Date

11/21/2023

Created with DIALux


Preliminary remarks

Notes on planning:

The energy consumption quantities do not take into account light


scenes and their dimming levels.
Content

Cover page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ..........................


Preliminary remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
2
Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3. . . . . . . . . . . . . . . . . . . . . .
.
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..........................
5
Images . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6. . . . . . . . . . . . . . . . . . . . . .
.
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7. . . . . . . . . . . . . . . . . . . . . . . . . . .

Product data sheets


CALIX UK - CALIX DOWNLIGHT 30 W 6500 K IP65 (1x DOWNLIGHT 30 W 6500 K . . . . . . . . . . . . . . . . . . . . . 8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
IP65)
TRILUX GmbH & Co. KG - SFlow (1x LED) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Site 1

Building 1
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
.............................

Site 1 - Building 1

Storey 1
Room List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
.........................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15.............................
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 .............................

Site 1 - Building 1 - Storey 1

Room 1
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
.........................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
.............................
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 .............................
Workplane (Room 1) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 ..............................

Site 1 - Building 1 - Storey 1

Room 2
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
.........................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
.............................
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 .............................
Content

Workplane (Room 2) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35


..............................

Site 1 - Building 1 - Storey 1

Room 3
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
.........................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41............................
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Workplane (Room 3) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
44

Site 1 - Building 1 - Storey 1

Room 4
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
.........................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50............................
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
51. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Workplane (Room 4) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
53

Site 1 - Building 1 - Storey 1

Room 5
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
.........................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
.............................
Calculation objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 .............................
Workplane (Room 5) / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
62.............................

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
........................
Description

5
Images

6
Luminaire list

Φtotal Ptotal Luminous efficacy


334600 lm 3100.0 W 107.9 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

35 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm 100.0 lm/W
55530

41 TRILUX SFlow-Act SFlow 50.0 W 5600 lm 112.0 lm/W


H3-L
MRWD
LED6400
ETDD8LL
WS 01
(ActDSU)
ETDD8

7
Product data sheet

CALIX UK CALIX DOWNLIGHT 30 W 6500 K IP65

Article No. CLX8-55530

P 30.0 W

ΦLuminaire 3000 lm

Luminous efficacy 100.0 lm/W

CCT 6500 K

CRI 80
Polar LDC

UGR diagram (SHR: 0.25)

8
Product data sheet

TRILUX SFlow

Article No. SFlow-Act H3-L MRWD


LED6400 ETDD8LLWS
01 (ActDSU) ETDD8

P 50.0 W

ΦLamp 5600 lm

ΦLuminaire 5600 lm

Polar LDC
η 100.00 %

Luminous efficacy 112.0 lm/W

CCT 4000 K

CRI 100

SFlow-Act H3-L MRWD LED6400 ETDD8LLWS 01 (TOC 7922162):


LED-Hängeleuchte für Einzel- oder Lichtbandanwendungen. Leuchte
mit Active-Ausstattung zur Steuerung der Lichtfarbe mittels
separatem Steuergerät. Mit integriertem LiveLink Sensor zum
Anschluss an ein LiveLink Steuergerät zur tageslichtabhängigen
Regelung und Anwesenheitserfassung. LiveLink Sensor IR Micro zur
tageslichtabhängigen Regelung und Anwesenheitserfassung.
Konstantlichtregelung mit Abschaltfunktion bei ausreichendem
Tageslicht. Passiv-Infrarot-Anwesenheitssensor, mit hochsensiblem
multisegment Pyrosensoren, mit einstellbarer
Ausschaltverzögerungszeit, wahlweise im Automatik Betrieb
(automatisch Ein, automatisch Aus) oder Halbautomatik Betrieb
(automatisch Aus, manuell Ein). Spezieller IQ-Modus zur
automatischen Anpassung der Nachlaufzeit an die Raumnutzung.
Elektrische Versorgung über die DALI Schnittstelle des UGR diagram (SHR: 0.25)
Steuergerätes. Belegt 2 DALI Teilnehmer. Quadratische Erfassung,
Erfassungsquadrate Präsenz max. 4 m x 4 m (16 m2) / Radial max. 4
m x 4 m (16 m2) / Tangential max. 6 m x 6 m (36 m2) bei einer
empfohlenen Montagehöhe von 2,8 m,

9
Product data sheet

TRILUX SFlow

zulässige Montagehöhe 2,5 m bis 4 m. Für abgehängte Montage. Als


Einzelleuchte oder in Lichtbandanwendung. Optisches System in
Micro-Reflektor-Technology (MRWD) mit hocheffizienten, weiß-
polierten Reflektorkammern aus Kunststoff mit Diffusorscheibe für
ein gleichmäßig ausgeleuchtetet Lichtbild mit höchstem Sehkomfort.
Mit zusätzlicher, im optischen System integrierten, klaren
Abdeckscheibe für raumseitig flächenbündigen Abschluß und Schutz
der LED. Dezente seitliche Lichtauskopplung über die gesamte
Leuchtenlänge. Mit direkt-indirekt strahlender Lichtstärkeverteilung.
Bemessungslichtstrom 5600 lm, Bemessungsleistung 53,00 W,
Leuchten-Lichtausbeute 105 lm/W. Lichtfarbe variabel (warmweiß -
tageslichtweiß), ähnlichste Farbtemperatur (CCT) variabel (2700 K -
6500 K), allgemeiner Farbwiedergabeindex (CRI) Ra > 80. Die
Lichtquelle ist entsprechend der Ökodesign-Anforderungen (VO (EU)
2019/2020) austauschbar. Leuchtenkörper aus Stahlblech. (RAL
9016). Maße (L x B): 1473 mm x 84 mm, Leuchtenhöhe 45 mm.
Schutzklasse (EN 61140): I, Schutzart (DIN EN 60529): IP20,
Stoßfestigkeitsgrad nach IEC 62262: IK03, Prüftemperatur
Glühdrahttest gemäß IEC 60695-2-11: 650 °C. Gewicht: 5,2 kg. Mit
elektronischem Betriebsgerät zum schalten, dimmen und steuern
der Lichtfarbe mittels DALI Device Type 8 fähigem Steuergerät.
Betriebsgerät gemäß DALI-2-Standard (EN 62386). Das Betriebsgerät
ist entsprechend der Ökodesign-Anforderungen (VO (EU)
2019/2020) austauschbar. Das Produkt erfüllt die grundlegenden
Anforderungen der anwendbaren EU-Richtlinien und des
Produktsicherheitsgesetzes und trägt die CE-Kennzeichnung.

10
Building 1
Luminaire list

Φtotal Ptotal Luminous efficacy


334600 lm 3100.0 W 107.9 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

35 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm 100.0 lm/W
55530

41 TRILUX SFlow-Act SFlow 50.0 W 5600 lm 112.0 lm/W


H3-L
MRWD
LED6400
ETDD8LL
WS 01
(ActDSU)
ETDD8

11
Building 1 · Storey 1
Room List

12
Building 1 · Storey 1
Room List

Room 1

Ptotal ARoom Lighting power density Ēhorizontal (Workplane)


1200.0 W 144.63 m² 8.30 W/m² = 1.27 W/m²/100 lx (Room) 655 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

24 TRILUX SFlow-Act SFlow 50.0 W 5600 lm


H3-L
MRWD
LED6400
ETDD8LL
WS 01
(ActDSU)
ETDD8

Room 2

Ptotal ARoom Lighting power density Ēhorizontal (Workplane)


850.0 W 111.90 m² 7.60 W/m² = 1.29 W/m²/100 lx (Room) 591 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

17 TRILUX SFlow-Act SFlow 50.0 W 5600 lm


H3-L
MRWD
LED6400
ETDD8LL
WS 01
(ActDSU)
ETDD8

13
Building 1 · Storey 1
Room List

Room 3

Ptotal ARoom Lighting power density Ēhorizontal (Workplane)


510.0 W 45.51 m² 11.21 W/m² = 1.69 W/m²/100 lx (Room) 664 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

17 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm


55530

Room 4

Ptotal ARoom Lighting power density Ēhorizontal (Workplane)


270.0 W 14.54 m² 18.57 W/m² = 1.90 W/m²/100 lx (Room) 975 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

9 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm


55530

Room 5

Ptotal ARoom Lighting power density Ēhorizontal (Workplane)


270.0 W 15.89 m² 16.99 W/m² = 2.01 W/m²/100 lx (Room) 847 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

9 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm


55530

14
Building 1 · Storey 1
Luminaire list

Φtotal Ptotal Luminous efficacy


334600 lm 3100.0 W 107.9 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

35 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm 100.0 lm/W
55530

41 TRILUX SFlow-Act SFlow 50.0 W 5600 lm 112.0 lm/W


H3-L
MRWD
LED6400
ETDD8LL
WS 01
(ActDSU)
ETDD8

15
Building 1 · Storey 1
Calculation objects

16
Building 1 · Storey 1
Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index

Workplane (Room 1) 655 lx 248 lx 969 lx 0.38 0.26 S2


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Room 2) 591 lx 124 lx 1023 lx 0.21 0.12 S4


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Room 3) 664 lx 261 lx 919 lx 0.39 0.28 S6


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Room 4) 975 lx 614 lx 1177 lx 0.63 0.52 S8


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Workplane (Room 5) 847 lx 513 lx 1047 lx 0.61 0.49 S10


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

17
Building 1 · Storey 1 · Room 1
Summary

Ground area: 144.63 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.300 m 18
Building 1 · Storey 1 · Room 1
Summary

Results

Symbol Calculated

Workplane Ē 655 lx

g1 0.38

Consumption values Consumption 3300 kWh/a

Lighting power density Room 8.30 W/m²

1.27 W/m²/100 lx

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

24 TRILUX SFlow-Act SFlow 50.0 W 5600 lm 112.0 lm/W


H3-L
MRWD
LED6400
ETDD8LL
WS 01
(ActDSU)
ETDD8

19
Building 1 · Storey 1 · Room 1
Luminaire layout plan

20
Building 1 · Storey 1 · Room 1
Luminaire layout plan

Manufacturer TRILUX

Article No. SFlow-Act H3-L MRWD


LED6400 ETDD8LLWS
01 (ActDSU) ETDD8

Article name SFlow

6 x TRILUX GmbH & Co. KG SFlow

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 1.296 m, 16.804 m,
(X/Y/Z) 2.300 m 1.296 m 16.804 m 2.300 m 1

X-direction 6 pcs., Center - center, 1.296 m 13.744 m 2.300 m 2


3.060 m
1.296 m 10.684 m 2.300 m 3
Arrangement A1
1.296 m 7.625 m 2.300 m 4

1.296 m 4.565 m 2.300 m 5

1.296 m 1.505 m 2.300 m 6

6 x TRILUX GmbH & Co. KG SFlow

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 3.137 m, 16.804 m,
(X/Y/Z) 2.300 m 3.137 m 16.804 m 2.300 m 7

X-direction 6 pcs., Center - center, 3.137 m 13.744 m 2.300 m 8


3.060 m
3.137 m 10.684 m 2.300 m 9
Arrangement A2
3.137 m 7.625 m 2.300 m 10

21
Building 1 · Storey 1 · Room 1
Luminaire layout plan

X Y Mounting Luminaire
height

3.137 m 4.565 m 2.300 m 11

3.137 m 1.505 m 2.300 m 12

6 x TRILUX GmbH & Co. KG SFlow

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 5.057 m, 16.804 m,
(X/Y/Z) 2.300 m 5.057 m 16.804 m 2.300 m 13

X-direction 6 pcs., Center - center, 5.057 m 13.744 m 2.300 m 14


3.060 m
5.057 m 10.684 m 2.300 m 15
Arrangement A3
5.057 m 7.625 m 2.300 m 16

5.057 m 4.565 m 2.300 m 17

5.057 m 1.505 m 2.300 m 18

6 x TRILUX GmbH & Co. KG SFlow

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 6.898 m, 16.804 m,
(X/Y/Z) 2.300 m 6.898 m 16.804 m 2.300 m 19

X-direction 6 pcs., Center - center, 6.898 m 13.744 m 2.300 m 20


3.060 m
6.898 m 10.684 m 2.300 m 21
Arrangement A4
6.898 m 7.625 m 2.300 m 22

6.898 m 4.565 m 2.300 m 23

6.898 m 1.505 m 2.300 m 24

22
Building 1 · Storey 1 · Room 1
Luminaire list

Φtotal Ptotal Luminous efficacy


134400 lm 1200.0 W 112.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

24 TRILUX SFlow-Act SFlow 50.0 W 5600 lm 112.0 lm/W


H3-L
MRWD
LED6400
ETDD8LL
WS 01
(ActDSU)
ETDD8

23
Building 1 · Storey 1 · Room 1
Calculation objects

24
Building 1 · Storey 1 · Room 1
Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index

Workplane (Room 1) 655 lx 248 lx 969 lx 0.38 0.26 S2


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

25
Building 1 · Storey 1 · Room 1
Workplane (Room 1)

Properties Ē Emin Emax g1 g2 Index

Workplane (Room 1) 655 lx 248 lx 969 lx 0.38 0.26 S2


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

26
Building 1 · Storey 1 · Room 2
Summary

Ground area: 111.90 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 20.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.300 m 27
Building 1 · Storey 1 · Room 2
Summary

Results

Symbol Calculated

Workplane Ē 591 lx

g1 0.21

Consumption values Consumption 2350 kWh/a

Lighting power density Room 7.60 W/m²

1.29 W/m²/100 lx

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

17 TRILUX SFlow-Act SFlow 50.0 W 5600 lm 112.0 lm/W


H3-L
MRWD
LED6400
ETDD8LL
WS 01
(ActDSU)
ETDD8

28
Building 1 · Storey 1 · Room 2
Luminaire layout plan

29
Building 1 · Storey 1 · Room 2
Luminaire layout plan

Manufacturer TRILUX

Article No. SFlow-Act H3-L MRWD


LED6400 ETDD8LLWS
01 (ActDSU) ETDD8

Article name SFlow

5 x TRILUX GmbH & Co. KG SFlow

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 1.522 m, 15.143 m,
(X/Y/Z) 2.300 m 1.522 m 15.143 m 2.300 m 1

X-direction 5 pcs., Center - center, 1.522 m 11.778 m 2.300 m 2


3.365 m
1.522 m 8.413 m 2.300 m 3
Arrangement A1
1.522 m 5.048 m 2.300 m 4

1.522 m 1.683 m 2.300 m 5

5 x TRILUX GmbH & Co. KG SFlow

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 3.250 m, 15.143 m,
(X/Y/Z) 2.300 m 3.250 m 15.143 m 2.300 m 6

X-direction 5 pcs., Center - center, 3.250 m 11.778 m 2.300 m 7


3.365 m
3.250 m 8.413 m 2.300 m 8
Arrangement A2
3.250 m 5.048 m 2.300 m 9

3.250 m 1.683 m 2.300 m 10

30
Building 1 · Storey 1 · Room 2
Luminaire layout plan

4 x TRILUX GmbH & Co. KG SFlow

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 4.736 m, 15.143 m,
(X/Y/Z) 2.300 m 4.736 m 15.143 m 2.300 m 11

X-direction 5 pcs., Center - center, 4.736 m 11.778 m 2.300 m 12


Distances not equal
4.736 m 8.413 m 2.300 m 13

Arrangement A3 4.736 m 5.048 m 2.300 m 14

Individual luminaires

X Y Mounting Luminaire
height

6.550 m 15.143 m 2.300 m 15

6.550 m 11.778 m 2.300 m 16

6.550 m 8.413 m 2.300 m 17

31
Building 1 · Storey 1 · Room 2
Luminaire list

Φtotal Ptotal Luminous efficacy


95200 lm 850.0 W 112.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

17 TRILUX SFlow-Act SFlow 50.0 W 5600 lm 112.0 lm/W


H3-L
MRWD
LED6400
ETDD8LL
WS 01
(ActDSU)
ETDD8

32
Building 1 · Storey 1 · Room 2
Calculation objects

33
Building 1 · Storey 1 · Room 2
Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index

Workplane (Room 2) 591 lx 124 lx 1023 lx 0.21 0.12 S4


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

34
Building 1 · Storey 1 · Room 2
Workplane (Room 2)

Properties Ē Emin Emax g1 g2 Index

Workplane (Room 2) 591 lx 124 lx 1023 lx 0.21 0.12 S4


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

35
Building 1 · Storey 1 · Room 3
Summary

Ground area: 45.51 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 10.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m 36
Building 1 · Storey 1 · Room 3
Summary

Results

Symbol Calculated

Workplane Ē 664 lx

g1 0.39

Consumption values Consumption 1400 kWh/a

Lighting power density Room 11.21 W/m²

1.69 W/m²/100 lx

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

17 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm 100.0 lm/W
55530

37
Building 1 · Storey 1 · Room 3
Luminaire layout plan

38
Building 1 · Storey 1 · Room 3
Luminaire layout plan

Manufacturer CALIX UK

Article No. CLX8-55530

Article name CALIX DOWNLIGHT 30


W 6500 K IP65

5 x CALIX UK CALIX DOWNLIGHT 30 W 6500 K IP65

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 6.963 m, 8.959 m,
(X/Y/Z) 2.800 m 6.963 m 8.959 m 2.800 m 1

X-direction 5 pcs., Center - center, 6.963 m 6.968 m 2.800 m 2


1.991 m
6.963 m 4.977 m 2.800 m 3
Arrangement A1
6.963 m 2.986 m 2.800 m 4

6.963 m 0.995 m 2.800 m 5

4 x CALIX UK CALIX DOWNLIGHT 30 W 6500 K IP65

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 0.816 m, 3.542 m,
(X/Y/Z) 2.800 m 0.816 m 3.542 m 2.800 m 6

X-direction 4 pcs., Center - center, 2.516 m 3.542 m 2.800 m 7


1.700 m
4.216 m 3.542 m 2.800 m 8
Arrangement A2
5.916 m 3.542 m 2.800 m 9

39
Building 1 · Storey 1 · Room 3
Luminaire layout plan

4 x CALIX UK CALIX DOWNLIGHT 30 W 6500 K IP65

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 0.816 m, 2.015 m,
(X/Y/Z) 2.800 m 0.816 m 2.015 m 2.800 m 10

X-direction 4 pcs., Center - center, 2.516 m 2.015 m 2.800 m 11


1.700 m
4.216 m 2.015 m 2.800 m 12
Arrangement A3
5.916 m 2.015 m 2.800 m 13

4 x CALIX UK CALIX DOWNLIGHT 30 W 6500 K IP65

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 0.816 m, 0.515 m,
(X/Y/Z) 2.800 m 0.816 m 0.515 m 2.800 m 14

X-direction 4 pcs., Center - center, 2.516 m 0.515 m 2.800 m 15


1.700 m
4.216 m 0.515 m 2.800 m 16
Arrangement A4
5.916 m 0.515 m 2.800 m 17

40
Building 1 · Storey 1 · Room 3
Luminaire list

Φtotal Ptotal Luminous efficacy


51000 lm 510.0 W 100.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

17 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm 100.0 lm/W
55530

41
Building 1 · Storey 1 · Room 3
Calculation objects

42
Building 1 · Storey 1 · Room 3
Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index

Workplane (Room 3) 664 lx 261 lx 919 lx 0.39 0.28 S6


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

43
Building 1 · Storey 1 · Room 3
Workplane (Room 3)

Properties Ē Emin Emax g1 g2 Index

Workplane (Room 3) 664 lx 261 lx 919 lx 0.39 0.28 S6


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

44
Building 1 · Storey 1 · Room 4
Summary

Ground area: 14.54 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 50.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m 45
Building 1 · Storey 1 · Room 4
Summary

Results

Symbol Calculated

Workplane Ē 975 lx

g1 0.63

Consumption values Consumption 740 kWh/a

Lighting power density Room 18.57 W/m²

1.90 W/m²/100 lx

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

9 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm 100.0 lm/W
55530

46
Building 1 · Storey 1 · Room 4
Luminaire layout plan

47
Building 1 · Storey 1 · Room 4
Luminaire layout plan

Manufacturer CALIX UK

Article No. CLX8-55530

Article name CALIX DOWNLIGHT 30


W 6500 K IP65

3 x CALIX UK CALIX DOWNLIGHT 30 W 6500 K IP65

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 0.449 m, 4.191 m,
(X/Y/Z) 2.800 m 0.449 m 4.191 m 2.800 m 1

X-direction 3 pcs., Center - center, 0.449 m 2.504 m 2.800 m 2


1.687 m
0.449 m 0.818 m 2.800 m 3
Arrangement A1

3 x CALIX UK CALIX DOWNLIGHT 30 W 6500 K IP65

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 1.661 m, 4.190 m,
(X/Y/Z) 2.800 m 1.661 m 4.190 m 2.800 m 4

X-direction 3 pcs., Center - center, 1.661 m 2.504 m 2.800 m 5


1.687 m
1.661 m 0.817 m 2.800 m 6
Arrangement A2

3 x CALIX UK CALIX DOWNLIGHT 30 W 6500 K IP65

Type Line arrangement

48
Building 1 · Storey 1 · Room 4
Luminaire layout plan

1st luminaire 2.496 m, 4.190 m, X Y Mounting Luminaire


(X/Y/Z) 2.800 m height

X-direction 3 pcs., Center - center, 2.496 m 4.190 m 2.800 m 7


1.687 m
2.496 m 2.504 m 2.800 m 8
Arrangement A3
2.496 m 0.817 m 2.800 m 9

49
Building 1 · Storey 1 · Room 4
Luminaire list

Φtotal Ptotal Luminous efficacy


27000 lm 270.0 W 100.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

9 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm 100.0 lm/W
55530

50
Building 1 · Storey 1 · Room 4
Calculation objects

51
Building 1 · Storey 1 · Room 4
Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index

Workplane (Room 4) 975 lx 614 lx 1177 lx 0.63 0.52 S8


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

52
Building 1 · Storey 1 · Room 4
Workplane (Room 4)

Properties Ē Emin Emax g1 g2 Index

Workplane (Room 4) 975 lx 614 lx 1177 lx 0.63 0.52 S8


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

53
Building 1 · Storey 1 · Room 5
Summary

Ground area: 15.89 m² | Reflection factors: Ceiling: 70.0 %, Walls: 50.0 %, Floor: 10.0 % | Light loss factor: 0.80 (fixed) | Clearance
height: 2.800 m | Mounting height: 2.800 m 54
Building 1 · Storey 1 · Room 5
Summary

Results

Symbol Calculated

Workplane Ē 847 lx

g1 0.61

Consumption values Consumption 740 kWh/a

Lighting power density Room 16.99 W/m²

2.01 W/m²/100 lx

Utilisation profile: DIALux presetting, Standard (office)

Luminaire list

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

9 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm 100.0 lm/W
55530

55
Building 1 · Storey 1 · Room 5
Luminaire layout plan

56
Building 1 · Storey 1 · Room 5
Luminaire layout plan

Manufacturer CALIX UK

Article No. CLX8-55530

Article name CALIX DOWNLIGHT 30


W 6500 K IP65

3 x CALIX UK CALIX DOWNLIGHT 30 W 6500 K IP65

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 0.527 m, 4.267 m,
(X/Y/Z) 2.800 m 0.527 m 4.267 m 2.800 m 1

X-direction 3 pcs., Center - center, 0.527 m 2.580 m 2.800 m 2


1.687 m
0.527 m 0.893 m 2.800 m 3
Arrangement A1

3 x CALIX UK CALIX DOWNLIGHT 30 W 6500 K IP65

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire 1.644 m, 4.216 m,
(X/Y/Z) 2.800 m 1.644 m 4.216 m 2.800 m 4

X-direction 3 pcs., Center - center, 1.644 m 2.529 m 2.800 m 5


1.687 m
1.644 m 0.843 m 2.800 m 6
Arrangement A2

3 x CALIX UK CALIX DOWNLIGHT 30 W 6500 K IP65

Type Line arrangement

57
Building 1 · Storey 1 · Room 5
Luminaire layout plan

1st luminaire 2.793 m, 4.216 m, X Y Mounting Luminaire


(X/Y/Z) 2.800 m height

X-direction 3 pcs., Center - center, 2.793 m 4.216 m 2.800 m 7


1.687 m
2.793 m 2.529 m 2.800 m 8
Arrangement A3
2.793 m 0.843 m 2.800 m 9

58
Building 1 · Storey 1 · Room 5
Luminaire list

Φtotal Ptotal Luminous efficacy


27000 lm 270.0 W 100.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

9 CALIX UK CLX8- CALIX DOWNLIGHT 30 W 6500 K IP65 30.0 W 3000 lm 100.0 lm/W
55530

59
Building 1 · Storey 1 · Room 5
Calculation objects

60
Building 1 · Storey 1 · Room 5
Calculation objects

Work planes

Properties Ē Emin Emax g1 g2 Index

Workplane (Room 5) 847 lx 513 lx 1047 lx 0.61 0.49 S10


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

61
Building 1 · Storey 1 · Room 5
Workplane (Room 5)

Properties Ē Emin Emax g1 g2 Index

Workplane (Room 5) 847 lx 513 lx 1047 lx 0.61 0.49 S10


Perpendicular illuminance (adaptive)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: DIALux presetting, Standard (office)

62
Glossary

A Formula symbol for a surface in the geometry

Background area The background area borders the direct ambient area according to DIN EN 12464-1 and
reaches up to the borders of the room. In larger rooms, the background area is at least
3 m wide. It is located horizontally at floor level.

CCT (Engl. correlated color temperature)


Body temperature of a thermal radiator that serves to describe its light color. Unit: Kelvin
[K]. The lesser the numerical value the redder; the greater the numerical value the bluer
the light color. The color temperature of gas-discharge lamps and semi-conductors are
termed "correlated color temperature" in contrast to the color temperature of thermal
radiators.

Allocation of the light colors to the color temperature ranges acc. to EN 12464-1:

Light color - color temperature [K]


warm white (ww) < 3,300 K
neutral white (nw) ≥ 3,300 – 5,300 K
daylight white (dw) > 5.300 K

Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).

CRI (Engl. color rendering index)


Designation for the color rendering index of a luminaire or a lamp acc. to DIN 6169:
1976 or CIE 13.3: 1995.

The general color rendering index Ra (or CRI) is a dimensionless figure that describes
the quality of a white light source in regards to its similarity with the remission spectra of
defined 8 test colors (see DIN 6169 or CIE 1974) to a reference light source.

Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside to
the horizontal illuminance in the outer area under an unobstructed sky.

Formula symbol: D (Engl. daylight factor)


Unit: %

63
Glossary

Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.

Eta (η) (light output ratio)


The light output ratio describes what percentage of the luminous flux of a free radiating
lamp (or LED module) is emitted by the luminaire when installed.

Unit: %

g1 Often also Uo (Engl. overall uniformity)


Designates the overall uniformity of the illuminance on a surface. It is the quotient from
Emin to Ē and is required, for instance, in standards for illumination of workstations.

g2 Actually it designates the "non-uniformity" of the illuminance on a surface. It is the


quotient of Emin to Emax and is generally only relevant for certifying the emergency
lighting acc. to EN 1838.

Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be determined
anywhere in space (inside or outside). The illuminance is not a product feature because it
is a recipient value. Luxometers are used for measuring.

Unit: Lux
Abbreviation: lx
Formula symbol: E

Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.

Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.

Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.

64
Glossary

Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.

LENI (Engl. lighting energy numeric indicator)


Lighting energy numeric indicator acc. to EN 15193

Unit: kWh/m² year

Light loss factor See MF

LLMF (Engl. lamp lumen maintenance factor)/acc. to CIE 97: 2005


Lamp flux maintenance factor that takes the luminous flux reduction into account of a
luminaire or an LED module in the course of the operating time. The lamp flux
maintenance factor is specified as a decimal digit and can have a maximum value of 1
(no luminous flux reduction existing).

LMF (Engl. luminaire maintenance factor)/acc. to CIE 97: 2005


Luminaire maintenance factor that takes the soiling into account of the luminaire in the
course of the operating time. The luminaire maintenance factor is specified as a decimal
digit and can have a maximum value of 1 (no soiling existing).

LSF (Engl. lamp survival factor)/acc. to CIE 97: 2005


Lamp survival factor that takes the total failure into account of a luminaire in the course
of the operating time. The lamp survival factor is specified as a decimal digit and can
have a maximum value of 1 (no failures existing within the time concerned or prompt
replacement after the failure).

Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It is
the only photometric value that the human eye can perceive.

Unit: Candela per square meter


Abbreviation: cd/m²
Formula symbol: L

Luminous efficacy Ratio of the emitted luminous flux Φ [lm] to the absorbed electrical power P [W] Unit:
lm/W.

This ratio can be formed for the lamp or LED module (lamp or module light output), the
lamp or module with control gear (system light output) and the complete luminaire
(luminaire light output).

65
Glossary

Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux.

Unit: Lumen
Abbreviation: lm
Formula symbol: Φ

Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit.

Unit: Candela
Abbreviation: cd
Formula symbol: I

MF (Engl. maintenance factor)/acc. to CIE 97: 2005


Maintenance factor as decimal number between 0 and 1 that describes the ratio of the
new value of a photometric planning parameter (e.g. of the illuminance) to a
maintenance value after a certain time. The maintenance factor takes into account the
soiling of luminaires and rooms as well as the luminous flux reduction and the failure of
light sources.
The maintenance factor is taken into account either overall or determined in detail acc.
to CIE 97: 2005 by the formula RMF x LMF x LLMF x LSF.

P (Engl. power)
Electric power consumption

Unit: watt
Abbreviation: W

Reflection factor The reflection degree of a surface describes how much of the striking light is reflected
back. The reflection degree is defined by the color of the surface.

66
Glossary

RMF (Engl. room surface maintenance factor)/acc. to CIE 97: 2005


Room surface maintenance factor that takes the soiling into account of the space
encompassing surfaces in the course of the operating time. The room surface
maintenance factor is specified as a decimal digit and can have a maximum value of 1
(no soiling existing).

Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.

UGR (max) (unified glare rating)


Measure for the psychological glare effect in interiors.
In addition to luminaire luminance, the UGR value also depends on the position of the
observer, the viewing direction and the ambient luminance. Among other things, EN
12464-1 specifies maximum permissible UGR values for various indoor workplaces.

UGR observer Calculation point in the room, for the DIALux the UGR value is determined. The location
and height of the calculation point should correspond to the typical observer position
(position and eye level of the user).

Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN
12464-1. The height corresponds with the height at which the visual task is executed.

Wall zone Circumferential area between working plane and walls that is not taken into account for
the calculation.

Workplane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.

67