02 SEP671 REL670 Exercise 1 Distance Protection Characteristics
02 SEP671 REL670 Exercise 1 Distance Protection Characteristics
Copyright
This document and parts thereof must not be reproduced or copied without
written permission from ABB, and the contents thereof must not be imparted to
a third party, nor used for any unauthorized purpose.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
The settings for distance protection will be calculated with reference to the application example shown in figure
1 and table 1.
A B
Z1L = R1L + j X1L
Z0L = R0L + j X0L
3I 3U
Entity Value
Line length 100 km
Nominal Voltage Level 400 kV
Line Positive Sequence Impedance, Z1L = R1L + j X1L (0,032 + j 0,36) km (3,2 + j 36)
Line Zero Sequence Impedance Z0L = R0L + j X0L (0,13 + j 1,45) km (13 + j 145)
CT A ratio 1200 A / 1 A
Start point earthed towards the line
VT A ratio 400 kV / 100 V
Maximum Power Transfer over the line S = 700 MVA
P = 628 MW
Q = 308 Mvar
Cosphi = 0.89
REL670_1p2_Training.pcmp
In this project the relay settings are the default ones, and
will be changed in the following exercises.
Correct information of the main CTs is very relevant as the protection relay settings are in expressed in primary
quantities. Pay attention to the CT earthing point, as it influences the direction (phase angle) of the primary
currents calculated by the REL670.
4. Open the Parameter Setting Tool for the transformer card (6I and 6U)
Correct information of the main VTs is very relevant as the protection relay settings are in expressed in primary
quantities.
Settings are entered for the same transformer card (6I and
6U).
Calculating the settings for five zones distance protection, polygonal characteristic
The settings for the distance protection will be calculated in order to meet the requirements indicated in Table 2.
Zone Requirement
Zone 1 85% of the protected line
Forward direction
Instantaneous operate time
Load Encroachment Distance protection zones will not trip for exporting load equal or
smaller 700 MVA and for any cosphi between 1,00 than 0,89
The relay settings (reach) are calculated in way, according to the requirements in Table 2:
The distance protection zone 1 is requested to cover (see Table 2) 25 ohms of fault resistance for LE faults and
15 ohms for LL faults, at 80% of the protected line. Since the resistive reach of the REL670 characteristic is
parallel to the line impedance of the protected line, it is
enough to set the fault resistance settings at the
requested values:
and
The relay settings (reach) are calculated according to the requirements given in Table 2, where it has been
chosen to set zone 2 at 125% of the protected line:
and
Timers for LN and LL faults are set both activated (Timer tPP = Timer tPE = On) and their value is 0,4 s.
The relay is requested to trip for all the faults, hence PE (Phase-Earth) and PP (Phase-Phase) loops are activated
(OperationPP = OperationPE = On).
The relay settings (reach) are calculated according to the requirements given in Table 2:
It is meaningless to set the resistive value of zone3 to 400% of the protected line resistance, as this is a back-up
zone, protecting several objects after the line. It is chosen to have a characteristic angle of almost 90 degrees
hence the resistive value will be set to the small value of 1 ohm:
As well as for the resistive value of the zero sequence impedance, it is chosen to set it to a small value in order
to get a characteristic angle of 90 degrees:
and
The relay settings (reach) are calculated according to the requirements given in Table 2. It is assumed that 10%
of the forward protected line is equivalent to 20% of the shortest line behind REL670
and
Assuming that zone 2 at the remote line-end (B) is set as zone 2 of REL670, the settings for the zone 5 are
calculated this way:
and
Timers for LN and LL faults are both set deactivated (Timer tPP = Timer tPE = Off) and their value is 60s in
order to avoid misunderstandings in the setting file (no trip is requested by this zone).
The relay is requested to start for all the faults, hence PE (Phase-Earth) and PP (Phase-Phase) loops are
activated (OperationPP = OperationPE = On).
Base values are set according to the nominal primary quantities of main transformers, this means that:
The phase selector needs to be set in order to cover all the distance protection zones connected to the phase
selector signal “STCNDZ”. In A32 configuration these zones are zone 1, zone 2 and zone 5.
The settings can be calculated mathematically or simply graphically by using the Excel tool REL670_1.2 ==
PHS covering ZM.xls, which is available in the folder Files for SEP-602A REL670 / Excel Files on the desktop
of your training PC.
Figure 15: Impedance settings for phase selection to cover zone 2 and zone 5
Figure 16: Partial Impedance settings for phase selection to cover zone 2 and zone 5
The phase selector takes also care of the load encroachment area for all the distance protection zones. The
settings are calculated as function of the load data given in Table 1 and the requirements of Table 2.
The corresponding settings for the load resistance in phase selection are (considering equal exporting and
importing loads) and for the load angle are:
Figure 17: Final Impedance settings for phase selection including load encroachment
For the directional lines default settings will be applied, but it is needed to enter the correct settings for the base
values.
Base values are set according to the nominal primary quantities of main transformers, this means that:
The distance protection characteristic will be tested with the relay test set, where the shape of the characteristic
has been drawn manually for each fault type.
Connect also the trip contact from the REL670 to the binary input 1 of the test set:
15. Open the Omicron test file for LE faults and run the tests for zones 1, 2,3 and 4
16. Open the Omicron test file for LL faults and run the tests for zones 1, 2,3 and 4
17. Open the Omicron test file for LLL faults and run the tests for zones 1, 2,3 and 4
19. Open the Omicron test file for LE faults and run the tests for zone 5
20. Open the Omicron test file for LL faults and run the tests for zone 5
21. Open the Omicron test file for LLL faults and run the tests for zone 5