S400-NE Data Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

DATA SHEET: TEMBREAK 2 S400-NE MCCB

MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS 3947-2, NEMA AB-1
TB2 E/S 630
Max In (A) of Frame 630
Model S400
Number of Poles 3, 4
Type NE

Nominal current ratings


In (A) 50°C 250
400

Electrical characteristics
Rated operational voltage Ue (V) AC 50/60 Hz 690
DC -
Rated insulation voltage Ui (V) 800
Rated impulse withstand voltage Uimp (kV) 8

Ultimate breaking capacity I cu (kA) 690V AC 20


(IEC, JIS, AS/NZS) 525V AC 30
440V AC 45
400/415V AC 50
220/240V AC 85
250V DC -

Service breaking capacity I cs (kA) 690V AC 15


(IEC, JIS, AS/NZS) 525V AC 30
440V AC 45
400/415V AC 50
220/240V AC 85
250V DC -

Rated breaking capacity (NEMA) (kA) 480V AC 25


240V AC 85

Rated short-time withstand current I cw (kA) 0.3 Seconds 5

Protection
Adjustable thermal, adjustable magnetic
Fixed thermal, fixed magnetic
Microprocessor
Utilisation category B

Installation
Front connection (FC)
Extension bar (FB) •
Cable clamp (FW) •
Rear connection (RC) •
Plug-in (PM) •
DIN rail mounting (DA) -
Dimensions height (mm) 260
width (mm) 3 pole 140
(mm) 4 pole 185
depth (mm) 103
Weight weight (kg) 3 pole 4.2
4 pole 5.6

Operation
Direct Opening Action
Toggle operation
Door mounted (HS) / Breaker mounted handle (HB) •
Motor operation (MC) •
Endurance Electrical cycles 415V AC
Mechanical cycles 4,500
15,000

Standard • Optional - Not Available


Page 1 of 4
DATA SHEET: TEMBREAK 2 S400-NE MCCB

Outline Dimensions S400-NE

ASL: Arrangement Standard Line HL: Handle Frame Centre Line

Front connected

With extension bars


(optional)

30

Rear connected

Front connected with Motor Operator

With extension bars


(optional)

30

Rear connected with Motor Operator

Page 2 of 4
DATA SHEET: TEMBREAK 2 S400-NE MCCB

Outline Dimensions S400-NE Plug-in Version


ASL: Arrangement Standard Line HL: Handle Frame Centre Line

Outline Dimensions Termination of Busbar

Preperation of conductor
Support or rail

20 (max.)

11
Mounting screw
M10x30 max.
30 (max.) 8 (max.)

Mounting on a support or rails (shown with optional connection bars oriented for rear access)

Support or rail

Mounting through the backplate (shown with optional connection bars oriented for rear access)

Mounting plate 113


102
Mounting screw M5 x 20
6t
6t
260
102
90

198
258
276

97
138
4 142
180 65 48

Mounting on the backplate (optional connection bars must be oriented for front access)

Insulating plate
Mounting screw M6x70 Mounting plate
32 1
6t
260
102
90

97
32 1
204 12
4 208
246
Mounting M6 NUT
Insulating plate

Page 3 of 4
DATA SHEET: TEMBREAK 2 S400-NE MCCB
Time/Current Characteristic Curves
S400-NE

Percent Rated
Current In Percent Rated Current IR

In = 400A; 250A Note (1)


IR (A)
LTD Pick-up current IR xIn 0.4 0.5 0.63 0.8 0.9 0.95 1.0

Characteristics No. 1 2 3 4 5 6 7
11 21 21 5 10 19 29
LT tR (s)
at 200% x IR at 600% x IR
Standard xIR 2.5 5 10
ST
Isd
tsd (s) 0.1 0.2
INST Ii xIR 14(Max: 13 x In) Note (2)
xIR 0.8
PTA
Ip
tp (s) 40
gF Ig xIn 0.2
Option Note(4) tg (s) 0.2
xIR 1.0/0.5 Note (3)
NP
IN
tN (s) tN=tR

Note
(1) gF is not available when In is 250A. (2) Ii max. = 13 x In. (3) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN) is
identical to characteristic of phase protection (tR vs. IR). (4) When you specify gF on MCCBs with 3 poles the terminal block is automatically fitted to
connect with the external neutral CT for 3 phases 4 wires system. See terminal blocks in section 4.

Page 4 of 4

You might also like