06 SEP671 REL670 Exercise 5 Distance Protection Communication Scheme PO
06 SEP671 REL670 Exercise 5 Distance Protection Communication Scheme PO
1MRG005015
Exercise 5 - Distance protection communication scheme PO
Copyright
This document and parts thereof must not be reproduced or copied without
written permission from ABB, and the contents thereof must not be imparted to
a third party, nor used for any unauthorized purpose.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
- the carrier send signal is sent from the starting signal of zone 2
- the communication trip is issued by reception of the carrier receive signal together with starting signal
from zone 2.
In this section we will correctly set the REL670 to perform the permissive overreaching communication scheme
(PO) and will test the correct functionality. Weak-infeed logic will also be tested.
The function blocks managing the communication scheme ZCPSCH and ZCRWPSCH are already engineered in
the REL670-A32 and they only need to be correctly set.
Relay settings
Distance protection settings are the same as for the previous exercise.
ZCPSCH is the function block managing the main logic necessary for implementing the communication
scheme.
Figure 1 shows the correct settings for the permissive
overreaching scheme (PO).
ZCRWSCH is the function responsible of managing the logics for weak end-infeed and current reversal.
Injection tests
The relay test set must simulate carrier signal sent by the relay at the other line-end by activating one binary
output.
Additionally connect (if not done already from the previous exercise):
IOM INPUT 2 (Carrier Receive, “ZM_CR”) Binary Output 2 of the test set
IOM OUTPUT 5 (Carrier send, “ZM_CS”) Binary Input 5 of the test set
4. Open the Omicron test file simulating fault at 90% the line with the carrier sent by the remote relay
The test file is called REL670 PO Communication Scheme.seq. The file is available in the folder Files for SEP-
602A REL670 / OMICRON TESTS on the desktop of your training PC.
The sequence is shown in Figure 3 and it is the same as we have used previously, for the PU scheme.
Run the sequence and verify that REL670 does not trip instantaneously (by communication scheme) and that no
carrier is sent (Figure 7).
Which zone
operated in 800
ms?
Figure 7: Sequence for fault in reverse position and carrier received. Time delayed trip
In the next steps we will activate and test the weak-infeed logic for the PO scheme.
Relay settings
Distance protection settings are the same as for the previous exercise.
ZCRWSCH is the function responsible of managing the logics for weak end-infeed and current reversal.
Injection tests
The relay test set must simulate carrier signal sent by the relay at the other line-end (strong side) by activating
one binary output.
The carrier send (“ZM_CS”) signal from REL670 represents the “original carrier” (activated by zone 2 start)
and also the “echo carrier”, generated by weak-end infeed logic.
Additionally connect (if not done already from the previous exercise):
IOM INPUT 2 (Carrier Receive, “ZM_CR”) Binary Output 2 of the test set
IOM OUTPUT 5 (Carrier send, “ZM_CS”) Binary Input 5 of the test set
13. Open the Omicron test file simulating the weak fault at 40% the line with the carrier sent by the
remote relay
The test file is called REL670 PO WEI.seq. The file is available in the folder Files for SEP-602A REL670 /
OMICRON TESTS on the desktop of your training PC.
The relay operate time can be measured with the help of the two cursors directly on the “time signal view”.
Figure 10: Operate time of the PO with WEI scheme, and also echo carrier send
Notice also a relay operate time of 27 ms from the reception of the carrier signal (Figure 11).
In reality the REL670 is much faster than that: it trips in some 20 ms from the reception of the carrier signal.
You can verify this by measuring with another equipment the time from when the carrier signal is present on the
relay binary input and when the relay trip contact operates.
You can also verify this in the REL670 event list, remember to add ca 3 ms for the reaction time of the binary
output.
15. Remove the carrier signal and verify no trip from distance protection
Remove the carrier receive signal from the test set and run the sequence again.
Verify that the distance protection in REL670 does not operate.
16. Verify echo carrier send by REL670 (fault in zone1) when carrier is received
This has already been done in step 14.
QUESTION: Did you manage to get REL670 trip by weak-end infeed by only sending the carrier?
Did you manage to get the echo-carrier?
When all the three voltages are low, the weak-end infeed logic only trips if there is a voltage change in all the
three voltages. We need to test this with a more realistic situation, which means we need to create a sequence.
You will get the local trip signal with this sequence (Figure 13)
Figure 13: Local trip and echo carrier send for three-phase weak fault
19. Verify no trip and no echo-carrier sent when the fault is in reverse and carrier is received
Inject a fault in reverse position as indicated in Figure 14. This time the fault must not be “weak”, because it is
in reverse direction and it is the same fault that zone 2 sees from the other line-end.
Keep the simulation of
the carrier received from
the remote line-end
Figure 14: Sequence for fault in reverse position and carrier received
Run the sequence and verify that REL670 does not trip instantaneously (by communication scheme) and that no
carrier is sent (Figure 15).
Which zone
operated in 800
ms?
Figure 15: Sequence for fault in reverse position and carrier received. Time delayed trip
QUESTION: If Zone5 is switched off, the relay trips by WEI, when simulating a fault in reverse! Can you
explain why?