No : E19-LOC-269

TECHNICAL Issue :2
Date : 12-07-2019
SPECIFICATION Pages : 9 of 28

CONSTRUCTION
Cable Type : MGT/XLPE/OSCR/LSHF/SWA/LSHF-AT-AR
Voltage : 500V
Design Standard : BSEN 50288-7
Conductor Standard : IEC 60228, BSEN 60228
Flame Propagation : IEC 60332-3-22
Fire Integrity : IEC 60331-21

CABLE DESCRIPTION:
1
2
3
4
5
6
7

Part Description No.


Conductor Cu Plain annealed stranded circular copper conductor, Class 2 1
Fire Proof Layer MGT Mica glass tape 2
Insulation XLPE Cross-linked polyethylene compound
3
Pairing / Twining Two/Three/Four insulated cores are cabled together
Assembly Multiple pairs/triads/quads are cabled together, supplied with non- 4
hygroscopic filler (optional) to obtain a circular construction and covered
with a polyester tape wrapping
Overall Screen OSCR Min. 30% overlap of aluminium backed polyester tape in contact with
0.5mm² (16/0.20mm) tinned annealed drain wire followed by a polyester
tape wrapped over the screening tape
Inner Covering LSHF Low smoke halogen free compound. Black 5
Armouring SWA Galvanised steel wire armour 6
Outer Sheath LSHF- Low smoke halogen free compound with anti-termite and anti-rodent
AT-AR additives. Black 7

CABLE MARKING:
DRAKA 500V MXOLSL-AT-AR _ x _ x _MM2 BSEN 50288-7, IEC60332-3-22, IEC 60331-
Wording
21 YR-YYYY
Height of text Min. 3 mm
Type of Marking Ink-jet
Length marking Sequential length marking at 1 metre interval printed on outermost surface

CORE IDENTIFICATION:
1-pair : Black, White
Multi-pair : Black, White with pair numbering (on each core)
1-triad : Black, White, Red
Multi-triad : Black, White, Red with triad numbering (on each core)

This information contained in this data sheet is subject to normal manufacturing and internal standard practice.The data and properties may be changed as
a result of our efforts to improve the quality of our products.
No : E19-LOC-269

TECHNICAL Issue :2
Date : 12-07-2019
SPECIFICATION Pages : 10 of 28

TECHNICAL DATA TABLE

MGT/XLPE/OSCR/LSHF/SWA/LSHF-AT-AR 500V

DIMENSIONAL DATA IC

Voltage Unom V 500


Size Nominal mm2 1Tx1.5
Conductor Type Non Compact
Conductor Diameter Approx mm 1.56
Insulation Thickness Minimum mm 0.44
Insulation Diameter Approx mm 3.3
Inner Covering Thickness Min.Ave mm 0.9
Min.Spot mm 0.67
Inner Covering Diameter Approx mm 9.3
Armour Wire diameter Nominal mm 0.9
Diameter Over Armour Approx mm 11.0
Oversheath Thickness Min.Ave mm 1.4
Min.Spot mm 0.92
External diameter of cable Approx mm 14.0
Diameter Tolerance ±1.0 mm
Mass of cable Approx Kg/Km 335
Standard Length Nominal M 1500
Drum Size mm 1100
Bending Radius Minimum mm 140
Pulling Tension
Eye on Conductor Maximum Kgf 31.5

ELECTRICAL DATA
DC Resistance at 20 ºC Maximum Ω/Km 12.10
Mutual capacitance at 1kHz Maximum pF/m 150
Insulation Resistance Minimum MΩ.Km 1000
L/R Ratio Maximum μH/Ω 40
Conductor Operating Temperature Maximum °C 90
AC Voltage Test for 1 minute KV 2