Research Proposal Report
Research Proposal Report
Protection of a microgrid is one of the major decisive and daunting technical challenges for its
deployment into the power system and it must respond effectively to both internal faults and
external faults in both modes of operation. During the parallel operation, if there is any fault
occurs on the utility grid, then the desired response is to isolate microgrid from the utility grid to
protect the critical loads. Whereas, minimum possible section of the faulted feeder should be
isolated for any for any fault occurs inside the microgrid. The penetration of DERs not only
changes the power flow in the distribution system but also alters the level and direction of fault
currents because of dynamic characteristics and intermittent nature of the renewable energy
sources, which intensely affects the operation and co-ordination between the protection devices.
Since, most of the protection devices of the traditional distribution system like fuses, reclosers,
relays and circuit breakers are designed based on sensing of unidirectional fault current. Hence,
these traditional protective devices are incapable to provide proper protection for the reliable and
safety operation of microgrids.
In this report, the issues and coordination strategies of overcurrent protection of microgrid are
discussed apparently. Further, some research gaps have been found from the literature and some
research objectives are proposed for future work in this area.
i
Chapter 1 Introduction
Due to continues increase in power demand and scarcity of fossil fuels, the distributed energy
resources (DERs) are attractive option for several advantages such as reduction in the peak
demand, CO2 emission, line cost and increases supply reliability. The penetration of these DERs
in to electric grid results a new grid paradigm known as microgrid. A microgrid is an aggregated
power system, which comprises a cluster of interconnected loads, various distributed energy
resources and energy storage devices. It can operate in both grid connected and islanded mode of
operation and provides all the needs of its local customers [1].
From the utility view, the microgrid is supposed to be a single controllable unit of the traditional
power system network, which retaliates very quickly to meet the requirements of the
transmission system. From the customer’s view, the microgrid is a specifically designed power
system which ensures local reliability, enhances the safety of power, decreases the emission,
increases the efficiency, improves quality in supply by reducing the voltage sags, and provides
most economical power to the customers. From the environmental view, microgrids reduce the
effects of greenhouse gases such as global warming, depletion of the Ozone layer and
environmental pollution by using suitable low carbon technologies [2].
The typical schematic diagram of a microgrid is depicted in Fig. 1 [3]. The microgrid as shown
in Fig. 1 comprises of three feeders such as feeder A, feeder B, and feeder C. The circuit
breakers CB1, CB2, and CB3 are provided for connection and disconnection of feeders A, B, and
C respectively, and the sub-sections of each feeder are protected by operating sectional circuit
breakers (SCBs). The feeders A and B are connected by micro-sources and storage devices
through microcontrollers (MCs) and loads those are connected to feeder A and B are assumed to
be priority loads and receive a continuous power supply. But, the loads connected to the feeder C
are assumed as non-priority loads and which will be curtailed when necessary. The entire
microgrid is coupled with the macrogrid through a circuit breaker available at a point of common
coupling (PCC) and the breaker can be operated for connection and disconnection of microgrid.
The main objective of the MC is to control the power-flow and voltage-profile of DERs in
accordance with the load variations and various disturbances. The CC performs the overall
operation and protection of microgrid with help of microcontrollers.
In general, the microgrid has the ability to operate in two modes of operation, such as grid-
connected and islanded modes of operation. In grid-connected mode, the microgrid operates in
parallel with microgrid and it receives or sends the power from or to the macro-grid. Whereas in
the case of any abnormal conditions occur inside the macrogrid, the microgrid will be transferred
to islanded mode of operation. This will be attained by following three different cases [4]:
Case 1: The entire microgrid can be isolated by operating the circuit breaker available at the
PCC and both the critical loads and non-critical loads are supplied by micro-sources those are
connected to feeder A and feeder B.
1
Case 2: The feeders A and B are isolated together by using static switch (SS) and the priority
loads will receive power from micro-sources. Whereas, the non-critical loads connected to the
feeder C will be disconnected by opening CB3.
Case 3: The feeders A and B are isolated by operating the breakers CB1, and CB2, respectively.
The power will be supplied to critical loads of each feeder through the corresponding micro-
sources and the non-critical loads of feeder C are curtailed by opening the breaker CB3.
2
turbine generator systems are adopted with the rotating machine-based coupling units. Whereas,
the electronically coupled units are adopted by the solar photovoltaic systems, gas turbine
generator systems (high and medium speed) and few types of wind turbine generator systems.
These systems are either dispatchable systems or non-dispatchable systems. In order to increase
the efficiency of non-dispatchable units like wind turbine units, solar photovoltaic units, these
are set to operate at maximum power by using the Maximum Power Point Tracking (MPPT).
Also, every component of a microgrid is featured with the Plug-and-Play and Peer-to-Peer
capabilities. The Plug-and-Play functionality ensures that a unit can be connected to microgrid
at any point without altering the protection and control schemes of pre-existence units. The Peer-
to-Peer functionality implies that there is no requirement of any critical components like a master
controller or primary storage for the operation of the microgrid. Even though there is a loss of
any microsource or component, the microgrid insures its normal operation by adding an extra
source or component.
4
1.1.2 Bi-directional fault current
The power flow in the distribution system has been changed due to rapid growth in the number
of distributed energy sources incorporated into the network. The penetration of DERs not only
changes the power flow in the distribution system but also alters the level and direction of fault
currents because of dynamic characteristics and intermittent nature of the renewable energy
sources, which intensely affects the operation and coordination of the protection device. Hence,
the traditional protective devices like unidirectional over current relays and fuses are
incompatible to provide the reliability and safety operation for Microgrids. The principle of Bi-
directional fault current is illustrated in below Fig. 1.3. From the figure, it can be noticed that for
downstream fault the current flowing through the relay is in forward direction but whereas for
upstream fault the current sensed by the relay is in reverse direction.
5
1.1.4 Blinding of protection
In a microgrid, during the occurrence of fault on any feeder at a distant from the substation, then
the contribution of maingrid to total fault current is decreased due to the presence of DERs. In
Fig. 1.5, the current sensed by the relay is I Gf, which is comparatively less than the actual current
at fault point i.e. If = IGf +Ig1f. This difference between maingrid contribution and the total fault
current will become higher as more number of DERs connected to a microgrid. Consequently,
the over current relay of the feeder in microgrid is incapable to detect the fault condition and
which leads to faulty operation of whole protection system. This mechanism is known as
blinding of protection and this arises mostly when synchronous generators present in the
microgrid. In order to analyze the effect of above mentioned issue, a radial feeder with a DER
connected at a distance ‘d’ has been considered and assume a fault incepted at far end of the
feeder i.e. at a distance ‘L’, which is shown in Fig. 1.5.
The equivalent circuit of Fig. 1.5 is depicted in the Fig. 1.6. Let us consider VG and Vg are
the voltages of main grid and distributed generator respectively, the fault currents contributed by
both grid and distribution generator are represented as I Gf and Igf respectively, Zs, ZL and Zg are the
impedances of the main grid, line, and DER respectively and ‘l’ is the distance parameter which
indicates the location of DER with respect to the total feeder length and this is defined as:
(1)
6
To obtain the expressions for currents I Gf and Igf, the Thevenin’s theorem is implemented on the
network shown in Fig. 1.6 and the equivalent Thevenin’s circuit is shown below Fig. 1.7.
(2)
In equation (2), Zs=jXs is impedance of the main grid, Z g=jXg is impedance of distribution
generator, ZL=RL+jXL is total impedance of the line, l is the relative location of the generator as
stated in equation 1. Now, the three-phase fault current is determined as:
(3)
By substituting the equation 2 in equation 3 yields:
(4)
By applying current division rule, the fault current contributed by grid is given by
(5)
The combination of equation and equation gives:
(6)
The total fault current, If,3ph, which is calculated by the equation 4 is non-linear. So, I Gf,
the grid contributed current, which is obtained from equation 6 is also non-linear in nature. So,
whenever fault occurs at lower end of microgrid’s feeder, the grid contribution to total short
circuit current reduces because the source impedance, Z s, is comparatively higher than the
generator impedance, Zg and also because of distribution generator contribution. So, the fault
current flowing through relay of feeder is less than pickup setting of the relay and as a result
feeder relay cannot detect the fault condition, which leads to inadequate operation of whole
protection system.
7
To discuss the protection issues briefly, a 4-bus distribution network as shown in Fig. 1.8 with
grid, synchronous based DER (SBDER), Inverter based DER (IBDER) and having switches (S1-
S3) and relays (R1-R6) is considered. Each fault point in the network must has primary relay
(PR) and backup relay (BR) and the BR will operate after some pre-defined time when its
corresponding PR fails to operate.
For a fault ‘F’, the fault currents contributed by three sources are shown in figure. The fault
current contributed by SBDER is five times the rated current. So, fault current seen by the
relay R3 may be exceeded the pick-up current and which results in unnecessary isolation of
healthy section. Hence, directional overcurrent relays are employed to retain the selectivity. The
fault current flowing through relay R1 with presence of SBDER ( ) is decreased as fault
current contributed by both grid and SBDER. So, the relay R1 may not be detect the fault or it
will take more time to detect the fault. The maximum fault current flows through relay R6 is 2
times the rated current which will affect the sensitivity.
For fault point ‘F’, the R1 and R4 are backup relays to the primary relay R5. With the existence
of SBDER, the fault current ( ) flowing through relay R1 is less than the fault current (
) during the absence of SBDER. whereas, the fault current flowing through R5 is increased due
to presence DERs. Hence, the operation time of relays R1, R5 are increased and decreased
respectively. As a result, the protection co-ordination between the primary and backup relays are
affected due to presence of DERs in distributed networks.
8
Chapter 2 Literature survey
In order to overcome the protection issues, several researchers have been proposed various
approaches, namely adaptive protection based overcurrent techniques, multiagent protection
schemes, sequence component based schemes, protection schemes based on fault current
limiters, protection schemes based on variables namely current samples, travelling wave based
approach, and local variables and protection coordination strategies such as optimization
methods, communication based, and other strategies are discussed in this section.
9
whenever fault occurs the DERs connected to the distribution system are disconnected through
fast switches by sensing the fault current using current sensing device which is located at PCC.
It has some advantages such as the settings of protection devices need not to be changed and the
implementation cost is less. However, the disconnection of DERs is not appropriate because it
reduces the reliability of the system. Also, it prevents the operation of microgrid in islanded
mode.
10
A unidirectional fault current limiter (UFCL) is installed between the main grid and microgrid. It
only limits the contribution of microgrid during a fault in the main grid. Whereas, during a fault
in the microgrid, the UFCL is inactive and allows a full contribution main grid. Hence, with this
approach the proposed UFCL can preserve the coordination of main grid overcurrent relays, and
also as an added advantage, alleviate deep voltage sags caused by the main grid faults [14].
In [15], FCL is used to address the protection coordination of DOCRs in microgrid system by
considering both grid connected and islanded mode of operation simultaneously. Genetic
algorithm has been used to find the optimal settings of the relays and obtained results are
compared with particle swarm optimization technique. It is observed that GA gives the better
solution with fast convergence rate and it is able to exit local minima than the Particle swarm
optimization (PSO) technique. The main advantage of the proposed method is that it gives a
single relay setting for both grid connected and islanded mode of operation. However, some
relays are experiencing higher operating times that is not recommendable for feasible operation
of the relays. Also, it does not consider neither fault ride through of synchronous generator nor
the presence of inverter-interfaced DGs and energy storage devices.
In [16], the fault current limiters concept has been used in used to find the single relay settings
for both grid connected and islanded mode operations of microgrids. The optimization
techniques such as cuckoo search and linear programming have been used to find the pickup
current and time dial settings respectively. However, the constraints regarding limits on
operating times of the relays are not considered. As a result, few relays have experienced higher
operating times.
To sum up, this is one of the effective approaches to reduce effect of high fault current in
distribution network and also minimizes the operation time of each relay, co-ordination time of
relays irrespective of microgrid configuration. However, the usage of FCLs results in extra cost
and it is applicable only to systems with certain number of DERs. Also, the location of FCL is
difficult to find due to the dynamic configuration of microgrid.
11
In [18], an adaptive protection co-ordination scheme using DOCRs is proposed for effective
relay co-ordination under the variations of loads, outages of any lines and distributed generation.
An AMPL based IPOPT solver is used to find the optimal settings and the obtained results are
compared with GAMS based SNOPT solver, MATLAB based IPOPT solver, MATLAB based
interior point method, GA and DE.
In [19], an adaptive protection scheme is proposed to solve the protection co-ordination problem
in distribution networks with penetration of distributed generations. The proposed protection
scheme is having three layers such as execution layer, co-ordination layer, and management
layer to calculate the relay settings during any changes in the system. The proposed scheme has
been implemented on Hardware-in-loop test bed to validate its effectiveness using real time
digital simulator.
In [20], an adaptive protection approach has been proposed to solve directional relay co-
ordination in distribution system with distributed generation. The optimum relay settings have
been determined using ant colony optimization algorithm and compared with genetic algorithm.
The proposed approach has been successfully tested for topological changes of network,
contingencies such as line, generator outages, and load demand variations. However, finding the
optimal solution using optimization algorithm should take more time for any changes in the
network.
In [21], an adaptive multi-agent scheme has been proposed for co-ordination of relays in
distribution system with distributed generation. The proposed scheme consists of three agents
namely relay, equipment and DG. All these agents must communicate with each to share the
data. The proposed scheme does not require any central data processor and voltage transformers
result in the reduction of cost. Also, it works effectively for all types of faults including HIFs.
However, it requires the high-speed communication structure for reliable operation and there
could be uncertainties for proper operation of agents.
In [22], sequence currents based adaptive protection approach is proposed for the protection of
distribution network with the presence of DERs. Each relay of the distribution network is
provided with two settings for particular fault point and the selection of these settings is based on
the operation of relay (Primary or Backup). The positive sequence based directional over current
relay module will be selected for primary operation and negative sequence based directional over
current relay module is chosen for the backup operation. The direction of fault current is
measured using phase angle between superimposed and pre-fault currents. Mostly, the inverse
definite minimum time relay characteristics will be used for finding the time of operation for
each relay.
In [23], a new adaptive DOCR based on superimposed components of positive sequence and
negative sequence currents is presented for the protection of microgrid. The proposed method is
tested in four different modes such as islanded mode of operation with only IBDER, islanded
mode of operation with both IBDER and SBDER, Grid-connected mode of operation, and
connection/disconnection of DERs depending up on requirement. An impact factor is considered
12
based on these operations of microgrid. Depending on the mode of operation, this impact factor
is calculated using the pre-fault and fault currents seen by the relay.
13
drawback of both the methods, the initial solution of relay settings (PS and TDS) are determined
using GA and final optimum solution has calculated using NLP.
In [29], Biogeography-Based optimization (BBO) algorithm is applied to solve the directional
over current relay co-ordination problem. Further, a hybrid BBO with linear programing method
is proposed to enhance the performance of BBO. The proposed algorithm has been implemented
on five different systems and simulation results are compared with well known algorithms
available in recent literature. The results disclose that total operating time of relays has
minimized while using hybrid BBO.
In [30], a new seeker optimization algorithm has been implemented to find the optimal settings
of directional over current relays in multi loop systems. The co-ordination problem has been
converted into both linear (fixed IP, continues TDS) and mixed integer non-linear (discrete IP,
continues TDS) models and the results obtained in both the models are compared with simplex
method, GA, GA-LP, PSO and MINP standard branch and bound algorithm.
In [34], a two-stage analytical method depends on generalized Benders decomposition has been
used to find the optimal pick up current and time dial settings of directional over current relays.
The proposed method has been solved co-ordination problem by converting as multi integer
nonlinear programming problem. The obtained results are compared with two well known
MINLP solvers such as SBB and BARON.
14
In [35], a new time–current–voltage tripping characteristic depends not only on current
magnitude but also on voltage magnitude is proposed to reduce the overall operation time of
DOCRs in meshed distribution networks. The protection coordination optimization (PCO) model
is solved to obtain the optimal settings for proper coordination of all DOCRs under LG, LLG,
LL, and three phase faults. The main objective of the PCO is to minimize the total operating time
of all the relays subjected to the constraints namely protection coordination, relay setting, and
relay operating time. The proposed scheme obtained significant reduction in operating time when
compared to conventional technique in both presence and absence of DERs. However, it doesn’t
consider the effect of dynamic changes in network topology of the system.
In [36], a novel approach capable of finding one optimal settings of the relay is proposed to plan
the proper coordination and that settings are feasible for all possible future installation of DGs.
Consequently, it provides to the utility planners one set of relay settings valid for different
capacities of DG units varying between zero and the maximal desired capacity. It is observed
that the relay settings are need not to be changed with change in penetration of DGs and the
coordination is preserved during the outages of the DGs. However, it doesn’t implement on any
hardware prototype and only synchronous generators are considered but no other DGs namely
solar and wind are not included in test system.
15
In [39], a multi-terminal hybrid protection strategy is proposed for MGs consisting of both
traditional differential and adaptive protection schemes. The centralized adaptive protection is
used to find settings of relay and traditional differential scheme is used in highly sensitive areas
which include transformers and sensitive loads in the MG and the adaptive protection is also
used as backup strategy when the differential scheme fails in highly sensitive areas of the MG.
The protection strategy is robust against communication failures and can protect its expensive
and sensitive equipment. However, the performance of this strategy is yet to be tested
experimentally.
16
current, power angle, symmetrical components of voltage and current. These variables should be
computed in the relay and it will transfer to remaining all relays using communication system.
Then all the relays find the difference between local and remote variables and which will store in
new parameter Z. Lastly, based on the variable Z each relay will take the decision whether the
fault occurs or not by using statistical classifier. Hence, the fault should be detected and cleared
very easily using the statistical classifier [42]. This scheme provides reliable protection for all
types of faults and it has high classification accuracy. However, it is not adaptable to dynamic
changes of microgrid topology and it is worked for the only islanded mode.
17
It provides one relay setting for Use of FCLs results in extra
2 Fault current limiters
both grid connected and islanded cost.
mode of operation. Applicable only to systems
One of the effective approaches with certain number of DERs.
to decrease the effect of high
The location of FCL is
fault currents in DNs.
difficult to find due to
No need for communication and
dynamic configuration of
central controller
microgrid.
7 Optimization based It provides best optimal solutions Heuristic methods take more
18
for effective operation of time not suited for online
microgrids. operation of power system.
3.5 Conclusions
The protection is one of the major technical challenges in microgrid and it has to respond to both
internal and external faults for the adequate operation. However, by virtue of intermittent nature
of DERs and different configurations of microgrid result in several protection issues such as
dynamics in fault currents, bi-directional fault currents, spurious disconnection and blinding of
protection. To overcome these issues, several researchers have been proposed various
approaches, namely adaptive protection based overcurrent techniques, multiagent protection
schemes, sequence component based schemes, protection schemes based on fault current limiters
protection schemes based on variables namely current samples, travelling wave based approach,
and local variables and protection coordination strategies such as optimization methods,
communication based, and other strategies are discussed briefly along with their merits and
demerits. The research on microgrid protection is being in developed stage. There is need to
develop a better protection algorithm which will overcome all protection issues for reliable and
effective operation of microgrid.
19
References
[1] H. J. Laaksonen, “Protection principles for future microgrids,” IEEE Trans. Power Electron., vol.
25, no. 12, pp. 2910–2918, 2010.
[2] M. A. Zamani, T. S. Sidhu, and A. Yazdani, “Investigations into the control and protection of an
existing distribution network to operate as a microgrid: A case study,” IEEE Trans. Ind. Electron.,
vol. 61, no. 4, pp. 1904–1915, 2014.
[3] S. Chowdhury, S. P. Chowdhury, and P. Crossley, Microgrids and Active Distribution Networks.in
IET Renewable Energy Series 6, the Institute of Engineering and Technology, London, United
Kingdom, 2009.
[4] K. I. Jennett, C. D. Booth, F. Coffele, and A. J. Roscoe, “Investigation of the sympathetic tripping
problem in power systems with large penetrations of distributed generation,” IET Gener. Transm.
Distrib., vol. 9, no. 4, pp. 379–385, 2015.
[5] E. J. Coster, J. M. A. Myrzik, B. Kruimer, and W. L. Kling, “Integration Issues of Distributed
Generation in Distribution Grids,” Proc. IEEE, vol. 99, no. 1, pp. 28–39, 2011.
[6] E.Coster, J. Myrzik and Wil Kling,“Distributed Generation”, Publisher Intech, chapter 5, pp. 93-
106, 2010.
[7] S. Parhizi, H. Lotfi, A. Khodaei, and S. Bahramirad, “State of the art in research on microgrids: A
review,” IEEE Access, vol. 3, pp. 890–925, 2015.
[8] B. J Belwin, R. R. Prabu, “A review on issues and approaches for microgrid protection”, Renew.
Sustain. Energy Rev., vol. 67, pp. 988-997, 2017.
[9] S. A. Gopalan, V. Sreeram, and H. H. C. Iu, “A review of coordination strategies and protection
schemes for microgrids,” Renew. Sustain. Energy Rev., vol. 32, pp. 222–228, 2014.
[10] S.T. Basso, R.D. Blasio, “IEEE 1547 series of standards: interconnection issues”, IEEE Trans.
Power Electron., vol. 19, no. 5, pp. 1159-1162, 2004.
[11] T. Ghanbari, E. Farjah , “Unidirectional fault current limiter: an efficient interface between the
microgrid and main network”. IEEE Trans Power System, vol. 28, no. 2, pp. 1591–98, 2012.
[12] M. Ebrahimpour, B. Vahidi, and Hosseinian, “A hybrid superconducting fault current controller for
DG networks and microgrids”. IEEE Trans Appl Supercond, vol. 23, no.5, 2013.
[13] D.M. Vilathgamuwa, Loh Poh Chiang, Li Yunwei. “Protection of microgrids during utility voltage
20
sags”. IEEE Trans Ind Electron, vol. 53, no. 5, pp. 1427–36, 2006.
[14] T.Ghanbari and E. Farjah, ‘‘Unidirectional fault current limiter: An efficient interface between the
microgrid and main network,’’ IEEE Trans. Power Syst., vol. 28, no. 2, pp. 1591–1598, 2012.
[15] W.K. Najy, H.H. Zeineldin, and W.L.Woon, “Optimal protection coordination for microgrids with
grid-connected and islanded capability”. IEEE Trans Ind Electron, vol. 60, no.4, pp. 1668–77,
2013.
[16] E. Dehghanpour and H. Karegar “Optimal Coordination of Directional Overcurrent Relays in
Microgrids by Using Cuckoo-Linear Optimization Algorithm and Fault Current Limiter”. IEEE
Trans Smart Grid, pp, 2016.
[17] M. Y Shih, A. Conde, et al. “An Adaptive Overcurrent Coordination Scheme to Improve Relay
Sensitivity and Overcome Drawbacks due to Distributed Generation in Smart Grids” IEEE Trans
Ind Appl, pp, 2017.
[18] M.N Alam “Adaptive Protection Coordination Scheme using Numerical Directional Overcurrent
Relays”, IEEE Transactions on Industrial Informatics, pp, 2018.
[19] F. Coffele, C. Booth, and A. Dysko, “An adaptive overcurrent protection scheme for distribution
networks,” IEEE Trans. Power Del., vol. 30, no. 2, pp. 1–8, Apr. 2015.
[20] M.Y Shih, C. A Salazar, and A. C Enriquez “Adaptive directional overcurrent relay coordination
using ant colony optimization”, IET Gener. Transm. Distrib., vol. 9, no. 14, pp. 2040-2049, 2015.
[21] K. K. Li, K. P. Wong, “An Adaptive Multiagent Approach to Protection Relay coordination With
Distributed Generators in Industrial Power Distribution System”, IEEE Trans Ind Electron, vol. 46,
no. 5, pp. 2118–2124, 2010.
[22] H. Muda and P. Jena, “Sequence currents based adaptive protection approach for DNs with
distributed energy resources,” IET Gener. Transm. Distrib., vol. 11, no. 1, pp. 154–165, 2017.
[23] H. Muda, and P. Jena, “Superimposed Adaptive Sequence Current Based Microgrid Protection: A
New Technique,”IEEE Trans on Power deliv, vol. 32, no. 2, pp. 757–767, 2017.
[24] H. H. Zeineldin, H. M. Sharaf, et al. “Optimal protection coordination for meshed distribution
systems with DG using dual setting directional over-current relays” IEEE Trans Smart Grid, vol. 6,
no. 1, pp. 115-123, 2015.
[25] H. H. Zeineldin, H. M. Sharaf, and E. E. Saadany, “Protection coordination for microgrids with
grid-connected and islanded capabilities using dual setting directional overcurrent relays”. IEEE
Trans Smart Grid, pp, 2016.
[26] A. Srivastava, J. M. Tripathi, R. Krishan and S. K. Parida, "Optimal Coordination of Overcurrent
Relays Using Gravitational Search Algorithm With DG Penetration," in IEEE Transactions on
Industry Applications, vol. 54, no. 2, pp. 1155-1165, March-April 2018.
[27] K. S, Zeineldin, H. H. Zeineldin, and El-Saadany, “Optimal Protection Coordination for Microgrids
Considering N−1 Contingency”, IEEE Transactions on Industrial Informatics, 2017.
[28] P. P. Bedekar and S. R. Bhide, "Optimum Coordination of Directional Overcurrent Relays Using
the Hybrid GA-NLP Approach," in IEEE Transactions on Power Delivery, vol. 26, no. 1, pp. 109-
119, Jan. 2011.
[29] F. A. Albasri, A. R. Alroomi and J. H. Talaq, "Optimal Coordination of Directional Overcurrent
Relays Using Biogeography-Based Optimization Algorithms," in IEEE Transactions on Power
Delivery, vol. 30, no. 4, pp. 1810-1820, Aug. 2015.
[30] T. Amraee, "Coordination of Directional Overcurrent Relays Using Seeker Algorithm," in IEEE
Transactions on Power Delivery, vol. 27, no. 3, pp. 1415-1422, July 2012.
[31] J. Moirangthem, K. R. Krishnanand, S. S. Dash and R. Ramaswami, "Adaptive differential
evolution algorithm for solving non-linear coordination problem of directional overcurrent relays,"
21
in IET Generation, Transmission & Distribution, vol. 7, no. 4, pp. 329-336, April 2013.
[32] A. Tjahjono et al., "Adaptive modified firefly algorithm for optimal coordination of overcurrent
relays," in IET Generation, Transmission & Distribution, vol. 11, no. 10, pp. 2575-2585, 13 7 2017.
[33] A. Yazdaninejadi, M. S. Naderi, G. B. Gharehpetian and V. Talavat, "Protection coordination of
directional overcurrent relays: new time current characteristic and objective function," in IET
Generation, Transmission & Distribution, vol. 12, no. 1, pp. 190-199, 2 1 2018.
[34] H. Saberi and T. Amraee, "Coordination of directional over-current relays in active distribution
networks using generalised benders decomposition," in IET Generation, Transmission &
Distribution, vol. 11, no. 16, pp. 4078-4086, 9 11 2017.
[35] Saleh, A. Khaled, et al. “Optimal coordination of directional overcurrent relays using a new time–
current–voltage characteristic”. IEEE Trans on Power deliv, vol. 30, no. 2, pp. 537-544, 2015.
[36] L. Huchel, H. H. Zeineldin, et al. “Planning the coordination of directional overcurrent relays for
distribution systems considering DG”. IEEE Trans Smart Grid, vol. 7, no. 3, pp. 1642-1649, 2017.
[37] M.A. Zamani, A. Yazdani, and T.S. Sidhu, “A communication-assisted protection strategy for
inverter-based medium-voltage microgrids”. IEEE Trans Smart Grid, vol. 3, no. 4, pp. 2088–2099,
2012.
[38] M.A. Zamani, T.S. Sidhu, and A. Yazdani, “A communication-based strategy for protection of
microgrids with looped configuration”. Electr Power Syst Res, vol. 104, pp. 52–61, 2013.
[39] T.S. Ustun, R.H. Khan, “Multiterminal hybrid protection of microgrids over wireless
communications network”. IEEE Trans Smart Grid, vol. 6, no.5, pp. 2493–2500, 2015.
[40] Susmita Kar, Subhransu Rajan Samantaray, “Time-frequency transform-based differential scheme
for microgrid protection”, IET Gener. Transm. Distrib.,Vol. 8, Iss. 2, pp. 310–320, 2014.
[41] Xinyao Li, Adam Dysko, and Graeme Burt, “Traveling Wave-Based Protection Scheme for
Inverter-Dominated Microgrid Using Mathematical Morphology”, IEEE Trans Smart Grid, vol. 5,
no.5, pp, 2118-2218, 2014.
[42] E. Casagrande, W.L. Woon, H.H. Zeineldin , “A differential sequence component protection
scheme for microgrids with inverter-based distributed generators”. IEEE Trans Smart Grid, vol. 5,
no. 1, pp. 29–37, 2014.
[43] N. Hatziargyriou, Microgrids Architectures and Control, Wiley-IEEE Press, 2013.
[44] A. Aderibole, H. H. Zeineldin and M. A. Hosani, "A Critical Assessment of Oscillatory Modes in
Multi-Microgrids Comprising of Synchronous and Inverter Based Distributed Generation," in IEEE
Transactions on Smart Grid.
[45] S. D. Kermany, M. Joorabian, S. Deilami and M. A. S. Masoum, "Hybrid Islanding Detection in
Microgrid With Multiple Connection Points to Smart Grids Using Fuzzy-Neural Network," in IEEE
Transactions on Power Systems, vol. 32, no. 4, pp. 2640-2651, July 2017.
22