Be440015 Tc-Mini
Be440015 Tc-Mini
Be440015 Tc-Mini
TC-MINI
Read this instruction carefully prior to installation and/or use. Pay at-
tention particularly to all advises and safety instructions to prevent in-
juries. Bühler Technologies can not be held responsible for misusing
the product or unreliable function due to unauthorised modifications.
Document information
Document No.......................................................... BE440015
Version......................................................................... 05/2021
TC-MINI
Contents
1 Introduction..................................................................................................................................................................................................................... 2
1.1 Intended use ......................................................................................................................................................................................................... 2
1.2 Types ....................................................................................................................................................................................................................... 2
1.3 Scope of delivery .................................................................................................................................................................................................. 2
1.4 Ordering instructions ........................................................................................................................................................................................ 2
2 Safety instructions......................................................................................................................................................................................................... 3
2.1 Important advice ................................................................................................................................................................................................. 3
2.2 General hazard warnings ................................................................................................................................................................................. 4
3 Transport and storage .................................................................................................................................................................................................. 5
4 Installation and connection ........................................................................................................................................................................................ 6
4.1 Installation site requirements......................................................................................................................................................................... 6
4.2 Installation ............................................................................................................................................................................................................ 6
4.2.1 Connecting the filter gas connections (optional) ....................................................................................................................... 7
4.2.2 Flow adapter connection (optional)................................................................................................................................................ 7
4.2.3 Connecting the moisture detector (option).................................................................................................................................. 7
4.3 Electrical connections ........................................................................................................................................................................................ 7
4.4 Settings................................................................................................................................................................................................................... 9
5 Operation and control ................................................................................................................................................................................................. 11
5.1 Status Signal via LEDs and Status Relay ...................................................................................................................................................... 11
5.2 Using the Digital Interface .............................................................................................................................................................................. 11
5.3 Modbus Configuration ..................................................................................................................................................................................... 11
5.4 Modbus Communication ................................................................................................................................................................................ 12
5.5 Modbus Register................................................................................................................................................................................................. 13
6 Maintenance................................................................................................................................................................................................................... 17
7 Service and repair......................................................................................................................................................................................................... 18
7.1 Troubleshooting ................................................................................................................................................................................................ 19
7.2 Safety instructions ........................................................................................................................................................................................... 20
7.3 Cleaning and removal of the heat exchanger.......................................................................................................................................... 20
7.4 Replacing the fuse of the cooler................................................................................................................................................................... 20
7.5 Replacing the filter element (option) .......................................................................................................................................................... 21
7.6 Drying of the moisture detector (option)................................................................................................................................................... 21
7.7 Spare parts and accessories ........................................................................................................................................................................... 21
7.7.1 Consumables and accessories ....................................................................................................................................................... 22
8 Disposal ........................................................................................................................................................................................................................... 23
9 Appendices..................................................................................................................................................................................................................... 24
9.1 Gas cooler technical data ................................................................................................................................................................................ 24
9.2 Technical Data - Options ................................................................................................................................................................................. 24
9.3 Dimensions (mm).............................................................................................................................................................................................. 25
9.4 Performance data.............................................................................................................................................................................................. 25
9.5 Heat exchanger.................................................................................................................................................................................................. 26
9.5.1 Heat exchanger description ........................................................................................................................................................... 26
9.5.2 Heat exchanger overview................................................................................................................................................................ 26
10 Attached documents ................................................................................................................................................................................................... 27
1 Introduction
1.2 Types
The device is delivered with different configurations. The part number given on the type plate informs you about the specific
configuration of your device.
2 Safety instructions
Signal word for a hazardous situation with medium risk, possibly resulting in severe injuries or death if not
WARNING
avoided.
Signal word for a hazardous situation with low risk, resulting in damaged to the device or the property or
CAUTION
minor or medium injuries if not avoided.
Warning signs
These instructions use the following warning signs:
General information
Maintenance, Repair
Please note during maintenance and repairs:
– Repairs to the unit must be performed by Bühler authorised personnel.
– Only perform conversion-, maintenance or installation work described in these operating and installation instructions.
– Always use genuine spare parts.
– Do not install damaged or defective spare part. If necessary, visually inspect prior to installation to determine any obvious
damage to the spare parts.
Always observe the applicable safety and operating regulations in the respective country of use when performing any type of
maintenance.
4.2 Installation
Run the gas supply to the cooler with a downward slope. The gas inputs are marked in red and additionally labelled "IN".
If a large amount of condensate accumulates, we recommend using a condensate trap with automatic condensate drain. Our
condensate drains, 11 LD V38, AK 20, AK 5.5 OR AK 5.2, are suitable.
Glass vessels and automatic condensate drains are available for draining condensate for external mounting below the unit.
When using automatic condensate drains, the sample gas pump must be installed upstream of the cooler (pressure operation)
to ensure proper function of the condensate drain.
If the sample gas pump is located at the cooler outlet (suction operation), we recommend using glass condensate traps or peri-
staltic pumps.
Glass
PTFE
NOTICE
Installing filters limits the maximum approved operating pressure in the system!
Operating pressure ≤ 2 bar
The sample gas cooler features plug-in connectors at the top for connecting the power supply and the status outputs.
The unit features an output for status messages. Please refer to the technical data for ratings.
An alarm is triggered if the temperature of the cooler is outside the specified limits. It does not indicate if the alarm was
triggered due to excess temperature or insufficient temperature.
When the moisture detector (optional) is installed, an alarm is activated if the moisture is still present in the prepared sample
gas. This is the same alarm output as for the temperature.
X2.1 X2.5
X2.10
X2.6
X1.1
4.4 Settings
Remarks on outlet dew point
Not all applications require an outlet dew point of 5 °C. In some applications a higher dew point is sufficient. In other applica-
tions a stable outlet dew point doesn’t matter, it’s enough for the gas to be dry, so for the outlet dew point to have an adequate
difference in temperature below the ambient temperature.
The advantage of a higher outlet temperature is that at a given ambient temperature the Peltier cooler provides significantly
more cooling performance. So on the e.g. TC-MINI version model 6111, at an ambient temperature of 40 °C this means:
To fully utilize these advantages, the electronics feature several parameter settings:
1. Adjustable outlet dew point
An outlet dew point of 3, 5, 10 or 15 °C can be set to reach the specified values. Here it’s important the ambient temperature
is always ABOVE the outlet dew point setting, or condensation may form in the lines after the cooler. So the ambient tem-
perature range is limited.
2. Delta-T Control
Here the electronics measures the ambient temperature an regulates the outlet dew point to a an about 15 °C or 30 °C lower
value, but no less than the dew point set under 1. This extends the potential cooling capacity to the limits of the heat ex-
changer. Here it’s important to note the outlet dew point fluctuates along with the ambient temperature and a stable dew
point cannot be a prerequisite for the measurement.
As seen in the following graphics using the TC-MINI 6111 as an example, a difference of 15 °C from the ambient temperature
means the focus is on drying the sample gas. The stability of the dew point then takes a backseat to the high performance
which can be achieved.
At a difference of 30 °C, at a set outlet dew point of 10 °C this means the dew point remains stable up to an ambient temper-
ature of approx. 40 °C, and the safe drop is only preferred over the ambient temperature with ambient temperature peaks
over 40 °C.
Cooling capacity in kJ/h
10 °C
Output dew point
Ambient temperature in °C
DIP switch
The unit is configured using four DIP switches at the front of the cooler.
1 ON switch
SW1 0 1
0 OFF switch
SW2 0 1
SW Switch, the following numbering of the SWs corresponds with the numbering on the DIP
SW3 0 1
switch.
SW4 0 1
After switching on the supply voltage the cooler starts to cool the cooling block. When switched off the contact between X2.1 and
X2.2 is closed.
The target temperature is factory preset to 5 °C. The alarm limit is defined at +5/-2 K.
(Note deviating defaults with Modbus option enabled, see Modbus register table).
OK No error
Error Error present
xxx Status not defined
f =… LED flash frequency
X2.1, X2.2… Markings on terminals
(*) Also applies if no moisture detector connected
If the red LED lights up during operation, please refer to chapter ““.Troubleshooting [> page 19]“.
Data types:
TC-MINI
Bühler Technologies GmbH
Description FC Address Access Data type Default Min Max Selection Resolution Unit
Block temperature measurement 3 2000 R Float - - - - 0.5 °C
Block temperature status 3 2002 R Uint32 - - - 0 : = error
1..15 := reserved
16 := sensor not calibrated
17 := initialization / measurement invalid
18 := stabilization phase
19 := load limit reached
20 := measurement outside target range
21..31 := not used
Ambient temperature measurement 3 2004 R Float - - - - 0.5 °C
Ambient temperature status 3 2006 R Uint32 - - - 0 : = error
1..15 := reserved
16 := sensor not calibrated
17 := initialization / measurement invalid
18..31 := not used
Block temperature setpoint 3, 16 5000 R/W Float 5.0 3.0 15.0 - 0.5 °C
Positive alarm tolerance setpoint 3, 16 5002 R/W Float 3.0 1.0 7.0 - 1.0 K
Negative alarm tolerance setpoint 3, 16 5004 R/W Float -3.0 -3.0 -1.0 - 1.0 K
Temperature difference Delta-T 3, 16 5008 R/W Float -15.0 -30.0 0.0 - 1.0 K
Enable/disable Delta T 3, 16 9001 R/W Uint16 0 - - 0 := normal operation 1 -
1:= Delta-T control
Signal store 3, 16 9002 R/W Uint16 2 - - 1 := no 1 -
Moisture detector error 2 := yes
Signal store 3, 16 9003 R/W Uint16 1 - - 1 := no 1 -
Moisture alarm 2 := yes
Sensitivity moisture detector 1 3, 16 9004 R/W Uint16 0 - - 0 := sensitivity low
1 (with moisture detector) 1 := sensitivity high
2 (without moisture de- 2 := moisture detector inactive
tector)
Modbus Baudrate selection 3, 16 9009 R/W Uint16 3 - - 1 := 4800 - -
2 := 9600
3 := 19200
BE440015 ◦ 05/2021
4 := 38400
5 := 57600
6 := 115200
BE440015 ◦ 05/2021
Description FC Address Access Data type Default Min Max Selection Resolution Unit
TC-MINI
Modbus Parity selection 3, 16 9010 R/W Uint16 2 - - 0 := none 1 -
1 := odd
2 := even
Modbus Device address selection 3, 16 9011 R/W Uint16 10 1 247 - 1 -
TEST 3 9990 R Uint32 12648430 - -
TEST_UINT16 3, 16 9992 R/W Uint16 206 0 65535 - 1 -
TEST_INT16 3, 16 9993 R/W Int16 -206 -32768 32767 - 1 -
TEST_UINT32 3, 16 9994 R/W Uint32 2766 0 0xffffffff
TEST_INT32 3, 16 9996 R/W Int32 -2766 0x800 0x7fffffff
00000
TEST_Float 3, 16 9998 R/W Float -10.5
Status register overview 3 10000 R Uint16 0 - - Bit 0 := status information at
Register 10001
Bit n := status information at
Register 10000 + n + 1
Condition code register 1 3 10001 R Uint16 0 - - Bit 0 := device status - -
Bit 1 := device in error status
Bit 2 := set temperature range overrun
Bit 3 := set temperature range underrun
Bit 4 :=
Bit 5 :=
Bit 6 := moisture detector connected
Bit 7 :=
Condition code register 2 3 10002 R Uint16 0 - - Bit 0 := - -
Bit 1 :=
Bit 2 := initialization phase
Bit 3 := Delta-T active
Bit 4 :=
Bit 5 :=
Bit 6 := FF1 moisture alarm
Bit 7 :=
Bühler Technologies GmbH 14
Description FC Address Access Data type Default Min Max Selection Resolution Unit
TC-MINI
Condition code register 4 3 10004 R Uint16 0 Bit 0 :=
Bit 1 :=
Bit 2 :=
Bit 3 :=
Bit 4 :=
Bit 5 :=
Bit 6 :=
Bit 7 :=
Error register 1 3 10005 R Uint16 0 Bit 0 :=
Bit 1 := controller communication error
Bit 2 :=
Bit 3 := controller configuration error
Bit 4 :=
Bit 5 :=
Bit 6 :=
Bit 7 := gen. software error
Error register 2 3 10006 R Uint16 0 Bit 0 :=
Bit 1 :=
Bit 2 :=
Bit 3 :=
Bit 4 :=
Bit 5 :=
Bit 6 :=
Bit 7 :=
Error register 3 - moisture detector 1 3 10007 R Uint16 0 Bit 0 :=
Bit 1 :=
Bit 2 := cable break
Bit 3 :=
Bit 4 :=
Bit 5 :=
Bit 6 :=
Bit 7 :=
Bühler Technologies GmbH 15
Description FC Address Access Data type Default Min Max Selection Resolution Unit
TC-MINI
Error register 6 - PT100.2 3 10010 R Uint16 0 - - Bit 0 := general error
Bit 1 := short-circuit / temperature low
Bit 2 := cable break / temperature high
Bit 3 := measurement fluctuation
Bit 4 :=
Bit 5 :=
Bit 6 :=
Bit 7 :=
Utilisation controller 1 3 10017 R Uint16 - 0 100 10 %
Device run time 3 10100 R Float - 0 - 6 min h
Device restart / device reset 16 11000 W Uint16 0 - - 86 := device restart
17:= factory reset
Reset moisture detector 1 16 11002 W Uint16 170 - - -
Example:
Register 5000 = 0x1388
Read block temperature set values
A FC Start register HI Start register LO No. register HI No. register LO CRC CRC
Request 0x0A (10) 0x03 (3) 0x13 0x88 0x00 (0) 0x02 (2) 0x41 0xDE
A FC No. of byte DATA 3 DATA 2 DATA 1 Data 0 CRC CRC
Response 0x0A (10) 0x03 (3) 0x04 0x40 0xA0 0x00 0x00 0x55 0x11
Bühler Technologies GmbH 16
TC-MINI
6 Maintenance
The basic version of the cooler requires no special maintenance.
However, it may have different options depending on the configuration ordered. In this case the following routine maintenance
is required:
Filter option: Check filter element (see chapter Replacing the filter element (option) [> page 21].
During maintenance, remember:
– The equipment must be maintained by a professional familiar with the safety requirements and risks.
– Only perform maintenance work described in these operating and installation instructions.
– When performing maintenance of any type, observe the respective safety and operation regulations.
7.1 Troubleshooting
Problem/malfunction Possible cause Action
No LED lights up – Mains voltage interrupted – Connect to mains; check the plug is cor-
rectly inserted
– Fuse defective – Check fuse and replace if necessary
– LED defective – Send in cooler
– Internal error – Send in cooler
Red LED flashing – Operating point not yet reached – Wait (max. 15 min)
(f = 1 Hz) – Cooling output too low despite the cooler – Ensure the vents are not covered (heat
Excess temperature running buildup)
Temperature low – Flow rate too high/dew point too high/gas – Maintain limits / install pre-separator
temperature too high
– Built-in fan stopped – Check and replace if necessary
– Controller defective – Send in cooler
– Short circuit – Temperature sensor failure: Send in cooler
– Broken wire – Temperature sensor failure: Send in cooler
Red LED flashing – Internal error – Send in cooler
(f = 5 Hz)
Steady red LED – Cooler overloaded flow rate too high/dew – Maintain limits/install pre-separator
Moisture in sample gas point/gas temperature too high
(If the moisture detector was – Cooling output too low despite the cooler – Ensure the vents are not covered (heat
triggered it will then need to running buildup); maintain limits
be dried) – Condensate trap full – Empty condensate trap
– Water entering from water bag – Observe delivery rate of peristaltic pumps
– Install condensate drain with downward
slope
– Cable break in the moisture detector con- – Check connection line and plug-in connec-
nection line tion
Condensate inside the gas out- – Condensate trap full – Empty condensate trap
put – Valve inside the automatic condensate – Flush in both directions
drain may be stuck
– Cooler overload – Maintain limits
Reduced gas flow rate – Gas circuit clogged – Remove and clean heat exchanger
– if necessary, replace filter element
– Condensate output iced over – Send in cooler
Modbus communication error – Bus connection fault – Check electrical connections
– Line termination fault – Check bus line
– Check bus configuration – Check/reset configurator
8 Disposal
The heat exchanger is charged with glycol-based coolant.
In EU member states, as per Directive 2012/19/EU, device with electrical components must be recycled separately.
Dispose of parts so as not to endanger the health or environment. Follow the laws in the country of use for disposing of elec-
tronic components and devices as well as hazardous materials during disposal.
As an EU member state you have the option to return Bühler Technologies GmbH products to us. When returning the product,
the completed and signed RMA decontamination declaration must be attached to the packaging. You will find the form in the
appendix of these instructions, or simply request it by e-mail: [email protected].
9 Appendices
Air
OUT
Condensate
OUT
approx.
Optional filter
Air
IN
1)
Max. cooling capacity of the cooler must be considered.
2)
Models marked I have NPT threads or US tubes, respectively.
3)
Passive discharge via automatic condensate drains or traps not applicable for MTG heat exchanger. For passive discharge on
the MTS and MTV heat exchangers, use a screw connection with a clearance of at least 7 mm (see accessories).
4)
Gasket inside diameter
10 Attached documents
– Declaration of conformity: KX 440005
– RMA - Decontamination Statement
Das Gerät wurde gespült mit:/ The equipment was purged with:
Diese Erklärung wurde korrekt und vollständig ausgefüllt und von einer This declaration has been filled out correctly and completely, and signed by
dazu befugten Person unterschrieben. Der Versand der (dekontaminier- an authorized person. The dispatch of the (decontaminated) devices and
ten) Geräte und Komponenten erfolgt gemäß den gesetzlichen Bestim- components takes place according to the legal regulations.
mungen.
Falls die Ware nicht gereinigt, also kontaminiert bei uns eintrifft, muss die Should the goods not arrive clean, but contaminated, Bühler reserves the
Firma Bühler sich vorbehalten, diese durch einen externen Dienstleister right, to comission an external service provider to clean the goods and in-
reinigen zu lassen und Ihnen dies in Rechnung zu stellen. voice it to your account.
Die Analyse defekter Baugruppen ist ein wesentlicher Bestandteil der Qualitätssicherung der Firma
Bühler Technologies.
Um eine aussagekräftige Analyse zu gewährleisten muss die Ware möglichst unverändert untersucht
werden. Es dürfen keine Veränderungen oder weitere Beschädigungen auftreten, die Ursachen ver-
decken oder eine Analyse unmöglich machen.
Bei elektronischen Baugruppen kann es sich um elektrostatisch sensible Baugruppen handeln. Es ist
darauf zu achten, diese Baugruppen ESD-gerecht zu behandeln. Nach Möglichkeit sollten die Baugrup-
pen an einem ESD-gerechten Arbeitsplatz getauscht werden. Ist dies nicht möglich sollten ESD-
gerechte Maßnahmen beim Austausch getroffen werden. Der Transport darf nur in ESD-gerechten Be-
hältnissen durchgeführt werden. Die Verpackung der Baugruppen muss ESD-konform sein. Verwenden
Sie nach Möglichkeit die Verpackung des Ersatzteils oder wählen Sie selber eine ESD-gerechte Ver-
packung.
Beachten Sie beim Einbau des Ersatzteils die gleichen Vorgaben wie oben beschrieben. Achten Sie auf
die ordnungsgemäße Montage des Bauteils und aller Komponenten. Versetzen Sie vor der Inbetrieb-
nahme die Verkabelung wieder in den ursprünglichen Zustand. Fragen Sie im Zweifel beim Hersteller
nach weiteren Informationen.
To ensure conclusive analysis the goods must be inspected unaltered, if possible. Modifications or
other damages which may hide the cause or render it impossible to analyse are prohibited.
Electronic assemblies may be sensitive to static electricity. Be sure to handle these assemblies in an
ESD-safe manner. Where possible, the assembles should be replaced in an ESD-safe location. If un-
able to do so, take ESD-safe precautions when replacing these. Must be transported in ESD-safe con-
tainers. The packaging of the assemblies must be ESD-safe. If possible, use the packaging of the spare
part or use ESD-safe packaging.
Observe the above specifications when installing the spare part. Ensure the part and all components
are properly installed. Return the cables to the original state before putting into service. When in doubt,
contact the manufacturer for additional information.