MDB-102 3P

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Door Clamp

-H1 -H2 -H3

-H4
380 V
-PM

Swing
Handle -S1

Key
Live Busbar Behind
2000

Back Cover

380 V
100

2000 2000 2000

FRONT VIEW REAR VIEW


REAR VIEW
W/O COVER

Swing Out
Mounting Plate Gland Plate Alluminium 4mm
Fixing from Inside LIST MATERIAL (LV MDB-102) :
Cable Gland Brass -A1 = MTS 4P 800A GM1AD4N8004BEE
55

-Q1 = MCCB 3P 630A NSX630N C63N42D630 + ROTARY HANDLE


-Q2 = MCCB 3P 400A NSX400F LV432676
-Q3-7 = MCCB 3P 100A NSX100F C10F6TM100
-Q8-11 = MCCB 3P 80A NSX100F C10F6TM080
-Q12-15 = MCCB 3P 50A NSX100F C10F6TM050
-QC = MCB 2P 2A IC60N A9F74202

800

750
-QC = MCB 1P 2A IC60N A9F74102
-PM = POWER METER PM5330 METSEPM5330
-T1R,S,T = CT 500/5A METSECT5MD050
-H1 = PILOT LAMP (Red) XB5AVM4 230/240V AC/DC - PHASE R
-H2 = PILOT LAMP (Orange) XB5AVM5 230/240V AC/DC - PHASE S
-H3 = PILOT LAMP (Green) XB5AVM3 230/240V AC/DC - PHASE T
-H4 = PILOT LAMP (White) XB5AVM1 230/240V AC/DC - FAN ON
-S1 = EMERGENCY PUSH BUTTON XB5AS8442
-F1-X = HOLDER & CYLINDRICAL FUSE 2A
130 740 130 130 740 130 -V10 = THERMOSTAT TYPE. KTO - 10A (1NC) KTS 011-F
1000 1000 -FAN = FAN 10" (2 Unit) & FILTER (4 Unit)
1890

-S100 = DOOR SWITCH & COVER


-H100 = TL LAMP 10W 220VAC
BOTTOM VIEW -X3 = TERMINAL BLOCK CONTROL
-X0 = TERMINAL BLOCK POWER

800
Earthing bar
55

FOR APROVAL
2000
2000
750
PT. LINTECH DUTA PRATAMA
TOP VIEW
800

FRONT VIEW SECTION VIEW CLIENT :


W/O DOOR
PT.FREEPORT INDONESIA
PROJECT :
COAL FIRED POWER PLANT REPLACEMENT
& LNG SUPPLY PROJECT LNGPP EARLY WORK
DRAWING TITLE :
MDB-102

SCALE : 1:25 DATE DRAWING NO. REV.


DESIGNED :
A
DRAWING BY : ANA 12-12-2023
CHECKED BY : - -
-
APP. BY : ISO-A

You might also like