Envicool XRow Cooling Solution
Envicool XRow Cooling Solution
Envicool XRow Cooling Solution
XRow series row-based cooling unit MC series door mounted integrated air
conditioner
XRack series micro-modularized
MC series wall mounted integrated air
solution
conditioner
Cabicool series rack cooling solution MC series floor standing integrated air
XSpace series modularized solution conditioner
HumidMate series data center MC series corner standing integrated air
conditioner
constant
MX series heat exchanger
humidity solution
XFlex series IEC solution EMW series air cooled chiller
[email protected]
+65 6756 0833
www.bridex.fujielectric.com
The solutions and products are widely used in China and overseas market, including Data Center
Temperature Control and Energy-saving Solutions, S&M Data Center Temperature Control Solutions, Micro-
module Server Rack Solutions, Containerized & Modularized Data Center Solutions, Telecom Site Cooling
Solutions, Energy Storage Cooling Solutions, customized solutions for more applications, etc.
Envicool has obtained ISO9001, ISO14001 and ISO45001. The products are CCC, CE, UL, TUV and China
Energy- saving certified. Envicool adopts the Integrated Product Development (IPD) process to develop
products and technologies, and utilizes the JIT and TQC supply chain management modes to meet the
customers' requirement efficiently.
As a member of CCSA and CRA, Envicool takes an active part in the revision of relevant industry standards.
Certifications
National Hi-tech Shenzhen Hi-tech Patents Member of CCSA Outstanding Operation & Data Center Awards
Certification Certification Maintenance Team
Award
01
Company Profile
02
Efficient Cooling Solution for
XRow Row-based Cooling Unit
Section
■ Placed closely to the heat source, the return air temperature and evaporating pressure are increased, thus
cooling efficiency can be improved
■ Equipped with EC fan, short air supply distance, fan power consumption can be reduced by 20%~30%
■ Equipped with DC inverter compressor, 10%~100% cooling capacity stepless adjustment, efficiency under
partial load can be highly improved, suitable for data center load characteristics
■ Advanced EVO controller can control the airflow & cooling capacity output as required, realizing the best
cooling effect & lowest power consumption
03
XRow Series Configuration Nomenclature
No. Function Code Description
0
3 Cooling Capacity Eg.: 40kW cooling capacity
4
A Air cooled
C Chilled water
4 System Type
W Water cooled
R CRU
H Cooling, reheating
6 Function
C Cooling, humidifying
CRU CRU abbr: refrigerant and chilled water conversion distribution unit
1 Series Name
CDU CDU abbr: chiled water distribution unit
Applications
04
XRow Row-based Cooling Unit
Modularized DC
High Efficient Cooling
Flexible Configuration
High Reliability
■ DC inverter, starting current less than rated current ,
reducing impact on power grid
■ Excellent performance with stable dehumidification
under 10% load
■ Expert self-diagnosis and fault warning function
Flexible Cooling
■ Precise control of temperature and humidity
05
EVO Intelligent Control System
EVO Display System
■ 7-inch, 800×480 dot matrix true color touch
and maintenance
06
XRow Row-based Cooling Unit
Power Supply 380V 3Ph 50Hz 380V 3Ph 50Hz 380V 3Ph 50Hz 380V 3Ph 50Hz
35°C 37°C 35°C 37°C 35°C 37°C 35°C 37°C
Return Air Condition 26%RH 24% RH 26%RH 24%RH 26%RH 24%RH 26%RH 24%RH
Total Cooling Capacity - kW 11.5 12.2 22.2 24.2 37.7 39.5 45.5 47.8
Sensible Cooling Capacity - kW 11.5 12.2 22.2 24.2 37.7 39.5 45.5 47.8
Sensible Heat Ratio - % 100 100 100 100 100 100 100 100
Max. Power Consumption of Unit
8.0 8.0 12.0 12.0 21.7 21.7 27.1 27.1
- kW
Full Load Amps (FLA) - A 16.5 16.5 23.4 23.4 41.6 41.6 58.5 58.5
Quantity of Compressor 1 1 1 1 1 1 1
1
Rated Power Consumption of 10.6 11.4 12.1
2.7 2.9 5.45 5.95 10.0
Compressor - kW
Indoor EC Fan Technical Data
Heating Capacity - kW 3 3 3 3 6 6 6 6
Humidification
Connection Size
Gas - mm 16 16 19 22
Physical Data
Breakers
Breaker- A 32 40 63 80
07
XRow Air-cooled Condenser
■ Stepless speed regulation fan
■ Owl fan with low noise
■ Optional iFreecooling integrated refrigerant pump free
cooling solution
■ Fans and motors with easy maintenance, adapt to various
climate conditions
Quantity of Fan 2 1 1 2
Operating Temperature Range (Standard) -20 ~45°C -20 ~45°C -20 ~45°C -20 ~45°C
Operating Temperature Range (with Low Temperature
Startup Kits)
-40 ~45°C -40 ~45°C -40 ~45°C -40 ~45°C
Physical Data
Width - mm 1280 1610 1910 1910
Depth - mm 360 653 653 653
Height - mm 1260 982 1270 1270
Weight - mm 125 130 150 160
Breakers & Cables
Breaker - A 20 10 10 20
Outdoor Unit
Power Cables - mm² 4 1.5 1.5 1.5
Remark:
• XRC16 supports horizontal installation only
• CS series outdoor units support horizontal and vertical installation
08
XRow Row-based Cooling Unit
XRow + iFreecooling Data Sheet
Indoor Unit Model XR6020A XR6040A XR6050A
Power Supply 380V 3Ph 50Hz 380V 3Ph 50Hz 380V 3Ph 50Hz
Return Air Condition 37℃ DB/24%RH 37℃ DB/24%RH 37℃ DB/24%RH
DX Unit Performance
DX Cooling Capacity - kW 24.2 39.5 47.8
DX Sensible Cooling Capacity - 24.2 39.5 47.8
kW Sensible Heat Ratio - % 100 100 100
Indoor Fan Technical Data
Airflow - CMH 4800 7800 10000
Quantity of Fan 6 4 10
Heating
Heating Capacity - kW 3 6 6
Humidification
Humidification Capacity - kg/h 3 3 3
Connection Size
Liquid - mm 12.7 16 19
Gas - mm 16 19 22
Humidifier Inlet Pipe G1/2” G1/2” G1/2”
Condensate Pump Drain Pipe - ID, 10 10 10
mm Drain Pipe - ID, mm 19 19 19
Dimensions
Width - mm 300 600 600
Depth - mm 1200 1200 1200
Height - mm 2000 2000 2000
Breakers & Cables
Breaker - A 32 50 63
Cooling
Cables - mm² 6 10 16
Breaker - A 40 63 80
Cooling + Humidifying
Cables - mm² 6 10 16
Remark: the unit size is the footprint size, and the protruding part of the electric control box along the length direction is not included
10
XRow Row-based Cooling Unit
Total Cooling Capacity - kW 29.4 33.6 23.9 27.5 20.4 22.7 60.5 70.5 48.9 56.2 41.8 46.7
Sensible Cooling Capacity - kW 26.2 29.3 23.4 25.3 20.4 22.6 55.2 61.4 48.6 53.3 41.8 46.7
Sensible Heat Ratio - % 89.1 87.0 97.9 92.0 100 99.6 91.2 87.1 99.4 94.8 100 100
Rated Power Consumption of EC Fan - 0.75 0.75 0.75 0.75 0.75 0.75 3.50 3.50 3.50 3.50 3.50 3.50
kW Max. Power Consumption - kW 6.75 6.75 6.75 6.75 6.75 6.75 8.75 8.75 8.75 8.75 8.75 8.75
Full Load Amps (FLA) - A 14.7 14.7 14.7 14.7 14.7 14.7 16.97 16.97 16.97 16.97 16.97 16.97
Water Flowrate - m³/h 5.20 5.90 4.20 4.80 3.00 3.40 11.00 12.70 9.00 10.20 6.50 7.20
Water Side Pressure Drop - kPa 106.8 121.6 76.2 87.5 40.3 48.6 106.1 124.5 71.7 87.3 38.4 46.7
Quantity of Fan 6 3
Heating
Heating Capacity - kW 3 6
Humidification
Connection Size
Physical Data
- kg
Breakers
Breaker - A 20 32
11
CDU Chilled Water Distribution Unit
with XRow Series Chilled Water Unit
Features
Product Introduction
■ CDU chilled water distribution unit, to be flexibly used with XRow series chilled water unit
■ Achieve standardized connection between the chiller and the chilled water unit, and distribute chilled water evenly to each unit
■ Each water supply and return branch pipeline is equipped with a separate valve, independently control the cold water supply at
each end. The number of supply and return water branch pipelines can be designed according to actual needs
Performance Specification
12
XRow Row-based Cooling Unit
XRow + CRU
Product Introduction
CRU to be used flexibly with XRow series cooling unit, using
integration of pump circulation and multi-connected cooling
unit. The outer chilled water circuit, which can be integrated
with a dry cooler to use natural cold sources or with chiller,
and the inner circulation is refrigerant flow circuit. Achieve no
water into data center
Applications
■ Data center of core computer room
■ Financial data center
Value / Features
High Reliability
■ No water into the data center
■ CRU refrigerant pump has 1+1 redundancy
■ Redundant backup of fans
■ Support dual power supply
Intelligent Control
■ CRU is equipped with 7-inch touch screen
■ Advanced team work control function for multiple units
■ Graphical display of components operation and environmental
status
■ Standard RS485 interface, optional SNMP and TCP/IP interfaces
13
CRU Heat Pipe Air Conditioner System Diagram
Cooling Capacity - kW 100 150 240 400 Power Supply 220V 1Ph 50Hz
Inlet Water Temperature - ℃ 7 7
Power Supply 380V 3Ph 50Hz Outlet Water Temperature - ℃ 12 12
Full Load Amps (FLA) - A 2.7 8 Return Air Condition - ℃ 37 37
2.7 8
Performance Technical Data
Refrigerant Inlet Pipe 42 54 54 67 Total Cooling Capacity - kW 28.0 44.5
Diameter - mm Sensible Cooling Capacity - kW 28.0 44.5
Refrigerant Outlet Pipe Sensible Heat Ratio - % 100 100
28 28 35 35
Diameter - mm Max Power Consumption - kW 0.8 1.50
Chilled Water Inlet Pipe Main Fan Technical Data
DN50 DN65 DN80 DN100 4800 9000
Diameter Airflow - CMH
Quantity of Fan 6 12
Chilled Water Outlet DN50 DN65 DN80 DN100 Connection Size
Pipe Diameter 16
Liquid - mm 16
1100 1100 1100 1700 Gas - mm
Width - mm 22 28
850 850 850 1000 Physical Data
Depth - mm
Width - mm 300 600
Height - mm 1950 1950 1950 2000 Depth - mm 1200 1200
Height - mm 2000 2000
Weight - kg 460 520 620 950
Weight - kg 190 270
Applications
14