EE2004 3 Transformers - Part 1
EE2004 3 Transformers - Part 1
Chapter 3 Transformers
1. Magnetic Circuits (1/2)
2
1. Magnetic Circuits (2/2)
• The magnetic field intensity H is defined as the mmf per unit length,
i.e. where l is the magnetic path length.
• The variation of the magnetic flux density
(Weber/ or Tesla ) with H is depicted
by the magnetization BH curve on the right.
• For the linear region b, the relation of B
and H can be written as B = µH
where µ is the permeability (H/m).
• The permeability can be expressed as
where is the free space (air) permeability (4π H/m)
and is the relative permeability (air: , iron: )
• Hence the magnetic flux (Weber) φ = BA = µHA
where A the cross section of the core.
3
2. Ideal Transformer (1/5)
• The transformer has laminated iron-core and a primary and secondary windings.
4
2. Ideal Transformer (2/5)
• The AC flux links with the secondary winding. The flux changes( ) and
• The ratio of the primary and secondary voltages is the turns ratio:
6
2. Ideal Transformer (4/5)
7
2. Ideal Transformer (5/5)
Or and
• Turns ratio:
• Power factor angle:
°
• Primary current:
9
4. Non-Ideal Transformer (1/2)
• Part of the primary current generated flux will not link with the secondary
winding. This flux is the primary leakage flux .
• Part of the secondary current generated flux will not link with the primary
winding. This flux is the secondary leakage flux .
10
4. Non-Ideal Transformer (2/2)
• In a real transformer the iron core permeability is not infinite and the
magnetizing current is not negligible. In the equivalent circuit below,
the iron core is represented by a magnetizing reactance .
• Hysterises and eddy currents cause iron losses. These losses are represented
by a resistance , which is connected in parallel with .
11
5. Equivalent Circuits for Practical Transformers (1/3)
and
The division of the above two equation result in :
or
12
5. Equivalent Circuits for Practical Transformers (2/3)
• An impedance can be transferred from one side to the other by multiplying
the square of the turns ratio a. When the secondary impedance is referred to
the primary, the equivalent circuit becomes :
13
5. Equivalent Circuits for Practical Transformers (3/3)
• A further simplification can be made by omitting and and combining all
the series resistors into one equivalent and all of the series inductive reactances
into one, as shown below:
+
+
14
6. Tests on Transformers (1/4)
15
6. Tests on Transformers (2/4)
• The open-circuit test gives the magnetizing current , the supply voltage
and the iron loss . The equivalent circuit is as below :
16
6. Tests on Transformers (3/4)
2. Short-Circuit Test
• The series impedance (
of a transformer is calculated
from a short-circuit test.
• The secondary (LV) is short-circuited
and the primary (HV) is supplied by a
reduced voltage (usually less than 5% of rated voltage).
17
6. Tests on Transformers (4/4)
• The supply voltage ,current and input power are measured on the
primary side and the equivalent circuit is as below :
, and
18
7. Example 2 – Calc of equivalent circuit parameters (1/3)
A 100kVA, 2400V/240V single phase transformer was tested. The short circuit test :
measurement at the low voltage (LV) side with high voltage (HV) shorted. The
open-circuit test : measurement on the HV side with LV open. The results are :
• Open-circuit test (LV open): =2400V , = 2A, = 300W
• Short-circuit test (HV shorted): =80V , = 400A, = 800W
19
7. Example 2 – Calc of equivalent circuit parameters (2/3)
Calculation of the magnetizing impedance (on the high voltage side)
= (2400)(2) = 4800 VA
Calculation of the equivalent series impedance (on the low voltage side)
20
7. Example 2 – Calc of equivalent circuit parameters (3/3)
Equivalent circuit
= 0.005 Ω
= 0.2 Ω
= 19.2 kΩ
= 1.202 kΩ
= 0.005 Ω
= 0.2 Ω
= 192 Ω
= 12.02 Ω
21
8. Losses in Transformers
There are three sources of loss in a transformer: copper, hysteresis, and eddy
current. They use real power and reduce transformer efficiency. The losses appear
in the form of heat and produce an increase in temperature. For large power
transformers, the efficiency is may reach 99.5% under normal operating conditions.
22
8.1 Copper Losses – Winding Losses
• Copper losses are the power losses caused by current flowing through the
winding resistance, losses.
• Skin effect causes the ac resistance of the transformer windings to increase with
frequency, so copper losses increase with frequency if the winding current
remains constant.
• Proper sizing of the winding wire and proper cooling for the transformer
minimize copper losses and its impact.
23
8.2 Hysteresis Losses – Core Losses
• Hysteresis losses are the result of the energy needed to magnetize the core first
in one direction and then the other as the applied ac voltage reverses in polarity.
• The magnetic domains must form in one direction, and then in the other.
Hysteresis losses increase with frequency because the domains must be
reversed more frequently. This is why 50 Hz is used in most parts of the world.
• Hysteresis losses are minimized by the proper choice of magnetic material.
• A new magnetic material has been developed that is amorphous in structure
instead of having the small crystalline grain structure of most current magnetic
materials. This means the magnetic domains are almost atomic in size and
require very little energy to reverse.
• The amorphous magnetic materials have very low hysteresis losses, but
currently can be manufactured only in ribbon form. For this reason, and their
relatively high cost, they are not currently in wide use.
24
8.3 Eddy Current Losses – Core Losses
25
9. Relative Effects Due to Size of Transformer (1/2)
•
•
•
•
•
•
26
9. Relative Effects Due to Size of Transformer (2/2)
27