ATHENA C - Series - 16C - Manual
ATHENA C - Series - 16C - Manual
16C
TEMPERATURE/PROCESS
CONTROLLER
Instruction Manual
(Basic Operations)
1
Introduction
Congratulations on your purchase of an Athena Series 16C
Temperature/Process Controller. It is designed for ease of
use and reliability wherever accurate control is required.
After following the instructions for installation, simply
step through and set your operating parameters using the
controller’s easy menu system. The instrument may then be
automatically or manually tuned to your process for optimum
setpoint control.
A Quick Setup Reference Card is on page 5 and also attached
as a tear-off card to the back of the instruction manual for
experienced users of PID controllers.
As you look through this manual, you will notice blue
italicized text appearing in the margins and adjacent to
operating information. These notes impart important informa-
tion about the controller and may answer questions you may
have about its setup or operation. If you still have questions
or require any assistance, please contact your Athena repre-
sentative or call technical support at 1-800-782-6776. Outside
the USA, please call 610-828-2490.
Precautions
After unpacking, inspect the instrument for any physical
damage that may have occurred in shipping. Save all packing
materials and report any damage to the carrier immediately.
Features
Field-Selectable Thermocouple, RTD, Current or Voltage Input
On/Off Through Full PID Operation
Autotuning - Heat or Cool
Eight-Segment Ramp/Soak
On/Off Output with Adjustable Hysteresis and Deadband
Dual Output Capability
Field-Configurable Process or Deviation Alarms
Bumpless, Auto-Manual Transfer
NEMA 4X Front Panel, “Watertight”
Dual 4-Digit (0.36”), 7-Segment Alphanumeric Display
Selectable Ramp to Setpoint
Alarm Inhibit
Loop Break Alarm Capability
Available Options Include Serial Communications, Contact/
Digital Input, Remote Analog Setpoint, Transducer Excitation,
Auxiliary Output, Dual Alarms, or Electromechanical Relay
Alarm.
Approvals: UL, cUL, CE
© Copyright 2004, Athena Controls, Inc.
Safety Warning
In addition to presenting a potential fire hazard, high
voltage and high temperature can damage equipment
and cause severe injury or death. When installing or using
this instrument, follow all instructions carefully and use
approved safety controls. Electrical connections and wiring
should be performed only by suitably trained personnel.
Do not locate this instrument where it is subject to excessive
shock, vibration, dirt, moisture, oil, or other liquids. The safe
operating temperature range for this unit is 32°F to 140°F
(0°C to 60°C).
This unit has been tested and found to be compliant with
“NEMA Type 4X Enclosure - For Indoor Use Only.” When
properly installed, this controller will maintain the integrity
of a NEMA enclosure and remain “Watertight.” This rating is
only applicable when the controller is properly installed into a
suitably rated NEMA Type 4X housing.
UL C
UL
®
®
3
Table of
Contents
Installation 1
For information and Dimensions and Mounting 2
operating instructions
related to installed Wiring 3
options and digital
communications, Output Types 5
refer to the Series C Operation 6
Options and Digital
Communications Front Panel Controls 6
manual supplied with
your controller.
Power On 7
Security Levels 8
Operating Modes 9
Menu System Overview 10
Initial Setup Sequence 12
Parameter/Menu Descriptions 14
Input Menu 15
Temperature Input 16
Process (Linear) Input 16
Display Menu 17
Output Menu 17
PID Output and Control Menus 18
On/Off Output and Control Menus 19
Alarm Outputs 20
Autotune Damping 22
Ramp and Soak Menu 23
Supervisor Menu 24
Calibration Menu 25
Options Menu 25
AutoTuning 26
Manual Tuning 28
Error Codes 29
Technical Specifications 30
Ordering Codes 32
Recalibration Procedures 33
Quick–Helps 34
Warranty/Repairs 36
Glossary 39
4
Installation
Measurements between Unpacking and Inspection
centerlines of panel cut- 1. Inspect shipping carton for obvious signs of mishandling.
outs are the minimum
recommended. 2. After removing the controller from the shipping carton,
inspect it carefully for damage. Never attempt to install
and use a damaged unit.
3. Verify that the ordering code number indicated on the side
of the controller matches what was ordered.
Figure 1.
Recommended Panel Layout for Multiple Controllers
CL CL
2.850” (72.4 mm)
CL
CL
1
Dimensions
Figure 2. Case Dimensions
4.654"
2.100" (118.21mm) 3.937"
(53.3mm) 0.717"
(8.21 mm) (100 mm)
O1
O2 PV
A1
2.100" A2 1.750"
(53.3mm) F1 SV (44.5 mm)
F2
Mounting
Figure 3. Series C Mechanical Components
Insert the Series C through the front panel cutout and slide
When properly the mounting collar back onto the unit from behind the
installed through
a NEMA enclosure, panel. Push the mounting collar up tight to the back of the
the integrity of the mounting panel.
enclosure will be
maintained and will
remain “Watertight.” Bezel Case Clip
Grips
2
Wiring
IMPORTANT: All electrical wiring connections should be made
only by trained personnel, and in strict accordance with the
National Electrical Code and local regulations.
The Series C controller has built-in circuitry to reduce the
effects of electrical noise (RFI) from various sources.
However, power and signal wires should always be kept
separate. We recommend separating connecting wires into
bundles: power; signal; alarms; and outputs. These bundles
should then be routed through individual conduits. Shielded
sensor cables should always be terminated at one end only.
If additional RFI attenuation is required, noise suppression
devices such as an R.C. snubber at the external noise source
may be used. If you wish, you may order this suppressor
directly from Athena, part number 235Z005U01.
232/485
N.O. 1 6
GND COM ALARM
OUTPUT 1 A2 &
C 2 7 N.O. COMM.
13 14
N.C. 3 8
11 12
RTD SENSOR
N.O. 4 9
T/C INPUT
OUTPUT 2
C 5 10
L1 L2
100 - 250 V 50/60 Hz
100 - 250 Vdc (Auto Polarity)
24 Vac/Vdc (Auto Polarity)
3
Wiring
Figure 5. Thermocouple Input Wiring
Thermocouple circuit Make sure that you are using
resistance should not the appropriate thermocouple 8
3 8
11 12
4 9
5 10
100 - 250 V 50/60 Hz
100 - 250 Vdc (Auto Polarity)
4
L1 L2
Output Types
When you ordered your Series C controller specific output
The Type “B” output
types were specified, designated as “B”, “E”, “F”, “G”, “S”,
is a mechanical device “T” or “Y”. You also had the option of configuring your con-
and subject to wear. troller with either one or two output actions. The numbers
To extend the life of below are suggested for most typical applications.
the relay, set the Cycle
Time for the relay For Control Output Type — Select Cycle Time
output to the longest (in seconds)
duration that still
affords good control.
B >15
E 0.2
F 0.2
G 0.2
S 0.2
T 15*
Y >15
*“T” outputs directly driving non-inductive loads (small heaters) can have
cycle times as low as 0.2 seconds.
5
Operation
Figure 9. Front Panel Controls and Indicators
Mode/Enter Key
Used to enter Parameter selections,
access operating modes, release
latched alarms, and index through
menu items.
Lower Key
Used to decrease values.
(Hold for fast-step progression)
Raise Key
Used to increase values.
(Hold for fast-step progression)
Menu Access Key
Used to enter or exit the menu system, index to the next
menu, and enter the Security Level menu.
6
Power On
The Series C controller’s
functional hierarchy When power is first applied to the Series C, all segments of
is organized into three
distinct user-program- the LED displays will be momentarily illuminated while the
mable groupings: instrument goes through a series of diagnostic checks to
Security Level, Menu
System, and Operating
verify proper operation. A software version number will then
Mode. appear in the lower display, followed by a configuration code
(upper display) and the communications protocol which is
supported (lower display).
Operations Overview
The user interface of the Series C allows you to use menus to
set up the instrument, set the desired security level, change
the setpoint, and conveniently change operating modes.
Figure 9 on page 15 provides a functional representation of
the user interface and the key presses necessary to perform
the basic functions.
7
Security Levels
The security level feature allows you to limit access to the
menus, setpoint, and operating mode selection according to
The controller’s initial the needs of your application. The security levels provided
security level, set at the are Key Lockout, Setpoint, Setpoint plus Mode, User,
factory, is Configuration Configuration, and Factory. To view or change security
. When you have
completed configuring level from the Process Variable display, press and hold the
the instrument, we Menu Access key for approximately 10 seconds.
recommend the security (Ignore the menu label that will appear in the upper display
level be set to the most after approximately three seconds.) The controller will display
restrictive level suitable
for your application. (Access Level) and the current security level label,
e.g., . Use the Raise or Lower keys to index
through the security levels. Press the Mode/Enter key
once to select the new security level desired and return to the
Process Value display.
JMPØ3
8
Operating Modes
The Series C’s operating modes are: Manual, Standby, Normal,
Autotune, Ramp/Soak Recipe, Run and Hold. To select a different
Remember to press the operating mode, press the Mode/Enter key for three seconds.
Mode/Enter key after
making your selection. The operating mode that the controller is currently in will be dis-
played. To index through the available operating modes, press the
If both outputs are Raise or Lower keys. When the desired mode is displayed,
set to or , press the Mode/Enter key once to select the mode.
the Series C will func-
tion as a non-control-
ling indicator. Control
outputs will be disabled Manual
and the Operating
Modes will not be Standby
displayed.
Normal
Autotune
(Only available when unit is placed in Standby mode
and one output is PID.)
Start Ramp/Soak Recipe
(Only when programmed.)
Run
(Only available when recipe is active.)
Hold
(Only available when recipe is active.)
Operating Modes
Manual Used to set control output percentage
(Fixed Output Percentage) independent
Manual operating of Process Value. To set percentage,
mode overrides auto-
use the Menu Access key to select
matic control, allowing
you to control the and the Raise or Lower keys
outputs using a fixed to set the value. is displayed if
percentage of output Output 1 is a control output.
power, regardless of
the process variable is displayed if Output 2 is a control
or setpoint. output.
Standby Used to disable control outputs.
If current automatic
control is PID, transfer Normal Normal automatic control.
to Manual mode is
“bumpless.”
Autotune Used to initiate the autotuning
sequence (from Standby only).
Ramp/Soak Used to start ramp/soak recipe mode.
Recipe
Run Used to enable Run function
Hold Used to enable Hold function
9
Menu System
Overview
The Parameter Menu System is organized into ten basic
If a key press is not menus: Input, Display, Output, Control, Alarm, Tune,
sensed within five
minutes, the control- Recipe, Supervisor, Calibration, and Option. To access the
ler automatically exits Menus, press and hold the Menu Access key for approxi-
the Menu System and
reverts to the Process mately 3 seconds until a menu label appears in the upper dis-
Value display. play. There are additional menus presented when an option
is selected under the Option menu; however, the options
are non-functional unless the appropriate option board has
been installed. Pressing the Menu Access key indexes
from menu to menu. Pressing the Mode/Enter key
indexes through the parameters in a particular menu. The
Raise and Lower keys are used to modify the visible
menu parameter.
10
Figure 10. Series C Functional Diagram
Security
11
Levels
for 10 seconds once
for 3 seconds Process for 3 seconds
Menu Mode
Variable
System Selection
Display
for 3 seconds once
press and hold Menu
To return to Process
key for
Value at any time,
Menu System
three seconds
Overview
Access
Figure 11. Chart of Series 16C Menu System
Menu System and Security Levels
Overview (Continued on Next Page)
Mode/
Enter Key
(number)
(number)
(number)
(number)
(number)
12
Figure 11. Chart of Series 16C Menu System
and Security Levels
(Continued from Previous Page)
Mode/ Raise/
Enter Key Lower Key
Functional When Option Card Installed
(three seconds)
(User) = Plus
(Configuration) = Plus
(Factory) = Plus
13
Menus and Parameter
Descriptions Menus and Parameters
14
Input Menu
NOTE: FOR A MORE DETAILED DESCRIPTION OF MENU
PARAMETERS, REFER TO THE GLOSSARY
WHICH BEGINS ON PAGE 64.
The first parameter that needs to be set is Input Type. The remaining
Input Menu parameters will change, depending upon whether a linear
input type or a temperature input type is selected. Other menu param-
eters related to the sensor range may also change. After selecting
your Input Type, refer to the corresponding section on page 16 for the
remainder of the Input Menu parameters.
Input Menu
Display Parameter Selection
Input Type Type J thermocouple
Type B thermocouple
Type C thermocouple
Type E thermocouple
Type K thermocouple
Type N thermocouple
Type NIC thermocouple
Type NNM thermocouple
Type R thermocouple
Type S thermocouple
Type T thermocouple
Platinel II thermocouple
100 ohm
platinum RTD
15
Input Menu
Note: When you ordered your controller, an input type was specified and the controller was set up
accordingly and calibrated for that input type at the factory. If you decide to change input type from
thermocouple to RTD or vice-versa, you will need to recalibrate the controller unless you ordered the
JMPØ1
“Calibrate All” option. (Refer to page 56 for information on recalibration.) If you are changing from a
temperature input type to a linear input type, you MUST recalibrate and change the jumper settings as
indicated in the above table.
Input Menu
Temperature Input Type
Display Parameter Selection
Bias (Display offset) -100 to 100
Lower Setpoint Limit Span of Sensor
Upper Setpoint Limit Span of Sensor
Filtering 0.1-10.0 sec.
Output Menu
The first parameter that needs to be set in the Output Menu is the
Output Type. There are three possible Output Type configurations:
PID, On/Off, Alarm, or Off. (If you are not sure which Output Type
is best for your particular application, refer to the Glossary for an
explanation of Output Types.) The remaining menu parameters in the
Output Menu will change, depending on the Output Type selected.
The Control Menu will also change, depending on the Output Type
selected. If you ordered two outputs, you can select two different
Output Types. After setting your Output Type, refer to the correspond-
ing sections below for the remaining Output Menu parameters. For
simplification purposes, the following sections assume the same
Output Type for both outputs. If you selected different Output Types,
refer to both of those sections.
Output Type
JMPØ1
Display Parameter Selection
Output 1 Type
Output 2 Type
17
Output Menu
PID Output Type
Output 1 Action Reverse-acting (Heating)
Direct-acting (Cooling)
Output 1 Cycle Time* 0.2; 1 to 120 seconds
Output 1 Low Limit 1-100%
Output 1 High Limit 1-100%
**“T” outputs directly driving non-inductive loads (small heaters) can have
cycle times as low as 0.2 seconds.
Control Menu
PID Output Type
As with the Output Menu, the Control Menu will change, depending
upon the Output Type selected. Note: These parameters are auto-
matically set during the autotune procedure. We do not recommend
altering the value of these control parameters unless your process
requires manual tuning.
Display Parameter Selection
Proportional Band 1 1...to span of sensor
Setting Derivative Proportional Band 2 1...to span of sensor
(Rate) or Integral
(Reset) to Derivative Action (Rate) 0 to 2400 seconds
disables that aspect
Manual Reset OFF, -100% to 100%
of PID control.
NOTE: The Integral Action (Auto Reset) parameter appears only if OFF
If BOTH outputs are is selected in the Manual Reset parameter.
set to direct-acting or
BOTH outputs are set Integral Action (Auto Reset) 0 to 9600 seconds
to reverse-acting, then
only one proportional
band selection will be
displayed.
18
Output Menu
On/Off Output Type
Display Parameter Selection
Output 1 Action Reverse-acting (Heating)
Direct-acting (Cooling)
Control Menu
On/Off Output Type
If both outputs are set to in the Output Type Menu, the
controller will function as a non-controlling indicator. Control
outputs will be disabled and the Operating Modes will not be
displayed.
19
Notes On Alarms
Outputs can be set up as an alarm, similar to the standard
alarm format. Four types of alarms are available: Process,
Deviation, Inverse Band, and Normal Band. All alarms may be
configured to be inhibited on power-up for a configurable
time duration.
Process Alarm: Activates at preset value, independent
of setpoint. “High” process alarm
activates at and above alarm setting.
“Low” process alarm activates at and
Deviation, Inverse below alarm setting.
Band, and Normal Deviation Alarm: Activates at a preset deviation value
Band Alarms track
with setpoint.
from setpoint. “High” or “Low” deviation
alarm activates above or below setpoint
according to the preset deviation value.
Inverse Band Alarm: Activates when the process is within
a specified band centered around the
setpoint.
Normal Band Alarm: Activates when the process exceeds
a specified band centered around the
setpoint.
When a latching alarm Latching Alarms
has been activated and
the alarm condition The Series C’s alarms may also be configured as latching
has been removed, the alarms by selecting in the Alarm Action parameter
Mode/Enter key selection.
must be pressed to
unlatch the alarm.
20
Output Menu
Alarm Output Type
Display Parameter Selection
Output 1 Alarm Action
(Latching)
(Normal)
Output 1 Alarm Operation (Process Low)
(Process High)
(Inverse Band)
(Normal Band)
Note: The Control (Deviation Low)
Menu does not apply (Deviation High)
to an Alarm Output Output 1 Alarm Delay 0-9999 sec
Type; therefore, the
Control Menu does Output 1 Alarm Inhibit 0-9999 sec
not appear. Output 1 Alarm Setpoint Span of Sensor
*Alarm Delay - the time delay between the detection of the alarm condition and the
initiation and indication of the output action.
**Alarm Inhibit - prevents low setpoint alarm activation during cold startup applications.
21
Autotune
Damping Menu
Display Parameter Selection
Damping Low
Normal
High
Recipe (Ramp/
Soak) Menu
Single Setpoint Ramp Time
This selection will cause the controller to ‘ramp’ the
process from the starting point (current process value)
to the setpoint in the time specified. This ramp will take
place at startup when selected from the Ramp/Soak menu.
The setpoint must be at least ±0.2% of sensor span for the
ramp to be employed.
Multi-Step Ramp
This selection will enable the programming of a recipe (make
all ramp/soak recipe variables visible). Recipes can be resumed
on startup if interrupted by a power failure or initiated, held, and
terminated from the front panel via the Mode Menu or with the
logic input option (initiate and held/resumed only).
Holdback Band
Specifies the maximum number of degrees above or below
setpoint that the process can be for the segment timer to keep
going. The timer will hold while the process settles back into the
band and then continue. If this feature is not desired, this param-
eter should be set to which will disable it.
Termination State
This parameter determines what the control will do at the
completion of a recipe. Last Setpoint refers to the last
temperature specified in the ramp/soak recipe. Default
Setpoint refers to the standard setpoint which was in effect prior
to recipe initiation.
Recycle Number
Specifies the number of times after the first time that the recipe
is run before the program terminates.
22
Recipe (Ramp/
Soak) Menu
Power Fail Resume
Setting this parameter to On will cause the control to resume
a recipe which was active when a power failure occurred. The
recipe will resume at the start of the last active ramp or soak
segment.
23
Recipe (Ramp/
Soak) Menu
NOTE: The following seven parameters are only available when
For Ramp Events and multi-step ramp is selected.
Soak Events to be
employed, Alarm 1 or
Alarm 2 must be set for Display Parameter Selection
event usage in the
Alarm Menu. Recycle Number 0-99,
(Recipe Executions)
Power Fail Resume Off
On
Ramp Times 1-8 0-9999 mins.
Ramp Events 1-8 Alarm 1 On
Alarm 1 Off
Alarm 2 On
Alarm 2 Off
Disabled
Soak Levels 1- 8 Display Units, FS
Soak Times 1-8 0-9999 mins.
Soak Events 1-8 Alarm 1 On
Alarm 1 Off
Alarm 2 On
Alarm 2 Off
Disabled
Supervisor Menu
Display Parameter Selection
Output 1 0 to 100%
Failsafe State of output
Output 2 0 to 100%
Failsafe State of output
Loop Break Time Off, 4-9600 sec
Highest Reading n/a
Lowest Reading n/a
The Failsafe State is Load Default
only enforced when
Parameters
a problem is detected
with the process Choosing “Yes” to Load Default Parameters resets all menu
input. It is not reli- parameters to factory settings.
ably enforceable in
instances of internal
circuitry failure such as
EEPROM problems.
24
Calibration Menu
Toggles with the temperature value that should be input to
perform the low calibration operation.
The low calibration operation is triggered by pressing the up
arrow key.
Options Menu
Display Parameter Selection
Installed Card
Serial Communications
Serial Communications
with Switch Input
Remote Analog Setpoint
Auxiliary Output
Alarm
Switch Input with Alarm
25
Autotuning
To place the controller in Autotune mode:
In order for the controller 1) Configure the controller by following the directions for
to autotune properly, the Initial Setup Sequence through Step 3 on page 7. Set
setpoint value must be at damping parameter. (See page 22.)
least 1% of span above or
below the initial process 2) If the controller is not already in Standby mode, place it
value. Make sure that in Standby now as follows. Press and hold the
the Setpoint Target Time Mode/Enter key for three seconds. Display will indicate
parameter is set to OFF.
your current operating mode. Press the Raise key or
Tuning accuracy increas-
Lower key to select Standby. Press Mode key again
es as the spread between and the display will alternate between and the pro-
ambient and setpoint cess value. This will deactivate all outputs.
value increases.
3) If Setpoint Value has not been entered, adjust setpoint
Tuning should be
performed with system
now by using the Raise or Lower key to set the desired
in equilibrium (no latent setpoint.
energy remaining). 4) Wait for process to stabilize before proceeding, e.g., in the
case of a heating and cooling process, return to ambient
temperature.
5) Initiate Autotuning. Press and hold the Mode/Enter key
again for three seconds, then press the Raise or Lower
key repeatedly until appears. Finally, press the
Mode/Enter key again. The display will alternately indicate
and process value as the controller “learns” the
proper proportional band, derivative, and integral values
for the process. If unacceptable overshoot occurs on
restart, shut down the process and increase the damping
setting. If sluggish response is observed, shut down the
process and decrease the damping setting.
26
Autotuning
If a tune error condition occurs, the upper display will toggle
between and a numeric error code for three seconds before
the tune process terminates. The controller will then automatically
go into Standby mode when a tuning error occurs. Possible error
codes are:
02 = No PID Device Configured
03 = Incorrect Output Action
05 = Insufficient Setpoint-Process Value Deviation
08 = Invalid Tune Results
09 = Tune Timeout
Current Standby
Mode Mode Flashes
Standby Autotune
Mode Mode Flashes
27
Manual Tuning
Manual Tuning Procedure
While some processes (Zeigler-Nichols PID Method)
other than heat or This tuning method may be used for non-temperature control
cool applications may
processes or if the spread between ambient temperature and
respond successfully to
autotuning procedures, process operating temperature is small. For best results, the
the controller may need use of a recording device is required when tuning with this
to be manually tuned method.
for non-temperature
processes. 1) For temperature control processes, disable any cooling
device used.
2) With the power off and the controller NOT in the Key
Lockout security level, apply power and immediately put
the controller in Standby mode by pressing the Mode/
Enter key for three seconds, the Raise key until
appears and press the Mode/Enter key again.
3) If you have a direct-acting output, it must be disabled
before proceeding further = .
4) Under the Control menu, make sure that the derivative
term , the offset term , and the integral
term are all set to zero, and the proportional
band or is set to the maximum setting.
5) Adjust setpoint to the desired value with the Raise/Lower
keys.
6) Press the Mode/Enter key for four seconds, the Raise
key twice , and the Mode/Enter key again to
return the controller to normal operation.
7) While monitoring the recording device, decrease the
proportional band value by repeatedly halving the
value until a small, sustained temperature oscillation is
observed. Measure the period of one cycle of oscillation
(“T” on the diagram below).
Autotune Errors
If a tune error condition occurs, the upper display will toggle
between and a numeric error code for three seconds before
the tune process terminates. The controller will then automatically
go into Standby mode when a tuning error occurs. Possible error
codes are:
02 = No PID Device Configured
03 = Incorrect Output Action
05 = Insufficient Setpoint-Process Value Deviation
08 = Invalid Tune Results
09 = Tune Timeout
Ramp/Soak Errors
Possible error codes are:
02 = Recipe Empty (i.e. no non-zero ramp times)
05 = Insufficient Setpoint-Process Value Deviation
29
Technical
Specifications
Operating Limits
Ambient Temperature 32°F to 140°F (0°C to 60°C)
Relative Humidity Tolerance 90%, Non-Condensing
Power 100 to 250 V
50/60 Hz (Single-Phase)
100 to 250 Vdc
24 Vac/dc
Power Consumption Less than 6 VA
Performance
Accuracy ±0.20% of Full Scale
(±0.10% Typical), ±1 Digit
Setpoint Resolution 1 Count / 0.1 Count
Repeatability ±1 Count
Temperature Stability 5 µV /°C (Maximum)
TC Cold-End Tracking 0.05°C /°C Ambient
Noise Rejection >100 dB Common Mode,
>70 dB Series Mode
Process Sampling 10 Hz (100 ms)
Control Characteristics
Setpoint Limits Automatically Adjust to
Selected TC/RTD
Alarms Adjustable for High/Low;
Selectable Process, Deviation,
or Band Alarms
Proportional Band 1 to Span of Sensor
Integral 0 to 9600 Seconds
Derivative 0 to 2400 Seconds
Cycle Time 200 ms; 1 to 120 sec
Control Hysteresis 1 to Span of Sensor
Autotune Operator Initiated from
Front Panel
Manual Control Operator Initiated from
Front Panel
Mechanical Characteristics
Display Dual, 4-digit 0.36” (9.2 mm)
LED display
Process Value: Orange
Setpoint Value/Menu: Green
Numeric Range -1999 to 9999
Front-Panel Cutout 1.771” x 1.771”
(45 mm x 45 mm)
Depth Behind Panel 3.937” (100 mm)
Front Panel Rating NEMA 4X
Operating Temperature 32 to 140° F (0 to 60° C)
Humidity Conditions 90% R.H. max.,
non-condensing
Parameter Retention Solid-state, non-volatile
memory
Connections Input and output via barrier
strip with locking terminals
Contacts Twin bifurcated
30
Technical
Specifications
Input Type
Thermocouple B, C, E, J, K, N, NIC, NNM, R, S, T, Platinel II
Maximum lead resistance 100 ohms
for rated accuracy
RTD Platinum 2- and 3-wire, 100 ohms at
0° C, DIN curve standard (0.00385)
1000 ohms available
Linear 0-50 mV/10-50 mV, 0-5 V/1-5 V
0-20 mA/4-20 mA, 0-100 mV, 0-10 V
Output Device
B 5 A (120/240 Vac) relay, normally
open, used for switching resistive loads. If
relays or solenoids are to be driven, select
the “T” output. If a “B” output is selected,
order snubber network 235Z005U01.
E 0-20 mA
F 4-20 mA, full output to load with 500 ohm
impedance max.
G High impedance ‘F’ (800 ohms max.)
S 20 Vdc pulsed output for solid-state relays.
T 1 A @ 120/240 Vac , solid-state relay, zero
voltage-switched and optically isolated from
drive signal. Only resistive loads to 1A may
be controlled directly. Larger loads may be
controlled using an external contactor.
Y 5 A (120/240 Vac) relay, but normally
closed (output 2 only).
Alarm Type
See ordering code on page 55.
31
Ordering Codes
16 C
32
Recalibration
Procedures
1) Remove power from the controller and disconnect all
The Series C controller output devices. Disconnect input. Attach an appropriate
is precalibrated at the calibrator to the input terminals.
factory. Under normal
circumstances, the 2) Apply power to the calibrator, making sure that the dis-
factory calibration played value is not outside the range of the controller.
should be valid for the Then, apply power to the controller.
life of the instrument. 3) Index to the Calibration Low menu item in the Calibration
If recalibration should
be required, allow the Menu.
controller to warm up (You must have Security Level set to “Factory” to access this menu.)
for 15 minutes and 4) Dial Calibrator to prompted value on the controller’s dis-
follow these steps
carefully. play. See chart below for RTD resistance vs. temperature
values.
5) Allow the controller to settle for at least one minute.
6) Press Raise Key.
7) Repeat Steps 4, 5, and 6 for the Calibration High setting.
8) Press the Menu Access key for three seconds to return to
the Process Value display.
33
Quick-Helps
1. To return the unit to last operating mode
(Normal, Standby, FOP, or Tune):
Action Display
From Menu System: Press and hold PV + SV + Mode
for 3 sec.
From Security Level Menu: Press PV+ SV + Mode
2. To enter Standby
operating mode:
Action Display
From Normal Press and hold
operating mode: for 3 sec.
Press
Press + PV + SV
From FOP (Manual) Press and hold
operating mode: for 3 sec.
Press
Press + PV + SV
Press + PV + SV
3. To escape from Standby Action Display
operating mode: Press and hold
for 3 sec.
Press
Press PV + SV
4. To initiate Autotuning: Action Display
Enter Standby
operating mode
(See Quick-Help #2)
Press
Press
34 Press + PV + SV
Quick-Helps
5. To abort Autotuning Action Display
and return to normal Press and hold
operation: for 3 sec.
Press
Press PV + SV
6. To enter FOP (Manual) Action Display
operating mode: Press and hold
for 3 sec.
Press + PV +
% of Power
Value
Press
to set new
% of Power Value
Press to + PV +
set % of Power % of Power
for Output 2 Value
if desired.
7. To escape from FOP Action Display
(Manual) operating mode: Press and hold
for 3 sec.
Press
Press PV + SV
35
Warranty/
Repairs
Two-Year Limited Warranty
THIS EQUIPMENT IS WARRANTED TO BE FREE FROM
DEFECTS OF MATERIAL AND WORKMANSHIP. IT IS SOLD
SUBJECT TO OUR MUTUAL AGREEMENT THAT THE LIABILITY
OF ATHENA CONTROLS, INCORPORATED IS TO REPLACE OR
REPAIR THIS EQUIPMENT AT ITS FACTORY, PROVIDED THAT
IT IS RETURNED WITH TRANSPORTATION PREPAID WITHIN
TWO (2) YEARS OF ITS PURCHASE.
THE PURCHASER AGREES THAT ATHENA CONTROLS,
INCORPORATED ASSUMES NO LIABILITY UNDER ANY
CIRCUMSTANCES FOR CONSEQUENTIAL DAMAGES
RESULTING FROM ITS USE OR FROM IMPROPER HANDLING
OR PACKAGING OF SHIPMENTS RETURNED TO THE FACTORY.
COMPONENTS WHICH WEAR OR WHICH ARE DAMAGED BY
MISUSE ARE NOT WARRANTED. THESE INCLUDE CONTACT
POINTS, FUSES, ELECTROMECHANICAL RELAYS, AND TRIACS.
UNITS WHICH HAVE BEEN MODIFIED BY A CUSTOMER IN
ANY WAY ARE NOT WARRANTED.
Other than those expressly stated herein, THERE ARE NO
OTHER WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED,
AND SPECIFICALLY EXCLUDED BUT NOT BY WAY OF
LIMITATION, ARE THE IMPLIED WARRANTIES OF FITNESS
FOR A PARTICULAR PURPOSE AND MERCHANTABILITY.
IT IS UNDERSTOOD AND AGREED THE SELLER’S LIABILITY
WHETHER IN CONTRACT, IN TORT, UNDER ANY WARRANTY,
IN NEGLIGENCE OR OTHERWISE SHALL NOT EXCEED THE
RETURN OF THE AMOUNT OF THE PURCHASE PRICE PAID
BY THE PURCHASER AND UNDER NO CIRCUMSTANCES
SHALL SELLER BE LIABLE FOR SPECIAL, INDIRECT,
INCIDENTAL OR CONSEQUENTIAL DAMAGES. THE PRICE
STATED FOR THE EQUIPMENT IS A CONSIDERATION IN
LIMITING SELLER’S LIABILITY. NO ACTION, REGARDLESS
OF FORM, ARISING OUT OF THE TRANSACTIONS OF THIS
AGREEMENT MAY BE BROUGHT BY PURCHASER MORE
THAN ONE YEAR AFTER THE CAUSE OF ACTION HAS ACCRUED.
SELLER’S MAXIMUM LIABILITY SHALL NOT EXCEED AND
BUYER’S REMEDY IS LIMITED TO EITHER (i) REPAIR OR
REPLACEMENT OF THE DEFECTIVE PART OR PRODUCT, OR
AT SELLER’S OPTION (ii) RETURN OF THE PRODUCT AND
REFUND OF THE PURCHASE PRICE, AND SUCH REMEDY
SHALL BE BUYER’S ENTIRE AND EXCLUSIVE REMEDY.
THE SPECIFICATIONS PUT FORTH IN THIS MANUAL ARE
SUBJECT TO CHANGE WITHOUT NOTICE.
36
Warranty/
Repairs
Unit Repairs
It is recommended that units requiring service be returned to
an authorized service center. Before a controller is returned
for service, please consult the service center nearest you. In
many cases, the problem can be cleared up over the telephone.
When the unit needs to be returned, the service center will
ask for a detailed explanation of problems encountered and a
Purchase Order to cover any charge. This information should
also be put in the box with the unit. This should expedite
return of the unit to you.
This document is based on information available at the time
of its publication. While efforts have been made to render
accuracy to its content, the information contained herein does
not purport to cover all details or variations in hardware, nor
to provide for every possible contingency in connection with
the installation and maintenance. Features may be described
herein which are not present in all hardware. Athena Controls
assumes no obligation of notice to holders of this document
with respect to changes subsequently made.
Proprietary information of Athena Controls, Inc. is furnished
for customer use only. No other use is authorized without the
written permission of Athena Controls, Inc.
37
IEC
Requirements
USE OF THIS EQUIPMENT IN A MANNER NOT SPECIFIED BY
THE MANUFACTURER MAY IMPAIR PROTECTION PROVIDED
BY THE EQUIPMENT!
38
Glossary
Alarm Delay - the time delay between the detection of the alarm condi-
tion and the initiation and indication of the output action.
Alarm Inhibit - prevents low setpoint alarm activation during cold startup
applications.
Bias - allows the operator to compensate for any difference between sensor
temperature and the point to be measured. The process display and set-
point will be offset by the value entered in the Bias parameter in the input
menu. Ex: Desired temperature is 150 degrees. Sensor is adjacent to heater
and reads 50 degrees higher than the actual process temperature. Enter
bias of -50. Enter setpoint of 150. Process will display 150 even though
sensor will be measuring 200 degrees.
Blanking - controls the time the setpoint value display remains on. After the
set time, the setpoint value display turns off. Pressing any button causes the
setpoint value display to reappear for the selected time interval.
Cycle Time - The period of time in which the controller’s output completes
an on-off cycle (Proportional Output Type only).
Example: Output type = Mechanical relay
Cycle time = 10 seconds
Output power = 50%
Controller output = 5 seconds closed,
5 seconds open
Deadband - In On/Off temperature control, it is the band above or below
the setpoint where there is no output action. It has the effect of moving the
apparent setpoint.
Derivative (rate) - Adjusts the controller gain quickly in response to load
changes.
Failsafe State - designates the percentage of power output that the con-
troller defaults to after it detects a loop break condition and after the loop
break time has elapsed.
Filter (in Display menu) - changes the filtering speed for the process value
display only. It does not affect control. This parameter is mainly used to
slow down the flickering of the display when the decimal position chosen is
greater than zero.
Filtering (in Input menu) - sets the time period over which the process
value is averaged.
Highest Reading - records the highest process value read by the controller.
It may be reset to zero by using the Raise or Lower arrow keys.
Hysteresis - In On/Off temperature control, hysteresis represents the band
where the output changes state from deactivated to activated. It prevents
chattering around the setpoint and prevents rapid output cycling.
Integral (automatic reset) - slowly adjusts the position of the Proportional
Band (range of power output) to eliminate offset error.
Loop Break - a condition where the input is not changing or responding
properly to the output action. This could be caused by a thermocouple or
39
Glossary
input failure, or a heater or load failure.
Loop Break Time - the time interval from when the controller detects a
loop break condition and the initiation of the failsafe state.
Lowest Reading - records the lowest process value read by the controller.
May be reset to zero by using the Raise or Lower arrow keys.
Lower Setpoint Limit - prohibits users from adjusting the setpoint lower
than the selected value.
Manual Reset - an adjustment that moves the Proportional Band up or
down by a fixed percentage so that more or less power is applied at set-
point. It is used to eliminate offset error.
On/Off Output Type - In a heating application, the controller applies 100%
output power if the process temperature is below the setpoint and 0% at
the setpoint. For a cooling application, the controller applies 100% output
power if the process temperature is above the setpoint and 0% output
power at the setpoint. There are only two output states: fully on and fully
off.
Applications for On/Off Control:
1. When temperature oscillation is acceptable.
2. When constant cycling of mechanical devices is
prohibited (Compressors, Blowers, etc.)
3. Under-powered processes
Output Low Limit % - Prohibits the controller’s output from going
below the specified percentage.
Output High Limit % - Prohibits the controller’s output from going above
the specified percentage.
PID Output Type (Proportional - Integral - Derivative) - The controller
modulates output power by adjusting the output power percentage within
a proportional band. Power is proportionally reduced as the process
temperature gets closer to the setpoint temperature. PID control helps
reduce overshoot on start-up, enhances stability, and compensates for
process lag. The PID parameters are automatically calculated for a par-
ticular application during the autotune procedure.
Applications for PID Control:
1. Where process temperature lags exist
2. When load changes are present
3. When overshoot is prohibited
4. When very accurate control is required
40
Quick Setup Instructions - Series 16C Temperature Controller
Experienced users, already familiar with the Series 16C, and using the
controller with PID outputs, may follow these condensed instructions to
autotune the controller and get started quickly once the instrument is prop-
erly mounted and wired, and the Security Level is set to . Once setup
is complete, we recommend changing the Security Level back to the most
restrictive level suitable for your application.
These quick setup instructions are not meant as a substitute for reading the
full instruction manual supplied with the controller. Please be sure to read
through the manual for specific details of operation and, most importantly, for safety precautions.
If you have any questions, or experience problems with setting up your controller, consult the full
instruction manual first and, if you still need assistance, contact your Athena representative or call
1-800-782-6776.
1. Apply power. After self-check display stops, place controller in Standby mode by pressing and holding the
Mode/Enter key for 3 seconds, the or key until appears, and then the key again.
will flash, alternating with the Process Value.
2. Press and hold the Menu Access key for 3 seconds until is displayed. Press key once until
appears, then use or keys to select sensor input type.
4. Press the key until Output 1 Action is displayed. Select the desired output action using the
or keys. (Reverse = Heating)
41
Keep This Information in a Safe Place
Configured Parameters Reference Data
Dear Customer:
Please keep this information handy – in case your controller should lose its configured initial parameter
values or for easy reference when setting up a new controller.
After auto-tuning, and when your controller is controlling well, we suggest you
write the displayed value for each of the menu parameters listed below. If you do not use a listed param-
eter, indicate “N/A”. Using this information to document your parameter settings could reduce your
downtime. If you have any questions, or need further assistance, please contact Athena Controls Technical
Support:
Toll-free (in USA): 800.782.6776
Telephone: 610.828.2490
Fax: 610.828.7084
E-Mail: [email protected]
Website: athenacontrols.com
43
For Toll-FreeTechnical Assistance in the USA,
Call Toll Free: 1-800-782-6776
44
900M011U00 REVISION “C” / 04-25-2005