Main
Range of product Zelio Control
Product or component type Modular measurement and control relays
Relay type Multifunction control relay
Product specific application For 3-phase supply
Relay name RM17TE
Relay monitored parameters Undervoltage and overvoltage in window mode
Asymmetry
Phase sequence
Phase failure detection
Time delay type Adjustable 0.1...10 s, +/- 10 % of the full scale value
Switching capacity in VA 1250 VA
Measurement range 208...480 V voltage AC
Complementary
Reset time 1500 Ms time delay
Maximum switching voltage 250 V AC
250 V DC
Minimum switching current 10 MA 5 V DC
Maximum switching current 5 A AC
5 A DC
Supply voltage limits 183…528 V AC
Control circuit voltage limits - 12 % + 10 % Un
Power consumption in VA 0…22 VA 400 V AC 50 Hz
Control circuit frequency 50...60 Hz +/- 10 %
Output contacts 1 C/O
Nominal output current 5A
Measurement voltage limits 183…528 V AC
Hysteresis 2%
Run-up delay at power-up 650 Ms
Environment
Electromagnetic compatibility Emission standard for industrial environments EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environ-
ments EN/IEC 61000-6-3
Immunity for industrial environments EN/IEC 61000-6-2
Standards EN/IEC 60255-1
Product certifications GOST
C-tick
CSA
UL
GL
Directives 89/336/EEC - electromagnetic compatibility
73/23/EEC - low voltage directive
Ambient air temperature for storage -40…158 °F (-40…70 °C)
Ambient air temperature for operation -4…122 °F (-20…50 °C)
Relative humidity 95 % 131 °F (55 °C) IEC 60068-2-30
2
Vibration resistance 0.35 mm 5…57.6 Hz)IEC 60068-2-6
1 gn 57.6…150 Hz)IEC 60255-21-1
Shock resistance 15 gn 11 ms IEC 60255-21-1
IP degree of protection IP20 IEC 60529 terminals)
IP30 IEC 60529 casing)
Pollution degree 3 IEC 60664-1
Dielectric test voltage 2 KV AC 50 Hz, 1 min IEC 60255-5
2 KV AC 50 Hz, 1 min IEC 60664-1
Non-dissipating shock wave 4 KV IEC 60255-5
4 KV IEC 60664-1
4 KV IEC 61000-4-5
Packing Units
Unit Type of Package 1 PCE
Package 1 Height 1.06 In (2.7 cm)
Package 1 width 3.03 In (7.7 cm)
Package 1 Length 3.78 In (9.6 cm)
Unit Type of Package 2 S02
Number of Units in Package 2 48
Package 2 Weight 11.06 Lb(US) (5.017 kg)
Package 2 Height 5.91 In (15 cm)
Package 2 width 11.81 In (30 cm)
Package 2 Length 15.75 In (40 cm)
Offer Sustainability
Sustainable offer status Green Premium product
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
WEEE The product must be disposed on European Union markets following speci-
fic waste collection and never end up in rubbish bins.
Contractual warranty
Warranty 18 months
3
Product data sheet RM17TE00
Dimensions Drawings
4
Product data sheet RM17TE00
Connections and Schema
Wiring Diagram
5
Product data sheet RM17TE00
Technical Description
Function Diagrams
Phase Sequence Control, Phase Failure Detection (U measured < 0.7 x nominal supply voltage) and Asymmetry
Detection
Legend
A Asymmetry thershold (adjustble from 5...15% of the nominal supply voltage)
Tt Time delay after crossing of threshold (adjustable on front panel)
H Hysteresis
U> Overvoltage threshold
U< Undervoltage threshold
L1, L2, L3 Phases of the supply voltage monitored
11-12, 11-14 Output relay connections (refer to Connections and Schema)
Relay status: black color = energized.