Power Distribution White Paper
Power Distribution White Paper
Power Distribution White Paper
Power Distribution
Executive summary
For data centers, hospitals and other mission-critical applications, the reliability
and resilience of power distribution systems are top priorities and essential to
securing the critical ICT load.
Equally essential are maintaining safety and eliminating risk to personnel and
equipment during both normal and fault conditions.
This white paper looks at how to improve power supply reliability and safety,
including the dangers of arc flash and how to mitigate against it through careful
power system design and the benefits of power distribution monitoring.
Introduction to power distribution Distribution of power to the load
For hospitals, data centers and other mission-critical applications, A distribution configuration is used to deliver power to the load.
power distribution system integrity is essential in securing the critical This configuration usually comprises a main load breaker (LB) and
ICT load. Accordingly, emergency diesel generators and UPSs are multiple branches, each protected by their own breaker as shown
used to ensure the level of integrity required; these can be used in Fig.3. Sometimes the power distribution is integrated into a
in many different ways to achieve reliable power distribution. For single Power Distribution Unit, or PDU. If an electrical problem
UPSs in particular, there are many factors to be included as part such as a short circuit or overload occurs, it should be limited to
of these considerations. the affected branches without reaching others. This containment
can be achieved by designing in selectivity between the branch
Elements of a power distribution system circuit breakers and the upstream protection. Accordingly, it is
important to use circuit breakers that allow discrimination.
For the reasons above, mission critical applications use a dual-sourced
feed for their power input. One source is the utility grid, while
the other is an emergency supply, often a standby generator. Both
supplies are rated for the total load, which comprises the ICT load LB
and services such as cooling essential to keep the load running. The
input configuration must support automatic transfer of the load
to an alternative supply; this function should be implemented as a
complete solution integrated into the input switchgear and should
include a starting signal for the generator set.
Critical Load
Fig.3: Power distribution configuration with upstream
and downstream breakers
G
Power distribution systems that contain UPSs typically include
an input and output configuration with a load distribution part.
Below we look at examples of these, from the most basic to
more complex and sophisticated.
Static bypass
Battery Inverter
LBB LB
Distribution
Fig.4: Basic power distribution configuration
Output
Fig.2: UPS configuration overview
Load Bank
Comprehensive UPS configuration
Components can be added to the basic configuration to develop a
more comprehensive solution as appropriate to a particular installation.
UPS abbreviations Additional possibilities include: Critical Loa
Abbreviations as below are often used for UPSs, breakers • Rectifier Input Breaker (RIB)
and modules:
• Static Bypass Input Breaker (BIB)
• UPS Uninterruptible Power Supply
• Maintenance bypass switch (MBS)
• ISB Integrated Static Bypass
• Maintenance isolation switch (MIS)
• SBM Static Bypass Module (often a distributed unit)
• Load Bank Breaker (LBB)
• Load Breaker (LB)
To protect each device independently, a separate Rectifier Input 4. Vertically arranged indicators do not ignite (indicators ignited
Breaker (RIB) and static Bypass Input Breaker (BIB) can be used as a result of paint or stickers burning are excluded from
instead of a rectifier and static bypass with one common input. this assessment)
The rectifier input typically also carries the battery charging current. 5. The protective circuit for accessible parts of the enclosure
A further benefit of separated breakers is that the load can be is still effective
supplied via the static bypass. 6. The ASSEMBLY is capable of confining the arc to the defined
area where it ignited, and there is no propagation of the
Maintenance Bypass Switch
arc to other areas within the ASSEMBLY
Adding a Maintenance Bypass Switch (MBS) allows an entire UPS
module to be bypassed and taken off line. The MBS is primarily used In addition, if specified by the manufacturer, criterion 7 applies
to allow voltage free maintenance work on the UPS modules without where the ASSEMBLY is to be suitable for limited continued
disconnecting the load. The MBS can comprise two breakers and operation:
a cable connection between the input and output switchboard. 7. After clearing of the fault or after isolation or disassembly
Alternatively, these switchboards can be combined into a single of the affected functional units in the defined area, emergency
unit if only one MBS is required. operation of the remaining ASSEMBLY is possible. This is
verified by a dielectric test with a value of 1.5 times the
Load Bank Breaker rated operational voltage for 1 minute.
For load testing, UPSs have a test mode that feeds battery stored
energy back into the supply grid. However, some applications require 4.1 Classification with regard to the protection characteristic
testing via a load bank. If so, a Load Bank Breaker (LBB) can be According to their characteristics under arcing conditions
added to handle the load bank connection. ASSEMBLIES can be classified by the manufacturer into:
Maintenance Isolation Switch Arcing class A – ASSEMBLY providing personnel protection
under arcing condition by arc tested zones conforming to arcing
A maintenance isolation switch (MIS) can be added to allow UPS conditions in 8.7, criteria 1 to 5, and by arc ignition protected
testing and servicing without affecting the load. zones, if any;
Arcing class B – ASSEMBLY providing personnel and ASSEMBLY
Latest norms for power distribution protection under arcing conditions by arc tested zones conforming
to arcing conditions to 8.7, criteria 1 to 6, and by arc ignition
IEC regulations set standards for safe products. Often, they also protected zones, if any;
provide guidelines on specifications that should be agreed
between power system manufacturers and their users. Arcing class C – ASSEMBLY providing personnel and ASSEMBLY
protection under arcing conditions by arc tested zones conforming
Possible consequences of inadequate specification to arcing conditions with limited operation in 8.7, criteria 1 to 7,
and by arc ignition protected zones, if any;
Mission critical systems place high demands on the power distribution
equipment they use. IEC standards provide a good starting point Arcing class I – ASSEMBLY providing a reduced risk of arcing
for protecting users, however they are open to interpretation. faults solely by means of arc ignition protected zones.
Therefore, expectations should be discussed and agreed between The power switchgear’s manufacturer and user must agree on
the manufacturer and user, to avoid delivery of a system that is low the arcing class.
cost and IEC-compliant, yet not fit for purpose.
IEC norms and arc flash Customers embrace the ARMS functionality of the Magnum/NRX
ACBs. Door switches connected to the Digitrip with ARMS
Naturally, switchgear must be built according to IEC 61439. Eaton functionality allow for better personnel safety in abnormal
is proud that all its products are verified by testing, which is the most conditions such as maintenance operations.
rigid of IEC’s verification methods.
Yet a potential danger still exists because IEC 61439 does not place Arc detection
any demand on open arc switchgear behavior. Though IEC TR 61641 An arc detection system should only operate when it ‘sees’ an internal
does act as a guideline, unfortunately most end-customers lack arc, preferably in combination with a current surge. The duration of
detailed awareness of this standard. See under ‘Latest norms the arc flash is limited to approximately 100 ms; the time needed
for power distribution’ for more information about IEC TR 61641. to detect and switch off the incoming breaker current. Energy within
the arc flash is equal to l2t. The 100ms reduction decreases the arc
Arc flash free designs flash energy level.
As indicated above, achieving a 100% arc-free low voltage system
is not possible. Some areas such as the incoming cable connections Arc mitigation
and the outgoing functional unit behind the short circuit protection An arc mitigation device should only operate when it ‘sees’ an
device cannot be made arc-free. The rest of the system, including internal arc. Its use will cause limited system damage, but it will
the main and vertical busbars can be made arc-free by using epoxy mean that at least the quenching device must be removed before
coated insulated bars or shrink sleeve covered bars. the system can resume operation after an arc flash. This may be
acceptable in some applications such as hospitals, large commercial
buildings and general industries, but in most cases such a safety
option is viewed as an add-on to an intrinsically safe (arc proof)
design and not as the only way to protect a switchboard.
Description Form
Form 1separation
No internal Form 3a 1 Form 4a
Separation between busbar and functional units 2a
Separation between busbar and functional units, terminals for external
conductors separate from busbar 2b
Separation between busbar and functional units, separation of functional
units from each other, terminals for external conductors separate from 3a
functional units (not from each other)
Separation between busbar and functional units, separation of functional
units from each other, terminals for external conductors separate from 3b
busbar and functional units (not from each other)
Separation between busbar and functional units, separation of functional
units from each other, terminals for external conductors separate from 4a
functional units and each other.
Separation between busbar and functional units, separation of all functional
units from each other. Terminals for external conductors from the functional 4b
units are separate from busbar, the functional units, and each other.
Internal separation forms and their implications Form of internal separation according to British Standard
for de-energization
Although IEC 61439-2 clearly indicates the separation between
Different forms of internal separation allow different degrees busbars, functional units and terminals for external conductors, it
of de-energization when performing maintenance work such as does not specify cable glanding. Therefore, the British Standard
connecting a new cable, as shown in Table 2 below. version of IEC 61439 has added types of Form 4b to cover this.
Form De-energize with cable work Form Type De-energize with cable work
1 Whole board, all loads. 1 1 Separation by insulation, Cables may be glanded elsewhere
2a Whole board, all loads. 2a 2 Separation by metal, Cables may be glanded elsewhere
2b Whole board, all loads. 2b 3 Each functional unit has its own integral glanding facility
3a Whole panel, all loads in that panel Separation by metal, Each functional unit has its own integral
3a 4
3b Whole panel, all loads in that panel glanding facility
4a Whole panel, all loads in that panel, or functional unit depending on construction Terminals separated by insulated coverings, and glanded in
3b 5 common cabling chambers
4b Only functional unit
All separation is by metallic or non-metallic rigid barriers or
4a 6 partitions. Cables are glanded in common cabling chamber.
Table 2: Forms of internal separation and de-energizing implications
All separation is by rigid barriers or partitions. The termination for
4b 7 each functional unit has its own integral glanding facility.
G A E
G C C H
G G G G G
G
D H B D
H
H H H H H H H H H H H H
C C C
F F F F F F F F F F F F F F F
Eaton
EMEA Headquarters
Route de la Longeraie 7
1110 Morges, Switzerland
Eaton.eu
Follow us on social media to get the
© 2018 Eaton Eaton is a registered trademark. latest product and support information.
All Rights Reserved
Publication No. WP155004EN / CSSC-1238 All other trademarks are property
May 2018 of their respective owners.