructions, please
contact the service engineer.
With all other 'Faults', the service provider in account must be contacted.
See also
2 Insert printing paper [➙ 111]
174
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
System maintenance
Maintenance recommendation
11
11 System maintenance
Regular maintenance of the 'Site' is necessary in order to ensure the system will
function reliably.
The fire detection installation has a reminder function that informs you of imminent
maintenance. When the service reminder is displayed, regular maintenance by the
service technician is required.
NOTICE
See also
2 Switching off sabotage evaluation [DE] [➙ 61]
175
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Glossary
12
12 Glossary
Term Definition
A
Addressed detector line Detector line technique which gives each device its unique address. → Collective detector line
AI Abbreviation for → Alarm indicator.
Alarm device Element in the fire detection system for acoustic and/or visual alarming, e.g. alarm sounder,
beacon.
Alarm indicator Visual display to signal an alarm or pre-alarm.
Alarm organization Covers all measures which are used for alarming, rescue, preventing a fire from spreading, fire
fighting, and orientation in the event of a fire. Alarm organization may differ depending on the
→ 'Manned' or → 'Unmanned' operation mode. → Alarm verification concept
Alarm verification concept Concept for preventing false alarms which takes into account the interaction of the operating
personnel in the alarming sequence.
Alarming control Monitoring and controlling the alarming equipment
Alarming equipment Alarm devices and transmission equipment
Area The top level in the → Detection tree. Assigned to the area are → Sections and → Zones.
Auto-configuration A zone is created for each sensor channel (automatic detector and manual call point). A control
is created for each alarm sounder. IO-modules, FT2010, FT2011, and external alarm indicators
are not auto-configured.
Automatic fire detector Device which measures a physical parameter (e.g. warmth) in order to detect a fire.
AVC Abbreviation for Alarm Verification Concept → Alarm verification concept
B
BACnet Abbreviation for 'Building Automation and Control Networks'. It is a network log for building
automation, such as for communication between a Management station (MMS) and a fire
detection installation.
BDV Abbreviation for 'Basis Data Variant'.
Blocking of the isolation Setting to ensure that a → Zone cannot be switched off.
C
CAP Term valid up to MP2.1. >MP2.1 is also used in the tool for corresponding systems.
Connection station between the SAFEDLINK and Ethernet sub-nets.
Collective detector line Detector line technique which gives one address to all detectors on a detector line. This makes
it impossible to identify individual detectors.
Control group Combination of several similar → Controls
Control tree Structure tree with → Control group and → Control.
CPU Abbreviation for 'Central Processing Unit'. The computing unit of the → Fire control panel.
→ CPU module
176
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Glossary
12
Term Definition
D
Danger level A fire detector signal which expresses the probability of a fire. Automatic fire detectors, for
example, have danger levels 0 to 3. Manual call points only have danger levels 0 and 3.
0 = no danger, 1 = possible danger, 2 = probable danger, 3 = highly probable danger
Degraded mode Defined reduced mode of operation which occurs when part of the fire detection installation
(e.g. main CPU) fails.
Detection tree Diagram of the geographical and organizational arrangements for → Sensors in a building. This
is a hierarchical structure comprising → Area, → Section, → Zone
Detector line The detector line is the electrical link between the detectors and fire control panel. There are
collective and addressed detector lines.
Detector line topology The arrangement of devices on the detector line. Depending on the detector line, up to 3
topology types are possible: → Loop, → Stub, stub on loop.
E
Effect An impact caused by a control, e.g. activation of a hardware output or a → Command. → Cause
Emergency power → Fire detection installation is supplied by the second source of power, e.g. → Batteries.
operation
Extended networking Connection between several SAFEDLINK networks → FCnet/SAFEDLINK → FCnet/LAN
External alarm indicator Optical element for indicating the site of the fire which is positioned at some distance from the
detector. Is usually fitted at point at which the room where the corresponding detector is
accessed.
Extinguishing control → Control which controls a connected extinguishing system and evaluates and displays its
states.
F
False alarm General: A false alarm is an alarm not triggered by a danger.
False alarm → False alarm
FCnet FCnet is the protocol in the SAFEDLINK. → SAFEDLINK → System bus
FCnet/Ethernet FS20-specific term for networking with electric Ethernet → FCnet/LAN
FCnet/LAN FS20-specific term for loop-shaped networking with optical Ethernet → FCnet/Ethernet
FCnet/SAFEDLINK FS20 system bus → FCnet → SAFEDLINK
FDnet addressed → detector line for FDnet devices
FDnet device A device to which the FDnet detector line is connected.
Fire control → Control which is activated in the event of a → Fire alarm.
Fire control group Level in → Control tree of → Fire detection system. The fire control group contains the → Fire
controls.
Floor repeater display A display device without operating elements.
Floor repeater terminal A display device with operating elements for acknowledging and resetting alarms and faults.
G
GAP Abbreviation for 'Global Access Point'. Participant in the Ethernet sub-net for the connection
between the Ethernet sub-net and a management station (BACnet client) and/or for remote
access with SintesoWorks or SintesoView. If there is a → Secondary GAP, the GAP becomes
the main GAP. Can be operated as a DHCP server in the Ethernet sub-net.
Gateway Network bridges which link two different systems/networks with one another and transfer the
different communication and transmission standards/protocols.
Global alarming Global alarming equipment (e.g. remote transmission) is actuated and external intervention
forces (e.g. the fire brigade) are alerted. → Local alarming
H
Hardware tree Depiction of the hardware of a → Fire detection installation
177
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Glossary
12
Term Definition
I
IC Abbreviation for Intervention Concept → Intervention concept
Intervention concept Concept with two independent verifications: Presence check for rapid local intervention and
intervention check for service intervention.
Isolation Status of one part of the → Fire detection installation, which suppresses the evaluation of all
signals.
L
License key Hardware modules for activating functions.
Line card Umbrella term for module bus cards for connecting detectors.
Line driver Hardware driver (repeater) for the detector lines.
Line separator An electronic switch in devices on the detector line which automatically disconnects the
defective part of the line in the event of a short-circuit.
Link Establishing a reference between two elements. (e.g. logical channel and physical channel)
Local alarming Local alarming equipment (e.g. acoustic or optical) is actuated in order to call up intervention
personnel and to alert people of a possible fire hazard. → Global alarming
Logical channel Depiction of a device's logical function in the → Detection tree or control tree. The logical
channel is always the bottom level in the structure tree.
Loop → Detector line topology which runs from the → Fire control panel via the → Fire detectors and
back to improve operational reliability (UL864 Class A Wiring). This type of wiring allows all
detectors to communicate with the control panel even in the event of an open line or short-
circuit. → Stub.
Loop line Expression for → Loop
M
Main GAP GAP = Global Access Point. Participant in the Ethernet sub-net for the connection between the
Ethernet sub-net and a management station (BACnet client) and/or for remote access with
SintesoWorks or SintesoView. If there is a secondary GAP, the GAP becomes the main GAP.
Management station A management station is a superordinate system for monitoring and operating safety-related
sites and buildings, e.g. fire, intrusion, access, heating, ventilation.
Manned Switching status of the → Alarm organization, if operating personnel are present and cant
intervene should an event arise (alarm, fault).
Maximum current Calculation unit for planning the detector lines → Outline quantities. Maximum current value that
connection factor a device obtains from the detector line.
Minor incident Alarm situation which the operating personnel can handle themselves and does not therefore
trigger → Global alarming. → Major incident
Multi-detector When using multi-detector dependency, the → Danger levels of several detectors are included
dependency in the alarm decision. Measures such as → Alarming or closing the fire doors are only initiated
when the defined dependencies occur (e.g. two detectors detect → Danger level 3). → Single-
detector dependency
178
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Glossary
12
Term Definition
N
Network module FS20 network card
(SAFEDLINK)
Network tree Figure of the network in a → Fire detection installation.
Networked fire detection Site with more than one fire control panel and at least two sub-nets.
system
Non-stationary FDnet Devices mounted with a base (exception: alarm sounders and radio detectors).
devices
Normal operation The → Fire detection installation is supplied with mains voltage.
Normally closed contact Opens a power circuit when activated. → Normally open contact
Normally open contact Closes a power circuit when activated. → Normally closed contact
O
Outline quantities Defines the number of permissible elements of one sort in a system. For example, maximum
number of → FDnet devices on a → Detector line.
P
Parameter set Defined detector behavior, e.g. in terms of sensitivity, resistance to deceptive phenomena,
response time. Detectors can be operated with different parameter sets.
Physical channel Depiction of a device's physical function in the → Hardware tree. The physical channel is the
bottom level in the hardware tree.
Pre-alarm Stage before an → Alarm for information early on should an event occur.
Pre-configuration A sub-configuration of the → Hardware tree, → Detection tree and → Control tree created before
commissioning the → Fire detection installation.
Q
Quiescent current Factor for the current that a device obtains from the detector line when in quiescent condition.
connection factor
R
Radio gateway Interface converter for converting from detector line protocol to radio
Remote transmission → Remote transmission
Renovation mode Mode of operation of the → Zone for maintaining a minimum detection ability during renovation
work. In renovation mode, the detectors are operated at low sensitivity.
Router station Participant in the SAFEDLINK sub-net for the connection between the SAFEDLINK sub-net
and the Ethernet sub-net (FCnet/LAN) via the Ethernet switch (MM) FN2008-A1.
RT The abbreviation for → Remote transmission.
RT The abbreviation for → Remote transmission equipment.
179
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Glossary
12
Term Definition
S
SAFEDLINK SAFEDLINK is the physical network of an FS20 fire detection system with the → Network
module (SAFEDLINK) and the network cable
SAFEDLINK station Participant in the SAFEDLINK sub-net with local connection for the PC
Secondary GAP Participant in the Ethernet sub-net, in redundancy to the main GAP, for the connection between
the Ethernet sub-net and a standby management station (BACnet client) and/or for remote
access with SintesoWorks or SintesoView. Cannot be operated as a DHCP server in the
Ethernet sub-net. → GAP
Section Level in → Detection tree of → Fire detection system. The → Section is assigned to the → Area.
It is used to combine → Zones.
Separator connector Specifies whether a device on the detector line features a line separator.
factor
Single-detector With single-detector dependency, the alarm decision depends on the → Danger level of one
dependency detector. The first detector in the → Zone which detects the corresponding → Danger level,
triggers a → Fire alarm. → Multi-detector dependency
Site Representation of the → Fire detection installation: The top level in the figure showing the
installed system. Includes → Hardware tree, → Detection tree and → Control tree.
Stand-alone station Stand-alone station with local connection for the PC.
Standby router station Participant in the SAFEDLINK sub-net, in redundancy to the router station, for the connection
between the SAFEDLINK sub-net and the Ethernet sub-net (FCnet/LAN) via the Ethernet
switch (MM) FN2008-A1.
Station Fire control panel or fire terminal
Stub Detector line which is only connected to the fire control panel on one side. In the event of an
open line or short-circuit, not all the → Fire detectors can still communicate with the → Fire
control panel. → Loop
System bus Loop-shaped, redundant networking by means of FCnet/SAFEDLINK → FCnet → SAFEDLINK
T
Technical message Events (e.g. from third-party systems) evaluated via Sensors or Contacts which are
forwarded to the → Fire control panel.
Test activation Activation of → Fire detectors in the → Detector test or → Effects in the → Control test.
U
Unmanned Switching status of the → Alarm organization, if operating personnel are not present and cannot
intervene should an event arise (alarm, fault).
V
VdS Abbreviation for 'Vertrauen durch Sicherheit', a company in the Gesamtverband der Deutschen
Versicherungswirtschaft e.V. (GDV). Inspection and certification body for fire detection systems
in Germany.
Visibility Defines which part of a → Site can be seen and operated on a station.
Z
Zone Level in the → Detection tree. A zone has at least one detector. The alarm decision is made on
the zone. The zone is assigned to the → Section or→ Area.
180
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Index
Index
A B
Access level Buttons on the PMI, 20
Levels, Access rights, 120 Buzzer
Logout, 61 'Buzzer off' button, 20
Access levels Testing, 81
Commands with required access levels, 124 Volume setting, 108
Access rights
C
Access level, stages, 120
Change language, 106
Acknowledge
Command response window, 30, 30
Button / Functions, 20
Commands
Acoustic signals
Commands with required access levels, 124
Button / functions, alarm devices, 21
Configuration
Deactivating / Activating alarm devices, 86
Note on the fire detection installation, 115
Activating / Deactivating
Parameter sets manned/unmanned, customer
Activating / resetting zone, 87 text, 95
Activating an alarm indicator (AI), 83 Control
Alarm devices, 86 Testing, 79
Evac control, 91 Control test, 79
Universal control, 89 Control tree
Universal control group, 91 Topology, selection, 73
WARNING, 83 Customer text
Activating / deactivating universal control, 89 Entering / changing, 110
Activating / resetting zone, 87 Entry of characters, 37
Activating an alarm indicator (AI), 83
Activating evac controls, 91 D
ALARM Deactivating / Activating
Procedure, 42 Activating / resetting zone, 87
Alarm counter Activating an alarm indicator, 83
Show information, 93 Alarm devices, 86
Alarm delay off Evac control, 91
Button / Functions, 20 Universal control, 89
Alarm evaluation Universal control group, 91
Switch off, 60 WARNING, 83
Alarm verification concept Deactivating / Activating alarm devices, 86
AVC, 159 Button 'Acoustic signals', 86
Example of verification process, 160 Detection tree
Auto-configuration Topology, selection, 73
Line, 97 Detector
station, 96 Switching off / Switching on, 51
AVC Temporary switching-off, 53
Alarm verification concept, 159 Testing, 77
Example of verification process, 160 Detector exchanger and tester
Enabling communication, 81
181
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Index
Detector test
Commands, 77
F
Faults
Display, 28
List, cause / rectification, 174
Brightness setting, 109
Favorites, 36
Displaying variants, 28
Fire department view, 29
Extended view / Switching over, 29
Fire department view, 29 G
How displays are represented in the document, Global alarming, 134
11
Input field, 30 H
Normal view, 28 Hardware tree
Download center Topology, selection, 73
URL, 12 Hardware version
Module, 41, 95
E Polling, 41, 94
Elements Station, 41, 94
List of elements, 131
Search by address / category, 75 I
Enable, 104 Indicators
Enabling the communication with the detector Buzzer test, 81
exchanger and tester, 82 Display and test LEDs, 81
Entering characters Input field
Keypad, 37 Display with window and input field, 30
Entering commands Installation test
Function-oriented, 71 WARNING, 79
Hiding confirmation, 71
Object-oriented, 68 K
Principles, 66 Key switch, 31
Entry of characters Keypad
Numbers, letters (customer text), 37 Entry of characters, 37
Event memory, 105 L
Deleting, 106 LEDs
Navigating, 105 Colors, 30
Polling, 105 Testing, 81
Sort, filter list, 169 License key
Events SintesoView, 100
Categories, 168 Line
Event memory, 105 Auto-configuration, 97
Labeling, 169 Local alarming, 134
Selecting, 72 Log in, 40
Expanded visibility Login, 40
Visibility, 123 Logout, 61, 61
Expiry reminder, 56
182
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Index
P
M PIN, 40
Main menu
Input dialog, 40
Menu button, 65
Manage, create, delete, change, 107
Maintenance
Releasing an access level, 40
Opening the control panel, 175
PINs
Manned / unmanned
Managing, 121
Button / Functions, 20
PMI, 19
Manned / Unmanned
Buttons, 20
Switching the operating mode, 62
Polling
Menu Item
Hardware version, 41, 94
Main menu / Open menu item, 65
Reports, 41, 94
Module
Software version, 41, 94
Hardware version, 41, 95
Polling the switching-off time, 55
Report, 41, 95
Print
Software version, 41, 95
Reports, 41, 94
Monitoring sabotage
Printer
Deactivate, 61
Inserting paper, 111
Switch off, 61
Switch off, 114
N R
Numeric key
Releasing an access level, 40
Shortcut, 36
Remote transmission
O Show information, 93
Opening the control panel Remote transmission, fire
Maintenance, 175 Switching off / Switching on, 56
Sabotage ALARM, 175 Remove, 105
Operate Report
SintesoView, 102 Module, 41, 95
Operating condition, 116 Station, 41, 94
Operating function Reports
Scrolling, 35 Polling, 41, 94
Selection and opening / execution, 35 Print, 41, 94
Operating sequence in an operation sequence Reset
Favorites, 36 Button / Functions, 20
Operation Reset alarm (password), 42
Switching off / Switching on, 46
Switching the operating mode, 62
Operation modes, 116
Manned / unmanned, Button / functions, 20
Normal operation, 116
Sinteso Mobile, 39
SintesoView, 38
Switching to Manned / Unmanned, 62
Override
Temporary switching-off, 53
183
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Index
station
S Auto-configuration, 96
Sabotage ALARM
Switch off
Opening the control panel, 175
Alarm evaluation, 60
Sabotage evaluation
Sabotage evaluation, 61
Switch off, 61
Switch off alarm delay, 42
Scrolling
Switching off / Switching on, 46
Indication of the position and length of the list, 36
Detector, 51
Scroll bars, 36
Remote transmission, fire, 56
Scroll in option lists, command lists, element
Temporary switching-off, 53
category lists, 35
WARNING, 46
Service reminder
Switching on / Switching off
System maintenance, 175
Detector, 51
Setting the date, 109
Remote transmission, fire, 56
Setting the system time, 109
Temporary switching-off, 53
Setting time and date, 109
WARNING, 46
Settings / Administration
System maintenance
Setting time and date, 109
Service reminder, 175
Shortcut, 36
Show information T
Alarm counter, remote transmission, 93 Temporary switching-off, 53
Sinteso Mobile, 34 Expiry reminder, 56
License key, 34 Override, 53
Operation modes, 39 Polling the switching-off time, 55
Specify operation mode, 103 Section, duration, 53
SintesoView, 33 Testing
Connect, 101 Control, 79
Enabling/disabling, 100 Time setting
General function, 33 Setting time and date, 109
License key, 100 Topology, 134
Operate, 102 Selecting an element, 73
Operation modes, 38
Permanent enabling, 100 V
Visibility, 100 Version
Software version Indicators, 114
Module, 41, 95 Visibility
Polling, 41, 94 Definition, 122
Station, 41, 94 expanded visibility, 123
Standby Standby, 122
Visibility, 122
Station
Enable smartphone, 104
Hardware version, 41, 94
Removing a smartphone, 105
Report, 41, 94
Software version, 41, 94
184
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Index
185
Building Technologies 008838_p_en_--
Fire Safety 2014-02-18
Issued by © 2006-2014 Copyright Siemens Switzerland Ltd
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Infrastructure & Cities Sector
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 24 24
www.siemens.com/buildingtechnologies