S400-NE Data Sheet
S400-NE Data Sheet
S400-NE Data Sheet
MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS 3947-2, NEMA AB-1
TB2 E/S 630
Max In (A) of Frame 630
Model S400
Number of Poles 3, 4
Type NE
Electrical characteristics
Rated operational voltage Ue (V) AC 50/60 Hz 690
DC -
Rated insulation voltage Ui (V) 800
Rated impulse withstand voltage Uimp (kV) 8
Protection
Adjustable thermal, adjustable magnetic
Fixed thermal, fixed magnetic
Microprocessor
Utilisation category B
Installation
Front connection (FC)
Extension bar (FB) •
Cable clamp (FW) •
Rear connection (RC) •
Plug-in (PM) •
DIN rail mounting (DA) -
Dimensions height (mm) 260
width (mm) 3 pole 140
(mm) 4 pole 185
depth (mm) 103
Weight weight (kg) 3 pole 4.2
4 pole 5.6
Operation
Direct Opening Action
Toggle operation
Door mounted (HS) / Breaker mounted handle (HB) •
Motor operation (MC) •
Endurance Electrical cycles 415V AC
Mechanical cycles 4,500
15,000
Front connected
30
Rear connected
30
Page 2 of 4
DATA SHEET: TEMBREAK 2 S400-NE MCCB
Preperation of conductor
Support or rail
20 (max.)
11
Mounting screw
M10x30 max.
30 (max.) 8 (max.)
Mounting on a support or rails (shown with optional connection bars oriented for rear access)
Support or rail
Mounting through the backplate (shown with optional connection bars oriented for rear access)
198
258
276
97
138
4 142
180 65 48
Mounting on the backplate (optional connection bars must be oriented for front access)
Insulating plate
Mounting screw M6x70 Mounting plate
32 1
6t
260
102
90
97
32 1
204 12
4 208
246
Mounting M6 NUT
Insulating plate
Page 3 of 4
DATA SHEET: TEMBREAK 2 S400-NE MCCB
Time/Current Characteristic Curves
S400-NE
Percent Rated
Current In Percent Rated Current IR
Characteristics No. 1 2 3 4 5 6 7
11 21 21 5 10 19 29
LT tR (s)
at 200% x IR at 600% x IR
Standard xIR 2.5 5 10
ST
Isd
tsd (s) 0.1 0.2
INST Ii xIR 14(Max: 13 x In) Note (2)
xIR 0.8
PTA
Ip
tp (s) 40
gF Ig xIn 0.2
Option Note(4) tg (s) 0.2
xIR 1.0/0.5 Note (3)
NP
IN
tN (s) tN=tR
Note
(1) gF is not available when In is 250A. (2) Ii max. = 13 x In. (3) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN) is
identical to characteristic of phase protection (tR vs. IR). (4) When you specify gF on MCCBs with 3 poles the terminal block is automatically fitted to
connect with the external neutral CT for 3 phases 4 wires system. See terminal blocks in section 4.
Page 4 of 4